| 1.00 | Supply and replacement of Medical Isolation Panel of rating 10 KVA for OT / ICU (critical area), medical grade as per specifications mentioned below including removing old unsv panel any type complete with elct connections etc :-
(a) The panels shall be isolated panel system as per IEC 61439-1&2 only, having critical (isolated) and non-critical circuits. Both circuits shall be monitored on the building management system. The monitoring parameters shall include On/Off status, load monitoring and shall generate alarms if any critical parameters such as isolation is anomalous. The panel shall enable electrical shock protection: according the IEC 60364-7-710 standard the solution is in compliance with the group 2 location through isolation transformer and associated monitoring system.
(b) The system shall be according the IEC standard, the switchgear is energy by 2 separate sourcing.
(c) The “Main incomer supply” is coming from the UPS system. The “Safety incomer supply” is coming directly from the other part of the main low voltage switchgear. An automatic change over shall transfer the energy sourcing from the “Main incomer supply” to the “Safety incomer supply” in case of outages in less than 30ms. | 4 | Each | 5,45,000 ₹21,80,000 Lowest | 6,56,250 ₹26,25,000 | 6,33,900 ₹25,35,600 |
| 1.01(d) The Utility and Genset sourcing should limit by 15 seconds at least any potential outage to re- energise the Main and Safety incomers. The wiring shall be in compliance with the recommendations of IEC latest standard. It shall be possible for the protective devices to be controlled by the maintenance staff, without risk of direct contact. (e) The power and communication circuit routing shall be completely separate. Pulse energy meters with inbuilt CTs shall be provided with incomers to the panel for getting the energy consumption data for operation theatre. (f) The system should be able to locate faults in case of tripping Communication auxiliaries, for communicating ON/OFF/Trip status shall be provided with all MCBs, RCCBs, RCBOs used for protection. The status shall be available over Modbus TCP/IP network. Smartlink or equivalent shall be used for communicating the status of protection devices. | ||||||
| 1.02(g) The System Controller shall transfer all data to BMS/ Central Monitoring room, shall include suitable number of DI/DOs to control and monitor the panels. The controller has 01 Nos. isolated RS 485 communication port, 1 Nos. Ethernet communication port with 10BASE-T/ 100BASE-TX, support : Modbus master/slave, BACnet, MBUS and DNP 3.0 protocols, and shall conform to ANSI/ISA 12-12- 01, CSA C22.2 No 142, CSA C22.2 No 213, EN/IEC 61131-2:2007 standards, 230VAC with inbuild 4G modem and has DIDO Capability for adding upto 256 DI/DOs/AI/AOs. The controller sends data with TLS encryption and the data on controller shall be encrypted. The controller shall be able to store data till it is received by the BMS room to avoid any data loss. The system shall have the following components :- (i) 63A, FP, Isolator, Complies to IEC/EN 60947-3- 2 Nos (ii) Contactor = or > 60A, FP AC-1 duty 230V 50/60Hz for 10 KVA- 2 Nos (iii) Mechanical interlock for LC1 D60- 1 No. (iv) On delay Timer 2C/O, 230V AC- 1 No. (v) Miniature circuit breaker ACTI 9, C60, 2 poles, 2A, C Curve - 2 Nos (vi) Polybloc 160A 1P - 2 Nos (vii) Miniature circuit breaker ACTI 9, C60, 2 poles, 2A, D Curve- 1 No. | ||||||
| 1.03(viii) AC Residual Current Circuit Breaker, 40A, 100mA- 1 No. (ix) Digital VAF Meter With RS 485 Modbus Port- 1 No. (x) Current transformer 40/5A Class 1 10VA- 3 Nos (xi) CT Shorting Links- 3 Nos (xii) Miniature circuit breaker ACTI 9, C60, 2 poles, 16A, C Curve- 6 Nos (xiii) Auxiliary contact, 1 OC- 6 Nos (ix) Multiclip distribution block- 1 No. (x) Miniature circuit breaker ACTI 9, C60, 2 poles, 4A, C Curve- 1 No. (xi) Universal Power Supply 24V DC 5A- 1 No. (xii) Miniature circuit breaker ACTI 9, C60H-DC, 500Vdc, 2A, 2 poles, C Curve- 1 No. (xiii) IMD Vigilohm IM20-H a positive safety 220/240V AC, 50H- 1 No. (xiv) Current transformer 50/5A class 3 for cable - 1 No. (xv) Insulation Fault detectors (12 channel)- 1 No. (xvi) Sensor Vigilohm TA30- 6 Nos (xvii) Miniature circuit breaker ACTI 9, C60, 2 poles, 16A, C Curve- 6 Nos (xviii) Auxiliary contact, 1 OC- 6 Nos (xix) Multiclip distribution block, 4P, 80A, 1 row- 1 No. (xx) Smart Link Modbus TCP/IP Communicating I/O Module- 1 No. (xxi) Field Controller with Bacnet, Modbus, DNP3.0, MBUS protocols- 1 No. | ||||||
| 1.04(xxii) Prefabricated Cables, Long: 870mm- 1 No. (xxiii) 10 KVA Isolation Transformer 3Phase, 415V AC- 1 No. (xxiv) Type Tested IEC 61439- 1&2 - 1 No. or equivalent. (xxv) A programmable controller unit or RTU based on 800MHz processor and 512MB RAM, should be included to connect the panel to building management system and should support Modbus DNP3, MBUS, Bacnet protocols (all mandatory and selectable). The controller shall have following type test certificates from any NABL approved lab (The certificates must bear the NABL logo on it). CISPR 22:2018, IEC 61000-4-2 ::2008, IEC 61000-4-3-2010, IEC 61000-4-42012, IEC 61000-4-5:2014 (Up to 2 KV), IEC 61000-4-6:2013, Power frequency IEC 61000-4-8. The controller shall be with suitable Digital Inputs / outputs and GPRS modem with 4G and fallback to 3G/2G, having QMI/MBIM/ or any other non-proprietary programming interface, based on Qualcomm/ Motorola processors. It shall connect to the centralized building management system for centralized operations. The controller shall send data with TLS encryption and the data on controller shall be encrypted. The controller shall be able to store data till it is received by the data center to avoid any data loss. Note:- Warranty for the Isoltaion Panel will be 2 yrs. | ||||||
| 2.00 | Supply, installation, testing and commissioning PVC insulated Copper Conductor (Sheathed), flexible cable, 1100 volts grade of size 4 core 10 Sq mm including taking out old un-serviceable cable of any type complete all as specified and directed by Engr-in-Charge. | 72 | RM | 450 ₹32,400 | 500 ₹36,000 | 400 ₹28,800 Lowest |
| 3.00 | Supply, installation, testing and commissioning PVC insulated Copper Conductor (Sheathed), flexible cable, 1100 volts grade of size 4 core 6 Sq mm including taking out old un-serviceable cable of any type complete all as specified and directed by Engr-in-Charge. | 67 | RM | 300 ₹20,100 | 300 ₹20,100 | 250 ₹16,750 Lowest |
Tender Value
₹25 L
EMD Value
₹50,000
Closing Date
13 Jun 2025, 6:00 pmClosed
GE E/M RR HOSPITAL DELHI CANTT-10
GE E/M RR HOSPITAL DELHI CANTT-10
REPAIR / REPLACEMENT OF ISOLATION PANEL AND ALLIED WORKS FOR ICU-I AND OTS AT AHRR UNDER GE E/M RR HOSPITAL DELHI CANTT-10
2025_MES_692815_4
GE/H-68/2024-25
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
GE E/M RR HOSPITAL DELHI CANTT-10
Please refer Tender documents.
10 documents required · 10 mandatory
₹500
GE E/M RR HOSPITAL DELHI CANTT-10
₹50,000
Yes
28 Aug 2025
23 May 2025
16 Jun 2025
23 May 2025
13 Jun 2025
30 May 2025
Amount
Supply and replacement of Medical Isolation Panel of rating 10 KVA for OT / ICU (critical area), medical grade as per specifications mentioned below including removing old unsv panel any type complete with elct connections etc :- (a) The panels shall be isolated panel system as per IEC 61439-1&2 only, having critical (isolated) and non-critical circuits. Both circuits shall be monitored on the building management system. The monitoring parameters shall include On/Off status, load monitoring and shall generate alarms if any critical parameters such as isolation is anomalous. The panel shall enable electrical shock protection: according the IEC 60364-7-710 standard the solution is in compliance with the group 2 location through isolation transformer and associated monitoring system. (b) The system shall be according the IEC standard, the switchgear is energy by 2 separate sourcing. (c) The “Main incomer supply” is coming from the UPS system. The “Safety incomer supply” is coming directly from the other part of the main low voltage switchgear. An automatic change over shall transfer the energy sourcing from the “Main incomer supply” to the “Safety incomer supply” in case of outages in less than 30ms.
(d) The Utility and Genset sourcing should limit by 15 seconds at least any potential outage to re- energise the Main and Safety incomers. The wiring shall be in compliance with the recommendations of IEC latest standard. It shall be possible for the protective devices to be controlled by the maintenance staff, without risk of direct contact. (e) The power and communication circuit routing shall be completely separate. Pulse energy meters with inbuilt CTs shall be provided with incomers to the panel for getting the energy consumption data for operation theatre. (f) The system should be able to locate faults in case of tripping Communication auxiliaries, for communicating ON/OFF/Trip status shall be provided with all MCBs, RCCBs, RCBOs used for protection. The status shall be available over Modbus TCP/IP network. Smartlink or equivalent shall be used for communicating the status of protection devices.
(g) The System Controller shall transfer all data to BMS/ Central Monitoring room, shall include suitable number of DI/DOs to control and monitor the panels. The controller has 01 Nos. isolated RS 485 communication port, 1 Nos. Ethernet communication port with 10BASE-T/ 100BASE-TX, support : Modbus master/slave, BACnet, MBUS and DNP 3.0 protocols, and shall conform to ANSI/ISA 12-12- 01, CSA C22.2 No 142, CSA C22.2 No 213, EN/IEC 61131-2:2007 standards, 230VAC with inbuild 4G modem and has DIDO Capability for adding upto 256 DI/DOs/AI/AOs. The controller sends data with TLS encryption and the data on controller shall be encrypted. The controller shall be able to store data till it is received by the BMS room to avoid any data loss. The system shall have the following components :- (i) 63A, FP, Isolator, Complies to IEC/EN 60947-3- 2 Nos (ii) Contactor = or > 60A, FP AC-1 duty 230V 50/60Hz for 10 KVA- 2 Nos (iii) Mechanical interlock for LC1 D60- 1 No. (iv) On delay Timer 2C/O, 230V AC- 1 No. (v) Miniature circuit breaker ACTI 9, C60, 2 poles, 2A, C Curve - 2 Nos (vi) Polybloc 160A 1P - 2 Nos (vii) Miniature circuit breaker ACTI 9, C60, 2 poles, 2A, D Curve- 1 No.
(viii) AC Residual Current Circuit Breaker, 40A, 100mA- 1 No. (ix) Digital VAF Meter With RS 485 Modbus Port- 1 No. (x) Current transformer 40/5A Class 1 10VA- 3 Nos (xi) CT Shorting Links- 3 Nos (xii) Miniature circuit breaker ACTI 9, C60, 2 poles, 16A, C Curve- 6 Nos (xiii) Auxiliary contact, 1 OC- 6 Nos (ix) Multiclip distribution block- 1 No. (x) Miniature circuit breaker ACTI 9, C60, 2 poles, 4A, C Curve- 1 No. (xi) Universal Power Supply 24V DC 5A- 1 No. (xii) Miniature circuit breaker ACTI 9, C60H-DC, 500Vdc, 2A, 2 poles, C Curve- 1 No. (xiii) IMD Vigilohm IM20-H a positive safety 220/240V AC, 50H- 1 No. (xiv) Current transformer 50/5A class 3 for cable - 1 No. (xv) Insulation Fault detectors (12 channel)- 1 No. (xvi) Sensor Vigilohm TA30- 6 Nos (xvii) Miniature circuit breaker ACTI 9, C60, 2 poles, 16A, C Curve- 6 Nos (xviii) Auxiliary contact, 1 OC- 6 Nos (xix) Multiclip distribution block, 4P, 80A, 1 row- 1 No. (xx) Smart Link Modbus TCP/IP Communicating I/O Module- 1 No. (xxi) Field Controller with Bacnet, Modbus, DNP3.0, MBUS protocols- 1 No.
Supply, installation, testing and commissioning PVC insulated Copper Conductor (Sheathed), flexible cable, 1100 volts grade of size 4 core 10 Sq mm including taking out old un-serviceable cable of any type complete all as specified and directed by Engr-in-Charge.
Supply, installation, testing and commissioning PVC insulated Copper Conductor (Sheathed), flexible cable, 1100 volts grade of size 4 core 6 Sq mm including taking out old un-serviceable cable of any type complete all as specified and directed by Engr-in-Charge.
Pall Associates (BID ID -3322441)
ISHWAR ENTERPRISES (BID ID -3319923)
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .