EXECUTIVE ENGINEER ED KUGLAM
EXECUTIVE ENGINEER ED KUGLAM
Providing of Separate electrical connection for Fast DC Electrical Vehicle Charging Station at Abshar Filling Station IOCL Petrol Pump Laroo Kulgam
2025_PDD_292406_1
EDK/e-tender/33 of 2025-26
Open Tender
Electrical Works
Turn-key
30 days
KULGAM
Please refer Tender documents.
7 documents required · 7 mandatory
₹500
EXECUTIVE ENGINEER ED KUGLAM
₹16,840
Yes
29 Oct 2025
17 Oct 2025
29 Oct 2025
17 Oct 2025
28 Oct 2025
17 Oct 2025
17 Oct 2025 - 20 Oct 2025
Amount
Providing of Electricity Connection to Fast DC EV Charging Station
Supply, Installation, Testing and commissioning of 200 kVA,11/0.433KV, 3-phase Distribution Transformers (level-II) with Bimetallic Terminal connrction and with LV Cable box having detachable Aluminium Gland Plate. Transformer should be arranged for vertical takeoff.
Supply,erection, testing and commissioning of S.T Pole 9mtr Long SP-33 with base plate & cap for HT. Strictly as per REC standards
Supply, laying, installation and testing of 35 mm² AB (HT) Cable (3x35+1x35 mm² insulated) mm² XLPE
Supply,laying and testing of 50sqmm LTAB Cable (3x50+1x16+1x35) sqmm XLPE (1.1KV, 3+1C, Al)
Providing and fixing of Suspension/Tension Clamp, fitting with eye hook complete job
11kV Pilfer resistant metering cubicle for 3phase 4 wire metering system made of MS Sheet steel thickness not less than 2mm duly power coat painted suitable for indoor as well as outdoor as per the site requirement. The cubicle shall be painted through 7-tank process. The External dimensions should be adequate. Panel having two compartments upper Meter compartment and lower CT/PT compartment. Provided with synthetic or semi synthetic gasket firmly glued to the sufrace, Dust, weather and Vermin proof and shall comply degree of protection IP 65 both the chambers having one sided hinged door arrangments. The metering panel shall be provided with two No MS channels of size 100 x 50 mm on the front and rear sides duly welded and 4 No of lifting hooks. It should be possible to take meter reading manually, through CMRI and computer without opening the LV chamber door. Single Phase, Single core, single ratio, Epoxy resin Cast Current Transformers suitable for 11kV, copper wound primary type with rated burden 5VA and accuracy class 0.5 or better and conforming to IS2705 (part-I & II) amended upto date. ISF shall be upto 5 The CT ratio shall be 20/5 for 250kVA DT 11kV/ 110 V, Three phase epoxy resin cast PT with rated burden 15VA per phase and accuracy class 0.5 or better and conforming to IS:3156 (part-I&II) amended upto date with proper colour coded identification. PTs shall be of uniform insulating and withstand separate source 23kV pf for one minute. Bus Bar details: CTs bus bar:- 40x6 mm copper strip or adequate size PTs bus bar: Copper wire 8 SWG or 30x0.6mm copper flat strip to connect PT terminal or adequate size duly insulated by the monoplast tape PVC Copper wire flexible multi-strand of required size for secondary connections for CT wiring the minimum wire size shall be 4 mm2 (RYB) and for PT wiring minimum wire size shall be 2.5 mm2 (RYB). Copper Lugs preferably ring type duly crimped for termination of wires and tapes Grounding bus of minimum 40mm copper, 25cm long fixed to the unit in HV chamber. The CTs, PT meter and 11kV Cable sheath shall be grounded to the bus through grounding wire (green) of min size 10sqmm 3Ph3 Wire HT CT/PT operated Fully static Smart Tri-Vector Energymeters DLMS Compliant Category 'C' with RS 232 port for modem compatibility. 11kV/110V, Ph-Ph (3P,3W) meters for measurement of different electrical parameters including Active Energy (kWh/ MWh), Reactive Energy (kVArh/MVArh), Apparent Energy (kVAh/ MVAh) etc. (make L&T, Secure, ABB) Independent flexible PVC pipes for CT wiring and PT wiring of appropriate size from HT compartment to meter compartment Pedestal made out of G.I Channel of size 75 x 40 mm or angle iron of size (65 x 65 x 5) mm, duly painted as per site requirement for mounting of metering panel including concrete foundation wherever required including cost of nuts and bolt
SITC of 3 Core 11 kV Aluminium cable XLPE armoured 35 mm2 including cost of clamp for its fixing where ever required
SITC of Cable termination kits suitable for 3 x 35 mm2 XLPE Cable (Outdoor)
Providing and fixing of GI Barbed Wire for anti climbing Device
Supply, laying of 240 mmsq Single Core cable, 1.1KV Grade, XLPE insulated stranded conductor, FRLS unaroumed Cable
Providing & fixing of GI Channel/Angle/Flat of sizes including clamps
Supplying and fixing of Earthing Complete by GI Pipe 40 mm or GI Rod 20mm 2.5 mtr long through GI Strip as per REC standards.
Painting of poles with one coat of red oxide and two coats of Aluminium paint as per Standards. This also includes numbering of ploes with paint, submission of Pre and Post Execution photographs duly anthenticated by AEE concrened.
Supply,fixing, testing & commissioning of 11kV GO, AB Switch 3-Phase, 3-Pole, 200 Amp, Vertical Type as per IS Standards
Supply,fixing, testing & commissioning of 11 kV Horn Gap Fuse Set 3-Phase 200A as per IS Standards
Supply,fixing, testing & commissioning of 11 kV Gapless Surge Arrestor, 3-Phase, 9 kV ,10 kA ,LA with polymer housing, Stn. Type as per IS Standards
Supply,fixing, testing & commissioning of 11 KV Pin Insulators (polymer/porcelain) with Pins(5KN)
Cement bottoming 1:2:4 mix as per REC Standards 0.5cum/pole
Providing & fixing of Sundry items like aluminium lugs, Jumpers, binding Tape etc
Supply Installation Testing and commissioning of 11kV Polymeric composite Disc Insulator 12kV,min failing load 45kN, Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 320mm
Supplying and fixing of Earthing of substation --Excavation of earth pit of dia 650 mm & depth 3000 mm, installation of Earthing pipe of 40 mm Nominal bore & 4mm wall thickness & length 2.5 mtr long as Per IS 1239.GI Strip for neutral earthing of size 25 mm x 3 mm for connection of transformer body,G.O Set & lightening arrestor as per IS 2629/85, GI nuts & bolts,refilled with earth enhancement materials and earth Chamber made of brick masonary with RCC slab cover.
Providing, Fixing of GI nuts and bolts for fixing of x-arms and other accessories.
LT Distribution Box for 200 kVA DTR with 315 Amp MCCB 3P 25 kA for incomer & 160 Amp MCCB 3P 16 kA 3 No.s for Outgoing Circuits
Providing and fixing of wedge connector/PG Clamps
Supply of Al 20 ft foldable telescopic ladder EN131 Certified, lightweight collapsable out of T&P items
Providing and fixing of Danger Plates with clamps.
M/S Itoo Electrical (BID ID -2619901)
M/S Soban Electrical (BID ID -2619918)
finance_943385.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.18 MB
StandardDrawings.pdf
Other Document • 36.45 MB
BOQ_943385.xls
BOQ • 0.34 MB
SBD.pdf
Tender Documents • 0.95 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .