Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹125.2 CrAccepted-AOC | ₹125.2 Cr | L1 | Accepted-AOC Being the lowest tenderer L1 and reasonable |
| 2 | L2₹133.2 CrRejected-Finance | ₹133.2 Cr | L2 | Rejected-Finance Not being the lowest |
| 3 | L3₹133.4 CrRejected-Finance | ₹133.4 Cr | L3 | Rejected-Finance Not being the lowest |
| 4 | L4₹135.8 CrRejected-Finance | ₹135.8 Cr | L4 | Rejected-Finance Not being the lowest |
| 5 | L5₹141.5 CrRejected-Finance | ₹141.5 Cr | L5 | Rejected-Finance Not being the lowest |
Tender Value
₹135 Cr
EMD Value
₹15 L
Closing Date
24 Apr 2021, 6:00 pmClosed
Chief Engineer (Navy) Mumbai
HQ CE (Navy) Mumbai, 26 Assaye Buildings, SBS Road, Colaba, Mumbai-05
DEMOLITION OF BUILDING P51, 53, R, L, M and N AND PROVISION OF DEFICIENT TYPE II MARRIED ACCOMMODATION FOR DEFENCE CIVILIANS AT NCHC POWAI
2021_MES_417763_2
87820/E8
Open Tender
Civil Works
900 days
Powai
As per tender documents
7 documents required · 7 mandatory
₹3,000
GE (P) Bhandup
₹15 L
Yes
10 Jun 2021
31 Mar 2021
26 Apr 2021
31 Mar 2021
24 Apr 2021
10 Apr 2021
31 Mar 2021 - 6 Apr 2021
Amount
SCHEDULE "A" Part - I (BUILDING WORKS) Details of prepriced schedule is given in tender documents.
SCHEDULE "A" PART-II ( EARTH WORK AND SITE CLEARANCE) Details of prepriced Schedule is given in tender documents.
SCHEDULE "A" PART-III DEMOLITION Details of prepriced Schedule is given in tender documents.
SCHEDULE "A" PART-IV (INTERNAL WATER SUPPLY) Details of prepriced Schedule is given in tender documents.
SCHEDULE "A" PART-V (INTERNAL ELECTRIC SUPPLY) Details of prepriced Schedule is given in tender documents.
SCHEDULE "A" PART- VI (ROAD/PATH/CULVERT) Details of prepriced Schedule is given in tender documents.
SCHEDULE "A" PART- VII (MINOR BRIDGE) Details of prepriced Schedule is given in tender documents.
SCHEDULE "A" PART-VIII (SEWAGE DISPOSAL) Details of prepriced Schedule is given in tender documents.
SCHEDULE "A" PART-IX (AREA DRAINAGE) Details of prepriced Schedule is given in tender documents.
SCHEDULE "A" PART-X (EXTERNAL ELECTRIC SUPPLY) Details of prepriced Schedule is given in tender documents.
SCHEDULE "A" PART-XI (EXTERNAL WATER SUPPLY) Details of prepriced Schedule is given in tender documents.
SCHEDULE "A" PART-XII (SECURITY WALL) Details of prepriced Schedule is given in tender documents.
SCHEDULE "A" PART-XIII (STEEL GATE) Details of prepriced Schedule is given in tender documents.
SCHEDULE "A" PART-XIV (RAINWATER HARVESTING) Details of prepriced Schedule is given in tender documents.
SCHEDULE "A" PART-XV (FIRE PROTECTION) Details of prepriced Schedule is given in tender documents.
SCHEDULE "A" PART-XVI ( STAIRCASE PRESSURIZATION ) Details of prepriced Schedule is given in tender documents.
SCHEDULE "A" PART-XVII (ELEVATORS) Details of prepriced Schedule is given in tender documents.
SCHEDULE "A" PART-XVIII ( SPECIAL ITEM - TV & TELEPHONE CONDUITS ) Details of prepriced Schedule is given in tender documents.
SCHEDULE "A" PART-XIX (SPECIAL ITEM - GRANITE) Details of prepriced Schedule is given in tender documents.
SCHEDULE "A" PART-XX (SPECIAL ITEM- SOCKETS ) Details of prepriced Schedule is given in tender documents.
SCHEDULE "A" PART -XXI (MISCELLANIOUS ITEMS) Note:- This schedule is not pre-priced by MES and the pre-priced rate indicated as "Rs 0.00" under Col.' E ' signifies this fact only.
INTERNAL WATER SUPPLY S & F Hand shower (Health faucet) with 1 meter long easy flex tube in chrome finish and wall hook with NRV (Back flow preventer) complete all as specified and directed.
Supply & Fix Toilet Paper holder (Make: Jaquar) Chromium plated brass body (Product Code : AKP-CHR-35751P) complete all as specified and directed.
S & F 15 mm bore dia 2 way bib cock equipped with automizer nozzle and wall flange (Water saving type) complete all as specified and directed.
S & F 15 mm bore dia Sink cock with swinging spout (Wall Mounted Model) & equipped with automizer nozzle (Water saving type) complete all as specified and directed.
S & F 15 mm bore dia Basin tap 1/2'' with 200 mm extension body & equipped with automizer nozzle (Water saving type) complete all as specified and directed.
S & F Overhead shower 105mm dia Round Shape Single flow with air Effect ( ABS Body & Face Plate Chrome plated) with Rubit Cleaning system (Water saving type) complete all as specified and directed.
Supply & Fix Pressure relief valve (PRV) (a) 80mm dia
(b) 32mm dia
INTERNAL ELECTRIC SUPPLY S & F 20 W surface/wall mounted LED batten having high efficiency long life LED chips with luminous efficacy of > 100 lumen/W, independent isolated SMPS based constant current electronic LED driver with THD < 20%, surge voltage protection and other safety tests as per IS: 15885 (Part-2/Sec-13): 2012, polycarbonate diffuser, housed in powder coated white extruded aluminium channel housing and white coloured ABS end caps having input voltage 220- 240 V, input frequency 50- 60 Hz, PF > 0.95, including electrical connection with 3 core flexible Cu conductor cable of appropriate size from ceiling rose to the fixture complete all as specified and directed. Make: BAJAJ Cat-Part No. 112785 BCLAB 20W or equivalent model of Havells, Philips or Wipro
S & F 10 W surface/wall mounted LED batten having high efficiency long life LED chips with luminous efficacy of > 100 lumen/W, independent isolated SMPS based constant current electronic LED driver with THD < 20%, surge voltage protection and other safety tests as per IS: 15885 (Part-2/Sec-13): 2012, polycarbonate diffuser, housed in powder coated white extruded aluminium channel housing and white coloured ABS end caps having input voltage 220- 240 V, input frequency 50- 60 Hz, PF > 0.95, including electrical connection with 3 core flexible Cu conductor cable of appropriate size from ceiling rose to the fixture complete all as specified and directed. Make: BAJAJ Cat-Part No. 112407 BCLSB 10 WH or equivalent model of Havells, Philips or Wipro
S & F 9 W LED Lamp, 3 star rating, cool day light complete all as specified and directed. Make: Philips, Havells or Wipro
S & F 25 W LED street light having high efficiency long life LED module with SMD LED package mounted on MCPCB with high LED efficacy of ≥ 100 lumen/W, integral SMPS based constant current electronic LED driver with THD < 20%, surge voltage protection and other safety tests as per IS: 15885 (Part-2/Sec-13): 2012, IP 66 protection, high effiency polycarbonate cover with integrated lens housed in pressure die-cast aluminium alloy heat sink for effective thermal management, sturdiness, excellent corrosion resistance, separate optical and control gear compartment & top opening for easy maintenance, suitable for side entry, pole mounting with bracket arm OD 35 mm to 42 mm including necessary electrical connection to the fixture with 3 core flexible Cu conductor cable of appropriate size and 1.5 m long bracket, having 40 mm diameter light grade GI pipe, including GI clamps, nuts, bolts & washers with two coats of synthetic enemal paint over a coat of red oxide primer complete in all respect as specified and directed by engineer-in-charge. Make: BAJAJ Cat-Part No. BAJAJ BCLST 25W LED I LED I or equivalent model of Havells, Philips or Wipro
S & F BEE five star rated energy efficient high-speed ceiling fan having 1200 mm blade sweep, air-flow not less than 200 CMM, operating voltage 220-240 V and frequency 50 Hz, including a downroad of suitable size complete with electrical connection through 3 core PVC insulated copper conductor unarmoured cable of suitable size as specified and directed by engineer-in-charge. Make: Havells, Bajaj, Crompton, Usha
S & F engery efficient metalic exhaust fan having blade sweep 300 mm, air delivery not less than 6000 CMH, operating voltage 220-240 V and frequency 50 Hz, including electrical connection with 3 core flexible Cu conductor cable of appropriate size from ceiling rose to the fresh-air fan complete all as specified and directed. Make: Crompton Cat-Part No. EXHD300- 4-1 or equivalent model of Usha, Havells or BAJAJ
S & F engery efficient non-metalic fresh air fan having blade sweep 250 mm, air delivery not less than 860 CMH, operating voltage 220-240 V and frequency 50 Hz, including electrical connection with 3 core flexible Cu conductor cable of appropriate size from ceiling rose to the fresh-air fan complete all as specified and directed. Make: Crompton Cat-Part No. VENTILUS 10" or equivalent model of Usha, Havells or BAJAJ
Supply, installation, testing and commissioning of sandwich type (3L+N+PE) busbar trunking system complete with two runs of 50 mm X 6 mm aluminium earthing strip and accessories all as specified and directed by engineer-in-charge. Make: L & T, Schneider, Siemens The BBT shall conform to the following technical specifications: [A] GENERAL [i] The busbar trunking system (BTS), both feeder and plug-in, shall be of sandwich construction. All components and fittings (straight length, elbow, tee, flanged end, cable tap-off box and circuit breaker etc.) shall conform to IEC 61439-6:2012 or UL 857 and shall be procured from the OEM of BTS. The BTS shall have IP 66 protection for outdoor application and IP 54 protection for indoor application in accordance with IEC 60529: 1989. [ii] The rated operation voltage of BTS shall not be less than 1 kV. The neutral conductor shall have the same cross-sectional area as the phase conductor and the earth busbar shall be provided on both sides of the housing. [B] CERTIFICATE [i] The busbar , of full range and each rating, shall pass full type tests specified in IEC 61439-6-2012. The certificate shall be issued by an international independent testing authority, e.g. ASTA. KEMA. UL and ERDA etc. [ii] A product safety mark, e.g. KEMA-KEUR, ASTA DIAMOND, UL and ERDA, etc. shall be on the product offering a visual assurance of full product safety testing, factory inspection and ongoing surveillance under independent authority. [iii] The BTS shall have UBC seismic zone 5 compliance tested with busduct and plug-in box assembly by an internationally recognized earthquake research body, e.g. Asian Pacific Network of Centres for Earthquake Engineering Research (ANCER) as per IEEE 693- 2018. The OEM shall also furnish a certificate to confirm that the BTS assembly is capable of withstanding the additional vibration in shaft owing to air movements.
[C] SHORT-CIRCUIT RATINGS & TESTS [i] The entire BTS (busduct and plug-in box assembly) shall be capable of withstanding the short-circuit of electrical installation without undergoing any electrical, mechanical or thermal stress under fault condition at a service voltage of 1 kV at 50 Hz frequency. The minimum rated insulation voltage shall be 1 kV. [ii] The minimum certified short-circuit withstand capacity for 400 A rating shall be 25 kA for 1 sec. [iii] The minimum certified short-circuit withstand capacity for 800 A rating shall be 50 kA for 1 sec. [iv] The minimum certified short-circuit withstand capacity for 1250 A rating shall be 65 kA for 1 sec. [v] The minimum certified short-circuit withstand capacity for 2000 A rating shall be 80 kA for 1 sec. [D] HOUSING [i] The busbar trunking housing shall be constructed of 1.6 mm thick electro- galvanised steel and shall be provided with a suitable protective finish of epoxy paint. [ii] The busbar trunking housing shall be totally enclosed non-ventilated for protection against mechanical damage and dust accumulation and it shall be tested for its characteristics offering resistance against corrosion [iii] The totally enclosed housing shall be manufactured by the BTS OEM and modifications of busbar trunking to make it totally enclosed by housing other than the busbar trunking OEM shall be unacceptable without written consent of the OEM. [E] BUSBARS [i] The busbars shall be of aluminium with tin / silver plating at joint. [ii] There shall be no bolts passing through the busbars of the BBT. [iii] Each busbar shall be insulated with Class- F (155 ˚C) insulation. Epoxy insulation shall be unacceptable. [iv] The temperature rise at any point of busbar trunking enclosure shall not exceed 55 ˚C above the ambient temperature of 40 ˚C when operated at the rated current.
[F] JOINTS [i] The busbar trunking joint shall be of one-bolt type utilizing high strength steel bolt(s) and Belleville washers to maintain proper pressure over a large contact surface area. [ii] The bolt(s) shall be torque indicating and at earth potential. [iii] The bolt shall be of two-headed design to indicate proper torque has been applied and shall require only a standard long handle wrench to be properly activated. [iv] Access shall be required to only see one side of the busbar trunking to tighten joint bolts. [v] It shall be possible to remove any joint connection assembly to allow electrical isolation or physical removal of a busbar trunking length without disturbing adjacent busbar trunking lengths. [G] PLUG-IN OPENING [i] The connecting jaw of a plug-in unit shall plug directly onto the busbar and have full contact with busbar itself. Welded tab at plug-in busbar is unacceptable. [ii] All contact on joint and plug-in opening shall be of copper strip in order to avoid external force damage on busbar while plugging in or plugging out operation. [iii] On plug-in busbar trunking there shall be three dead front, hinged cover type plug-in opening on each side. [iv] All openings shall be usable simultaneously. Busbar trunking shall be installed in such a manner that plugs are side mounted to permit practical use of all plug-in openings. [v] It shall be possible to inspect the plug-in opening and busbars prior to the installation of plug-in units. [H] SUPPORT STRUCTURE [i] Support structure shall be provided as per OEM's recommendation. [ii] Indoor feeder and plug-in busbar trunking shall be approved for hanger spacing of up to 3 m for horizontally mounted run and 4.88 m for vertically mounted runs. Outdoor feeder busbar trunking shall be approved for spacing up to 1.5 m for horizontally or vertically mounted runs.
[I] VOLTAGE DROP [i] The voltage drop (sending end voltage minus receiving end voltage) specified shall be based on the busway operating at full rated current and stabilized operating temperature in [ii] The 3- Phase line to line voltage drop shall not exceed 3.4 V per 100 feet length at 40% power factor concentrated load which may exist during motor starting. [iii] The line to line voltage drop shall not exceed 4.1 V per 100 feet at the load power factor which produces the maximum voltage drop in the busway. [J] INSPECTION / SUPPORT OF INSTALLATION [i] The installation of BBT shall be executed by skilled professionals with minimum experience of 4 yrs. having sufficient installation base and pre-commissioning experience. [ii] The entire installation shall be directly supervised by the OEM. [iii] The OEM shall also furnish a commissioning report underlining satisfactory installation after the commissioning of BBT system.
800 A BBT (for Main Building Supply) 800 A Straight Run Feeder (IP 54 protection)
Flange End with Equilizer / Shorting Plate
Horizontal / Vertical Bend
Plug-in Point
Vertical Spring Hanger / Fix Hanger
Expansion Joint
Tinned Copper Braided Flexibles with Hardware- Nuts & Bolts
Adapter Box
400 A BBT (for Common Services / Utility) 400 A Straight Run Feeder (IP 54 protection)
Flange End with Equilizer / Shorting Plate
Horizontal / Vertical Bend
Plug-in Point
Vertical Spring Hanger / Fix Hanger
Expansion Joint
Tinned Copper Braided Flexibles with Hardware- Nuts & Bolts
Adapter Box
STANDARD PLUG-IN BOX / TAP-OFF UNIT WITH FP MCCB PIB / TOU with 32 A, 415 V, 25 kA, 50 Hz, FP MCCB
PIB / TOU with 63 A, 415 V, 25 kA, 50 Hz, FP MCCB
PIB / TOU with 100 A, 415 V, 25 kA, 50 Hz, FP MCCB
E.F.U. with 200 A, 415V, 36 kA, 50 Hz, FP MCCB
E.F.U. with 630 A, 415V, 50 kA, 50 Hz, draw-out type FP ACB
SUPPORTING STRUCTURE Horizontal Fixing Clips
S & F MCB for AC applications conforming to IS/IEC 60898-1-2002, having breaking capacity Icn = 10 kA, sliding bottom clamp, colour coded on/off indication on dolly, biconnect IP 20 protected lower terminals and sliding shutters, etc. complete as specified and directed by engineer-in-charge. Make:Legrand, Schneider, Siemens, ABB a) 6- 32 A, 230 V, 50 Hz SP MCB (c- curve)
(b) 6- 32 A, 230 V, 50 Hz SPN MCB (c- curve)
(c) 40- 63 A, 230 V, 50 Hz SPN MCB (c- curve)
Supply and installation of smart single phase meter with the following specifications: [i] AC single phase two wire, tamper proof, static meter of class 1.0, 240 V, 50 Hz, 10 A-60 A conforming to IS-16444 and relevent IEC standards with inbuilt Radio Frequency (RF) communication facility in cyanconnode or equivalent mesh netwok with default and on demand display, billing data generation facility, anti- tamper features, Microprocessor and LED/LCD based circuitry. [ii] Meter should support the following data : 30 min instantaneous data for voltage, current, power factor, power, cumulative energy, cumulative apparent energy and frequency, 30 load survey data for energy, monthly billing survey for cumulative energy and max demand. [iii] Meter should have connect / disconnect functionality operatble from preparied billing software. Make : Secure, L&T, Schneider
Supply and installation of Data Concentrator Unit (DCU) with IP-67 protection with the following specifications: [i] Data Concentrator Unit (DCU) compatible for remote Automatic Meter Reading (AMR) solution and capable of communicating with te static energy meter in the corresponding frequency band and with the data server through GPRS and shall have minimum data transfer rate of 9600 bps, internal memory to store data of upto 200 modules. Make : Secure, L&T, Schneider
Note: The smart meters shall be configured and customised according to the central smart meter system software and server program functioning in the station at the time of commissioning, The rate quoted are deemed to be included.
ROAD/ FOOT PATH M & L for providing and laying dry lean concrete (DLC) over a prepared subgrade with coarse and fine aggregate confirming to IS:383, size of aggregate not exc 40 mm (grading and other parameters as per table 600-2 of MORTH, IRC SP : 49 Specification), of design mix, minimum cement content shall not less than 250kg/ Cum mixed in batching plant, transported to site laid with sensor paver including spreading and compacted by using 8 to 10 tones vibratory roller including necessary formwork finishing etc complete all as specified and directed by Engineer-in-Charge. (Average Thickness 100mm)
Supply Only Non Circular Synthetic Fibre reinforcement @ 0.25% weight of cement complete all as specified and directed by Engineer-in-Charge.
MINOR BRIDGE M & L for RCC- M-35 (Design Mix) using 20mm graded stone aggregate for Footing & Plinth Beam Including rafts as mass concrete complete all as specified and directed by Engineer-in-Charge.
M & L for RCC- M-35 (Design Mix) using 20mm graded stone aggregate for Column & Rcc Wall complete all as specified and directed complete all as specified and directed by Engineer-in-Charge.
M & L for RCC- M-35 (Design Mix) using 20mm graded stone aggregate for Slab & Landing complete all as specified and directed by Engineer-in-Charge.
Providing and fixing in position Strip Seal Type Expansion Joint (for movement of 50mm) as per detailed drawing MORTH specification. The rate is inclusive of supplying, fixing with contractor's own materials, equipments, machineries, labour, transport, testing, bolts, socket tubes, neoprene sheet/cap etc. complete. The rate is finished item complete and will be paid after fixing in all respect.The Contractor shall procure Strip Seal Expansion Joint, confirming to relevant MORTH specification from reputed manufactures of Strip Seal Expansion Joint with prior approval complete all as specified and directed by Engineer-in-Charge.
Providing and fixing 'W' type safety barrier using M.S. iron channel 150mm x 75m x 5mm size erected at 2.0 Mt. center to center and providing 'W' shaped galvanised steel sheet guard rail 3mm thick for crash barrier in single row as per detailed drawing with fabrication and installation charges including providing foundation block of size 0.60 x 0.60 x 0.75 Mt. in C.C. 1:2:4 and oil painting two coats with one coat of red oxide etc. complete all as specified and directed by Engineer-in-Charge.
Providing and casting in situ controlled cement concrete M 40 for average 75 mm. thick wearing coat laid as directed including tamping vibrating finishing curing and filling in joints with bitumen complete all as specified and directed by Engineer-in-Charge.
S & F 6 mm tar paper bearing complete all as specified and directed by Engineer-in-Charge.
SEWAGE DISPOSAL M & L For RCC- M-35(Design Mix) using 20mm graded aggregate for Raft Foundation, RCC Wall, Slabs complete all as specified and directed by Engineer-in-Charge.
S & F 150mm Wide PVC Water Bar complete all as specified and directed by Engineer-in-Charge.
SEWAGE TREATMENT PLANT (MBBR PACKAGED TYPE STP) Design, supplying, installing, testing & commissioning of Sewage Treatment Plant 300 KLD PACKAGE STP WITH ANOXIC & UF (excluding excavation, back filling & disposal of surplus earth Civil construction work) for the following duty: Raw Sewage (Inlet) Parameters Daily average flow - 300 Cum / Day pH - 6.5 – 8.5 BOD5 - 250 – 300 Mg/L COD - 400 – 500 Mg/L Total Suspended Solids -150 Mg/L Oil & Grease - 20 Mg / L Tempearture : 25 to 30 Deg C Total Nitrogen -45 Mg/L Ammonical Nitrogen - 10 Mg / L Effuluent Discharge Standard After Tertiary Treatment pH - 6.5 – 8.0 BOD5 - 5 Mg/L S. Solids - 10 Mg/L COD - 30 Mg/L Oil & Grease - 10 Mg/L Tempearture : 25 to 30 Deg C Total Nitrogen -10 Mg/L Ammonical Nitrogen - 5 Mg / L S. Solids after UF- 2 Mg/L
Sewage treatment plant shall include the following items: Wet-Well submersible pump -7.0 m3/hr -12 mt head (2 Working + 1stand by) with all accessaries MAKE -KSB /GRUNDFOS /KIRLOSKAR/ WILO
Primary Treatment System Supply, installation, testing & commissioning of 1 Nos SS-304 Perforated, Screens with suitable lifting arrangement (size 1000 mm wide x 1500 mm hight x 3.5 mm thick & 10mm Openings ) to be fitted within Bar Screen Chamber
Supply, installation, testing & commissioing of Manual overflow type Oil Skimmer within Oil & Grease Chamber
Secondary Treatment System Raw Sewage Trabsfer Pump (Eq. Tank to MBBR Tank) : Supply, installation, testing & commissioning of non clogging type pumps capable of handling solids upto 30 mm having CI casing & impeller complete with all accessories, motor of required capacity. Delivery header with isolation valve, pressure gauge on delivery line with isolation cock, level controller (with wiring) to control the level of sump automatically. Pumps Capacity :7 m3/hr at 10 Mtr Head. Make: (Johnson / KSB / Grundfos/Wilo)Qty :2 Working +1 Standby
Supply ,Installation ,Testing & Commissioning of Indion 150, Prefabricated 150 KLD MSEP x2nos sewage treatment plant Mild steelanticorrosive epoxy coated Tank Design of MBBR Tank comprising of in built compartments of Entry zone & Aeration zones 1& 2 (2 Nos) all required valves piping.SIZE - 9.41X2.13 X2.2 MT Make :IONEXCHANGE /Thermax
Twin lobe rotary air blowers capable of delivering 210.0 m3/hr. of free air at 0.37kg/cm2. driven through “V” belt or directly coupled through flexible coupling to a TEFCmotor of suitable HP@1500 rpm Suitable for 415 ± 10% volts, 3 phase, 50 cycles A/C supply (1W+1SB). (Blower Make: IONEXCHANGE /A ONE BLOWER /Everest ) Qty : 2 Working +1 Standby
Air piping shall comprise of pipes droppers/ laterals with M S (epoxy coated) Header complete with all fittings such as tees, crosses, plugs, sockets, elbows, reducers, supports & clamps, puddle flanges etc cutting chases & making good.
Air dispersion system shall be provided for Eq tank & Aeration Tank with fine & coarse bubblers of EDI USA Make IONEXCHANGE /THERMAX UPVC with EPDM : Air Grid & Diffuser System-16 nos MS Epoxy : Non Submerged Air Piping
Supply ,Installation ,Testing & Commissioning of Indion 150- Prefabricated 150 KLD MSEP sewage treatment plant with MBBR Tank comprising of in built compartments of (2 Nos),Lamella settling zone with FRP Plates and chlorination Zone for disinfaction with all required valves piping. Make :IONEXCHANGE /Thermax
Supplying, installing, testing and commissioning of Sodium Hypochlorite dosing system consisting of one HDPE tank of 100 litres capacity.A positive displacement diphragm dosing pump having variable flowrate of 0-6 lph. The motor shall be suitable for operation at 240 V / single phase /50 Hz. Supply. The pump shall be supplied complete with necessary polypropylene piping, valves, strainers, low level switch and injection fittings. The pump shall be speed & stroke control Make :Asia LMI / ION EXCHANGE /MILTON ROY
ANOXIC SYSTEM WITH ANOXIC MIXER WITH RECIRCULATION PUMP - Supplying, installing, testing and commissioning of anoxic mixer with recirculation pump 1w + 1S, ANOXIC RECIRCULATION PUMP OF 22M3/HR & ANOXIC SUBMERGED MIXER SYSTEM-1NO . Make :Ion Exchange/Thermax
ANOXIC SYSTEM WITH ANOXIC TANK MSEP WITH ANTICORROSIVE PAINT Supplying, installing, testing and commissioning of anoxic system with Anoxic tank MSEP with anticorrosive paint Make :Ion Exchange/Thermax
Tertiary System Supplying, installing, testing & commissioning of Horizontal centrifugal filter feed water pumps CI Head & Base, SS 304 Impeller along with motor, pressure gauge with isolation cock, Isolation valve, NRV on delivery line. Isolation valve, strainer at suction. Mechanical seal, suitable vibration elimination pads of approved design, drain pipe with valve for the pump. The pump shall be suitable for 415±10% volts 3 phase AC supply (solid handling size for this pump shall be – 5 mm). Pumps Make: (Johnson / Kirloskar / Grundfos/Wilo) Capacity : 13.0 m3/Hr at 35 Mtrs (1 Set =1 Working+1 Standby)
Multigrade Sand Filter :Supplying, installing, testing and commissioning of MS vessel filter (Dia 1000 mm x 1875 mm HOS). Filter shall be suitable for test pressure of 5.0 kg / cm2 and Working Pressure of 3.5 kg/cm2 shall include media(Pebbles,Sand, Silex, Fine Sand, Fine Silex), standard fittings like pressure gauges, sampling cock, backwash, including frontal piping and,valves. (Shell Thk min 4.0 mm & Dishend Thk min 4.0mm) Make :Ion Exchange /Thermax
Activated Carbon Filter : Supplying, installing, testing and commissioning of MSEP vessel filter (Dia 1600 mm x 1875 mm HOS). Filter shall be suitable for test pressure of 5.0 kg / cm2 and Working Pressure of 3.5 kg/cm2 shall include media(Activated Carbon with supporting Media ), standard fittings like pressure gauges, sampling cock, backwash, including frontal piping and,valves. (Shell Thk min 5.0 mm & Dishend Thk min 6.0mm) Make :Ion Exchange/Thermax
ULTRAFILTRATION SYSTEM : Supplying, installing, testing and commissioning of ULTRAFILTRATION SYSTEM -IONEXCHANGE MEMBRANE -SIZE 10 INCH DIA WITH 5.0 M3/HR FLOW RATE WITH TOTAL 3NOS SKID TO PROVIDE 300 KLD TREATED WATER . Make :Ion Exchange/Thermax
Supplying, installing, testing & commissioning of Horizontal centrifugal ultrafiltration feed water pumps CI Head & Base, SS 304 Impeller along with motor, pressure gauge with isolation cock, Isolation valve, NRV on delivery line. Isolation valve, strainer at suction. Mechanical seal, suitable vibration elimination pads of approved design, drain pipe with valve for the pump. The pump shall be suitable for 415±10% volts 3 phase AC supply (solid handling size for this pump shall be – 5 mm). Pumps Make: (Johnson / Kirloskar / Grundfos/Wilo) Capacity : 13.0 m3/Hr at 25 Mtrs (1 Set =1 Working+1 Standby)
ULTRAFILTRATION SYSTEM :PLC PANEL & PIPING WITHCABLING
Sludge Dewatering System Supplying, installing, testing and commissioning of Filter Press Feed Screw Pumps, 1.0 m3/Hr at 60 mtr, with valves, N.R.V. etc. Make: (ROTO/Equivalent)
Supplying, installation, testing & commissioning of hydraulic type filter press Capacity : less then 55 Kgs/ Day M.O.C. plates : PPE Filter cloth : Polyester / PPE / Cotton. Make :Universal /Precision/Equivalent
Control Panel for Sewage Treatment Plant Supply ,Installation ,Installation & Commissioning of Common control panel and Cabling for all electrical items like sewage transfer pumps, air blowers filter feed pumps, sludge removal pump as well as dosing system
Inter Connecting Pipe Work within Battery Limit : For Sewage ,Treated water and tank overflow/backwash pipe line with valves,Fittings and acessories.
PART I Manning and operation of sewage treatment plant in three shits 6000 to 1400 hours, 1400 to 2200 hes & 2200 to 0600 hours having ane FGM (skilled) and one mate (semi skilled) in each shift of plant of capacity 300 KLD with MBBR package type STP complete instalation including pumping of treated water to building OH tanks for flushing purpose complete all as specified and directed
(a) 11 months after completion of first year
(b) 11 months after completion of second year
(c) 11 months after completion of third year
(d) 11 months after completion of fourth year
(e) 11 months after completion of fifth year
(f) 05 months after completion of sixth year
Equipments a) wet well submersible pumps -2 working and 01 standby (b) Raw sewage transfer pumpe - 02 working and stanby (c) Air blower 02 working and 01 standby (d) Sodum hypocloride dosing system with suitable diapham pump. (e) Recirculation pumps - 01 working and 01 standby (f) Pump sets 01 working and Hot standby (Tertiary treatment) (g) Ultra filtration feed pump- 01 working and 01 standty (h) Sludge dewatering filter press feed screw pump - 01 working and 01 standby (i) Hydraulic type filter press of capacity 55 Kg per day - 01 working (j) Control panels for STP plant (k) MBBR of aeration tanks 02 nos (l) Lamella clarification - 02 nos (m) Activated carbon filter - 01No (n) Multigrade Filter 01 No Activities (a) Cleaning of entire plant room & equipments daily. (b) Overhauling / greasing & replacement of pump gland packings monthly and as and when required. (c) Filling of overhead tanks with treated water for high rise building G+26 (3 towers) by operating distribution valve & overhead tank by deploying required manpower to ensure sufficient STP treated water is made available round the clock to the blds Note for the item.no 01 (i) All chemicals required for addition in the STP plant will be measured and paid separately as supply only under Sch A Part Il (ii) Testing of water sample shall be carried out by the contractor from govt approved lab/ registered lab/NABL certified lab for BOD five days), PH, TDS & turbidity and kept on record on weekly basis (iii) Frequency of test (a) BOD Five days) twice a month (b) PH, TDS, turbidity, free chlorine - Daily (iv) Non compliance of testing of water samples will invite penalty at triple the rate of testing charges from govt approved / lab registered lab / NABL.certified.lab. (v) the electricity and water required for running of STP will be provided free of cost by the department.
Sch A PART II Supply only sodium hypochloride solution of 06% concentration in suitable non corrosive cans (The chemical will be supplied as and when required and demanded by E-in-Charge and not in bulk to avoid loss of chlorine in the solution considering its shelf life)
Sch A PART III Annual comprehensive Maintenance of 300 KLD STP plant of G+26 floor three towers) complete by deploying qualified man power and material as required with the following (i) Regular Oiling of All machinery and moving parts (ii) Regular Greasing of All machinery and moving parts (iii) Carrying out regular preventative maintainence of all electrical panels and their parts and Repairs / replacement of electrical worn out parts if needed. (iv) Toping up of filter media as and when required or as per manufacturers recommendations (v) Toping up / changing of activated carbon as and when required or as per manufacturers recommendations (vi) Changing of ultra filtration membrane as and when required or as per manufacturers recommendations (vii) Carrying out Daily, weekly, monthly quarterly, half yearly and Yearly maintenance as per manufacturers recommendations ( viii) Defective material produced after repairs / replacement of worn out or defective parts will be departments property and shall be deposited to E/M store yard. Note-i) Non functioning of STP due to any problem / due to non functioning of machinery or defect in plant will invite penalty at Rs 15000 per day. ii) Cost of replacement of Filter media, activated carbon and ultra filteration membrane as and when required or as per manufacturers recommendations is inclusive of rate quoted for AMC. (iii) The dry sludge sewage cakes shall be removed from site by the contractor in consultation with Garrison Engineer and deposit wherever directed, Cost of the same shall be included in Rate quoted for the item.
1st year after expiry of defect liability period
2nd year after expiry of defect liability period
3rd year after expiry of defect liability period
AREA DRAINAGE S & F medium duty rectangular manhole cover of grade MD-10 as per IS-12592 (470mmx450mm) complete all as specified and directed by Engineer-in-Charge.
M & L for Flyash AAC Blocks (600 x 200 x 100 -300 mm BIS Certified Grade-1 complete all as specified complete all as specified and directed by Engineer-in-Charge.
EXTERNAL WATER SUPPLY M & L for ductile iron pipe (K9 class) spigot & socketd, centrifugally cast confirming to IS 8329-2000 in any length laid in trenches complete suitable for rubber tyton joints as specified and directed by the engineer-in-charge. A) 200 mm NB
B) 150 mm NB
C) 100 mm NB
M & L for ductile iron bends, tapers, tee pieces (single & double branch) any type and angle/radius and straight connecting pieces but all ends flanged complete as specified and directed by the engineer-in-charge.
Supply, installation, testing and commissioning of normex ball foot valve, with flange drilling standard end connection and necessary accessories complete as specified and directed by the engineer-in-charge. A) 200 mm NB
B) 100 mm NB
Supply, installation, testing and commissioning of end-suction & top-discharge, non-self-priming, single-stage, centrifugal volute type pump having cast iron casing, enclosed type dynamically balanced phosphor-bronze/SS impeller, high tensile steel shaft, carbon steel stuffing box (sealed by mechanical seal), deep groove ball bearings, TEFC squirrel cage induction motor having IE- 3 efficiency, conforming to IS: 12615- 2018 at 2900 RPM speed star/delta starter panel, base plate, mounting channel frame, accessories and fittings, viz. mechanical seal, pressure gauges, thermometers, drains, coupling, coupling guard, vibration isolation arrangement by means of spring/rubber type mounting suitable for operation on 3- Phase, 415 V ± 10%, 50 Hz AC supply all complete with suitable PCC / RCC foundation as per manufacturer's recommendation as specified and directed by engineer-in-charge. A) Horizontal End Suction Long Coupled type pump with insulation suitable for 950 LPM water flow rate at 120 m head.
B) Horizontal End Suction Long Coupled type pump with insulation suitable for 400 LPM water flow rate at 120 m head.
Supply, installation, testing and commissioning of factory made, CPRI type tested, indoor cubical compartmental type DOMESTIC WATER SUPPLY PANEL of suitable size, conforming to IEC 61439-1 & 2 and IEC 61641, having both sides openable with hinged double doors and locking arrangement, IP 43 protection made out of 2.0 mm thick mild steel CRCA sheet, supported and fixed on structural frame of angle iron of suitable size, including earthing stud, labelling, painting to all internal & external exposed steel surfaces with powder coating paint (7 tank process), duly fixed in ground with PCC foundation (1:2:4) type B1, with danger notice plate of 1.6 mm thick mild steel vitreous enamelled (white) with letters, figures and conventional skull and bones in signal red colour suitable for 3- Phase, 4 Wire system, 500 V grade with necessary wiring, PVC sheathed stranded copper conductor of appropriate length and size, including fixing lugs, bolts, screws, etc. complete as specified and directed by engineer-in-charge. BUSBAR CHAMBER[i] 01 Set (3L + N) of copper busbar of rated capacity 320 A, covered with PVC insulated sleeves including insulator, nuts, bolts, etc. with complete connection INCOMING [i] 200 A, 415 V, Ics = 100% Icu = 25 kA, 50 Hz FP MCCB, conforming to IEC 60947-2, having microprocessor based trip unit, adjustable overload setting (0.7 - 1 X In), adjustable short-circuit setting (5 - 10 X Ir), adjustable neutral protection (N, N/2, OFF), front indication LEDs (Ready, Overload and pre-alarm & Overload), etc.- 01 Nos. [ii] Cl 1.0 multi-function meter capable of measuring V, A, F, PF, W/VA, Wh/VAh, Runhrs. Onhrs & interupts- 01 Nos. [iii] LED phase indicators (Red, Yellow, Blue)- 01 Set
Supply, installation, testing and commissioning of factory made, CPRI type tested, indoor cubical compartmental type FLUSHING WATER SUPPLY PANEL of suitable size, conforming to IEC 61439-1 & 2 and IEC 61641, having both sides openable with hinged double doors and locking arrangement, IP 43 protection made out of 2.0 mm thick mild steel CRCA sheet, supported and fixed on structural frame of angle iron of suitable size, including earthing stud, labelling, painting to all internal & external exposed steel surfaces with powder coating paint (7 tank process), duly fixed in ground with PCC foundation (1:2:4) type B1, with danger notice plate of 1.6 mm thick mild steel vitreous enamelled (white) with letters, figures and conventional skull and bones in signal red colour suitable for 3- Phase, 4 Wire system, 500 V grade with necessary wiring, PVC sheathed stranded copper conductor of appropriate length and size, including fixing lugs, bolts, screws, etc. complete as specified and directed by engineer-in-charge. Make: L & T, Schneider, Siemens, ABB The FLUSHING WATER SUPPLY PANEL shall comprise of the following: BUSBAR CHAMBER[i] 01 Set (3L + N) of copper busbar of rated capacity 200 A, covered with PVC insulated sleeves including insulator, nuts, bolts, etc. with complete connection INCOMING [i] 100 A, 415 V, Ics = 100% Icu = 25 kA, 50 Hz FP MCCB, conforming to IEC 60947-2, having microprocessor based trip unit, adjustable overload setting (0.7 - 1 X In), adjustable short-circuit setting (5 - 10 X Ir), adjustable neutral protection (N, N/2, OFF), front indication LEDs (Ready, Overload and pre-alarm & Overload), etc.- 01 Nos. [ii] Cl 1.0 multi-function meter capable of measuring V, A, F, PF, W/VA, Wh/VAh, Runhrs. Onhrs & interupts- 01 Nos. [iii] LED phase indicators (Red, Yellow, Blue)- 01 Set
M & L for earthing complete with GI earth plate electrode of 60 cm x 60 cm x 6 mm size, buried directly in ground (earth pit not less than 2.25 m deep below ground level) with top edge of the plate not less than 1.5 m below normal ground level, connected to GI strip of size 32x6 mm as earth lead, by means of bolts, buts, check nuts and washers of galvanised iron or steel, galvanized iron pipe of 40 mm diameter, connected to earthing test point, all as shown in electrical plate No. 5 connected to earthing test point all as specified or indicated including testing on completion and including excavation, earthwork, PCC earth pit of dimensions 550 mm X 550 mm (outer) and 300 mm X 300 mm (inner) and 250 mm deep, with a 10 mm thick CI cover, hinged to CI frame on ground level, GI watering pipe, funnel, etc. as all specified and directed.
M & L for ISI marked 1.1 kV grade copper conductor, XLPE insulated unarmoured cables, conforming to IS: 7098 (Part 1)- 1988 having stranded aluminium compact shaped conductor as per Cl. 2, IS: 8130- 1984, PVC inner sheath, single armouring of galvanized steel strip/wire and PVC Type ST- 2 outer sheath conforming to IS: 5831- 1984, including termination complete as specified and directed. a) 3 core 25 SQ MM (for Domestic Water Supply Pump)
b) 3 core 4 SQ MM (for Flushing Water Supply Pump)
Supply, installation and testing of Electromagnetic Water Flow Meter of size 150 mm bore dia, both ends flanged mounted In-Line Horizontal, full bore with PTFE line Tube SS 316 Seam suitable for operating pressure upto 10 kg/ cm² and flow range upto 1600 LPM with SS 316 electrodes, suitable coil with Carbon steel coil housing complete housed in a Aluminium Die Cast Weather Proof IP-65 enclosure along with Integral Flow Transmitter with LCD display and push button for working on 230 Volts, 50 Hz, Single Phase AC supply complete all as specified and as directed.
M & L for construction of brick masonry valve chamber of size 90 cm x 90 cm x 90 cm (internal dimensions) with one brick thick wall in CM (1:4) on 100 mm thick PCC (1:4:8) type D2 using 40 mm graded broken aggregate as in foundation lean concrete, incl. PCC (1:3:6) type C1(using 20 mm graded stone aggregate) as in bedding & coping & 10 mm thick cement plaster in CM (1:4) internally & externally upto 15 cm below ground level. Fixing 40 mm x 40 mm x 6 mm angle iron frame all round the chamber with 04 nos of holdfasts 150 mm long made out of 40 mm x 6 mm flat iron embedded in PCC block (1:2:4) type B1 of size 250 mm x 200 mm x 15o mm incl. provision of hinges welded with cover of MS sheet 3 mm thick, MS handle of of suitable size welded with MS cover & suitable locking arrangement incl. padlock & applying two coats of synthetic enamel paint over a coat of red oxide primer incl. necessary excavation & earth work in soft/loose soil complete all as specified and directed.
EXTERNAL ELECTRIFICATION S & F HT cable route indicator duly painted with two coats of grey colour synthetic enamel paint two over one coat of red oxide primer, oval shape of size 200 mm X 150 mm X 6 mm thick cast iron disc with letters HT 11 kV embossed and fixed on 25 mm x 25 mm x 5mm thick MS angle for 50 mm long including necessary PCC in 1:3:6 type C1 cement concrete 20 mm aggregate and 15 mm thick, plastering all around below ground level of size 300 mm X 300 mm X 250 mm embedded in PCC block complete as specified and directed by the engineer-in-charge.
Supply, installation, testing and commissioning of dry-type cast resin 11 kV class, 11 kV / 0.433 kV step-down, 3-Ph distribution transformer conforming to IS 11171: 1985 and suitable for indoor use with class F thermal insulation, MV windings encapsulated in cast resin, pre-impregnated LV windings, natural air cooling system (AN type), core and frame covered with protective coating & anti-corrosion surface treatment and having IP31 metal enclosure (the bottom shall be IP21) with 2 lifting lugs for transformer and enclosure assembly, 1 earthing point on enclosure, access to HV tapping by removing a bolted panel, etc. complete as specified and directed by the engineer-in-charge. Make: Schneider, Siemens, Voltamp, BHEL The transformer shall conform to following technical specifications. [i] Manufacturing Standards: IS 11171: 1985 [ii] BLANK [iii] Installation: IP 31 (with enclosure), C2 corrosivity class, medium durability (in compliance with ISO 12944-6) [iv] Winding Material: Cu [v] Phases: 3- Phase [vi] Cooling System: AN (natural air) [vii] Maximum ambient temperature / altitude: 40 ºC at any time / 1000 m [viii] Thermal class insulation: Class F, conforming to IEC 60085 [ix] Rated frequency: 50 Hz [x] Impedance Voltage Uk: 4 to 6% [xi] Vector group: Dyn11 [xii] Rated HV insulation: 12 kV [xiii] HV tapping: Off-circuit tapping links: 5 positions, ±2.5% [ixv] HV terminals: Standard HV connections
[xv] Rated LV insulation: 1.1 kV [xvi] LV terminal: Standard LV connections [xvii] Thermal protection: AN cooling system with 6 PTC sensors + thermal relay a) 500 kVA indoor transformer (one for each block)
b) 630 kVA indoor transformer utilities load. NOTES: [i] The bidder shall furnish dimensional drawings of the items offered indicating all the fittings, dimensional tolerances, typical GADs of the windings with details of insulation at each point and core construction, etc. for approval of the Garrison Engineer. [ii] The bidder shall intimate the Garrison Engineer for the routine tests in accordance with IS: 2026 in the OEM factory in presence of a representative nominated by the Garrison Engineer before dispatch.
Supply, installation, testing and commissioning of free-standing indoor semi-compartmentalised cubical type 125 kVAr APFC CAPACITOR BANK made out of 2.0 mm thick CRCA sheet and built upon rigid framework, having MPP type capacitor with 7% aluminium wound reactor units type tested in accordance with IS 16636: 2017 with contactor switching, IP 4X protection and including air system provided by axial flow fan or centrifugal fan, control wiring with FR-LSH copper wires complete as specified and directed by the engineer-in-charge. Make: L & T, Schneider, Siemens The APFC Capacitor Bank shall comprise of the following: [i] 320 A, 415 V, Ics = Icu = 36 kA, 50 Hz, TP MCCB with adjustable overload settings, adjustable short-circuit settings, adjustable earth- fault settings, current limiting type double break roto active type, instantaneous protection and microprocessor based trip unit- 01 Nos. [ii] High performance microprocessor based APFC relay (8 stages) with auto / manual switch option- 01 Nos. [iii] 3- Phase power analyser with in-built digital VAF meter, phase indicating LED lamps (R, Y, B), step indicating LED lamps, ON / OFF push buttons, timer, CT- 320/5 A, Cl1.0, 15 VA- 01 Nos. [iv] MPP capacitor of 125 ( 2 X 12.5 + 2 X 25 + 1 X 50) kVAr [v] 12.5 kVAr- 02 STEPS [a] 40 A, 415, Ics = 100% Icu = 36 kA, 50 Hz TP MCCB with fixed magnetic settings and adjustable thermal settings- 02 Nos. [b] 3P, 12.5 kVAr power contactor (capacitor duty), 415 V, 50 Hz 230 VAC coil- 02 Nos. [c] 7% detuned reactor, 3- Ph, 12.5 kVAr, 440 V, 50 Hz- 02 Nos. [v] 25 kVAr- 02 STEPS [a] 50 A, 415, Ics = 100% Icu = 36 kA, 50 Hz TP MCCB with fixed magnetic settings and adjustable thermal settings- 02 Nos. [b] 3P, 25 kVAr power contactor (capacitor duty), 415 V, 50 Hz 230 VAC coil- 02 Nos. [c] 7% detuned reactor, 3- Ph, 25 kVAr, 440 V, 50 Hz- 02 Nos.
[vi] 50 kVAr- 01 STEPS [a] 100 A, 415, Ics = 100% Icu = 36 kA, 50 Hz TP MCCB with fixed magnetic settings and adjustable thermal settings- 01 Nos. [b] 3P, 50 kVAr power contactor, 415 V, 50 Hz 230 VAC coil- 01 Nos. [c] 7% detuned reactor, 3- Ph, 50 kVAr, 440 V, 50 Hz- 01 Nos. NOTES: [i] The APFC Panel shall be sourced directly from the OEM only. [ii] The APFC Relay shall be of Schneider, L & T, Seimens or Beluk make only. [iii] The APFC Panel shall have 10% extra space for future expansion. [iv] The bidder shall furnish dimensional drawings of the items offered indicating all the fittings, dimensional tolerances, typical GADs of the windings with details of insulation at each point and core construction, etc. for approval of the Garrison Engineer.
Supply, installation, testing and commissioning of free-standing indoor semi-compartmentalised cubical type 150 kVAr APFC CAPACITOR BANK made out of 2.0 mm thick CRCA sheet and built upon rigid framework, having MPP type capacitor with 7% aluminium wound reactor units type tested in accordance with IS 16636: 2017 with contactor switching, IP 4X protection and including air system provided by axial flow fan or centrifugal fan, control wiring with FR-LSH copper wires complete as specified and directed by the engineer-in-charge. Make: L & T, Schneider, Siemens The APFC Capacitor Bank shall comprise of the following: [i] 400 A, 415 V, Ics = Icu = 36 kA, 50 Hz, TP MCCB with adjustable overload settings, adjustable short-circuit settings, adjustable earth- fault settings, current limiting type double break roto active type, instantaneous protection and microprocessor based trip unit- 01 Nos. [ii] High performance microprocessor based APFC relay with auto / manual switch option- 01 Nos. [iii] 3- Phase power analyser with in-built digital VAF meter, phase indicating LED lamps (R, Y, B), step indicating LED lamps, ON / OFF push buttons, timer, CT- 320/5 A, Cl1.0, 15 VA- 01 Nos. [iv] MPP capacitor of 150 ( 2 X 12.5 + 1 X 25 + 2 X 50) kVAr [v] 12.5 kVAr- 02 STEPS [a] 40 A, 415, Ics = 100% Icu = 36 kA, 50 Hz TP MCCB with fixed magnetic settings and adjustable thermal settings- 02 Nos. [b] 3P, 12.5 kVAr power contactor (capacitor duty), 415 V, 50 Hz 230 VAC coil- 02 Nos. [c] 7% detuned reactor, 3- Ph, 12.5 kVAr, 440 V, 50 Hz- 02 Nos. [v] 25 kVAr- 01 STEPS [a] 50 A, 415, Ics = 100% Icu = 36 kA, 50 Hz TP MCCB with fixed magnetic settings and adjustable thermal settings- 01 Nos. [b] 3P, 25 kVAr power contactor (capacitor duty), 415 V, 50 Hz 230 VAC coil- 01 Nos [c] 7% detuned reactor, 3- Ph, 25 kVAr, 440 V, 50 Hz- 01 Nos.
[vi] 50 kVAr- 02 STEPS [a] 100 A, 415, Ics = 100% Icu = 36 kA, 50 Hz TP MCCB with fixed magnetic settings and adjustable thermal settings- 02 Nos. [b] 3P, 50 kVAr power contactor (capacitor duty), 415 V, 50 Hz 230 VAC coil- 02 Nos. [c] 7% detuned reactor, 3- Ph, 50 kVAr, 440 V, 50 Hz- 02 Nos. NOTES: [i] The APFC Panel shall be sourced directly from the OEM only. [ii] The APFC Relay shall be of Schneider, L & T, Seimens or Beluk make only. [iii] The APFC Panel shall have 10% extra space for future expansion. [iv] The bidder shall furnish dimensional drawings of the items offered indicating all the fittings, dimensional tolerances, typical GADs of the windings with details of insulation at each point and core construction, etc. for approval of the Garrison Engineer.
Supply, installation, testing and commissioning of sandwich type (3L+N+PE) busbar trunking system complete with two runs of 50 mm X 6 mm aluminium earthing strip and accessories all as specified and directed by engineer-in-charge. Make: L & T, Schneider, Siemens The BBT shall conform to the following technical specifications: [A] GENERAL [i] The busbar trunking system (BTS), both feeder and plug-in, shall be of sandwich construction. All components and fittings (straight length, elbow, tee, flanged end, cable tap-off box and circuit breaker etc.) shall conform to IEC 61439-6:2012 or UL 857 and shall be procured from the OEM of BTS. The BTS shall have IP 66 protection for outdoor application and IP 54 protection for indoor application in accordance with IEC 60529: 1989.[ii] The rated operation voltage of BTS shall not be less than 1 kV. The neutral conductor shall have the same cross-sectional area as the phase conductor and the earth busbar shall be provided on both sides of the housing. [B] CERTIFICATE [i] The busbar , of full range and each rating, shall pass full type tests specified in IEC 61439-6-2012. The certificate shall be issued by an international independent testing authority, e.g. ASTA. KEMA. UL and ERDA etc. [ii] A product safety mark, e.g. KEMA-KEUR, ASTA DIAMOND, UL and ERDA, etc. shall be on the product offering a visual assurance of full product safety testing, factory inspection and ongoing surveillance under independent authority. [iii] The BTS shall have UBC seismic zone 5 compliance tested with busduct and plug-in box assembly by an internationally recognized earthquake research body, e.g. Asian Pacific Network of Centres for Earthquake Engineering Research (ANCER) as per IEEE 693- 2018. The OEM shall also furnish a certificate to confirm that the BTS assembly is capable of withstanding the additional vibration in shaft owing to air movements.
[C] SHORT-CIRCUIT RATINGS & TESTS [i] The entire BTS (busduct and plug-in box assembly) shall be capable of withstanding the short-circuit of electrical installation without undergoing any electrical, mechanical or thermal stress under fault condition at a service voltage of 1 kV at 50 Hz frequency. The minimum rated insulation voltage shall be 1 kV. [ii] The minimum certified short-circuit withstand capacity for 400 A rating shall be 25 kA for 1 sec. [iii] The minimum certified short-circuit withstand capacity for 800 A rating shall be 50 kA for 1 sec. [iv] The minimum certified short-circuit withstand capacity for 1250 A rating shall be 65 kA for 1 sec. [v] The minimum certified short-circuit withstand capacity for 2000 A rating shall be 80 kA for 1 sec. [D] HOUSING [i] The busbar trunking housing shall be constructed of 1.6 mm thick electro- galvanised steel and shall be provided with a suitable protective finish of epoxy paint. [ii] The busbar trunking housing shall be totally enclosed non-ventilated for protection against mechanical damage and dust accumulation and it shall be tested for its characteristics offering resistance against corrosion [iii] The totally enclosed housing shall be manufactured by the BTS OEM and modifications of busbar trunking to make it totally enclosed by housing other than the busbar trunking OEM shall be unacceptable without written consent of the OEM.
[E] BUSBARS [i] The busbars shall be of aluminium with silver plating at joint. [ii] There shall be no bolts passing through the busbars of the BBT. [iii] Each busbar shall be insulated with Class- F (155 ˚C) insulation. Epoxy insulation shall be unacceptable. [iv] The temperature rise at any point of busbar trunking enclosure shall not exceed 55 ˚C above the ambient temperature of 40 ˚C when operated at the rated current. [F] JOINTS [i] The busbar trunking joint shall be of one-bolt type utilizing high strength steel bolt(s) and Belleville washers to maintain proper pressure over a large contact surface area. [ii] The bolt(s) shall be torque indicating and at earth potential. [iii] The bolt shall be of two-headed design to indicate proper torque has been applied and shall require only a standard long handle wrench to be properly activated. [iv] Access shall be required to only see one side of the busbar trunking to tighten joint bolts. [v] It shall be possible to remove any joint connection assembly to allow electrical isolation or physical removal of a busbar trunking length without disturbing adjacent busbar trunking lengths. [G] PLUG-IN OPENING [i] The connecting jaw of a plug-in unit shall plug directly onto the busbar and have full contact with busbar itself. Welded tab at plug-in busbar is unacceptable. [ii] All contact on joint and plug-in opening shall be of copper strip in order to avoid external force damage on busbar while plugging in or plugging out operation. [iii] On plug-in busbar trunking there shall be three dead front, hinged cover type plug-in opening on each side.[iv] All openings shall be usable simultaneously. Busbar trunking shall be installed in such a manner that plugs are side mounted to permit practical use of all plug-in openings. [v] It shall be possible to inspect the plug-in opening and busbars prior to the installation of plug-in units.
[H] SUPPORT STRUCTURE [i] Support structure shall be provided as per OEM's recommendation. [ii] Indoor feeder and plug-in busbar trunking shall be approved for hanger spacing of up to 3 m for horizontally mounted run and 4.88 m for vertically mounted runs. Outdoor feeder busbar trunking shall be approved for spacing up to 1.5 m for horizontally or vertically mounted runs. [I] VOLTAGE DROP [i] The voltage drop (sending end voltage minus receiving end voltage) specified shall be based on the busway operating at full rated current and stabilized operating temperature in [ii] The 3- Phase line to line voltage drop shall not exceed 3.4 V per 100 feet length at 40% power factor concentrated load which may exist during motor starting. [iii] The line to line voltage drop shall not exceed 4.1 V per 100 feet at the load power factor which produces the maximum voltage drop in the busway. [J] INSPECTION / SUPPORT OF INSTALLATION [i] The installation of BBT shall be executed by skilled professionals with minimum experience of 4 yrs. having sufficient installation base and pre-commissioning experience. [ii] The entire installation shall be directly supervised by the OEM. [iii] The OEM shall also furnish a commissioning report underlining satisfactory installation after the commissioning of BBT system.
1000 A BBT (from 630 kVA T/R to Essential Supply Panel) 1000 A Straight Run Feeder (IP 54 protection)
Flange End with Equilizer / Shorting Plate
Horizontal / Vertical Bend
Vertical Spring Hanger / Fix Hanger
Tinned Copper Braided Flexibles with Hardware- Nuts & Bolts
Adapter Box
800 A BBT (from 500 kVA T/R to Block LT Panel) 800 A Straight Run Feeder (IP 54 protection)
Flange End with Equilizer / Shorting Plate
Horizontal / Vertical Bend
Vertical Spring Hanger / Fix Hanger
Tinned Copper Braided Flexibles with Hardware- Nuts & Bolts
Adapter Box
Horizontal Fixing Clips
S & F LED Bolard light fittings 8/9/10 Watt integral decorative with opal acrylic cone series IP 65 protection, and electronic LED driver, etc. with all accessories internal prewired & including connecting up with 2 core flexible copper conductor cable and foundation made of bricks with cement plaster of size 30 cm x 30 cm x 45 cm (height), including sintex box with heavy duty four pole connector 32 A - one no. and 6 A- MCB, sintex box of size 20 cm x 15 cm housed in the foundation with incoming/ outgoing PVC pipe of suitable size of cable all specified and directed. Make : Bajaj cat No. -BGBOM6509WLEDW or equivant model of Phillips and Crompton.
M & L for earthing complete with galvanized steel earth plate electrode of 60 cm x 60 cm x 6 mm size, buried directly in ground (earth pit not less than 2.25 m deep below ground level) with top edge of the plate not less than 1.5 m below normal ground level, connected to galvanised strip of size 32 mm x 6 mm as earth lead, by means of bolts, buts, check nuts and washers of galvanised iron or steel, galvanized iron pipe of 40 mm diameter, connected to earthing test point, all as shown in electrical plate No. 5 connected to earthing test point all as specified or indicated including testing on completion and including excavation, earthwork, PCC earth pit of dimensions 550 mm X 550 mm (outer) and 300 mm X 300 mm (inner) and 250 mm deep, with a 10 mm thick CI cover, hinged to CI frame on ground level, GI watering pipe, funnel, etc. as all specified and directed.
Supply, installation, testing and commissioning of intelligent street light control (ATSC) suitable for 6 kW maximum load, wall/pole mounted, having built-in networking support, built-in astronomical timer, 32 A TP contactor, 40 A TPN MCB housed in 3.15 mm thick powder CRCA sheet housing all complete as specified and directed. (for street light and bolard light)
M & L for GI octagonal poles complete with single armed brackets as specified all for 6 m long with 70 mm top diameter and 130 mm bottom diameter, made of 3 mm thick tensile sheet along with base plate of size 225 X 225 X 12 mm thick, including 04 Nos. of M24 X 750 long 'J' type foundation bolts, MCB 6 A with 4-way heavy duty connector 32 A and RCC foundation as per manufacturer's drawing(s) complete as specified and directed by engineer-in-charge. Make: Jindal, Crompton, Bajaj
S & F 35 W LED street light having high efficiency long life LED module with SMD LED package mounted on MCPCB with high LED efficacy of > 100 lumen/W, integral SMPS based constant current electronic LED driver with THD < 10%, surge voltage protection and other safety tests as per IS: 15885 (Part-2/Sec-13): 2012, IP 66 protection, high effiency polycarbonate cover with integrated lens housed in pressure die-cast aluminium alloy heat sink for effective thermal management, sturdiness, excellent corrosion resistance, separate optical and control gear compartment & top opening for easy maintenance, suitable for side entry, pole mounting with bracket arm OD 35 mm to 42 mm including necessary electrical connection to the fixture with 3 core flexible Cu conductor cable of appropriate size and 1.5 m long bracket, having 40 mm diameter light grade GI pipe, including GI clamps, nuts, bolts & washers with two coats of synthetic enemal paint over a coat of red oxide primer complete all as specified and directed.
M & L for earthing complete with galvanized steel earth plate electrode of 60 cm x 60 cm x 6 mm size, buried directly in ground (earth pit not less than 2.25 m deep below ground level) with top edge of the plate not less than 1.5 m below normal ground level, connected to galvanised steel wire of diameter 4.0 mm as earth lead, by means of bolts, buts, check nuts and washers of galvanised iron or steel, galvanized iron pipe of 15 mm diameter, connected to earthing test point, all as shown in electrical plate No. 5 connected to earthing test point all as specified or indicated including testing on completion and including excavation, earthwork, PCC earth pit of dimensions 550 mm X 550 mm (outer) and 300 mm X 300 mm (inner) and 250 mm deep, with a 10 mm thick CI cover, hinged to CI frame on ground level, GI watering pipe, funnel, etc. as all specified and directed by engineer- in- charge.
SECURITY WALL Providing Material and labour AAC Block jointed in 600x200x 200 mm Flyash Masonary work using Aerated light weight concrete block having crushing strength not less than 35 kg/sqcm complete as per Technical Specification complete all as specified and directed by Engineer-in-Charge.
RAINWATER HARVESTING Supply, Install, Testing & Commissioning (SITC) of Rain Water Harvesting (RWH) 70KLD capacity including cost of filtration (sand filters) & disinfection (Hypo chloride solution) units including all necessary pumps, fittings & fixtures, electrical control panels, Instrumentation & Control etc complete RAIN WATER TREATMENT SYSTEM: 1. First-flushing A first flush device is a valve that ensures that runoff from the first spell of rain is flushed out and does not enter the system. This needs to be done since the first spell of rain carries a relatively larger amount of pollutants from the air and catchment surface. The water after the first flush shall be collected in a sedimentation tank, where it will be stored for 24 hours. The water from the tank shall be pumped to the filter and then also be used for backwashing the filter.
2. Filter The filter is used to remove suspended pollutants from rainwater collected over roof. A filter unit is a chamber filled with filtering media such as fibre, coarse sand and gravel layers to remove debris and dirt from water before it enters the storage tank or recharge structure. Charcoal can be added for additional filtration. Pumps shall be used to feed the filter and the same pumps shall be used for backwashing the filter. The backwashed water shall be recirculated to the sedimentation tank. Sandfilters: Sand filters shall be used for filtration. These filters can be employed for treatment of water to effectively remove turbidity (suspended particles like silt and clay), colour and micro organisms. The sand filter shall have layers of fine sand, coarse sand, gravel and charcoal. 3. Disinfection: The filtered water is then disinfected on line with Hypo chloride solution. The disinfected water is then stored in the treated water tank.
FIRE DETECTION & ALARM SYSTEM Supply, installation, testing and commissioning of FM approved and UL listed microprocessor- based 10 loop, true peer-to-peer networkable, addressable Fire Alarm Control Panel (FACP) with its own microcontroller memory, communication module, fire device loop interface cards for intelligent initiating and indicating devices and peer-to-peer networkable with other addressable fire alarm panels. conforming to UL 2572 mass notification systems & NFPA 72, complete with accessories all as specified and directed by engineer-in-charge. (one for each blocks) The FACP shall meet the following specifications / functional requirements. [i] The FACP shall have one to ten isolated intelligent Signalling Line Circuits (SLCs) capable of connecting up to 159 detectors and 159 modules per SLC or 318 devices per loop. [ii] The FACP shall have a degrade mode and the loops shall work in degrade mode in case of the CPU failure. [iii] The FACP shall have 6 line 640 character LCD backlit display, full QWETRY program keypad, LED indicators viz. power; fire alarm; supervisory; system trouble; other event; signals silenced; point disabled; CPU failure; controls active; etc. membrane switch controls viz. acknowledge; signal silence; drill; system reset; lamp test; etc [iv] The FACP shall have four access levels, flash EPROM, 240 VAC power supply, automatic battery charger, 24 V sealed lead acid batteries, sufficient for 24 hrs normal working and 30 min in alarm condition. [v] The FACP shall have manual sensitivity adjustment up to nine levels, built-in alarm; trouble; security and supervisory relays, history file with 4000-event capacity in nonvolatile memory plus separate 1000-event alarm-only file, keypad operation, LCD unit to indicate fire / fault signal of individual unit, in built printer to log all incoming data, etc. [vi] The FACP shall have integrated 8 channel digital voice evacuation system controller capable of broadcasting evacuation messages on the same peer-to-peer network, fire fighter's telephone two-way communication system capable of supervising all the speaker circuits with adequate zone control and accessories etc. Make: ONYX- Notifier, XLS-3000- Honeywell, IFC-JC
Supply, installation, testing and commissioning of FM approved and UL listed intelligent plug-in photoelectric smoke detector, conforming to UL 268 7th Edition, sealed against back pressure, with sensitivity range 0.5 % to 4.0 % per foot obscuration, two-wire SLC connection, fixed-temperature setpoint 135°F (57°C), built-in functional test switch activated by external magnet, built-in tamper resistant feature, remote test feature from the panel, dual LED design provideing 360° viewing angle, visible bi-color LEDs blink green every time the detector is addressed, and illuminate steady red on alarm, compatible with FlashScan® and CLIP protocol systems, Rotary, decimal addressing, etc. and having the ability to combine temperature thermal sensing with optical sensing, complete with all accessories viz. base, base box, etc. to be installed below / above false ceiling, roof and concealed space, etc. complete as specified and directed by engineer-in-charge. Make: ONYX- Notifier, XLS-3000- Honeywell, IFC-JC
Supply, installation, testing and commissioning of FM approved and UL listed intelligent plug-in intelligent thermal detector, two-wire SLC connection, fixed-temperature setpoint 135 °F (57 °C), rate of temperature rise 15 °F (8.3 °C) per minute, built-in functional test switch activated by external magnet, built-in tamper resistant feature, remote test feature from the panel, dual LED design provideing 360° viewing angle, visible bi-color LEDs blink green every time the detector is addressed, and illuminate steady red on alarm, compatible with FlashScan® and CLIP protocol systems, rotary & decimal addressing, etc. complete with all accessories viz. base, base box, etc. to be installed below / above false ceiling, roof and concealed space, etc. complete as specified and directed. (for kitchen) Make: ONYX- Notifier, XLS-3000- Honeywell, IFC-JC
Supply, installation, testing and commissioning of FM approved and UL listed dual- action, surface / semi- flush mounted break-glass type addressable manual call point (MCP) including an addressable interface for the intelligent FACP having built-in bicolour LED which is visible through the handle of the MCP, flashing in normal operation and latching steady red in alarm condition, captive screw terminals wire-ready for easy connection to SLC loop complete with accessories as specified and directed by engineer-in-charge. Make: ONYX- Notifier, XLS-3000- Honeywell, IFC-JC
Supply, installation, testing and commissioning of FM approved & UL listed of Horn Strobe, wired as a primary notification appliance, flashing 75 cd at 1 Hz over the strobe's entire operating voltage range, xenon flash tube and associated lens / reflector system, buil-in synchronization feature keeping strobes in sync for up to 30 minutes, horn producing audible annunciation of 75 dBA at 3 m distance complete with accessories as specified and directed by engineer-in-charge. Make: ONYX- Notifier, XLS-3000- Honeywell, IFC-JC
Supply, installation, testing and commissioning of FM approved and UL listed addressable control module to provide FACP a circuit for notification appliances (e.g. Horns, Strobes, Horn Strobes, etc.) having built-in type identification, integral LED indicators, high noise immunity, SMES screws with clamping plates for wiring ease, direct-dial entry of address, etc. complete with accessories as specified and directed by engineer-in-charge. Make: ONYX- Notifier, XLS-3000- Honeywell, IFC-JC
Supply, installation, testing and commissioning of FM approved and UL listed addressable relay module to provide FACP a dry-contact output for activating a variety of auxiliary devices, viz. fans, dampers, control equipment, etc. having built-in type identification, integral LED indicators, high noise immunity, SMES screws with clamping plates for wiring ease, direct-dial entry of address, etc. complete with accessories as specified and directed by engineer-in-charge. (for pressurisation fan panel) Make: ONYX- Notifier, XLS-3000- Honeywell, IFC-JC
Supply, installation, testing and commissioning of FM approved and UL listed intelligent monitor module, with built-in type identification automatically identifying the device as a monitor module to the FCAP, to supervise a circuit of dry-contact input devices, viz. flow switch of sprinkler line, powered directly by two-wire SLC loop, high noise immunity, SEMS screws with clamping plates for ease of wiring, direct-dial entry of addresses, LED indicators, etc. complete with accessories as specified and directed by engineer-in-charge.(sprinkler flow switch) Make: ONYX- Notifier, XLS-3000- Honeywell, IFC-JC
S & F plug-in gas leak detector to provide an early warning for LPG or CNG/PNG gas leakage from cylinders or through pipelines calibrated to give an alarm at about 2000 ppm along with separate heat and gas sensors with LEDs, audible buzzer alarm, etc. complete as specified and directed by the engineer-in-charge. (for kitchen)
M & L for low smoke zero helogen (LS0H) flame retardant fire alarm cable, conforming to BS 7629-1, BS 6387 & BS EN 50200 and rated for 500 V, having plain annealed stranded copper conductor with primary insulation of glass mica fire resistant tape and secondary insulation of high performance silicone rubber, earth/drain wire of annealed tinned copper, electrostatic screen of aluminium fire barrier and type LTS3 outer sheath conforming to BS 7655, suitable for operating temperature range -30 ˚C to +70 ˚C and minimum bending radius being 6 times the overall cable diameter, RED in colour, including laying, termination and ferruling complete all as specified and directed by engineer-in-charge. Make: RR Kabel, Havells or Polycab a) 2 core, 1.5 mm²
b) 2 core, 2.5 mm² (supply to hooter/strobe)
M & L for low smoke zero helogen (LS0H) fire survival control cable with circuit integrity, conforming to BS 7846 and rated for 600 V, having plain annealed stranded copper conductor with fire-resistant mica tapes covered by an extruded layer of cross-linked polyethylene, extruded layer of thermoplastic low smoke zero helogen (LS0H) compound, single layr of galvanized steel wires and thermoplastic LS0H compound sheath, suitable for operating temperature range -40 ˚C to +90 ˚C and minimum bending radius being 12 times the overall cable diameter, including laying, clamping, termination and ferruling complete as specified and directed by the engineer-in-charge. Make: Havells, Polycab, Finolex, RR Kabel a) 2 core, 2.5 mm² (for instrumentation)
b) 3 core, 2.5 mm² (for auto start/stop panel)
c) 12 core, 2.5 mm² (for diesel engine pump)
M & L for earthing complete with galvanized steel earth plate electrode of 60 cm X 60 cm X 6 mm size, buried directly in ground (earth pit not less than 2.25 m deep below ground level) with top edge of the plate not less than 1.5 m below normal ground level, connected to galvanized strip of size 32 mm X 6 mm as earth lead by means of bolts, nuts, checknuts and washers of galvanized iron or steel, galvanized iron pipe of 40 mm diameter connected to earthing test point, all as shown in electrical plate No. 5, connected to earthing test point including testing on completion, excavation, earthwork, PCC earth pit of dimensions 550 mm X 550 mm (outer) and 300 mm X 300 mm (inner) and 250 mm deep with a 10 mm deep CI cover hinged to CI frame on ground level, GI watering pipe, funnel, etc. complete as specified and directed by the engineer-in-charge.
M & L for earthing complete with galvanized steel earth plate electrode of 60 cm x 60 cm x 6 mm size, buried directly in ground (earth pit not less than 2.25 m deep below ground level) with top edge of the plate not less than 1.5 m below normal ground level, connected to galvanised steel wire of diameter 4.0 mm as earth lead, by means of bolts, buts, check nuts and washers of galvanised iron or steel, galvanized iron pipe of 15 mm diameter, connected to earthing test point, all as shown in electrical plate No. 5 connected to earthing test point all as specified or indicated including testing on completion and including excavation, earthwork, PCC earth pit of dimensions 550 mm X 550 mm (outer) and 300 mm X 300 mm (inner) and 250 mm deep, with a 10 mm thick CI cover, hinged to CI frame on ground level, GI watering pipe, funnel, etc. as all specified and directed by engineer- in- charge.
M & L for ISI marked MS ERW pipes conforming to IS: 1239 (Part 1 & 2) with all accessories like all fittings including tees, elbows, reducers, union, flanges, rubber gaskets, GI nuts bolts, washer, including supporting/fixing the pipe on floor/wall/ceiling with clamps, hangers, angles, channels (using anchor fastners) with painting of one coat primer and 2 or more coats of synthetic enamel paint complete as specified and directed by the engineer-in-charge. NOTES: [i] Standard MS fittings with welded joint shall be used on the pipes. [ii] All hangers, clamps, brackets etc. shall be of galvenized iron [iii] Welding of any kind on the galvenised support / hanger shall not be permitted. [iv] The pipe size 150 mm NB & below shall be MS 'C' class as per IS 1239 (Part- 1): 2004 & IS 1239 (Part- 2): 2011. [v] The pipe size above 150 mm NB shall be welded black steel pipe heavy class as per IS 3589: 2001. [vi] Pipes of size more than 50 mm NB shall be butt welded with fittings of equal or higher thickness whereas pipes below 50 mm NB size shall be socket welded. Make: Tata, Jindal, BST a) 250 mm NB
b) 200 mm NB
c) 150 mm NB
d) 125 mm NB
e) 50 mm NB
f) 40 mm NB
M & L for PN 1.6 rated 250 mm NB polypropelene vortex inhibitor suction lift, conforming to BS 4504 with stainless wire mesh, bolts, nuts and washers, etc. complete all as specified and directed by engineer-in-charge.
M & L for PN 1.6 rated 250 mm NB CI 'Y' -type strainer for suction conforming to IS: 907- 1984 with SS filter screen and flange drilling standard end connection conforming to IS: 1538- 1993 and necessary accessories for suction side of fire pumps complete as specified and directed by the engineer-in-charge. Make: Leader, Sant, Venus
S & F PN 1.6 rated CI sluice valve, conforming to IS: 14846- 2000, with SS spindle conforming to IS: 6603- 2001 and flange drilling standard end connection conforming to IS: 1538- 1993 and necessary accessories complete as specified and directed by the engineer-in-charge. Make: Leader, Sant, Venus a) 250 mm NB
b) 125 mm NB
Supply, installation, testing and commissioning of PN 1.6 rated CI swing check type reflux (non return) valve, conforming to IS: 5312 (Part 1)- 2004 with flange drilling standard end connection conforming to IS: 1538- 1993 and necessary accessories complete as specified and directed by the engineer-in-charge. Make: Leader, Sant, Venus a) 40 mm NB
b) 125 mm NB
S & F of CL 150 # rated 40 mm NB ball valve, designed & manufactured as per IS: 9890 (1981) and tested as per BS 6755 Part- I, having floating type three piece design, CS body, SS- 304 ball, PTFE seal/packing/gasket, CS fastners and lever and screwed/socket weld end connection, etc. with accessories complete as specified and directed by the engineer-in-charge.
M & L for ISI marked 150 mm NB MS ERW pipe conforming to IS: 1239 (Part 1 & 2) with all accessories like all fittings including tees, elbows, reducers, union, flanges, rubber gaskets, GI nuts bolts, washer, including supporting/fixing the pipe in excavated trenches with painting of one coat primer and 2 or more coats of synthetic enamel paint of and wrapping of 4 mm thick protection coating by thermo fusion process complete as specified and directed by the engineer-in-charge. NOTES: [i] Standard MS fittings with welded joint shall be used on the pipes. [ii] All hangers, clamps, brackets etc. shall be of galvenized iron. [iii] Welding of any kind on the galvenised support / hanger shall not be permitted. [iv] The pipe size 150 mm NB & below shall be MS 'C' class as per IS 1239 (Part- 1): 2004 & IS 1239 (Part- 2): 2011. [v] The pipe size above 150 mm NB shall be welded black steel pipe heavy class as per IS 3589: 2001. [vi] Pipes of size more than 50 mm NB shall be butt welded with fittings of equal or higher thickness whereas pipes below 50 mm NB size shall be socket welded. Make: Tata, Jindal, BST
M & L for ISI marked MS ERW pipes conforming to IS: 1239 (Part 1 & 2) with all accessories like all fittings including tees, elbows, reducers, union, flanges, rubber gaskets, GI nuts bolts, washer, including supporting/fixing the pipe on floor/wall/ceiling with clamps, hangers, angles, channels (using anchor fastners) with painting of one coat primer and 2 or more coats of synthetic enamel paint complete as specified and directed by the engineer-in-charge. NOTES: [i] Standard MS fittings with welded joint shall be used on the pipes. [ii] All hangers, clamps, brackets etc. shall be of galvenized iron. [iii] Welding of any kind on the galvenised support / hanger shall not be permitted. [iv] The pipe size 150 mm NB & below shall be MS 'C' class as per IS 1239 (Part- 1): 2004 & IS 1239 (Part- 2): 2011. [v] The pipe size above 150 mm NB shall be welded black steel pipe heavy class as per IS 3589: 2001. [vi] Pipes of size more than 50 mm NB shall be butt welded with fittings of equal or higher thickness whereas pipes below 50 mm NB size shall be socket welded. Make: Tata, Jindal, BST a) 100 mm NB (for wet riser)
b) 80 mm NB (for Hydrant / landing valve or connection)
c) 25 mm NB (for hose reel branch connection)
S & F of CL 150 # rated 25 mm NB ball valve, designed & manufactured as per IS: 9890 (1981) and tested as per BS 6755 Part- I, having floating type three piece design, CS body, SS- 304 ball, PTFE seal/packing/gasket, CS fastners and lever and screwed/socket weld end connection, etc. with accessories complete as specified and directed by the engineer-in-charge.
S & F of orifice plate made out of 6 mm thick SS 304 with orifice of required size to be fitted between flange and landing valve of external and internal hydrants to reduce pressure at the outlet to the level of 3.5 kg/cm2 complete as specified and directed by the engineer-in-charge.
Supply, installation, testing and commissioning of 2- way fire brigade draw- off connection with two 63 mm NB inbuilt gunmetal non-return valves instanteneous coupling type arranged on 100 mm NB pipe manifold and connected to wet riser main as well as to fire water tank including CI butterfly valve, CI non-return valve and MS cabinet with mounting supports, etc. all complete as specified and directed by the engineer-in-charge. Make: Newage, AAAG, Minimax
M & L for ISI marked MS ERW pipes conforming to IS: 1239 (Part 1 & 2) with all accessories like all fittings including tees, elbows, reducers, union, flanges, rubber gaskets, GI nuts bolts, washer, including supporting/fixing the pipe in excavated trenches with painting of one coat primer and 2 or more coats of synthetic enamel paint of and wrapping of 4 mm thick protection coating by thermo fusion process complete as specified and directed by the engineer-in-charge. NOTES: [i] Standard MS fittings with welded joint shall be used on the pipes. [ii] All hangers, clamps, brackets etc. shall be of galvenized iron [iii] Welding of any kind on the galvenised support / hanger shall not be permitted. [iv] The pipe size 150 mm NB & below shall be MS 'C' class as per IS 1239 (Part- 1): 2004 & IS 1239 (Part- 2): 2011. [v] The pipe size above 150 mm NB shall be welded black steel pipe heavy class as per IS 3589: 2001. [vi] Pipes of size more than 50 mm NB shall be butt welded with fittings of equal or higher thickness whereas pipes below 50 mm NB size shall be socket welded. Make: Tata, Jindal, BST
a) 150 mm NB
b) 100 mm NB
M & L for ISI marked MS ERW pipes conforming to IS: 1239 (Part 1 & 2) with all accessories like all fittings including tees, elbows, reducers, union, flanges, rubber gaskets, GI nuts bolts, washer, including supporting/fixing the pipe on floor/wall/ceiling with clamps, hangers, angles, channels (using anchor fastners) with painting of one coat primer and 2 or more coats of synthetic enamel paint complete as specified and directed by the engineer-in-charge. NOTES: [i] Standard MS fittings with welded joint shall be used on the pipes. [ii] All hangers, clamps, brackets etc. shall be of galvenized iron [iii] Welding of any kind on the galvenised support / hanger shall not be permitted. [iv] The pipe size 150 mm NB & below shall be MS 'C' class as per IS 1239 (Part- 1): 2004 & IS 1239 (Part- 2): 2011. [v] The pipe size above 150 mm NB shall be welded black steel pipe heavy class as per IS 3589: 2001. [vi] Pipes of size more than 50 mm NB shall be butt welded with fittings of equal or higher thickness whereas pipes below 50 mm NB size shall be socket welded. Make: Tata, Jindal, BST Note: Sprinkler pipes inside qtrs shall be concealed in walls and rate quoted for the same shall be included in the rate quoted against the items
a) 100 mm NB
b) 80 mm NB
c) 65 mm NB
d) 40 mm NB
e) 32 mm NB
f) 25 mm NB
M & L for FM approved and UL listed standard response, standard coverage glass-bulb type spray sprinklers, conforming to IS 15105: 2002, and having discharge coefficient K = 8.0, maximum working pressure 175 psi (12.1 bar), bronze frame, brass/copper button, bronze compression screw, copper defletor, TEFLON sealing assembly, etc. with 15 mm NB screwed emd connection, suitable for 68° C temperature rating complete as specified and directed by the engineer-in-charge. Extended coverage sidewall Sprinkler
M & L for Construction of fly-ash brick masonary valve chamber of size 1000 mm X 800 mm X 1000 mm (internal dimenssions) with PCC foundation 1:4:8 type D2 using 40 mm graded stone aggregate, 150 mm thick & 150 mm wide offsets around over 100 mm thick hardcore , 200 mm thick fly-ash brick masonry walls built in CM 1:6, 100 mm thick PCC 1:2:4 Type B1 coping finished even and smooth, rendering 10 mm thick in cement mortar (1:6) finished even and smooth, with out using extra cement internally including top of floor including excavation earth work in hard/Dense soil 6 mm thick MS sheet cover fixed on 25 mm X 25 mm X 6 mm thick angle iron frame with hold fasts embedded in PCC coaping with locking arrangement, mild steel handle and painting to steel surfaces with two coats of synthetic enamel paint over one coat of primer including disposal of surplus soil to a distance not exceeding 50 m etc complete all as specified and directed.
STAIRCASE PRESSURIZATION Supply, installation, testing and commissioning of UL 705 listed airfoil wheel single inlet single width (SWSI) centrifugal fan capable of airflow delivery upto 40000 CFM, having 3" w.g. static pressure, etc. complete with electric connection complete as specified and directed by engineer-in-charge.
Supply, installation, testing & commissioning of removable air grilles of duly powder coated extruded aluminum sections complete as specified and directed by engineer-in-charge.
Supply, installation, testing and commissioning of factory made, CPRI type tested, indoor cubical compartmental type STAIRCASE PRESSURIZATION PANEL of suitable size, conforming to IEC 61439-1 & 2 and IEC 61641, having both sides openable with hinged double doors and locking arrangement, IP 43 protection made out of 2.0 mm thick mild steel CRCA sheet, supported and fixed on structural frame of angle iron of suitable size, including earthing stud, labelling, painting to all internal & external exposed steel surfaces with powder coating paint (7 tank process), duly fixed in ground with PCC foundation (1:2:4) type B1, with danger notice plate of 1.6 mm thick mild steel vitreous enamelled (white) with letters, figures and conventional skull and bones in signal red colour suitable for 3- Phase, 4 Wire system, 500 V grade with necessary wiring, PVC sheathed stranded copper conductor of appropriate length and size, including fixing lugs, bolts, screws, etc. complete as specified and directed by engineer-in-charge. Make: L & T, Schneider, Siemens, ABB The STAIRCASE PRESSURIZATION PANEL shall comprise of the following: [A] BUSBAR CHAMBER [i] 01 Set (3L + N) of copper busbar of rated capacity 200 A, covered with PVC insulated sleeves including insulator, nuts, bolts, etc. with complete connection [B] INCOMING [i] 100 A, 415 V, Ics = 100% Icu = 25 kA, 50 Hz FP MCCB, conforming to IEC 60947-2, having microprocessor based trip unit, adjustable overload setting (0.7 - 1 X In), adjustable short-circuit setting (5 - 10 X Ir), adjustable neutral protection (N, N/2, OFF), front indication LEDs (Ready, Overload and pre-alarm & Overload), etc.- 01 Nos. [ii] Cl 1.0 multi-function meter capable of measuring V, A, F, PF, W/VA, Wh/VAh, Runhrs. Onhrs & interupts- 01 Nos. [iii] LED phase indicators (Red, Yellow, Blue)- 01 Set
ELEVATORS Supply, installation, testing and commissioning of factory made, CPRI type tested, indoor cubical compartmental type ELEVATOR PANEL of suitable size, conforming to IEC 61439-1 & 2 and IEC 61641, having both sides openable with hinged double doors and locking arrangement, IP 43 protection made out of 2.0 mm thick mild steel CRCA sheet, supported and fixed on structural frame of angle iron of suitable size, including earthing stud, labelling, painting to all internal & external exposed steel surfaces with powder coating paint (7 tank process), duly fixed in ground with PCC foundation (1:2:4) type B1, with danger notice plate of 1.6 mm thick mild steel vitreous enamelled (white) with letters, figures and conventional skull and bones in signal red colour suitable for 3- Phase, 4 Wire system, 500 V grade with necessary wiring, PVC sheathed stranded copper conductor of appropriate length and size, including fixing lugs, bolts, screws, etc. complete as specified and directed by engineer-in-charge. Make: L & T, Schneider, Siemens, ABB The ELEVATOR PANEL shall comprise of the following: [A] BUSBAR CHAMBER [i] 01 Set (3L + N) of copper busbar of rated capacity 200 A, covered with PVC insulated sleeves including insulator, nuts, bolts, etc. with complete connection [B] INCOMING [i] 100 A, 415 V, Ics = 100% Icu = 25 kA, 50 Hz FP MCCB, conforming to IEC 60947-2, having microprocessor based trip unit, adjustable overload setting (0.7 - 1 X In), adjustable short-circuit setting (5 - 10 X Ir), adjustable neutral protection (N, N/2, OFF), front indication LEDs (Ready, Overload and pre-alarm & Overload), etc.- 01 Nos. [ii] Cl 1.0 multi-function meter capable of measuring V, A, F, PF, W/VA, Wh/VAh, Runhrs. Onhrs & interupts- 01 Nos. [iii] LED phase indicators (Red, Yellow, Blue)- 01 Set
[C] OUTGOING [i] 63 A, 415 V, Ics = 100% Icu = 25 kA, 50 Hz FP MCCB, conforming to IEC 60947-2, having microprocessor based trip unit, adjustable overload setting (0.7 - 1 X In), adjustable short-circuit setting (5 - 10 X Ir), adjustable neutral protection (N, N/2, OFF), front indication LEDs (Ready, Overload and pre-alarm & Overload), etc.- 01 Nos. [ii] 32 A, 415 V, Ics = 100% Icu = 25 kA, 50 Hz FP MCCB, conforming to IEC 60947-2, having microprocessor based trip unit, adjustable overload setting (0.7 - 1 X In), adjustable short-circuit setting (5 - 10 X Ir), adjustable neutral protection (N, N/2, OFF), front indication LEDs (Ready, Overload and pre-alarm & Overload), etc.- 02 Nos. [iii] ISI marked 32 A, 300 mA, 415 V, 50 Hz, FP RCBO for AC applications, conforming to IS 12640 (Part-2)- 2016, having front face indication for earth leakage fault, sliding bottom clamp, colour coded on/off indication on dolly, biconnect IP 20 protected lower terminals and sliding shutters- 04 Nos. [iv] 32 A, 10 kA, 230 V, 50 Hz SPN MCB- 01 Nos. [v] LED phase indicators (Red, Yellow, Blue)- 04 Set [vi] Digital ammeter of suitable capacity with suitable CTs for each feeder- 04 Nos. NOTES: [i] The bidder shall furnish dimensional drawings of the items offered indicating all the fittings, dimensional tolerances, typical GADs of the windings with details of insulation at each point and core construction, etc. for approval of the Garrison Engineer.
M & L for earthing complete with copper earth plate electrode of 60 cm x 60 cm x 3.15 mm size, buried directly in ground (earth pit not less than 2.25 m deep below ground level) with top edge of the plate not less than 1.5 m below normal ground level, connected to copper strip of size 20 mm x 3 mm as earth lead, by means of bolts, buts, check nuts and washers of galvanised iron or steel, galvanized iron pipe of 40 mm diameter, connected to earthing test point, all as shown in electrical plate No. 5 connected to earthing test point all as specified or indicated including testing on completion and including excavation, earthwork, PCC earth pit of dimensions 550 mm X 550 mm (outer) and 300 mm X 300 mm (inner) and 250 mm deep, with a 10 mm thick CI cover, hinged to CI frame on ground level, GI watering pipe, funnel, etc. complete as specified and directed by the engineer-in-charge.
Comprehensive maintenance of lifts Comprehensive maintenance and repair of fully automatic electrically operated passenger lift of any make and 16 Passenger capacity (06 nos) installed against Sch 'A' Part- XVII. Item No. 1, herein before building (G+26). (Total Lifts) comprising of all devices and accessories through out months on all days including holidays for period of 03 years after expiry of defects liability penod as shown below and all as specified and directed by GE Note - Contractor shall carry out comprehensive mainenance (routine, daily. weekly, monthly, quarterly, half yearly, yearly) and maintain all the lifts in serviceable condition 24 Hrs X 365 days without any extra cost
1st year after expiry of defects liability period
2nd year after expiry of defects liability period
3rd year after expiry of defects liability period
Annual Comprehensive maintenance of Passenger Lift, 13 passengers fully automatic electrically operated gear/ gearless with machine room, to serve upto G + 26 upper floors with speed of 2.5 mtr sec, with single/ variable speed motor with AC variable voltage variable frequency drive, OLD with all standard accessories, automatic leveling device, ARD, system Infrared sensors to bring the lift car to the exact landing level, simplex automatic operation with or without attendant including telescopic/ centre opening stainless steel sliding doors and landing door shutters with stainless steel finish and indicators at each floor including all lift parts which are connected for sale operation of 06 No. lifts at G+26 Residential accn at Powai
1st year after expiry of defects liability period
2nd year after expiry of defects liability period
3rd year after expiry of defects liability period
DG SET Supply, installation, testing and commissioning of silent DG Set, conforming to IS: 10002- 1981, complete with Diesel Engine of suitable BHP & AC Brushless SPDP alternator, conforming to IS: 13364- 1992, mounted on a common base frame & coupled through a flexible coupling or close coupled and AMF Panel complete with platform, control panel having meters, sound-proof canopy, etc. of capacity 500 kVA complete all as specified and directed. Make: Kirloskar, Crompton Greaves, Cummins, Mahindra [a] Engine: 6/12 cylinder, in-line, 4 stroke, radiator cooled engine, well designed air handling system with dry type, heavy duty, replaceable paper element air cleaner with restriction indicator, air to air aftercooling, optimised turbocharger for increased altitude,Inline fuel pump with class H electronic governing, spin on fuel filter, standard integral set-mounted radiator system, designed and tested for 50°C ambient temperature, full flow spin on lube oil filter, electrical starter motor with soft start engagement feature, battery charging alternator with 1 x 24 or 2 X 12 V DC dry type battery. [b] Alternator: Brushless type, screen protected, revolving field, self-excited alternator, conforming to IS/IEC 60034-1 3-phase reconnectable winding with 12 terminals brought out for connection, dedicated winding specially designed for single operation, impregnation on all wound components for better mechanical strength [c] Control Panel: Manufactured with 14/16 gauge CRCA sheet and powder coated for weather-proof and long lasting finish. The control panel consists of the following parts: [i] Controller: Copper bus bars with suitable capacity with incoming/outgoing terminals [ii] Indicating lamps for ‘Load ON’ and ‘Set Running’ [iii] Instrument fuses duly wired and ferruled [iv] Microprocessor based MCCB of suitable rating with overload and short circuit protections
[d] Microprocessor based generator set monitoring and control system including an intuitive operator interface that allows for complete generator set control as well as system metering, fault annunciation, configuration and diagnostics, LED backlit LCD display with tactile feel soft-switches & generator set status LED lamps, remote START-STOP [e] Engine Metering: Oil pressure, engine temperature, starting battery voltage, engine running hours [f] AC Alternator Metering: L-L voltage and L-N voltage, current (phase and total), kVA (phase and total) and frequency [g] Engine Protection: Low lube oil pressure, high/low coolant temperature, battery over/under/weak volts, fail to crank/start, sensor failure, cranking lockout, low fuel level [h] AC Alternator Protection: Over/under voltage, over/under frequency, loss of AC sensing. [i] Data Logging: Engine hours, control hours and upto 5 recent fault codes [j] Configurable glow plug control [k] 24 V DC operation [l] Silencer: Critical grade silencer suitably optimized to meet stringent noise emission standards laid down by MoEF / CPCB [m] Mounting Arrangement: Engine and alternator are mounted on a common MS fabricated base frame with AVM pads. [n] Base frame with integral fuel tank is provided with drain plug, air vent, inlet and outlet connection, level indicator and provision for cleaning [o] Suitable stack height as per CPCB norms for exhaust piping to be provided
M & L for earthing complete with galvanized steel earth plate electrode of 60 cm x 60 cm x 6 mm size, buried directly in ground (earth pit not less than 2.25 m deep below ground level) with top edge of the plate not less than 1.5 m below normal ground level, connected to galvanised strip of size 32 mm x 6 mm as earth lead, by means of bolts, buts, check nuts and washers of galvanised iron or steel, galvanized iron pipe of 40 mm diameter, connected to earthing test point, all as shown in electrical plate No. 5 connected to earthing test point all as specified or indicated including testing on completion and including excavation, earthwork, PCC earth pit of dimensions 550 mm X 550 mm (outer) and 300 mm X 300 mm (inner) and 250 mm deep, with a 10 mm thick CI cover, hinged to CI frame on ground level, GI watering pipe, funnel, etc. as all specified and directed.
M & L for GI strip of size 32 mm x 6 mm as earth lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc complete all as specified and directed.
AVIATION LIGHT S & F LED aviation/obstruction light having intensity > 40 cd, die-cast aluminium body, UV stabilized optical lens for 360◦ illumination, inbuilt on-off photo cells, ERDA type tested and comforming to ICAO/FAA standards, IP 65 rated operating on 90- 270 V, 50 Hz, 1- Ph AC supply.
M & L for IS 694 marked, FIA/TAC approved 2 core, 1.5 sqmm stranded copper conductor (as per IS 8130), XLPE insulated, extruded PVC type ST-2 (as per IS: 5831) sheathed, single layer of galvanized steel flat strip armoured cable of 1.1 kV grade, conforming to IS 7098 (Part-2), including cable termination and cable glanding.
TV CONDUIT S & F modular type 1 module TV socket complete all as specified and directed.
S & F RG 11 coaxial cable having solid electrolytic grade annealed plain copper central condutor of 1.63mm nominal diameter, gas injected physical polythylene foam insulated, wrapped with aluminium mylar tape aluminium alloy wire braided, jelly flooded and PVC jacketed including termination complete all as specified and directed.
S & F RG 6 coaxial cable having solid electrolytic grade annealed plain copper central condutor of 1.02mm nominal diameter, gas injected physical polythylene foam insulated, wrapped with aluminium mylar tape aluminium alloy wire braided, jelly flooded and PVC jacketed including termination complete all as specified and directed.
Supply & installation of 04 way splitter box for TV cable terminajtion incl all necessary hardware accessories complete all as specified and directed.
TELEPHONE CONDUITS S & F modular type 1 module RJ 11 telephone socket with shutter complete all as specified and directed.
Supplying & erecting 50 pairs x 0.5 mm dia PVC insulated armoured telephone cable 0.5 sq.mm PVC Sheathed solid tinned copper conductor cable laid in provided trench/ cable tray complete all as specified and directed.
Supplying & erecting 10 pairs x 0.5 mm dia PVC insulated armoured telephone cable 0.5 sq.mm PVC Sheathed solid tinned copper conductor cable laid in provided trench/ cable tray complete all as specified and directed.
S & F for 2 pair telephone cable having solid electrolytic annealed bare copper conductor of 0.5 mm nominal diameter with high density polyethylene insulation, paired, polyester taped, nylon rip cord and grey colour sheathed with FR PVC, conforming to ITD specification S/WS 113 C including termination complete all as specified and directed.
S & F 10 pair telephone distribution box with suitable S.S. frame for mounting tag module, Krone module and incorporated in 16 SWG MS box with proper lockable cover. The box should be fixed on wall with suitable fasteners including painting & earthing. This also includes fixing the cable, distribution chart sufficient space for the cables, wires etc. complete all as specified and directed.
S & F 50 pair telephone distribution box with suitable S.S. frame for mounting tag module, Krone module and incorporated in 16 SWG MS box with proper lockable cover. The box should be fixed on wall with suitable fasteners including painting & earthing. This also includes fixing the cable, distribution chart sufficient space for the cables, wires etc. complete all as specified and directed.
SOCKETS S & F modular type 25 A socket conforming to IS: 1293-1988 complete as specified and directed by engineer-in-charge.
S & F modular type 25 A one-way SP switch, conforming to IS: 3854- 1997 with finger proof terminal & indicator complete as specified and directed by engineer-in-charge.
SS RAILING S & F SS Railing 304 grade all as shown on drawing and diretced by Engineer-in-Charge.
ARBORICULTURE & LANDSCAPING Digging pits,Supply and planting 1 to 2 feet high boundry plantation with ferns and colourful, Plants as in hedges and refilling soil around the Plantation,complete all as specified and directed by Engr-in-Charge etc.
Digging pits of size 0.6x0.6x0.9m, making berms /bumds and supply and planting 6 to 8 feet high Areca palms trees & all other Mature / ever green trees, refilling soil around the plantation,wearing etc complete all as specified and as directed by Engr-in-Charge. Note: Item No. 24.44 & 24.45 above shall be maintained for 12 months with proper care like watering, plucking of weeds etc., The rate quoted by the contractor shall be deemed to include for maintaining the planitation and grass for a perod of 12 Months and nothing extra shall be payable on this account etc., complete all as specified and directed.
Supply and laying factory made PCC blocks (kerb stone) of size 500 x 325 x 150 mm top edge chamfered as in kerbs,in PCC 1:3:6 type C -0 (using 12.5 mm graded stone aggregate),at the edges of hedges and ferns etc allas directed by Engr-in-Charge etc.complete all as specified and directed.
Supplying and planting grown trees as mentioned below: I. TREES a) Ficus Bengalensis commonly known as Banyan Tree
b) Azadirachta indica commonly known as Neem Tree
c) Polyalthia longifolia commonly known as Ashoka Tree
d) Ficus Religiosa commonly known as Peepal Tree
e) Areca catechu commonly known as Areca palm
f) Ixora Coccinea commonly known as Jungle flame
g) Garuga Pinnata commonly known as Grey Downy Balsum
II. SHRUBS a) Wedelia trilobata commonly known as singapore daisy
b) Duranta erecta Note:- The rate of the following item, should - include for supply of plants as specified , transportation to site, excavation of pits as follows: i) 0.6x0.6x0.9m for large shrubs and climbers ii) Filling pits with Prepared manure soil ( Ratio 1:2 i.e. 1 sludge : 2 good earth by volume) iii) Supply, transportation and mixing of soil improvement nutrients as required, inside coat of Aldrin in all pits, flooding with waterdressing including removal of rubbish & surplus earth if any with all lead & lifts, planting and stacking in full and final locationincluding all locations specified and maintenance of plants for a period of 12 months, replacement of any dead & sickly plants inthis period, supply & spraying of insecticides as required.,
EARTHING AND LIGHTNING PROTECTION SYSTEM- CLASS I TIER-I AIR TERMINATION
Supply, Installation, Testing and Commissioning of 1 metre Vertical Aluminium Air terminal of dia 15mm to meet the requirement of IS/IEC 62305.Tested for Electrical, Mechanical, Environmental test and should have Impulse current withstand capability of 100KA (Class H)and as per IEC 62561-1&2.
Supply, Installation, Testing and Commissioning of Aluminium Air terminal base for dia15mm,1 meter long Air terminal to meet the requirement of IS/IEC 62305 .Tested for Electrical, Environmental test and should have Impulse current withstand capability of 100KA (Class H)and as per IEC 62561-1&2.
Supply, Installation, Testing and Commissioning of 25x3mm Aluminum Tape Conductor with fixing accessories and should be tested for electrical resistivity test , Tensile strength, Environmental Test (salt spray & humidity test) to meet the requirements of IS/IEC 62305 and IEC 62561-1&2.
Supply, Installation, Testing and Commissioning of Aluminum Square Tape Clamp for Cross connection and T connection of 25x3mm Aluminium Tape should be tested for electrical resistivity test ,Environmental Test (salt spray & humidity test),Mechanical test and Impulse current withstand capability of 100KA (Class H)to meet the requirements of IS/IEC 62305 and IEC 62561-1&2.
Supply, Installation, Testing and Commissioning of U bolt rebar to Cable Clamp should be tested for Environmental Test (salt spray & humidity test),Contact resistance test and Impulse current withstand capability of 100KA (Class H)to meet the requirements of IS/IEC 62305 and IEC 62561-1&2.
Supply, Installation, Testing and Commissioning of 50sq mm Green/Yellow PVC insulated Copper cable with terminal Lug, should have Each stranded of 1.7 mm diameter as per requirements of IS/IEC 62305 and IEC 62561-2:2012.
SITC of Bi-mettalic Connector should be tested for Environmental Test (salt spray & humidity test), Contact resistance test ,Mechanical test and Impulse current withstand capability of 100KA (Class H)to meet the requirements of IS/IEC 62305 and IEC 62561-1&2.
TIER II - DOWN CONDUCTORS / RING CONDUCTORS Supply, Installation, Testing and Commissioning of U bolt rebar to Cable Clamp should be tested for Environmental Test (salt spray & humidity test),Contact resistance test and Impulse current withstand capability of 100KA (Class H)to meet the requirements of IS/IEC 62305 and IEC 62561-1&2.
Supply, Installation, Testing and Commissioning of 50sq mm Green/Yellow PVC insulated Copper cable with terminal Lug, should have Each stranded of 1.7 mm diameter as per requirements of IS/IEC 62305 and IEC 62561-2:2012.
Supply, Installation, Testing and Commissioning of Bi-mettalic Connector should be tested for Environmental Test (salt spray & humidity test), Contact resistance test ,Mechanical test and Impulse current withstand capability of 100KA (Class H)to meet the requirements of IS/IEC 62305 and IEC 62561-1&2.
Supply, Installation, Testing and Commissioning of 25x3mm Aluminum Tape Conductor with fixing accessories and should be tested for electrical resistivity test , Tensile strength, Environmental Test (salt spray & humidity test) to meet the requirements of IS/IEC 62305 and IEC 62561-1&2.
SITC of Aluminum Square Tape Clamp for Cross connection and T connection of 25x3mm Aluminium Tape should be tested for electrical resistivity test ,Environmental Test (salt spray & humidity test),Mechanical test and Impulse current withstand capability of 100KA (Class H)to meet the requirements of IS/IEC 62305 and IEC 62561-1&2.
Supply, Installation, Testing and Commissioning of Moisturing inhibiting compound to meet the requirements of IS/IEC 62305.
TIER III - TESTING / DISCONNECTING LINK Supply, Installation, Testing and Commissioning of 50sq mm Green/Yellow PVC insulated Copper cable with terminal Lug, should have Each stranded of 1.7 mm diameter as per requirements of IS/IEC 62305 and IEC 62561-2:2012.
Supply, Installation, Testing and Commissioning of U bolt rebar to Cable Clamp should be tested for Environmental Test (salt spray & humidity test),Contact resistance test and Impulse current withstand capability of 100KA (Class H)to meet the requirements of IS/IEC 62305 and IEC 62561-1&2.
Supply, Installation, Testing and Commissioning of Test link should be tested for Environmental Test (salt spray & humidity test),Contact resistance test, Mechanical test and Impulse current withstand capability of 100KA (Class H)to meet the requirements of IS/IEC 62305 and IEC 62561-1&2.
TIER IV - EARTHING SYSTEM Supply, Installation, Testing and Commissioning of maintenance free Earthing system comprising of 250micron copper bonded earth rod 3 mtr x 3/4" Dia long Earth electrode, inspection pit with polymer lid is load rated to 5000kg and suitable for general to heavy duty, copper rod to tape clamp and 25Kg of Earth Enhancing compound whose resistivity is less than 0.12 as per IEEE 80-2013 & IS 3043-2018 for normal soil condition . The compound shall be free from carbon and graphite and conductive in nature and should accomodate 60% of its volume. The rod should be threaded on both ends and all component should be tested as per IEC 62561. Note: 3m length shall vary depending upon soil resistivity.
Supply, Installation, Testing and Commissioning of 25x3mm Copper Tape Conductor with fixing accessories and should be tested for electrical resistivity test , Tensile strength, Environmental Test (salt spray & humidity test) to meet the requirements of IS/IEC 62305 and IEC 62561-1&2.
Supply, Installation, Testing and Commissioning of Copper Square Tape Clamp for Cross connection and T connection of 25x3mm Aluminium Tape should be tested for electrical resistivity test ,Environmental Test (salt spray & humidity test),Mechanical test and Impulse current withstand capability of 100KA (Class H)to meet the requirements of IS/IEC 62305 and IEC 62561-1&2.
SIGNAGES M & L for Signages for high rise buildings for Fire exit/ Refuge area/ fire extinguishers/ emergency telephone/alarm sounder/manual activating device etc as per NBC 2016 and IS-9457 (2005)and IS-12349 (1988)
M & L for Signages for high rise buildings for Fire exit / Refuge area/ fire extinguishers etc with aluminium frame and LED light inside as NBC 2016 and IS-9457 (2005)and IS-12349 (1988)
HDPE DWC PIPES IN ROAD CROSSING FOR LAYING OF CABLES IN FUTURE Supply and lay in trenches HDPE DWC pipe 300 mm dia IS- 16098, SN4 RM stiffness class complete with fittings
M & L for chamber ( inspection Pit) of size 750x750mm and 750mm deep ( Internal diamensions)with MS sheet 3.15 mm cover on top
SHANTI CONSTRUCTION (GUJ) PVT. LTD.
Rds Project ltd.
IRON TRIANGLE LIMITED
Som Projects Pvt. Ltd.
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.05 MB
Download all tender documents and submit your bid