Loading…
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹5.4 LAccepted-AOC 24C GOABAGAN LANE KOLKATA 700 006 | KOLKATA | KOLKATA | WEST BENGAL | 700006 | L1 | Accepted-AOC L1 Bidder | |
| 2 | L2₹5.8 L+₹35,074 (6.44%)Rejected-Finance 3 C DR JAGABANDHU LANE KOLKATA 700012 | KOLKATA | KOLKATA | WEST BENGAL | 700012 | L2 | Rejected-Finance quoting higher rate | |
| 3 | L3₹5.9 L+₹45,512 (8.35%)Rejected-Finance 9 PATALDANGA STREET KOLKATA 700009 | KOLKATA | KOLKATA | WEST BENGAL | 700009 | L3 | Rejected-Finance quoting higher rate |
| Sl No | Description | Qty | Unit | CITY ELECTRIC CO L3 | ALPHA ELECTRICALS L1 | S. A. ENTERPRISE L2 |
|---|---|---|---|---|---|---|
| 1.00Supplying and fixing 240/415 V MCB of Breaking capacity 10kA & C characteristics on din rail of existing DBs and necessary connectionas per GS [ Make-Legrand/Siemens/L&T as approved by E.I.C ] | ||||||
| 1.10 | 6-32 Amps SP MCB | 5 | No | 228 ₹1,140 | 226 ₹1,130 Lowest | 230 ₹1,150 |
| 2.00Distribution wiring in 2 x 22/0.3 (1.5 sqmm) single core stranded 'FR' PVC insulated & unsheathed copper wire (Polycab/Finolex/Havells /RR Kabel) in 20mm size PVC rigid conduit 'FR' (Precision make), with 1x22/0.3 (1.5 sqmm) single core stranded 'FR' PVC insulated & unsheathed copper wire for ECC, to light/fan/call bell points with Modular type switch (Legrand Myrius/Arterior or Roma Urban as approved by EIC) fixed on Modular GI switch board with top cover plate and 2 no. suitable size “Ph & N” copper bar & earthing attachment fixed on wall incl. mending good damages to original finish. | ||||||
| 2.10 | Av. run 9 mtr | 26 | Pt | 1,310 ₹34,060 | 1,257 ₹32,682 Lowest | 1,300 ₹33,800 |
| 3.00Distribution wiring in 2 x 22/0.3 (1.5 sqmm) single core stranded 'FR' PVC insulated & unsheathed copper wire (Polycab/Finolex/Havells /RR Kabel) in 20mm size PVC rigid conduit 'FR' (Precision make), with 1x22/0.3 (1.5 sqmm) single core stranded 'FR' PVC insulated & unsheathed copper wire for ECC, to light/fan/call bell points with Modular type switch (Legrand Myrius/Arterior or Roma Urban as approved by EIC) fixed on Modular GI switch board with top cover plate and 2 no. suitable size “Ph & N” copper bar & earthing attachment fixed on wall incl. mending good damages to original finish | ||||||
| 3.10 | On Board | 5 | Pt | 258 ₹1,290 | 257 ₹1,285 | 250 ₹1,250 Lowest |
| 4.00Supplying and fixing of PVC Rigid Conduit 'FR' [Precision Make] on wall, ceiling with saddles and other accessories as required and mending good damages to building works of following size: | ||||||
| 4.10 | 20 mm size | 289 | Mtr | 66 ₹19,074 | 61 ₹17,629 Lowest | 65 ₹18,785 |
| 5.00Supplying and Drawing 1.1 KV single core stranded 'FR' PVC insulated & unsheathed single core stranded copper wire (Polycab/Finolex/Havells /RR Kabel) of the following sizes in the prelaid polythene pipe/rigid conduit and by the prelaid GI fish wire and making necy. connection as required | ||||||
| 5.10 | i) 3 x 22/0.3 (1.5 sqmm) | 140 | Mtr | 72 ₹10,080 | 65 ₹9,100 Lowest | 70 ₹9,800 |
Tender Value
Refer Docs
EMD Value
₹10,896
Closing Date
28 Jan 2026, 1:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
The Executive Engineer PWD,ECD
New office Complex Building(5th Floor) Bhabani Bhawan Alipore, Kolkata 700027
Setting up of exclusive POCSO Court at 1st Floor Tramline building in Alipore District Judges Court Compound Electrical work
2025_WBPWD_953568_2
WBPWD/EE-ECD/e-NIQ-40/2025-26
Open Tender
ELECTRICAL WORKS ORG
Item Rate
15 days
Alipore
please refer tender documents
5 documents required · 5 mandatory
₹10,896
O/O The Executive Engineer PWD ECD
26 May 2026
14 Jan 2026
30 Jan 2026
14 Jan 2026
28 Jan 2026
22 Jan 2026
14 Jan 2026 - 20 Jan 2026
20 Jan 2026
Supplying and fixing 240/415 V MCB of Breaking capacity 10kA & C characteristics on din rail of existing DBs and necessary connectionas per GS [ Make-Legrand/Siemens/L&T as approved by E.I.C ]
6-32 Amps SP MCB
Distribution wiring in 2 x 22/0.3 (1.5 sqmm) single core stranded 'FR' PVC insulated & unsheathed copper wire (Polycab/Finolex/Havells /RR Kabel) in 20mm size PVC rigid conduit 'FR' (Precision make), with 1x22/0.3 (1.5 sqmm) single core stranded 'FR' PVC insulated & unsheathed copper wire for ECC, to light/fan/call bell points with Modular type switch (Legrand Myrius/Arterior or Roma Urban as approved by EIC) fixed on Modular GI switch board with top cover plate and 2 no. suitable size “Ph & N” copper bar & earthing attachment fixed on wall incl. mending good damages to original finish.
Av. run 9 mtr
Distribution wiring in 2 x 22/0.3 (1.5 sqmm) single core stranded 'FR' PVC insulated & unsheathed copper wire (Polycab/Finolex/Havells /RR Kabel) in 20mm size PVC rigid conduit 'FR' (Precision make), with 1x22/0.3 (1.5 sqmm) single core stranded 'FR' PVC insulated & unsheathed copper wire for ECC, to light/fan/call bell points with Modular type switch (Legrand Myrius/Arterior or Roma Urban as approved by EIC) fixed on Modular GI switch board with top cover plate and 2 no. suitable size “Ph & N” copper bar & earthing attachment fixed on wall incl. mending good damages to original finish
On Board
Supplying and fixing of PVC Rigid Conduit 'FR' [Precision Make] on wall, ceiling with saddles and other accessories as required and mending good damages to building works of following size:
20 mm size
Supplying and Drawing 1.1 KV single core stranded 'FR' PVC insulated & unsheathed single core stranded copper wire (Polycab/Finolex/Havells /RR Kabel) of the following sizes in the prelaid polythene pipe/rigid conduit and by the prelaid GI fish wire and making necy. connection as required
i) 3 x 22/0.3 (1.5 sqmm)
ii) 2 x 36/0.3 (2.5 sqmm) + 1 x 22/0.3 (1.5 sqmm) ECC
iii) 2x56/0.3 (4 sqmm) + 1x36/0.3 (2.5 sqmm) as ECC
Finishing of the PVC insulated wire ends by socketting with pin/ ring type copper sockets and insulated tapes etc., including supplying sockets, tapes.
a)1.5 sq mm
b) 2.5 sq mm
c) 4 sq mm
Supply & Fixing 240 V, 4 nos. 6 A, 3 pin Modular type plug socket with 4 nos. 6A Modular type switch (Legrand Myrius/Arterior or Roma Urban as approved by EIC), 16A Modular switch type MCB (C-Curve) and Indicator without plug top on 2 row 18 Module GI Modular type switch board with 2 row 18 Module top cover plate flushed in wall incl. S&F switch board and cover plate and making necy. connections with PVC Cu wire and earth continuity wire etc..
Supply & Fixing 240 V, 25 A, 3 pin Modular type plug socket(Legrand Myrius/Arterior or Roma Urban as approved by EIC), without plug top and switch with 2 Module GI Modular type switch board with top cover plate flushed in wall and making necy. connections with PVC Cu wire and earth continuity wire etc.
Supply & Fixing 240 V,25 A, 3 pin Modular type plug top with indicator (Legrand Myrius/Arterior or Roma Urban as approved by EIC) & necy. Connections
Supply & Fixing 240 V, 16 A, 3 pin Modular type plug socket (Legrand Myrius/Arterior or Roma Urban as approved by EIC) with 16A Modular type switch, without plug top on 4 Module GI Modular type switch board with top cover plate flushed in wall incl. S&F switch board and cover plate and making necy. connections with PVC Cu wire and earth continuity wire etc
Supplying & Fixing GI Modular Switch Board of the following sizes complete with three no. suitable size Copper bar with holes (for Ph, N & E) fixed on bakelite/Hard Rubber insulator over the MS welded chairs incl. top cover flushed in wall for housing the board after cutting the brick wall incl. making earthing attachment, painting and mending good damages to building works. a) 6 Module
Supply & Fixing 240 V 6 A Modular type switch (Legrand Myrius/Arterior or Roma Urban as approved by EICC) on existing GI Modular type switch board having top cover plate and making necessary connections as required.
Supply & Fixing 240 V, 6A, 5 pin Modular type plug socket (Legrand Myrius/Arterior or Roma Urban as approved by EIC), without switch & plug top, on existing GI Modular type switch board with top cover plate and making necy. connections with PVC Cu wire and earth continuity wire etc.
Fixing only single/twin fluorescent light fitting suspended 25 cm bellow the ceiling with 2 No. 20 mm dia EI conduit (14 SWG) supports fixed with “L” type MS clamp whose one side fixed on ceiling with sutable size 4 nos. fastener and other side connected with the conduit with suitable size of bolts and nuts incl. S&F EI conduit, “L” type (125mmx125mm) 6mm thick and 25mm with MS clamps and connecting the length of PVC insulated wire and mending good damages to original finish and painting etc. by 2x24/0.20 mm (1.5sqmm.) flexible copper wire of 1.10 mt. length.
Supplying & Fixing MS fan clam of two piece type for RC ceiling as per approved specification, fabricated from 40 mm x 9 mm MS flat including making good damages to building roof with satisfactory finishing and painting – (As per Drawing no. 475 of PWD Specification Book – May 1991)
Extra for suspension exceeding 25 cm with S&F additional 1 no. 20 mm dia EI conduit (10 SWG) supports & necy. PVC insulated wire and painting etc. as required by 2x24/0.20 mm (1.5sqmm.) flexible copper wire of 1.10 mt. length as directed by EIC.
Supply & Fixing 240V, Modular Socket (2 Module) type fan regulator (Legrand Myrius/Arterior or Roma Urban as approved by EIC) (Brand approved by EIC) on existing Modular GI switch board with top cover plate incl. making necy. connections etc.
Engraving the deptt. number with 10 mm lettering on the body as per GS.
Painting upto 10 letters of the engraved number with approved black /red paint as required as per GS
Fixing only exhaust fan after making hole in wall and making good damages and smooth cement finish etc. as practicable as possible and providing necy. length of PVC insulated wire and making connection for exhaust of following diameter
Supply & fixing louver shutter/cowl on wall with necy. bolts & nuts (6 mm dia x 62 mm long) For AL. 23 cm (9") Exhaust fan
Fixing only ceiling fitting on wall /ceiling by screws etc.
Fixing only cabin fan on wall/ceiling by S&F rag bolts, nuts & washers (6 mm dia x 62 mm long) or as reqd. incl. S&F 24/0.20PVC insulated flexible copper wire 0.5 mt. lengthas per GS
Supply & Fixing 230V Dingdong call bell (Anchor make) with H.W board as to GS
Supply & delivery of Single LED tube light fitting complete with all accessories [Philips make Cat No. TMC 502 1xT-LED 22W or equivalent model of Wipro] incl. supply of 1 nos. MAS Led Tube 1200mm 18W 865 T8I -2100lm tube (Make -Philips/ Wipro) complete with all accessories.
Supply, Installation, testing & commissioning of 230 V 1200 mm sweep Ceiling fan complete with all accessories. The capacitor of fan must be P2 type burst proof & must have safety wire directly linked from fan hook to stator of fan, complete with blades, canopy, fork, rubber bush etc. incl. S&F connecting wire for down rod upto 30 cm incl.painting the rod with approved paint and making necessary connection as required by 3x1.5 sqmm flexible copper wire. (Make - Orient New Breeze/ Crompton Aura 1200 or equivalent of Havells)
Supply & delivery of heavy duty Exhaust fan(Make-EPC-Heavy Duty]
9"( 300mm ) Speed 1370 RPM
Supply & delivery of Full metal body & blade wall bracket fan 18inch (1420 RPM)(make -EPC/Crompton 450mm ACVORTEX 18 WM/ Storm II plus)
Supply & fixing automatic single phase AC starter of 21Amp capacity equipped with Timecheck, Voltcheck & Ampcheck and 3-digit display (Make- Electron-model no.-OPL-3+ or equivalent model of LT/Legrand as per dierction of E.I.C) to be fixed on 4Module GI box with all fixing accessories complete as to G.S.
Supply & delivery of round LED 18W surface mounted down light fittings with Aluminium di-cast housing and poly carbonate diffuser, having system lumen output not less than 1200 lumen, colour temparature 6500K (as per site requirement), Luminous efficiency - 120 luman/watt, IP rating 20 (Make- Philips-SM251/261 LED20S-6500 PSU WH /Wipro LD06 -221 -xxx-57SMG1), As per direction by EIC.
Supply & delivery of 2x2 full glow recessed mounted 35/36w ultra slim panel light fittings with Aluminium di-cast housing and poly carbonate diffuser, having system lumen output not less than 1200 lumen, power input not more than 10 watt, colour temparature 6500K (as per site requirement), Luminous efficiency - 120 luman/watt, IP rating 20 (Make- Philips- RC380B LED42S-6500 PSUG6 L60W60 PSU OD S1 /Wipro CRCO10RO30HP57G3), As per direction by EIC.
Supply & delivery of 11W LED mirror light with aluminium die cast and poly carbonate diffuser, having Colour temparature (CCT) -4000K , Luminous efficiency - 110 lumen/watt (Make- Philips ( Signify) 31165 or equivalent model of Wipro as approved by E.I.C)
Supply & delivery of Inverter type split Air-conditioner machine having Cooling Capacity- 6.5 kW (Minimum), 3/4 star rated, noise level not more than 51 db. This Split Air Conditioning machine should be fitted with Rotary/Scroll compressors, LCD remote & all other accessories suitable for Refrigerant- R32 having both condenser & cooling coil made of copper tube, connecting cord with plug top of suitable capacity with indicator(brand approved by E.I.C) conforming to IS:-1391(Part-I & Part- II) with all ammendments. (Make:- Mitsubishi Heavy Industries/ Mitsubishi Electric/O-General as approved by EIC)
Supply & delivery of inverter type split Air-conditioner machine having Cooling Capacity- 3.4 kW (Minimum), 3-star rated. This Split Air Conditioning machine should be fitted with Rotary compressors, LCD remote & all other accessories suitable for Refrigerant- R32, having both condenser & cooling coil made of copper tube, connecting cord with plug top of suitable capacity with indicator(brand approved by E.I.C) conforming to IS:-1391(Part-I & Part- II) with all ammendments. (Make:- Mitsubishi Heavy Industries/ Mitsubishi Electric/O-General as approved by EIC)
Installation, testing & commissioning of the above-said split ACs on wall with appropriate fixing arrangements as per OEM recommendations, including wall openings, mending well the damages and making necessary connections including T&P & labour etc as required complete in all respect as per the direction of EIC.
SITC including vaccumiazation and Nitrogen of testing of following nominal size of soft/hard drawn copper refrigerent piping for package RAC system, complete with fittings, with adjustable ring type hanger supports, jointing/brazing including accessories, insulated with XLPE class -O tubular insulation/withClass-O closed cell elastometric nitrile rubber tubular sleevessections of specified thickness as given below for suction andliquid lines, all accessories as per specification etc. as required.
a) 5/8" (15.88 mm.) (for suction) dia (Soft drawn) Cu. Pipes (As per standard BS864 or ANSIB 16.22) mm incl. 19mm thick insulation. (Make- Approved by EIC)
b) 1/4" (6.4 mm) ( for discharge) dia (Soft drawn) Cu. Pipes (As per standard BS864 or ANSIB 16.22) mm incl. 19mm thick insulation. (Make- Approved by EIC)
Supply & Laying of 4 core 1.5 sq.mm 1.1 KV insulation grade sheathed Cu cable with gas line as per direction of EIC for making interconnection between Indoor to Outdoor unit of Split AC m/c (Polycab/Gloster/Finolex/Havells /RR Kabel as approved by E.I.C)
Supply & Laying of 3 core 2.5sq.mm 1.1 KV insulation grade sheathed Cu cable with gas line as per direction of EIC for making interconnection between Indoor to Outdoor unit of Split AC m/c (Polycab/Gloster/Finolex/Havells /RR Kabel as approved by E.I.C)
Supply and laying 25mm PVC pipe (heavy type) for water drainage.(25mmOD, 1mm thick) with 6mm nitrile rubber insulation with proper support & bracket as per direction. (Make- Supreme/Oriplast).
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Tendernotice_1.pdf
PDF • 1.23 MB
Tendernotice_2.pdf
PDF • 0.51 MB
2911.pdf
Tender Documents • 0.50 MB
BOQ_2414317.xls
BOQ • 0.36 MB
eniq40.pdf
Tender Documents • 1.21 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .