Loading…
Loading…
Eligibility, documents, scope, Go/No-Go checksEligibility, required documents, scope of work and Go/No-Go checks for this tender, in one click.
Tender Value
₹70 L
EMD Value
₹1.4 L
Closing Date
14 Oct 2026, 3:00 pm4d left
Eligibility, documents, scope, Go/No-Go checksEligibility, required documents, scope of work and Go/No-Go checks for this tender, in one click.
Director IISER Pune
IISER Pune Dr Homi bhabha road Pashan Pune 411008
Replacement of old HVAC equipments of Guest House C wings at IISER Pune
2026_IISRP_928332_2
09/IISER/Pune/2026-27
Open Tender
Electrical Works
Works
180 days
IISER Pune
As per NIT
3 documents required · 3 mandatory
₹1,180
Director IISER Pune
₹1.4 L
8 Oct 2026
8 Oct 2026
15 Oct 2026
8 Oct 2026
14 Oct 2026
8 Oct 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | Cat (A) -Items to be supply and installation: Bidder Please note that, quoted rate are inclusive of tranportation, labour, royalties taxes etc. except GST. GST will be paid as Govt of India, rules and regulation. | - | - | - | - |
| 2 | VRF Capacity 12 HP
Supply, Installation, Testing & Commissioning of Modular type Variable Refrigerant Flow/Variable Refrigerant Volume air cooled Outdoor units suitable for cooling having 100% hermetically sealed inverter type twin Rotary/Scroll Compressor(s),microprocessor based Controller, top discharge type condensing unit(s), with R-410-A Refrigerant or equivalent, vibration Isolators with suitable foundation etc. complete as required. To have better efficiency condenser fan shall be capable to operate at different speed with respect to load. The unit shall deliver the rated capacity and in confirmation as per IS 18728:2024 and CPWD Specifications and work even at 50°C ambient temperature without tripping. The system shall be able to deliver 100% of the rated capacity upto 39 Degree Celcius.The unit shall be suitable to work on 400V +/- 10%, 3 Phase, 50Hz AC power supply. The unit shall be filled with first charge of the refrigerant and ready for use as required. The condenser should be coated with a hydrophilic film to prevent water accumulation on the surface of the heat exchanger, enhance water dispersion, and reduce the risk of degradation, thereby improving overall performance and durability. EER value at 100% load (at an outdoor ambient temperature of 35°C and an indoor temperature of 27°C (dry bulb) / 19°C wet bulb temp) for 12 HP VRF system (Single outdoor unit) shall be minimum 4.5
(Make- Carrier/Daikin/Toshiba/Hitachi/Mitsubishi) Warranty period -02 Years | 2 | Nos. | - | - |
| 3 | VRF Capacity 16 HP
Supply, Installation, Testing & Commissioning of Modular type Variable Refrigerant Flow/Variable Refrigerant Volume air cooled Outdoor units suitable for cooling having 100% hermetically sealed inverter type twin Rotary/Scroll Compressor(s), microprocessor based Controller, top discharge type condensing unit(s), with R-410-A Refrigerant or equivalent, vibration Isolators with suitable foundation etc. complete as required. To have better efficiency condenser fan shall be capable to operate at different speed with respect to load. The unit shall deliver the rated capacity and in confirmation as per IS 18728:2024 and CPWD Specifications and work even at 50°C ambient temperature without tripping. The system shall be able to deliver 100% of the rated capacity upto 39 Degree Celcius.The unit shall be suitable to work on 400V +/- 10%, 3 Phase, 50Hz AC power supply. The unit shall be filled with first charge of the refrigerant and ready for use as required. The condenser should be coated with a hydrophilic film to prevent water accumulation on the surface of the heat exchanger, enhance water dispersion, and reduce the risk of degradation, thereby improving overall performance and durability.EER value at 100% load (at an outdoor ambient temperature of 35°C and an indoor temperature of 27°C (dry bulb) / 19°C wet bulb temp) for 16 HP VRF system (Single outdoor unit) shall be minimum 4.1
(Make- Carrier/Daikin/Toshiba/Hitachi/Mitsubishi) Warranty period -02 Years | 2 | Nos. | - | - |
| 4 | VRF Capacity 20 HP
Supply, Installation, Testing & Commissioning of Modular type Variable Refrigerant Flow/Variable Refrigerant Volume air cooled Outdoor units suitable for cooling having 100% hermetically sealed inverter type twin Rotary/Scroll Compressor(s), microprocessor based Controller, top discharge type condensing unit(s), with R-410-A Refrigerant or equivalent, vibration Isolators with suitable foundation etc. complete as required. To have better efficiency condenser fan shall be capable to operate at different speed with respect to load. The unit shall deliver the rated capacity and in confirmation as per IS 18728:2024 and CPWD Specifications and work even at 50°C ambient temperature without tripping. The system shall be able to deliver 100% of the rated capacity upto 39 Degree Celcius.The unit shall be suitable to work on 400V +/- 10%, 3 Phase, 50Hz AC power supply. The unit shall be filled with first charge of the refrigerant and ready for use as required. The condenser should be coated with a hydrophilic film to prevent water accumulation on the surface of the heat exchanger, enhance water dispersion, and reduce the risk of degradation, thereby improving overall performance and durability. EER value at 100% load (at an outdoor ambient temperature of 35°C and an indoor temperature of 27°C (dry bulb) / 19°C wet bulb temp) for 20 HP VRF system (Single outdoor unit) shall be minimum 4.0 (Make- Carrier/Daikin/Toshiba/Hitachi/Mitsubishi) Warranty period -02 Years | 2 | Nos. | - | - |
| 5 | VRF Cassette indoor unit - 2.0 TR
Supply, Installation, Testing and Commissioning of following minimum capacity 4 way Cassette Type Indoor ceiling mounted unit equipped with synthetic washable media pre-filter, fan section with low noise fan / 7.4 DELHI SCHEDULE OF RATES (E&M) Volume-II 2025 82 dynamically balanced blower, multispeed motor, coil section with DX Copper coil, electronic expansion valve, outer cabinet, drain pump, grill, necessary supports, vibration Isolation, Corded remote control etc., suitable for operation on single phase 230 V ± 10%, 50Hz AC supply, complete, as required. The Indoor units must shut down upon receiving a singal from the BMS System/Fire Signals. The system shall be capable to adjust air flow as per room requirement in auto mode. The cooling capacity of indoor unit will be at air inlet conditions of 27 Degree C DB and 19 Degree C WB temperature. (Make will be same as of Outdoor) | 35 | Nos. | - | - |
| 6 | VRF Cassette indoor unit - 3.6 TR
Supply, Installation, Testing and Commissioning of following minimum capacity 4 way Cassette Type Indoor ceiling mounted unit equipped with synthetic washable media pre-filter, fan section with low noise fan / 7.4 DELHI SCHEDULE OF RATES (E&M) Volume-II 2025 82 dynamically balanced blower, multispeed motor, coil section with DX Copper coil, electronic expansion valve, outer cabinet, drain pump, grill, necessary supports, vibration Isolation, Corded remote control etc., suitable for operation on single phase 230 V ± 10%, 50Hz AC supply, complete, as required. The Indoor units must shut down upon receiving a singal from the BMS System/Fire Signals. The system shall be capable to adjust air flow as per room requirement in auto mode. The cooling capacity of indoor unit will be at air inlet conditions of 27 Degree C DB and 19 Degree C WB temperature. (Make will be same as of Outdoor) | 2 | Nos. | - | - |
| 7 | Supply, Installation, Testing and Commissioning of Y/T/Multi Joints. Joints shall be of same Original Equipment Manufacturer (OEM) make as of ODUs and IDUs.Branch joints (Y-joints/Refnet joints) as recommended by the manufacturer | 36 | Nos. | - | - |
| 8 | Supply, Installation, testing and commissioning including vaccumiazation and Nitrogen testing of following nominal sizes of soft/hard drawn copper refrigerant piping for VRV/VRF system, complete with fittings, with suitable adjustable ring type hanger supports, jointing/brazing including accessories, insulated with XPLE Class-O tubular insulation/with Class-O closed cell elastometric nitrile rubber tubular sleeves sections of 19 mm thick insulation as given below for Suction and Liquid lines, all accessories as per specifications etc. as required : ( Copper tube Make : Mandev/indigo/Mehta tubes) | - | - | - | - |
| 9 | 6.4 mm dia (OD) (Soft drawn) with tube thickness 1.2 mm | 50 | Mtr | - | - |
| 10 | 9.5 mm dia (OD) (Soft drawn) with tube thickness 1.2 mm | 250 | Mtr | - | - |
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 3.13 MB
Tenderdocumenst.pdf
Tender Documents • 23.02 MB
BOQ_976768.xls
BOQ • 0.31 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .