| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹36.7 LAccepted-AOC NO 07 MOOGAMBIKAI AVENUE BEHIND HOINA HOSTEL KANNADAPALAYAM THIRUNINRAVUR CHENNAI 602 024 | CHENNAI | THIRUVALLUR | TAMIL NADU | 602024 | L1 | Accepted-AOC Being L1 | |
| 2 | L2₹42.4 L+₹5.1 L (13.8%)Rejected-Finance 93 SRP KOVIL STREET PERAVALLUR CHENNAI 600 082 | CHENNAI | CHENNAI | TAMIL NADU | 600082 | L2 | Rejected-Finance Not Being L1 | |
| 3 | L3₹46.6 L+₹9.4 L (25.1%)Rejected-Finance NO 14 M C RAJA STREET MITTANAMALLI I A F AVADI CHENNAI 600 055 | CHENNAI | CHENNAI | TAMIL NADU | 600055 | L3 | Rejected-Finance Not Being L1 |
| Sl No | Description | Qty | Unit | SAMYDOSS CONSTRUCTIONS L3 | SAI SRI HARSHA ENTERPRISES L1 | JANANIKARTHIK ENTERPRISES L2 |
|---|---|---|---|---|---|---|
| 1.00PART -I -ADDN/ALTN TO STN SECURITY SECTION | ||||||
| 2.00 | M&L for Complete Removal of existing water proofing treatment over roof including PCC of any thickness description in any position including cleaning the surfaces with wire brushing, watering and removing debris up to 1500 mtr distance etc complete all as specified and directed. | 150 | Sqm | 50 ₹7,500 | 29 ₹4,350 | 20 ₹3,000 Lowest |
| 3.00 | M &L for PCC 1:2:4 type B-0 (using 12.50 mm stone aggregate) 25mm thick as in roof levelling course with integral water proofing compound as per manufacturers instructions all as specified and directed.
Note:- WPC shall be measured & paid seperately. | 150 | Sqm | 150 ₹22,500 | 149 ₹22,350 Lowest | 200 ₹30,000 |
| 4.00 | M &L for PCC 1:2:4 type B-0 (using 12.50 mm stone aggregate) Providing, cement concrete in roof kerbs or mud stops, rounded or chamfered on edges all as specified and directed. | 0.5 | Cum | 6,000 ₹3,000 | 3,499 ₹1,749.5 Lowest | 7,000 ₹3,500 |
| 5.00 | M&L for complete waterproofing treatment to roof surface, including rendering in cement mortar 10 mm thick in 1:3 mix on concrete surfaces finished even and smooth without using extra cement to receive waterproofing treatment, mixed with integral waterproofing compound as per manufacturer’s instructions (WPC shall be measured and paid separately); applying evenly a priming/tack coat of bituminous primer @ 10 kg per 10 sqm; preparing the rendered surface by thoroughly removing all loose particles, dirt and dust and applying one coat of water-based bituminous primer @ 0.40 Ltr/sqm followed by a uniform coat of hot-blown bitumen of grade VG-10 @ 1.20 kg/sqm conforming to IS 702; laying APP-based polymeric waterproofing membrane 3 mm thick (weighing not less than 3.6 kg/sqm) reinforced with non-woven polyester fabric (not less than 150 gsm) with minimum 100 mm side and end overlaps; and finishing the surface with one coat of solar-reflective aluminium paint @ 0.10 Ltr/sqm,complete all as specified and directed. NOTE :- a) Integral waterproofing compound (WPC) shall be measured and paid for separately under relevant item of Schedule.
b) Work shall be carried out strictly as per manufacturer’s specifications and as directed by the Engineer-in-Charge.
c) The rate quoted shall include cleaning, preparation, heating, and application of all materials complete for effective waterproofing.
The contractor shall provide a 10-year performance guarantee for the waterproofing system from an approved manufacturer. | 150 | Sqm | 600 ₹90,000 | 299 ₹44,850 Lowest | 500 ₹75,000 |
| 6.00 | Taking down Chowkhats or frames not exc. 1.5 sq. m each with shutters (without taking off shutters from the frames) complete all as specified and directed. | 15 | Each | 150 ₹2,250 Lowest | 199 ₹2,985 | 150 ₹2,250 Lowest |
| 7.00 | Taking down Chowkhats or frames exc. 1.5 sq. m and not exc 4.sq.m each with shutters (without taking off shutters from the frames) complete all as specified and directed. | 6 | Each | 200 ₹1,200 | 199 ₹1,194 Lowest | 200 ₹1,200 |
| 8.00 | Powder coated aluminium frame for doors, windows, ventilators with one or more rebates including joining cleat for fixing etc. complete all as specified and directed. | 110 | Kg | 600 ₹66,000 | 549 ₹60,390 Lowest | 625 ₹68,750 |
| 9.00 | Powder coated aluminium door shutters, aluminium section weighing 0.55 kg/m including necessary joining cleats, glazing clips, ruber neoprene packing, handles 2 Nos in each door, hinges, anodised aluminum snap beading screws etc. complete all as specified and directed. | 12 | Sqm | 3,500 ₹42,000 | 3,299 ₹39,588 Lowest | 3,500 ₹42,000 |
| 10.00 | Powder coated aluminium window and ventilator shutters, side hung type without sash bars, aluminium sections weighing 0.55 kg/m including necessary joining cleats, glazing clips, rubber packing, anodised aluminium snap beading, screws, anodised aluminium fittings such as peg stays 150mm long (1 no.). hinges type B-21 100mm long (2 no.) suitable handle (1 no.) complete all as specified and directed. | 18 | Sqm | 2,800 ₹50,400 Lowest | 3,499 ₹62,982 | 3,300 ₹59,400 |
Tender Value
₹46.1 L
EMD Value
₹92,300
Closing Date
24 Nov 2025, 6:00 pmClosed
Garrison Engineer Avadi
Garrison Engineer , Muthapudupet, Air Force Area, Avadi, Chennai-55
ADDN / ALTN TO STN SECURITY SECTION AT 23 ED AND PROVN OF FENCING AT CERTAIN PLACES IN TECH AREA INCLUDING CERTAIN MINOR WORKS AT AF STN UNDER GE AVADI.
2025_MES_739041_1
8324/E8
Open Tender
Miscellaneous Works
Item Rate
220 days
GE Avadi
As per Tender Document
7 documents required · 7 mandatory
₹500
GE Avadi
₹92,300
Yes
27 Jan 2026
10 Nov 2025
26 Nov 2025
10 Nov 2025
24 Nov 2025
19 Nov 2025
10 Nov 2025 - 17 Nov 2025
Amount
PART -I -ADDN/ALTN TO STN SECURITY SECTION
M&L for Complete Removal of existing water proofing treatment over roof including PCC of any thickness description in any position including cleaning the surfaces with wire brushing, watering and removing debris up to 1500 mtr distance etc complete all as specified and directed.
M &L for PCC 1:2:4 type B-0 (using 12.50 mm stone aggregate) 25mm thick as in roof levelling course with integral water proofing compound as per manufacturers instructions all as specified and directed. Note:- WPC shall be measured & paid seperately.
M &L for PCC 1:2:4 type B-0 (using 12.50 mm stone aggregate) Providing, cement concrete in roof kerbs or mud stops, rounded or chamfered on edges all as specified and directed.
M&L for complete waterproofing treatment to roof surface, including rendering in cement mortar 10 mm thick in 1:3 mix on concrete surfaces finished even and smooth without using extra cement to receive waterproofing treatment, mixed with integral waterproofing compound as per manufacturer’s instructions (WPC shall be measured and paid separately); applying evenly a priming/tack coat of bituminous primer @ 10 kg per 10 sqm; preparing the rendered surface by thoroughly removing all loose particles, dirt and dust and applying one coat of water-based bituminous primer @ 0.40 Ltr/sqm followed by a uniform coat of hot-blown bitumen of grade VG-10 @ 1.20 kg/sqm conforming to IS 702; laying APP-based polymeric waterproofing membrane 3 mm thick (weighing not less than 3.6 kg/sqm) reinforced with non-woven polyester fabric (not less than 150 gsm) with minimum 100 mm side and end overlaps; and finishing the surface with one coat of solar-reflective aluminium paint @ 0.10 Ltr/sqm,complete all as specified and directed. NOTE :- a) Integral waterproofing compound (WPC) shall be measured and paid for separately under relevant item of Schedule. b) Work shall be carried out strictly as per manufacturer’s specifications and as directed by the Engineer-in-Charge. c) The rate quoted shall include cleaning, preparation, heating, and application of all materials complete for effective waterproofing. The contractor shall provide a 10-year performance guarantee for the waterproofing system from an approved manufacturer.
Taking down Chowkhats or frames not exc. 1.5 sq. m each with shutters (without taking off shutters from the frames) complete all as specified and directed.
Taking down Chowkhats or frames exc. 1.5 sq. m and not exc 4.sq.m each with shutters (without taking off shutters from the frames) complete all as specified and directed.
Powder coated aluminium frame for doors, windows, ventilators with one or more rebates including joining cleat for fixing etc. complete all as specified and directed.
Powder coated aluminium door shutters, aluminium section weighing 0.55 kg/m including necessary joining cleats, glazing clips, ruber neoprene packing, handles 2 Nos in each door, hinges, anodised aluminum snap beading screws etc. complete all as specified and directed.
Powder coated aluminium window and ventilator shutters, side hung type without sash bars, aluminium sections weighing 0.55 kg/m including necessary joining cleats, glazing clips, rubber packing, anodised aluminium snap beading, screws, anodised aluminium fittings such as peg stays 150mm long (1 no.). hinges type B-21 100mm long (2 no.) suitable handle (1 no.) complete all as specified and directed.
S&F 5.5 mm thick sheet glass, ordinary quality and glazing with oil putty in square n exc 0.5 Sqm.m in each pane all as specified and directed.
M&L for prelaminated particle board 12mm thick, interior grade, prelaminated one side with decorative choice lamination & other siode balancing white lamination fixed with screws to timber frame work all as specified and directed.
Dismantling floor, hearth or wall tiling including cement mortar bedding (but not backing), removing serviceable tiles to store and rubbish off the premises. complete all as specified and directed.
Virified Ceramic tiles 10 mm thick (square/ rectangular) polished, area of each tiles exceeding 0.36 sqm but not exceeding 0.42 sqm, in floors etc. set and jointed in neat cement slurry and pointed in white or coloured cement to match over 20mm thick screed bed in CM (1:4) all as specified and directed
As per item No.14 above but on vertical surfaces such as skirtings, dados and risers to steps etc over 10mm thick rendering in CM (1:3) all as specified and directed
Taking down cement plaster on brick walls etc, incl racking out joints, hacking for key, scrubbing down with water etc.all as specified and directed.
M & L for rendering 15mm thick in cement mortar 1:4 on fair faces of brick / concrete surfaces and finished even and smooth without using extra cement (External surfaces) complete all as specified and as directed.
Rendering 15mm thick on fair faces of brick or concrete surfaces in CM 1:6 and finished even and smooth without using extra cement (Internal surfaces) complete all as specified and as directed.
M&L for rendering 5mm thick in cement mortar (1:3) on fair faces of concrete srufaces as in ceilings, finished even and fair without using extra cement etc complete all as specified and as directed.
M&L for preparation of newly plastered surface of walls and applying two coat of cement base paint over primer complete all as specified and as directed.
M&L for preparation of newly plastered surface of walls and applying two coats of oil bound distemper over primer for smooth surface complete all as specified and as directed.
M&L for preparation of newly plastered surfaces of ceilings and applying three coats of white wash all as specified and as directed.
Taking down carefully unserviceable point wiring copper / aluminium (light, fan, socket or power) complete, including removal of batten / conduit / gutties / wooden board etc., including fittings and fixtures such as switches, ceiling roses, regulators, sockets, light fittings, fans etc., removal from site under Sch of credit and removal of unserviceable items out of site and making good the disturbed surfaces of walls, ceilings etc.,complete all as specified and as directed.
Point wiring on stone / brick masonry wall complete with two 1.5 sqmm single core PVC insulated FRLSH ,1100 volts grade unsheathed cable confirming to IS-694, 1977 with multistranded copper conductor, drawn through and including non-metalic rigid PVC conduit, conduit fittings and conduit accessories not less than 20 mm dia concealed in walls and fixed with suitable clamps on ceiling / roof trusses etc., and including provision of one 1.5 sqmm PVC insulated single core multistranded copper conductor FRLSH green in colour as earth continuity conductor and connected to common earth dolly,including steel box of required module for modular switches/sockets and regulators all as specified and directed. (a) one light point controlled by one switch. Note : Cost of terminal box and cutting chases for concealing pipes is deemed to be included in the item rates quoted for point wiring.
(b) One ceiling fan point controlled by one switch and regulator
(c) One Exhaust fan point controlled by one switch.
(d) One switch socket outlet 3 pin 5 Amps on same board along with other switches
(e) One switch socket outlet 3 pin 5 Amps on independent board.
All as per item No 24.00 here-in-before but for point wiring with two 4.0 sqmm single core copper conductor multistranded FRLSH cable and one 4.0 sqmm PVC insulated single core multistranded cable as earth continuity conductor green in colour for one 3 pin switch socket outlet, 15 Amps, on independent board and industrial socket complete all as specified and as directed.
S&F Switch piano flush type, single pole,5 Amps, 240 volts complete all as specified and directed.
S&F Switch socket 3 pin 5 amps , multi pin , flush type,complete all as specified and directed.
S&F Switch socket 3 pin 15 Amps, multipurpose, flush type complete all as specified and directed.
S&F ceiling rose 65 X 50 mm , three terminals ,bakelite , surface complete all as specified and directed.
S&F electronic fan regulator, flush type phenolic laminated sheet etc; all as specified and directed.
Supply and Fixing of Single pole and neutral enclosure with a two pin and earth plug and socket complete with one single pole MCB 20 Amps complete all as specified and directed.
Taking down carefully Power / Sub main wirings with PVC aluminum conductor cables in PVC/STEEL conduits / TW battens up to 2/3 runs of 6 Sq.mm removing materials from site, taken as credit , making good the disturbed surfaces all as specified and as directed.
Power / Sub-main wiring with PVC insulated unsheathed, FRLSH ,1100 volts, grade multistranded copper conductor, two runs of single core 6 sqmm conforming to IS-694, drawn through and including suitable dia rigid PVC conduit, conduit fittings and conduit accessories alongwith one run 6 sqmm PVC insulated single core multistranded copper conductor cable (green) as earth continuity conductor concealed in walls and fixed with suitable clamps on ceiling / roof trusses etc. and connecting to common earth dolly complete all as specified and as directed.
S&F Load line MCB DB TP&N 4 way, vertical, double door, powder coated, 415 volts, AC, 50Hz, IP 54 protected, fixed on wall semi flush with provision for FP MCCB 100 Amps as incomer and SP MCBs 32 amps as outgoing with tinned copper bus bar, neutral link, earth link and connecting up complete all as specified and as directed. Note : Incoming MCCB and Outgoing MCB measured separately relevent items.
S&F MCB DB SPN 8 way, double door, powder coated, 240 volts, AC, 50Hz, IP 43 protected, with provision for MCB double pole as incomer and SP MCBs as outgoing with tinned copper bus bar, neutral link, earth link and connecting up complete all as specified and as directed. Note : Incoming and Outgoing MCB measured separately relevant items.
Supply and fixing 240V, 10 KA 'B' curve miniature circuit breaker (MCB) of single poles and current carrying capacity 6 to 32 AMP, in the MCB DB Complete with connection testing and commissioning complete all as specified and directed.
Supply and fixing 240V, 10 KA 'B' curve miniature circuit breaker (MCB) of SPN and current carrying capacity 40 Amps, in the MCB DB complete with connection testing and commissioning complete all as specified.
S&F MCCBs100 Amps 415V,16KA, 4 Pole complete all as specified and directed.
S&F in replacement of Surface and wall mounted LED tube light fitting, 20 W, batten type, PC housing provided for efficient heat dissipation with polycarbonate diffuser and integrated electronic driver complete with all accessories , suitable for operation on AC, single phase 220 / 230 Volts , 50 Hz supply, and including connecting up with PVC sheathed 1.5 sqmm 3 core copper conductor flexible wire from ceiling rose to fitting complete all as specified and as directed.
Supply & fix surface/recess mounting LED backlit panel ceiling light 2X2 environmental friendly new generation aesthetically designed ultra modern recess/surface mounting luminaire with high brightness SMD LEDs as light source, LED backlit luminaire suitable for armstrong/grid ceiling complete for low ceiling applications 34/36 Watt LED (2'X2') complete with electronic driver, suitable for operation on AC, single phase , 220/230V , 50 Hz , including provision of suitable twin core copper conductor PVC insulated , 1100 Volts grade cables not more than 5 m long and connecting up ceiling rose and fittings and testing, making good the disturbed any type of ceiling including taking down old fittings all as specified and as directed.
S&F LED building security light fitting 45 W made up of pressure die cast housing with toughened glass and individual high power LEDs with secondary optics, IP66 protection and impact resistance of IK07, complete pre-wired and connecting up with suitable twin core flexble copper wire including provision of necessary GI tubing medium grade 25mm bore of pipe 1.5 bent to shape with necessary clamps made out of mild steel, nuts and bolts etc., including two coats of synthetic enamel paint over a coat of red oxide primer on exposed steel surface for fixing the fitting to Bldg etc complete all as specified and as directed.
Taking down unserviceable fans,sealing cable end, dismantling blades and removing fan and deposit blades to store complete all as specified and as directed.
Supply & fix ceiling fans ceiling BLDC type complete with accessories 230 V,1400 mm sweep. BEE 5 star rated with provn of necesary hanging hook on ceiling complete all as specified and directed.
S&F of Exhaust fan, heavy duty, 300mm sweep, 1370 RPM, with louvers, metal body conforming to IS-2312-1967, AC single phase, 240 Volts, 50 Hz and connecting including provision of two way PVC connectors, 1 sqmm flexible three core multistranded copper conductor cable from ceiling rose or connector to fan including earthing and fixing arrangements like making hole in wall and finishing to shape to match adjoining surface and writing MES No.20mm height with synthetic enamel paint black complete all as specified and as directed.
Material and labour for earth continuity conductor or main earthing lead fixed to valve on batten or recess or chases or burried in ground or drawing in conduit or any other situation for loop earthing etc as reqd 4 mm dia galvanized steel wire all as specified and directed
Earthing complete with galvanised iron earth plate electrode 600mm X 600mm X 6mm thick, with and including earthing of 4mm dia GI wire protected by 15mm dia GI pipe light grade upto a length of 7.5m. The plate shall be buried directly in ground vertically to a depth not less than 2.25 metres below ground level with top edge of the earth plate at a depth not less than 1.5 metres below ground level, connected to earth lead as described here-in-before by means of bolts, nuts, washers and checknuts made out of galvanised iron or mild steel, earthing lead protected by as described here-in-before and connected to main switch board or main control board or electric pole all as shown on electrical plate No.3 of MES Sch Part-I including necessary earth work and excavation in any type of soil, plain cement concrete 1:3:6, type C1 chamber, reinforced cement concrete cover slab with locking arrangement and handle of 10mm dia MS round bars 450mm long, 1:2:4 type B1, 50mm thick with 8mm dia TMT bars at 140mm centre to centre both ways, GI pipe of bore 20mm medium grade for watering with funnel, wiremesh, salt, charcoal,lugs including testing complete all as specified and as directed.
PART II - PROVN OF HIGH VOLUME LOW SPEED HVLS INDUSTRIAL FAN FOR HANGAR NO 60 AND 66.
Supply and Fix Industrial duty High Volume low speed Fan copper winding and having diameter 20 feet, Aluminum body, air Volume 13400 Cum/Min, three phase complete including controller swith and other conneciton including provision of fixing arrangement complete all as specified and as directed.
M&L for Sub main wiring with 4 single core 6 sqmm, PVC insulated PVC unsheathed stranded copper conductor cable in and including steel concealed/surface conduit of suitable size. ISI marked, medium grade complete with all conduit accessories/ fittings including 02 Nos earth wire with 6 Sqmm single core PVC insulated, unsheathed copper cable fixed along with sub main in PVC conduit and connecting to earth dolly with all fixing material complete all as specified and directed. Note :- Six run of 6 sqmm copper cable measured as one unit.
S & F in replacement of MCB TPN 32 amps single pole with neutral, AC 415 volts , breaking capacity 10ka , 'C' series complete complete all as specified and directed.
Supply and fixing in replacement of sheet metal enlosure for Triple Pole and neutral DBs when MCBs to be used double door factory made flush fixed complete with 100 amps rated bus-bar 240 volts single phase 4 ways including necessary brick work and plaster to match with the existing surface complete all as specified and directed.
PART- III - ADDITION / ALTERATION TO EMPLOYEES CANTEEN AND FIRE CREW REST ROOM, WASH ROOM OF FIRE SECTION
Taking down Chowkhats or frames not exc. 1.5 sq. m each with shutters (without taking off shutters from the frames) complete all as specified and directed.
Taking down Chowkhats or frames exc. 1.5 sq. m and not exc 4.sq.m each with shutters (without taking off shutters from the frames) complete all as specified and directed.
Powder coated aluminium frame for doors, windows, ventilators with one or more rebates including joining cleat for fixing etc. complete all as specified and directed.
Powder coated aluminium door shutters, aluminium section weighing 0.55 kg/m including necessary joining cleats, glazing clips, ruber neoprene packing, handles 2 Nos in each door, hinges, anodised aluminum snap beading screws etc. complete all as specified and directed.
Powder coated aluminium window and ventilator shutters, side hung type without sash bars, aluminium sections weighing 0.55 kg/m including necessary joining cleats, glazing clips, rubber packing, anodised aluminium snap beading, screws, anodised aluminium fittings such as peg stays 150mm long (1 no.). hinges type B-21 100mm long (2 no.) suitable handle (1 no.) complete all as specified and directed.
S&F 5.5 mm thick sheet glass, ordinary quality and glazing with oil putty in square n exc 0.5 Sqm.m in each pane all as specified and directed.
M&L for prelaminated particle board 12mm thick, interior grade, prelaminated one side with decorative choice lamination & other siode balancing white lamination fixed with screws to timber frame work all as specified and directed.
Dismantling floor, hearth or wall tiling including cement mortar bedding (but not backing), removing serviceable tiles to store and rubbish off the premises. complete all as specified and directed.
Virified Ceramic tiles 10 mm thick (square/ rectangular) polished, area of each tiles exceeding 0.36 sqm but not exceeding 0.42 sqm, in floors etc. set and jointed in neat cement slurry and pointed in white or coloured cement to match over 20mm thick screed bed in CM (1:4) all as specified and directed
As per item No.65.00 above but on vertical surfaces such as skirtings, dados and risers to steps etc over 10mm thick rendering in CM (1:3) all as specified and directed
Taking down cement plaster on brick walls etc, incl racking out joints, hacking for key, scrubbing down with water etc., all as specified and directed.
M & L for rendering 15mm thick in cement mortar 1:4 on fair faces of brick / concrete surfaces and finished even and smooth without using extra cement (External surfaces) complete all as specified and as directed.
Rendering 15mm thick on fair faces of brick or concrete surfaces in CM 1:6 and finished even and smooth without using extra cement (Internal surfaces) complete all as specified and as directed.
M&L for rendering 5mm thick in cement mortar (1:3) on fair faces of concrete srufaces as in ceilings, finished even and fair without using extra cement etc complete all as specified and as directed.
M&L for preparation of newly plastered surface of walls and applying two coat of cement base paint over primer complete all as specified and as directed.
M&L for preparation of newly plastered surface of walls and applying two coats of oil bound distemper over primer for smooth surface complete all as specified and as directed.
M&L for preparation of newly plastered surfaces of ceilings and applying three coats of white wash all as specified and as directed.
M&L Pre painted galvalume aluminium zinc coating GI based corrugated steel sheet 0.50mm thickof an colour having tensile strength of 550 Mpa as in roof covering /cladding to wall,fixed with self tapping screws all as specified and directed.
M&L Pre painted galvalume aluminium zinc coating GI based plain steel sheet in ridges 0.50mm thickof an colour having tensile strength of 550 Mpa as in roof covering /cladding to wall,fixed with self tapping screws all as specified and directed.
S&F 1000 ltr capacity triple layer, rotational moulded polyethylene water storage tanks (cylindrical vertical with closed top) hoisted and fixed in position all as specified and directed
Disconnecting existing tanks, setting aside (or lowering if required) for repairs, cleaning, etc. and hoisting if required reconnecting and re-fixing in position cpacaity 1000 litres (Cleaning repairing, etc. measured separately) all as specified and directed.
S&F Ball valves, high pressure, with of PTMT with epoxy coated aluminium rod & high desity plastic ball screwed for iron pipe of 25 mm bore (Minimum weight 455 gms )and fixed complete all as specified and directed.
S&F of gun metal globe or gate valve with iron wheel head screwed both ends for iron pipe and fixed complete all as specified and directed.
Taking up or down steel tubing and connections, including removal to store etc all as directed for 15 mm bore all as specified and directed.
All as per item No. 80.00 above but 20mm bore all as specified and directed.
All as per item No. 80.00 above but 25mm bore all as specified and directed.
S&F Unplasticised PVC pipes and fittings of 15mm dia of pressure rating 10 kgf/cm2 fixed complete to walls, ceilings or in floors etc. complete all as specified and directed
All as per item No. 83.00 above but 20mm bore
All as per item No. 83.00 above but 25mm bore
S&F in repairs vitreous China squatting pan, ‘Orissa’ pattern, size 580 x 440 mm white, with integral foot rests (excluding flushing cistern and flush pipe) all as specified and directed
S&F in repairs Vitreous China bowl urinal flat back, size of 465 x 355 x 265 mm white (minimum), with grating and union for discharge pipe (excluding flushing cistern, flush pipe and waste pipe) all as specified and directed
S&F in repairs 10 litres capacity PVC valveless, syphonic action type, flushing cistern, low level, white, with inlet, ball valve, float and handle including brackets all as specified and directed
S&F in repairs Vitreous China wash basin, white, flat back, size 550x400mm excluding ditto but including brackets all as specified and directed
S&F in repairs Bib tap standard of PTMT any colour high pressure screwed for iron pipe and fixed. (Minimum weight 15mm 90gms/20mm- 125gms). Bore 15mm all as specified and directed
S&F in repairs Pillar taps of PTMT any colour high pressure screwed for iron pipe and fixed.(Minimum weight 15mm-110gms) Bore 15mm all as specified and directed
S&F in repairs Stop valve of PTMT any colour high pressure screwed for iron pipe and fixed. (Minimum weight 15mm-90gms/ 20mm- 92gms) Bore 15mm all as specified and directed
PVC connections 15mm size with PTMT nuts of length 600mm all as specified and directed
S&F in repairs Swivel shower of PTMT any colour for fixing with 15mm pipe. (Minimum weight 40gms) Shower arm 15 mm size, 195mm long with bend of 45degree with flange of PTMT any colour.(Minimum weight 40gms all as specified and directed
S&F in repairs Grating doom 125 mm dia with waste hole of PTMT. (Minimum weight 40gms all as specified and directed
Granite (of any type) tiles 20mm thick machine cut, bedded and jointed with grey cement slurry and pointed with white cement with admixture of pigment to match the shade of granite stone including grinding and polishing complete all as specified and directed
Screed bed or bedding layer of mortar 20 mm thick for laying floor finishes in CM 1 :4 complete all as specified and directed
Non - skid Ceramic tiles 7 to 8 mm thick (square/ rectangular) area of each tile exceeding 0.11 sqm but not exceeding 0.18 sqm, in floors etc. set and jointed in neat cement slurry and pointed in white or coloured cement to all as specified and directed
M&L Glazed ceramic tiles in vertical surface of size 450 x 350x 7mm thick set and jointed in neat cement slurry and pointed in white or coloured cement to match over 10mm thick rendering in CM ( 1:3 ) all as specified and directed
As per item No.99.00 above but on vertical surfaces such as skirtings, dados and risers to steps etc over 10mm thick rendering in CM (1:3) all as specified and directed
Cutting grooves in brick wall, 75mm wide and 65mm deep and shaping horizontal face of groove with cement morter (1:3) all as specified and directed
Taking down carefully unserviceable point wiring copper / aluminium (light, fan, socket or power) complete, including removal of batten / conduit / gutties / wooden board etc., including fittings and fixtures such as switches, ceiling roses, regulators, sockets, light fittings, fans etc., removal from site under Sch of credit and removal of unserviceable items out of site and making good the disturbed surfaces of walls, ceilings etc.,complete all as specified and as directed.
Point wiring on stone / brick masonry wall complete with two 1.5 sqmm single core PVC insulated FRLSH ,1100 volts grade unsheathed cable confirming to IS-694, 1977 with multistranded copper conductor, drawn through and including non-metalic rigid PVC conduit, conduit fittings and conduit accessories not less than 20 mm dia concealed in walls and fixed with suitable clamps on ceiling / roof trusses etc., and including provision of one 1.5 sqmm PVC insulated single core multistranded copper conductor FRLSH green in colour as earth continuity conductor and connected to common earth dolly,including steel box of required module for modular switches/sockets and regulators all as specified complete for (a) one light point controlled by one switch. Note : Cost of terminal box and cutting chases for concealing pipes is deemed to be included in the item rates quoted for point wiring.
(b) One ceiling fan point controlled by one switch and regulator
(c) One wall fan point controlled by one switch and regulator
(d) One Exhaust fan point controlled by one switch.
(e) One switch socket outlet 3 pin 5 Amps on same board along with other switches
(f) One switch socket outlet 3 pin 5 Amps on independent board.
All as per item No 103.00 here-in-before but for point wiring with two 4.0 sqmm single core copper conductor multistranded FRLSH cable and one 4.0 sqmm PVC insulated single core multistranded cable as earth continuity conductor green in colour for one 3 pin switch socket outlet, 15 Amps, on independent board and industrial socket complete all as specified and as directed.
S&F Switch piano flush type, single pole,5 Amps, 240 volts complete all specified.
S&F Switch socket 3 pin 5 amps , multi pin , flush type,complete all specified.
S&F Switch socket 3 pin 15 Amps, multipurpose, flush type complete all specified.
S&F ceiling rose 65 X 50 mm , three terminals ,bakelite , surface complete all specified.
S&F electronic fan regulator, flush type phenolic laminated sheet etc; as required.
Taking down carefully Power / Sub main wirings with PVC aluminum conductor cables in PVC/STEEL conduits / TW battens up to 2/3 runs of 6 Sq.mm removing materials from site, taken as credit , making good the disturbed surfaces all as specified and as directed.
Power / Sub-main wiring with PVC insulated unsheathed, FRLSH ,1100 volts, grade multistranded copper conductor, two runs of single core 6 sqmm conforming to IS-694, drawn through and including suitable dia rigid PVC conduit, conduit fittings and conduit accessories alongwith one run 6 sqmm PVC insulated single core multistranded copper conductor cable (green) as earth continuity conductor concealed in walls and fixed with suitable clamps on ceiling / roof trusses etc. and connecting to common earth dolly complete all as specified and as directed.
S&F Load line MCB DB TP&N 4 way, vertical, double door, powder coated, 415 volts, AC, 50Hz, IP 54 protected, fixed on wall semi flush with provision for FP MCCB 100 Amps as incomer and SP MCBs 32 amps as outgoing with tinned copper bus bar, neutral link, earth link and connecting up complete all as specified and as directed. Note : Incoming MCCB and Outgoing MCB measured separately relevent items.
S&F MCB DB SPN 8 way, double door, powder coated, 240 volts, AC, 50Hz, IP 43 protected, with provision for MCB double pole as incomer and SP MCBs as outgoing with tinned copper bus bar, neutral link, earth link and connecting up complete all as specified and as directed. Note : Incoming and Outgoing MCB measured separately relevant items.
Supply and fixing 240V, 10 KA 'B' curve miniature circuit breaker (MCB) of single poles and current carrying capacity 6 to 32 AMP, in the MCB DB Complete with connection testing and commissioning complete all as specified and directed
Supply and fixing 240V, 10 KA 'B' curve miniature circuit breaker (MCB) of SPN and current carrying capacity 40 Amps, in the MCB DB complete with connection testing and commissioning complete all as specified and directed
S&F MCCBs100 Amps 415V,16KA, 4 Pole complete all as specified and directed
S&F in replacement of Surface and wall mounted LED tube light fitting, 20 W, batten type, PC housing provided for efficient heat dissipation with polycarbonate diffuser and integrated electronic driver complete with all accessories , suitable for operation on AC, single phase 220 / 230 Volts , 50 Hz supply, and including connecting up with PVC sheathed 1.5 sqmm 3 core copper conductor flexible wire from ceiling rose to fitting complete all as specified and as directed.
Supply & fix surface/recess mounting LED backlit panel ceiling light 2X2 environmental friendly new generation aesthetically designed ultra modern recess/surface mounting luminaire with high brightness SMD LEDs as light source, LED backlit luminaire suitable for armstrong/grid ceiling complete for low ceiling applications 34/36 Watt LED (2'X2') complete with electronic driver, suitable for operation on AC, single phase , 220/230V , 50 Hz , including provision of suitable twin core copper conductor PVC insulated , 1100 Volts grade cables not more than 5 m long and connecting up ceiling rose and fittings and testing, making good the disturbed any type of ceiling including taking down old fittings all as specified and as directed.
S&F LED building security light fitting 45 W made up of pressure die cast housing with toughened glass and individual high power LEDs with secondary optics, IP66 protection and impact resistance of IK07, complete pre-wired and connecting up with suitable twin core flexble copper wire including provision of necessary GI tubing medium grade 25mm bore of pipe 1.5 bent to shape with necessary clamps made out of mild steel, nuts and bolts etc., including two coats of synthetic enamel paint over a coat of red oxide primer on exposed steel surface for fixing the fitting to Bldg etc complete all as specified and as directed.
Supply & fix ceiling fans ceiling BLDC type complete with accessories 230 V,1400 mm sweep. BEE 5 star rated with provn of necesary hanging hook on ceiling complete all as specified and directed.
Supply & fix wall mounted fans 450 mm sweep,1350 RPM, PVC blades 230 volts single phase oscillating suitable for wall mounting complete all as specifed and directed.
Supply & fix exhaust fans AC single phase 230/ 240 V of size 600 mm sweep, 900 RPM with louver complete all as specified and directed.
Supply & fix exhaust fans AC single phase 230/ 240 V of size 450 mm sweep, 900 RPM with louver complete all as specified and directed.
Supply & fix exhaust fans AC single phase 230/ 240 V of size 300 mm sweep, 1425 RPM with louver complete all as specified and directed.
M&L for making hole for fixing of Exhaust fan size 300 to 600 mm with necessary civil work, alteration in exist ventilation window of iron/aluminium frame for fixing of fan as per site requirement complete make good the wall/ventilation window match with exist complete all as specified and directed.
PART IV- IMPROVEMENT TO CIVIL ADMIN SECTION
Taking down carefully unserviceable point wiring copper / aluminium (light, fan, socket or power) complete, including removal of batten / conduit / gutties / wooden board etc., including fittings and fixtures such as switches, ceiling roses, regulators, sockets, light fittings, fans etc., removal from site under Sch of credit and removal of unserviceable items out of site and making good the disturbed surfaces of walls, ceilings etc.,complete all as specified and as directed.
Point wiring on stone / brick masonry wall complete with two 1.5 sqmm single core PVC insulated FRLSH ,1100 volts grade unsheathed cable confirming to IS-694, 1977 with multistranded copper conductor, drawn through and including non-metalic rigid PVC conduit, conduit fittings and conduit accessories not less than 20 mm dia concealed in walls and fixed with suitable clamps on ceiling / roof trusses etc., and including provision of one 1.5 sqmm PVC insulated single core multistranded copper conductor FRLSH green in colour as earth continuity conductor and connected to common earth dolly,including steel box of required module for modular switches/sockets and regulators all as specified complete for (a) one light point controlled by one switch. Note : Cost of terminal box and cutting chases for concealing pipes is deemed to be included in the item rates quoted for point wiring.
(b) One ceiling fan point controlled by one switch and regulator
(d) One switch socket outlet 3 pin 5 Amps on same board along with other switches
(e) One switch socket outlet 3 pin 5 Amps on independent board.
All as per item No 133.00 here-in-before but for point wiring with two 4.0 sqmm single core copper conductor multistranded FRLSH cable and one 4.0 sqmm PVC insulated single core multistranded cable as earth continuity conductor green in colour for one 3 pin switch socket outlet, 15 Amps, on independent board and industrial socket complete all as specified and as directed.
S&F Switch piano flush type, single pole,5 Amps, 240 volts complete all specified.
S&F Switch socket 3 pin 5 amps , multi pin , flush type,complete all specified.
S&F Switch socket 3 pin 15 Amps, multipurpose, flush type complete all specified.
S&F ceiling rose 65 X 50 mm , three terminals ,bakelite , surface complete all specified.
S&F electronic fan regulator, flush type phenolic laminated sheet etc; as required.
Supply and Fixing of Single pole and neutral enclosure with a two pin and earth plug and socket complete with one single pole MCB 20 Amps complete all as specified.
Taking down carefully Power / Sub main wirings with PVC aluminum conductor cables in PVC/STEEL conduits / TW battens up to 2/3 runs of 6 Sq.mm removing materials from site, taken as credit , making good the disturbed surfaces all as specified and as directed.
Power / Sub-main wiring with PVC insulated unsheathed, FRLSH ,1100 volts, grade multistranded copper conductor, two runs of single core 6 sqmm conforming to IS-694, drawn through and including suitable dia rigid PVC conduit, conduit fittings and conduit accessories alongwith one run 6 sqmm PVC insulated single core multistranded copper conductor cable (green) as earth continuity conductor concealed in walls and fixed with suitable clamps on ceiling / roof trusses etc. and connecting to common earth dolly complete all as specified and as directed.
S&F MCB DB SPN 8 way, double door, powder coated, 240 volts, AC, 50Hz, IP 43 protected, with provision for MCB double pole as incomer and SP MCBs as outgoing with tinned copper bus bar, neutral link, earth link and connecting up complete all as specified and as directed. Note : Incoming and Outgoing MCB measured separately relevent items.
Supply and fixing 240V, 10 KA 'B' curve miniature circuit breaker (MCB) of single poles and current carrying capacity 6 to 32 AMP, in the MCB DB Complete with connection testing and commissioning all as specified and directed
Supply and fixing 240V, 10 KA 'B' curve miniature circuit breaker (MCB) of SPN and current carrying capacity 40 Amps, in the MCB DB complete with connection testing and commissioning complete all as specified and directed
S&F in replacement of Surface and wall mounted LED tube light fitting, 20 W, batten type, PC housing provided for efficient heat dissipation with polycarbonate diffuser and integrated electronic driver complete with all accessories , suitable for operation on AC, single phase 220 / 230 Volts , 50 Hz supply, and including connecting up with PVC sheathed 1.5 sqmm 3 core copper conductor flexible wire from ceiling rose to fitting complete all as specified and as directed.
Supply & fix surface/recess mounting LED backlit panel ceiling light 2X2 environmental friendly new generation aesthetically designed ultra modern recess/surface mounting luminaire with high brightness SMD LEDs as light source, LED backlit luminaire suitable for armstrong/grid ceiling complete for low ceiling applications 34/36 Watt LED (2'X2') complete with electronic driver, suitable for operation on AC, single phase , 220/230V , 50 Hz , including provision of suitable twin core copper conductor PVC insulated , 1100 Volts grade cables not more than 5 m long and connecting up ceiling rose and fittings and testing, making good the disturbed any type of ceiling including taking down old fittings all as specified and as directed.
PART V - PROVN OF WINDOW GRILL IN OFFICE OF D (T) HANGAR AT MTTI.
S &F Framed work such as grills, gratings, etc.. with ends of bars shouldered and/or riveted, or forged into spikes; framed guard bars; barred iron doors; ladders; framed balusters; walk ways; railings; framework of water tanks and similar work conforming to Fe.290.Gde-E-165 all as specified and directed
M&L Preparation of new steel surfaces and applying two caot of synthetic enamel paint over a coat red oxide primer complete all as specified and directed
Cutting holes in brick walls built in cement mortar for inserting holdfasts and making good the disturbed portion in cement mortar 1:3 or cement concrete (1:2:4) Type B-1, exc half brick thick walls and not exceeding one brick thick, the depth of embedded portion of holdfast or lugs measured from the face of the jamb into the wall complete all as specified and directed.
PART VI - PROVN OF GLASS DOOR WITH ALUMINIUM FRAMES IN CERTAIN OFFICE OF HQ BLDG AT MTTI.
Taking down Chowkhats or frames exc. 1.5 sq. m and not exc 4.sq.m each with shutters (without taking off shutters from the frames) complete all as specified and directed.
M&L Powder coated aluminium frame for doors, windows, ventilators with one or more rebates including joining cleat for fixing etc. complete all as specified and directed.
M&L Powder coated aluminium door shutters, aluminium section weighing 0.55 kg/m including necessary joining cleats, glazing clips, ruber neoprene packing, handles 2 Nos in each door, hinges, anodised aluminum snap beading screws etc. complete all as specified and directed.
S&F 5.5 mm thick sheet glass, ordinary quality and glazing with oil putty in square n exc 0.5 Sqm.m in each pane all as specified and directed.
M&L for prelaminated particle board 12mm thick, interior grade, prelaminated one side with decorative choice lamination & other siode balancing white lamination fixed with screws to timber frame work all as specified and directed.
S&F Aluminium extruded section body door closer hydraulically regulated, designation No. 3, universal type, suitable for door shutters of 851 to 1000 mm in width and of weight between 61 to 80 kg and fixed all as specified and directed.
PART VII - PROVN OF FALSE CEILING AND ANTI TERMITE TREATMENT IN DRIVING TRAINING SQN OF MTTI.
S&F false ceiling of Non asbestos fibre cement building boards, manufactured from homogeneous mixture of cement, quartz and cellulose and cured with high pressure steam using auto claving process confirming to IS-14862, of size 600 mm x 600 mm x 4 mm thick fixed over snap grid frame work of T section (main & cross member) of size 25 mm x 25 mm x 1.5 mm thick in square pattern of grid size 600mm X 600mm . The aluminium fram work will supported on side wall with the used of aluminium 'L' section of size 25 mm x 25 mm x 1.5 angles etc. Snap grid shall be supported with hangers of 4 mm dia. Galvanised iron wire adjusting level fixed to roof slabs / truss etc by means of ceiling cleats made out of Galvanised iron flat of size 40 x 3 mm size 60 mm long and expansion hold fasteners 12.5 mm dia 40 mm long complete all as specified and directed . including necessary removal of existing electrical fittings and re-fixing in position without disturbing existing connected fittings.
Distmantling Wall and ceiling boards (fibre,pulp, insulation, etc.) or insulation boards/slabs/ blankets, any thickness, including cover fillets all as specified and directed.
Providing and injecting chemical emulsion for Post Constructional Antitermite Treatment along external wall where the apron is not provided using chemical emulsion at the rate of 7.5 litres per sq.m of the vertical surface of the sub-structure to a depth of 300mm including excavating channel along the wall and rodding etc. complete all as specified and directed.
Along the external wall below concrete or masonry apron using chemical emulsion @ 2.25 litres per linear metre including drilling and plugging holes etc. in apron all as specified and directed.
Treatment of soil under existing floors using emulsion @ one litre per hole, 300mm apart including drilling and plugging 12mm dia holes with cement mortar 1:2 (1 cement: 2 coarse sand) to match the existing floors all as specified and directed.
PART VIII - ADDN/ALTN OF FIRE FIGHTING SYSTEM INCLUDING INSTALLATION OF AUTOMATION SYSTEM AT FIRE SECTION.
M&L for servicing , cleaning, repainting of LT Panel of any size floor mounted for Fire Pumps panel board ,415 Volts Indoor type, cubical compartmentalised vermin and water proof fabricated out of 3.15mm thick CRCA sheet, front and back door openable with locking arrangement, necessary ventilation, internal wiring with suitable size including replacement of following items:- (a) Replacement of MCCB 4 Pole, 415 volts, 400 Amps 35 KA - 01 No (Incoming) (b) Replacement of MCCB 4 Pole, 415 volts, 160 Amps 25 KA - 01 (c) Replacement of MCCB 4 Pole, 415 volts 40 Amps 25 KA-05 (d) Replacement of Star Delta fully automatic Starter suitable for upto 75 HP fire pumps including suitable rating of 4 pole contactors (Main & Delta), 415 Volt (Make Seimens/ L&T/ C&S) - 01 No (e) Replacement of Star Delta fully automatic Starter suitable for upto 15 HP including suitable rating of 4 pole contactors (Main & Delta), 415 Volt (Make Seimens/ L&T/ C&S) - 01No (f) Replacement of DOL Starter suitable for upto 5 HP including suitable rating of 4 pole contactors (Main & Delta), 415 Volt (Make Seimens/ L&T/ C&S) - 01 No (for Vacuum Pump) (g) Replacement of Single phase preventor - 03 Nos (h) replacement of Set of control system components such as Aux. Switch, electronic relays, timers, contractors, triping relays, rotary switches for AC ON /DC ON etc. to make the equipment automatic as per functional requirements. (j) Replacement of Voltmeter, three phase, digital type, suitable for range (0-500) volts with selcetor switch - 01 No. (k) Replacement of Ammeter, digital type, three phase, (0-300 amp) with suitable CT's complete - 01 Set (l) Replacement of Indication lamp (R,Y,B), LED type, with toggle switches - 03 Set. (m) Replacement of Other connected accessories such as push buttons start/ stop etc as required Note :- (a) Operation of electrically operated Jockey pump should frequent start/ stop to operate in pressure falls below not less than 6 Kg/ Cm2 in hydrant system with electrical/ mechanical connection incl accessories etc as required incl wiring with PVC FRLS copper wiring cable 1100 V grade of suitable size complete. (b) Layout design of LT panel shall be submitted by the contractor to GE for approval before procurement.
Supply, installation, testing and commissioning of pressure switches (INDFOSS IPS 100 or approved equivalent) including making connections with the control panel and the pressure vessel including control cabling wk complete in all respects all aspecified and directed
M&L for installation of automation system for DG Engine Fire Pump suitable for 75 HP pump capacity complete all as specified and as directed.
M&L for installation of priming system for fire pump of cap 75 hp complete all as specified and as directed.
Supply and fix MS, Air vessel for Fire Pump, 300mm dia 2m height all as specified and directed
Supply and fix Pressure gauge 100 mm dia with ball valve of pressure 25 Kg/Sqcm all as specified and directed.
Providing & fixing and painting black steel pipes to I.S. 3589(6.35 mm thick) or IS 1239 heavy class including all fittings, like, fasteners, structural supports, clamps, couplings, bends, elbows, tees,offsets etc. welded or flanged joints as required, painting as per specifications, cutting holes and chases in brick or RCC walls and making good complete all as specified and directed for pump suction and delivery piping (a) 50 mm dia
(b) 150mm dia
M&L for 2 x 1.5 Sqmm FRLS unarmoured copper conductor cable complete all specified and directed
M&L in replacement for ball type foot valve thread/ flanged type 100 mm dia including providing new leather sheet after dismantling and taking up existing unserviceable old foot valve as per site requirement all as specified and directed.
M&L for earthing complete with galvanized steel earth plate electrode 600x600x6mm thick buried in ground vertical to a depth not less than 2.25 mtrs deep below ground level with top edge of plate not less than 1.5 mtr below normal ground level connected to galvanized GI strip of size 32 X 6 mm and 40 mm dia bore 7.5 mtr long light grade GI protection pipe for earth strip and GI watering pipe 40 mm dia medium grade from the top edge of earth plate fixed with deep cut on one end of pipe and fix from earth plate up to one feet above ground level of other end and plugged watering pipe at top with MS cap and grouted in PCC 1:2:4 of size 30 X 30 X 30 CM etc and 15 CM alternate layer of charcoal and salt around all sides of earth plate all as shown in electric plate no 3 of SSR part I of 2009 complete all as specified and directed. Note :- All joints either strip to strip of strip to earth plate are fixed with welded joints.
M&L for cutting existing size of MS pipe and installation of new Pipe of size 150mm dia for fixing of Air Vessel and welded the same with gas welding complete all as required at site all as specified and directed.
PART IX - PROVN OF 3 PHASE POWER SUPPLY FOR AGE B/R I.
Supply and Laying in trenches or passing through pipe UG cable XLPE insulated, armoured heavy duty electric cable with aluminium conductor, 1100 volts grade, cross-sectional area 35 sq. mm 3.5 Core complete all as specified and as directed. Note : (I) Earth work/ sand cushioning shall be measured and paid separately .
Supply,laying & fixing double wall corrugated (DWC) pipes made of high density polythyline (HDPE) with all accessories i.e. all type of joints,Sockets,Elbows,bends and End caps etc.. all as specified and directed of size 77mm outer dia and 63mm inner dia
Excavation in trenches in soft/loose soil n.exc. 1.5mtr wide and n. exc. 1.5mtr in depth and getting out for laying of cables all as specified and directed
Removing excavated material n. exc. 50m and depositing where directed at a level n. exc. 1.5 m above the starting point complete all as specified and directed.
Returning, filling in, and including spreading, levelling,watering and well ramming in layers not exceeding 25 cm thick complete all as specified and directed.
M & L for out door type aluminuam bus bar chamber feeder box of cap 300 Amp , 3 phase, 4 wire, 415 Volts of size 90 x 60 x 45 cm including incommer MCCB 250 Amp 4 Pole, 36 KA of make Havells/ Siemens/ Schneider ,The panel made out of 3.15 mm CRCA Sheet duly painted with two coats of synthetic enameld paint over a red oxide primer and fixed and supported with anlge iron grouted in PCC 1:2:4 upto 0.60 mtr high from ground level and 0.40 M below the ground level all as specified and directed . Note : Contractor is responsible to produce drawing and take approval before placing order.
S&F on load change over switch in sheet steel enclosure with front handle of capacity 100 Amps , four pole , 415 Volts complete all as specified and directed .
Material and labour for straight through joint heat shinkable suitable for upto 50 sqmm LT 3.5 core 1100 volts XLPE cable type complete all as specified and directed.
M&L for earthing complete with galvanized steel earth plate electrode 600x600x6mm thick buried in ground vertical to a depth not less than 2.25 mtrs deep below ground level with top edge of plate not less than 1.5 mtr below normal ground level connected to galvanized GI strip of size 32 X 6 mm and 40 mm dia bore 7.5 mtr long light grade GI protection pipe for earth strip and GI watering pipe 40 mm dia medium grade from the top edge of earth plate fixed with deep cut on one end of pipe and fix from earth plate up to one feet above ground level of other end and plugged watering pipe at top with MS cap and grouted in PCC 1:2:4 of size 30 X 30 X 30 CM etc and 15 CM alternate layer of charcoal and salt around all sides of earth plate all as shown in electric plate no 3 of SSR part I of 2009. Note :- All joints either strip to strip of strip to earth plate are fixed with welded joints.
Supply and laying or fixing 1100 Volts grade heavy duty cable with PVC insulated aluminium standard conductor served with an inner sheathing of PVC tape and over all PVC Sheathed in service connections , one twin core 10 Sqmm cable standard conductor cable flat or circular complete all as specified and directed .
Labour for drilling hole under the road with the help of drilling machine without damaging the road horizonally for rod crossing including laying GI tubing of any size for cable protection complete all as specified an directed.
Supply and fixing street light mounting bracket made out of GI pipe 40 mm dia light Grade not less than with 1.5 (90cmx60cm) mtr long in any shape including clamps, nuts, bolts, washers etc and painting with aluminium paint, duly completed with fixing on wall or where directed all as specified and as directed
Supply and fix LED type street light fitting made of pressure die-cast aluminium housing (heat sink) for effective thermal management, protection class IP-66, suitable for operation on 140 V – 270 V AC, power factor not less than 0.95, with asymmetric lens type optics, having a minimum luminous flux of ≥ 12,000 lumens and efficacy ≥ 130 lm/W; luminaire to have in-built surge protection, complete with 120 W LED lamp of colour temperature between 5500 K and 6500 K, including all accessories, connection and testing complete all as specified and directed.
JANANIKARTHIK ENTERPRISES (BID ID -3486725)
SAMYDOSS CONSTRUCTIONS (BID ID -3496377)
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.38 MB
BOQ_827524.xls
BOQ • 9.38 MB
8324TENDERDOCUMENT.pdf
Tender Documents • 0.94 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .