SITC of HVAC System work for Construction of Sub District Hospital at Makrana, Distt. Deedwan-Kuchaman.
2025_MEDIC_520907_1
NIT No.29/2025-26 EE M and H Div 2 Jaipur/
Open Tender
Electrical Works
Percentage
180 days
deedwana-Kuchaman
Please refer Tender documents.
4 documents required · 4 mandatory
₹2,000
RTGS/NEFT/Any other money Transfer System
₹5.3 L
16 Dec 2025
16 Dec 2025
31 Dec 2025
16 Dec 2025
30 Dec 2025
16 Dec 2025
A. Air washer comprising of 2nos Pre-Filters. First filter shall be 50mm thick Aluminium wiremesh filter & second filter shall be 50 mm thick MERV-8 synthetic media filter with efficiency 90 % down to 10 microns. Both filters to be placed over the common frame.
B. Humidification section comprising of Wet pads 200 mm thick impregnated cellulose paper media ( Celdec pads ) with 2 bend PVC eliminator. The End plates of Pad & Eliminator shall be in SS 304 construction. Also, the inner blank offs of Wet section shall be in SS304 construction.
C. Fan Section comprising of belt driven, DIDW Backward curved AMCA certified centrifugal fan with maximum air outlet velocity of 10m/s suitable for required cfm at 50 mm static pressure (Total static of the unit shall be verified by the OEM before the design & supply of the units). Fan & Motor should be mounted over Aluminium channel of suitable thickness and should be isolated from the unit's bottom panel by means of Spring isolators.
D. TEFC High efficiecny IE-3 class motors as required with pulley, belt , Guard
E. The unit shall be fabricated with frame work hollow extruded aluminium profile with 0.80 mm preplasticised GSS on outside and 0.80mm 275gsm plain GSS on inside complete with 25 mm thick CFC free PUF insulation of minimum 40 kg/cum density sandwiched in between inner and outer skins. Unit should have MS powder coated legs to give height to unit's base channel from the floor surface. SS-304 ( 18 g ) Sump, UPVC Internal piping, make up, drain & quick fill and drain connection, Butterfly/Gate valves for pumps, make up, drain & quick fill and drain connections of sump, 2 no. Vertical Pumps of suitable capacity to be placed inside the unit's housing (external pumps are not acceptable) ,Y strainers and necessary fittings, Concrete Blocks / M S stand, anti vibration pads etc.as required. All as per pre approved by Engineer in charge.
11000 CFM (26.0 per cfm)
17000 CFM (23.0 per cfm)
7500 to 15000 CFM
15000 to 25000 CFM
Supplying, installing, testing and balancing of double louvered of extruded Aluminium Powder coated supply/return air grills of various sizes, Each grill shall be with fixed horizontal front bar at 0 deflection and back adjustable vertical louvers, air distribution grid for straightening the air flow through the collar and register including fixing with steel screws etc. complete in all respect. All as per pre approved by Engineer in charge.
Supply air grill with key operated volume control damper
Return air grill without volume control damper
Supplying, installing, testing and balancing of extruded Aluminium powder coated Air Diffuser and complete with Flush, 20mm flanges with PVC/neoprene gasket, anti – smudge frame and removable inner core to facilitate the adjustable of air control damper, square/round/ rectangular as required.including fixing with steel screws etc. complete in all respect. All as per pre approved by Engineer in charge.
Supply Air Diffuser with Volume Control damper
Return Air Diffuser without Volume Control damper
Supply and fixing of acoustic lining of ducts with chemically cross link Oxide accetate foam open cell structure Acoustic Insulation with density 30 Kg / Sqm, UV protected and Class O Fire propperty Water Vapour absorption 0.002 gm / Sqcm, including cost of adhesive etc. complete in all respect. All as per pre approved by Engineer in charge. All as per pre approved by Engineer in charge.
15 mm thick
25 mm thick
Supply and fixing duct insulation with 50 mm thick Expanded Polystyrene Thermocol (ESP) sheet of density 24 kg/cu.m after applying two coats of cold setting adhesive (CPRX Compound) and binding sheet with chicken wire mesh and applying cement mortar plaster (1:4) including primer & painting (suitable for outdoor aplication) matching with building colour or as per direction of Engineer incharge as required. All as per pre approved by Engineer in charge.
Supply , Installation, Testing and Comissioning of Inverter type Air Cooled Hi Wall split type Air conditioners with latest star rating system as per BEE amended upto date complete with Indoor unit(IDU), Out door unit (ODU), surface / concealed copper Refrigerant piping with insulation (closed cell elastomeric nitrile rubber tubular pipe section) upto 3 Mtr (IDU to ODU), copper power cable upto 3.5 Mtr (IDU to ODU), R-32/R-410 Green Refrigerant, wireless Remote control, suitable for working between 230V +/- 10% with low & high voltage cutoff and 50 hz , single phase AC supply capable of performing cooling, dehumidification, air circulation of following capacity with Scroll / rotary compressor. All as per pre approved by Engineer in charge.
1.0 TR ISEER not less then 4.6
1.5 TR ISEER not less then 4.6
2.0 TR ISEER not less then 4.6
SITC of air cooled ducted split type air conditioning machine with each having a capacity and details as mentioned below suitable for operation on factory charged R-32/R-410A Green refrigerant comprising of Scroll /rotary type compressor hermatically sealed complete with automatic capacity, safety switches, lubrication system, Suitable capacity squirrel cage induction motor with class 'B' insulation suitable for operation on sigle / three phase supply, 50 Hz, A.C. supply for Blower motor, Necessary drive arrangement for blower motor, Matching Air cooled condenser with necessary fittings for refrigerant piping connections, necessary structural support for mounting condensers, Microprocessor based control panel complete with accessories, machine isolation / disconnect switch, valves and accessories to inter connect compressor and condender including pressure testing, vacuum. Necessary starters suitable for Indoor & outdoor unit complete with O/L , U/V, phase reversal protection, single phase preventors etc complete as required. All as per pre approved by Engineer in charge.
Supplying and drawing flexible / stranded bare copper conductor, PVC / XLPE insulated, overall aluminium mylar tape shielded ATC drain wire and outer PVC sheathed industrial Instrumentation (shielded)cables voltage grade 300/500 V as per BS /EN 50288-7 in existing surface or recessed PVC/ MS conduit/casing capping / Cable tray / Open Duct making connections, testing etc. as required. OEM Must have its own in house NABL lab setup for all testing facilities for cables. All as per pre approved by Engineer in charge.
Armoured
2 core x 1.5 Sq.mm
2 core x 2.5 Sq.mm
4 core x 2.5 Sq.mm
34.9 mm O.D., wall thinkness ≥ 1.4mm (insulation – 19 mm thick)
28.6 mm O.D., wall thinkness ≥ 1.2mm (insulation – 19 mm thick)
22.2 mm O.D., wall thinkness ≥ 1.0mm (insulation – 19 mm thick)
19.1 mm O.D., wall thinkness ≥ 1.0mm (insulation – 13 mm thick)
15.9 mm O.D., wall thinkness ≥ 0.8mm (insulation – 13 mm thick)
12.7 mm O.D., wall thinkness ≥ 0.8mm (insulation – 13 mm thick)
9.5 mm O.D., wall thinkness ≥ 0.8mm (insulation – 13 mm thick)
6.4 mm O.D., wall thinkness ≥ 0.8mm (insulation – 13 mm thick)
Providing & Fixing of IS : 4985 - 2000 Class -4 (10 Kgf / Sqcm) UPVC drain water piping with
fittings (IS:7834 & 10Kgf/sqcm) like elbow, socket, Tee, solvent cement jointing, support with MS hanger on ceiling or recessed in wall with chasing & plastering with 6 mm thick closed cell elastomeric nitrile rubber insulation including leakage testing etc. as required of following Nominal sizes. All as per pre approved by Engineer in charge.
BoQ_Ver4.0
Name of the Bidder/ Bidding Firm / Company :
PRICE SCHEDULE (This BOQ template must not be modified/replaced by the bidder and the same should be uploaded after filling the relevent columns, else the bidder is liable to be rejected for this tender. Bidders are allowed to enter the Bidder Name and Values only)
NUMBER #
Supply & fixing MS powder coated stand suitable for 1.0/1.5/ 2.0 Tr outdoor type of Split AC. All as per pre approved by Engineer in charge.
NON BSR
AIR HANDLING UNITS FOR OT VRV SYSTEM
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Tendernotice_1.pdf
PDF • 2.13 MB
Tendernotice_2.pdf
PDF • 7.44 MB
Tendernotice_3.pdf
PDF • 0.07 MB
Tendernotice_4.pdf
PDF • 2.69 MB
Tendernotice_5.pdf
PDF • 0.31 MB
BOQ_929355.xls
BOQ • 0.50 MB
RFP.pdf
Tender Documents • 5.54 MB
Annexure-A-BSR-2022.pdf
Tender Documents • 0.26 MB
TandC-for-Electrical-work-DLP-Annexure-B.pdf
Tender Documents • 0.24 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .