The Executive Engineer, PWD, Mahe
Public Works Department, Mahe. Near Sub Court, Mahe
Electrification to the newly constructed Mechanical Engineering Work shop at Indira Gandhi Polytechnic College, Mahe
2023_PWDC2_14552_1
73/EEM/23-24/29(23-24)
Open Tender
Electrical Works
Item Rate
120 days
Works at Mahe
Please refer Tender documents.
8 documents required · 8 mandatory
₹525
₹26,169
26 Mar 2024
13 Dec 2023
27 Dec 2023
13 Dec 2023
26 Dec 2023
13 Dec 2023
Amount
Code No. 1.21.2:-Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface / recess includingcutting the wall and making good the same in case of recessed conduit as required - 25mm
Code No. 1.22.7:- Supplying and fixing metal box of following sizes (nominal per size) on surface or inrecess with suitable size of phenoliclaminated sheet cover in front including painting etc.as required - 200 mm x 150 mm x 60 mm
Code No. 1.27.2:- Supplying and fixing following size / modules , GI box per alongwith modular base & cover plate for modular switches in recess etc. as required - 3 module (100mm x 75mm)
Code No.1.27.6:- Supplying and fixing following size / modules , GI box per alongwith modular base & cover plate for modular switches inrecess etc. as required - 12 module (125 mm x 125 mm)
Code No. 1.33:-Supplying and fixing 3 pin , 5 A ceiling rose on the existing per junction box / wooden block including connection etc asrequired
Code No. 1.14.2:- Wiring for circuit / submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor , single core cable in surface / recessed medium class PVC conduit as required - 2 X 2.5 sq.mm + 1 x 2.5 sq.mm earth
Code No. 1.14.3:- Wiring for circuit / submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor , single core cable in surface / recessed medium class PVC conduit as required - 2 X 4 sq.mm + 1 x 4 sq.mm earth wire
Code No. 1.14.9:- Wiring for circuit / submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor ,single core cable in surface / recessed medium class PVC conduit as required - 4 X 6 sq.mm + 2 x 6 sq.mm earth wire
Code No. 1.17.1:-Supplying and drawing following sizes of FRLS PVC insulated copper conductor single core cable in the existing surface / recessed steel / PVC conduit as required - 1 X 1.5
Code No. Non PSR:- Supplying and installation, testing and commissioning of surface/ recess mounting, vertical type 415 volts, TPN MCCB Distribution board of sheet steel, dust protected,duly phosphatised and powedered painted, inclusive of 200 amps tinned copper bus bar, 2 Nos of neutral link, earth eearth bar, din bar for mounting MCCB's detachable gland/knock out place of following ways (But without MCCB) a required make: Legrand , 6 way, TPN double door MCCB, DB, Vertical type including 6 mm dia rag bolts with nuts
Code No. 2.4.1:- Supplying and fixing following way , horizontal type three pole per and neutral , sheet steel , MCB distribution board , 415 V, on surface / recess , complete with tinned copper bus bar , neutral bus bar , earth bar , din bar, Interconnections , powder painted including earthing etc. as required (but without MCB / RCCB / Isolator ) 4way (4+12) , double door
Code No. 2.10.1:- Supplying and fixing 5 A to 32 A rating , 240/415 V, 10 kA, per "C" curve , miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections , testing and commissioning etc .as required. -Single Pole
Code No. Non PSR:- Supplying and fixing following rating, three pole 415 V miniature circuit breaker in the existing MCB DB complete with connection , testing and commisioning etc., as required 63 A Make : Legrand Polycab/Sncab
Code No. 1.24.1:- Supplying and fixing following modular switch / socket on the per existing modular plate & switch box including connections but excluding modular plate etc. as required - 5/6 A switch
Code No. 1.24.4:- Supplying and fixing following modular switch / socket on the per existing modular plate & switch box including connections but excluding modular plate etc. as required - 3 pin 5/6 A socket outlet
Code No. 1.24.3:- Supplying and fixing following modular switch / socket on the per existing modular plate & switch box including connections but excluding modular plate etc. as required - 15/16 A switch
Code No. 1227 :- Supply of AC Exhaust Fan 375mm (15'') Sweep (Light Duty)
Code No. 1207 :- Supply of 48W LED Street Light Fitting(Philips / Havells )
Code No.17.2.12:- Supply and fixing of wall mount bracket of 50 mm dia GI pipe per suitable for SVL / MH fittings with clamp , bolts and nuts as required
Code No. 17.2.11:- Fixing testing and commissioning of Sodium vapour / Mercury per vapour / Metal halide street light fittings on existing poles as required
Code No. 1.45:- Installation , testing and commissioning of ceiling fan , per including wiring the down rods of standard length (upto 30 cm) with 1.5 sq.mm FRLS PVC insulated , copper conductor , single core cable , including providing and fixing phenoliclaminated sheet cover on the fan box etc as required
Code No. 1.50.1:- Installation of exhaust fan in the existing opening , including per making good the damage , connection , testing ,commissioning etc. as required - Upto 450 mm sweep
Code No. Non PSR:- Supply and fixing of 20-24W LED tube light fitting Make Philips/Havells/Wipro
Code No. Non PSR: - Supplying of 3 1/2 x 95 Sqmm armoured aluminium UG cable 1.1 KV grade at site . Make : Polycab / Finolex /Havells.
Copde No. Non PSR:- Supplying of 4 x 50 sq.mm armoured aluminium UG cable 1-1 KV grade at site. Make Polycab /Finolex Havells.
Code No. 7.1.2:- Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 kV grade of following size direct in ground including excavation , sand cushioning, protective covering and refilling the trench etc.as required - above 35 sq.mm and upto 95 sq.mm
Code No. 7.7.2:- Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 kV grade of following size on wall surface as required - above 35 sq.mm and upto 95 sq.mm (clamped with 25 x3mm MS flat clamp)
Code No. 9.1.24:- Supplying and making end termination with brass compression per gland and aluminium lugs for following size of PVC insulatedand PVC sheathed / XLPE aluminium conductor cable of 1.1 kV grade as required - 31/2 X95 sq.mm (45 mm
Code No.9.1.36:- Supplying and making end termination with brass compression pergland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1kV grade as required - 4 X50 sq.mm (35 mm)
Code No. Non PSR: Supplying of energy efficient 5 star 1200 mm sweep AC ceilling fan complete with all accessories like down rod, canopy etc., with ,aking necessarry connection cable as requird etc. (Make : Orient/USHA/Crompton/ Havells/or equivalent)
Code No. 31.263.1:- Making earth pit of G.I. pipe for earthing in earth pit with 40mm dia. G.I. pipe medium class of length 3.05m perforated with 46 Nos of 12mm dia. holes, pipe lowered in bore holes of 150mm dia. and filled in with charcoal and salt in alternative layer of 300mm, the top of G.I. pipe shall be clamped. Earth pit shall be provided with 60cm dia precast ring with 60cm depth alround,covered with R.C.C. precast slab etc. as per I.E. standards.
Code No. 31.264.1A:- Supplying and fixing of copper wire 8 SWG (4 mm dia) for earthing arrangements including bolt and nuts etc., complete.
Code No. 2834:- Supply of 100 mm dia G.I.pipe (medium class)
Code No. 2.20:- Supplying and fixing 30 A, 415 V, TPN Industrial type socket per outlet, with 4 pole and earth , metal enclosed plug top alongwith 30A "C" curve, TPMCB< in sheet steel enclosure ,on surface or in recess , with chained metal cover for the socket out let and complete with connections , testing and commissioning ets as required
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .