Updated dates
Tender Value
₹14.1 Cr
EMD Value
₹3.5 L
Closing Date
5 Feb 2026, 6:45 pmClosed
Akash Bhatia
MATERIALS AND CONTRACTS, HEAD OFFICE INDIAN OIL CORPORATION LIMITED (MARKETING DIVISION) INDIAN OIL BHAVAN G-9, ALI YAVAR JUNG MARG, BANDRA (EAST), MUMBAI - 400051, INDIA
SUPPLY, INSTALLATION, TESTING And COMMISSIONING OF HT PANEL, TRANSFORMERS, DG SETS, LT PANELS, CABLING, LIGHTING, EARTHING AND ALLIED WORKS IN PETROLEUM STORAGE DEPOT AT DIMAPUR, NAGALAND.
2025_MKTHO_188189_1
MnC/ENG-18/PT-121/25-26
Open Tender
Electrical Works
365 days
As per NIT
As per NIT
2 documents required · 2 mandatory
₹3.5 L
Yes
Online through VC
30 Apr 2026
2 Jan 2026
6 Feb 2026
2 Jan 2026
5 Feb 2026
15 Jan 2026
2 Jan 2026 - 12 Jan 2026
12 Jan 2026
(A) SUPPLY OF FOLLOWING ITEMS :
Design, Engineering, Supply, Documentation, Factory acceptance Test, dispatch to site for the following items. General Notes: a. The respective items shall also include supply of commissioning spares as required. b. Third party inspection for the supply items shall be in tenderer's scope. c. Approval of TPI agency to be engaged for inspection by the successful bidder shall be obtained from IOCL on award of contract. d. Clearance of all materials to be supplied shall be based on compliance to Technical Specification/ Data Sheet to be submitted by successful bidder to Consultant of IOC, including applicable QAP/ITP upon placement of order by the Corporation.
H POLE STRUCTURE
Design, Engineering, Supply of H-pole Structure for 11 KV Incoming Power Supply with Gang operated isolator, D.O. fuse with base, lightning arrestors ,earth switch, Insulator, earthing, padlocking, for11 KV Supply as per attached specifications / Standard drawing. Work shall also include obtaining approval from local electrical inspectorate/CEA.
Supply of trivector meter as per state electricity approved make for tariff metering including metering enclosure. The rates shall be inclusive of calibration at State Electricity Board
POWER TRANSFORMER & LIGHTING TRANSFORMER
Design, Engineering, Supply of 1000KVA, 11KV/0.433KV, Dyn11 , Oil filled ,ONAN type with OLTC + AVR Tap changer Power Transformer ( Efficiency Class -2 ) along with weather proof double compression Ni plated brass cable glands and cable lugs for all incoming and outgoing cables and all other accessories as per attached specification and single line diagram /Data sheet and SLD - NO C241135-00-EL-SLD-4001.& MR NO-C241135-00-EL-MR-4002 (INCLUSIVE OF HEAT RUN TEST) Note: The civil works required for power transformer foundation is excluded and shall be paid separtely under respective civil item.
Design, Engineering, Supply of 150KVA, 0.433/0.415KV, Dyn11 dry type Lighting Transformer along with Weather proof double compression Ni plated brass cable gland and cable lugs for all incoming and outgoing cables as per attached specification and single line diagram SLD - NO C241135-00-EL-SLD-4001.(INCLUSIVE OF HEAT RUN TEST )
Design, Engineering, Supply of 50KVA, 0.433/0.415KV, Dyn11 dry type Lighting Transformer along with Weather proof double compression Ni plated brass cable gland and cable lugs for all incoming and outgoing cables as per attached specification and single line diagram SLD - NO C241135-00-EL-SLD-4001.(INCLUSIVE OF HEAT RUN TEST )
HT SWITCH BOARD
Design, Engineering, Supply of 11 KV, 630A, 26.3kA for 3 sec,VCB panelwith all metering and protection ,Vaccum Circuit breaker, Numerical relay,auxiliary relay,CTs,PTs ,indication lamp, switches along with Weather proof double compression Ni plated brass cable gland and crimping type cable lugs for all incoming and outgoing cables and as per specfication/Data sheet and SLD - NO C241135-00-EL-SLD-4001. & Data sheet C241135-01-EL-DS-4001.
DG SETS
Design, Engineering, Supply of 2x500 KVA ( 2 no. 500 KVA),415 V D.G. Set with 1 no. synchronising panel, Acoustic enclosure, complete with all required accessories like elbow, bellows, AVM pads, lube oil system,cooling system,Diesel oil system, battery system, all required piping, Day Tank of min 990 ltr capacity each along with all pipings with level switch, Exhaust pipe {(a) Asbestos rope lagging from DG exhaust up to silencer for isulation(dia 250mm). (b) Glass wool insulation and cladding in aluminium sheeting (28 G) for 500kVA DG sets beyond silencer (dia 250mm) as per manufacturer's recommendation/CPCB -IE rules)} up to building height( Appx 9.5 meter)+4.5 Mtrs & total stack height ( 14 meter) with bellows / bends insulation etc including civil foundation , Design of exhaust pipe support structure including it's foundation design ,inter connecting cables and cable accessories, Base Channels,minimum commissioning spares including fuel, lubricant etc, Third Party Inspection,Performance load test at site. Suitable size non- FLP , DC, cable glands shall be supplied. One number Lightning arrestor (1000mm long 20mm dia.) shall be supplied. Aviation obstruction lamp ( 2 x 15 W LED ultrabight ( RED) colour ) also be provided as a part of supply of DG Set stack . (Note: Separate rate for supporting arrangement of Exhaust pipe shall be applicable as per the structural rate). DG shall have Auto start, AUTO- Manual sink, Load sharing facility with complete protection.
Supply of exhaust piping for 250 kva dg set- Exhaust pipe {(a) Asbestos rope lagging from DG exhaust up to silencer for isulation(dia 250mm). (b) Glass wool insulation and cladding in aluminium sheeting (24 G) for 250kVA DG sets beyond silencer (dia 250mm) as per manufacturer's recommendation/CPCB -IE rules)} up to building height+3.5 Mtrs with bellows / bends insulation etc including civil foundation , Design of exhaust pipe support structure including it's foundation design ,inter connecting cables and cable accessories
Supply of Exhaust Pipe of suitable size as recommended by OEM including Asbestos rope, glass wool insulation &cladding in Aluminium sheeting. Exhaust pipe of suitable size as perIS:1239/3589 schedule 20 (a) Asbestosrope lagging from DG exhaust up to silencerfor insulation (dia 250mm or as per manufacturer) b) Glass wool insulation and cladding in Aluminiumsheeting (24 G) for DG sets beyond silencer (dia 350mm or as per manufacturer) as per manufacturer's recommendations/CPCB -CEARegulations}.Note: The measurement shall be done for the stack lengthbeyond the exhaust silencer.
Power Control Centre (PCC) : Design, Engineering, Supply of 415V, 3Ph, 4-wire,50Hz, 1600A, 50KA for 1 sec Aluminium busbar , SINGLE front fully draw out compartmentalize, indoor, floor mounted panel with incomers and outgoing feeders, Metering and protection, Numerical relay for ACB feeders, along with Weather proof double compression Ni plated brass cable glands and lugs for all incoming and outgoing feeders as per Technical Specification, -VCS – SS – EL - 4036 & SLD - NO C241135-00-EL-SLD-4001. All feeders shall have facility for safety lockout with padlocking.
Intelligent Motor Control Centre (IMCC) : Design, Engineering, Supply of 415V, 3Ph, 4-wire,50Hz,320A, 50KA for 1 sec Aluminium busbar ,SINGLE ront fully draw out compartmentalize, indoor, floor mounted panel with incomers and outgoing feeders, Metering and protection, Numerical relay for ACB feeders, Intelligent motor control unit for all motor feeders with modbus-TCP/IP communication link, auxiliary relay, ACB-EDO type, MCCBs (with extended operating handel ), contactors, CTs, PTs, indication lamp, switches etc., meters etc. along with Weather proof double compression Ni plated brass cable glands and lugs for all incoming and outgoing feeders as per Technical Specification VCS – SS – EL - 4036 & and SLD - NO C241135-00-EL-SLD-4001& Technical spscification VCS-SS-EL-4001 . All feeders shall have facility for safety lockout with padlocking.
Emergency switch Board (ESB): Design, Engineering, Supply ofSupply of 415V,3 phase 4 wire 50 Hz, 500 A,50 KA for 1 second, motor feeder (draw out ) and MCCB outgoing feeders are fixed type, SINGLE front compartmentalize, indoor, floor mounted panel with incomersand outgoing feeders, Metering and protection, Numerical relay for ACB feeders, Intelligent motor control unit for all motor feeders with modbus-TCP/IP communication link, auxiliary relay, ACB-EDO type, MCCBs (with extended operating handel ), contactors, CTs, PTs, indication lamp, switches etc., meters etc. along with Weather proof double compression Ni plated brass cable glands and lugs for all incoming and outgoing feeders as per technical specification,VCS – SS – EL-4036 and SLD - NO C241135-00-EL-SLD-4001. All feeders shall have facility for safety lockout with padlocking.
Main Power Dist. Board (MPDB) : Design, Engineering, Supply of 415V,3 phase 4 wire 50 Hz, 500 A, 50 KA for 1 second, fixed type, single front compartmentalize, indoor, floor mounted panel with incomers and outgoing feeders, Metering and protection, Numerical relay for ACB feeders along with Weather proof double compression Ni plated brass cable glands and lugs for all incoming and outgoing feeders as per technical specification -VCS – SS – EL-4036 and SLD - NO C241135-00-EL-SLD-4001. All feeders shall have facility for safety lockout with padlocking.
Emergency Main Lighting Distribution Board (EMLDB) : Design, Engineering, Supply of 415V,3 phase 4 wire 50 Hz,100 A, 25 KA for 1 second, fixed type, SINGLE front indoor, compartmentalized , floor mounted Switch Board with Metering and protection, auxiliary relay, MCCBs, Contractor, CTs, PTs, including clock/Timer along with Weather proof double compression Ni plated brass cable glands and lugs for all incoming and outgoing feeders as per technical specification , -VCS – SS – EL-4036 and SLD - NO C241135-00-EL-SLD-4001.All feeders shall have facility for safety lockout with padlocking.
Main Lighting Dist. Board (MLDB): Design, Engineering, Supply of 415V,3 phase 4 wire 50 Hz ,250 A, 25 KA for 1 second, fixed type,SINGLE front indoor, compartmentalized , floor mounted Switch Board with Metering and protection, auxiliary relay, MCCBs, Contractor, CTs, PTs, including clock/Timer along with Weather proof double compression Ni plated brass cable glands and lugs for all incoming and outgoing feeders as per technical specification VCS – SS – EL-4036 and SLD - NO C241135-00-EL-SLD-4001. All feeders shall have facility for safety lockout with padlocking.
CAPACITOR PANEL : Design, Engineering, Supply of 415V, 3Ph-N, 50Hz, 50KA 8 stage 420 KVAR capacitor panel ,IP42 with capacitor banks (50x6, 25x2, 15x3 10x2, 5x1 KVAR), with 14 stage APFC relay, protections ,filters etc. along with Weather proof double compression Ni plated brass cable glands and lugs for all incoming and outgoing feeders as per Technical Specification VCS – SS – EL-4036 and SLD - NO C241135-00-EL-SLD-4001.All feeders shall have facility for safety lockout with padlocking.
FIRE FIGHTING PANEL (FFP) : Design, Engineering, Supply of 415V, 3Ph-N, 50Hz, 50KA ,100A for 1 second, fixed type, single front compartmentalize, indoor,IP-55, floor mounted panel with incomersand outgoing feeders, Metering and protection, Numerical relay for ACB feeders, Intelligent motor control unit for all motor feeders with modbus-TCP/IP communication link, auxiliary relay, ACB-EDO type, MCCBs (with extended operating handel ), contactors, CTs, PTs, indication lamp, switches etc., meters etc. along with Weather proof double compression Ni plated brass cable glands and lugs for all incoming and outgoing feeders as per technical specification , /Data sheet and SLD - NO C241135-00-EL-SLD-4001. All feeders shall have facility for safety lockout with padlocking.
Design, Engineering, Supply of Flame Proof 80 A, 415V, 10KA,3Ph & N, 50HZ sheet steel enclosure flush / surface mounting MOV sub distribuition board (MOV SUB DB of the following incoming and outgoing feeders as per attached specifications technical specification -VCS-SS-EL-4013- and SLD - NO C241135-00-EL-SLD-4001) .i) 1no. - Incomer 80A, 4P MCCB ii) 36 nos.- O/G 16A , MPCB
Design, Engineering, Supply of Flame Proof 63A, 415V, 10KA, 3Ph & N, 50HZ sheet steel enclosure flush / surface mounting MOV Sub distribuition board (MOV SUB DB ) of the following incoming and outgoing feeders as per attached specificationstechnical specification VCS-SS-EL-4013-and SLD - NO C241135-00-EL-SLD-4001. i) 1no. - Incomer 63A, 4P MCCB ii) 24 nos.- O/G 16A , MPCB
BATTERY CHARGER WITH BATTERY & DC BOARD
Supply of Battery Charger (30 kw )cosisting of dual float cum load cum boast charger along with Ni-Cd batteries for half hour backup for 30 KW load as per attached specification along with Weather proof double compression Ni plated brass cable glands and cables lugs for all incoming and outgoing cables including 110V DC, 2 wire, 300A,Cu-Busbar, DC board fed by duel float cum load cum boost charger as per attached single line digram technical specification , /Data sheet and SLD - NO C241135-00-EL-SLD-4001 along with Weather proof double compression Ni plated brass cable gland and cable lugs for all incoming and outgoing cables. Vendor shall supply suitable battery of AH rating calculated as per duty cycle/load details attached SLD - NO C241135-00-EL-SLD-4001 and submit the sizing calculation accordingly.
Supply of Battery for Engine Starting ( Fire water pump) :-Design, Engineering, Manufacturing, assembly, packing and supply of complete set of battery banks. The battery bank shall be suitable for Deisel Engine starting( fire water pump). Battery detail - Exide /Reputed Make( mddel no -MDH-1800) 12 V ,180 AH -4 NOS( 2Working +2 STANDBY)
Supply of Battery for Engine Starting ( 250 kvaDG :-Design, Engineering, Manufacturing, assembly, packing and supply of complete set of battery banks. The battery bank shall be suitable for Deisel Engine starting( fire water pump). Battery detail - Exide /Reputed Make( mddel no -MDH-1800) 12 V ,180 AH -2 NOS( 1Working +1 STANDBY)
MARSHALLING CABINET:
Supply of wall /floor mounted type Marshalling Cabinet (Interphassing cabinet) having 200 terminals suitable for 2.5 mm2 / 1.5 mm2 (Cu.) with required Nos. of Cable Glands as per technical specification Marshalling cabinet shall be of free standing, enclosed type and shall be designed for bottom entry for cable connection. Cabinet structure shall be sound and rigid and shall be provided with removable lifting lugs. Cabinets shall be fabricated from cold rolled cold annealed (CRCA) steel sheet of minimum 1.5 mm thickness for sides and Top and 2 mm thickness for doors and suitably reinforced to prevent warping and buckling. The rack/ rail mounting plates inside the cabinets shall be of 3 mm thickness. Cabinets shall be thoroughly deburred, and all sharp edges shall be grounded smooth after fabrication. Cabinet frame shall be of 9-fold profiled CRCA steel sheet or of Angle iron frame using minimum section of 50 x 50 x 4 mm angle.
Supply of wall /floor mounted type Marshalling Cabinet (Interphassing cabinet) having 50 terminals suitable for 2.5 mm2 / 1.5 mm2 (Cu.) with required Nos. of Cable Glands as per technical specification Marshalling cabinet shall be of free standing, enclosed type and shall be designed for bottom entry for cable connection. Cabinet structure shall be sound and rigid and shall be provided with removable lifting lugs. Cabinets shall be fabricated from cold rolled cold annealed (CRCA) steel sheet of minimum 1.5 mm thickness for sides and Top and 2 mm thickness for doors and suitably reinforced to prevent warping and buckling. The rack/ rail mounting plates inside the cabinets shall be of 3 mm thickness. Cabinets shall be thoroughly deburred, and all sharp edges shall be grounded smooth after fabrication. Cabinet frame shall be of 9-fold profiled CRCA steel sheet or of Angle iron frame using minimum section of 50 x 50 x 4 mm angle.
GROUND MOUNTED STREET LIGHTING POLE
Supply of 9.0 meter height (from Finished ground level) G.I. Street lighting pole (octagonal/polygonal) double arm section; Galvanisation of 610gms/sq. mtr for ground mounting , complete with foundation bolts, all accessories, Zinc passivated hardware for fixtures support and pole support , GI pipe for cable (class B) protection , clamp, nuts, bolts,etc. including supply of commissioning spares, as required. (Specific requirement : Bottom dia : 150mm, Top dia-70mm , sheet thickness - 3mm relevant standard for section - Hot rolled MS plate equivalent to BS EN-10025:2004,Gr.5355JO, IS-2026 (latest updated) , Gr.E350A, for base plate & foundation bolt as per IS:2026:(latest updated), Gr.E250A) NOTE - FLAMEPROOF JBs inside the pole or at the foot of the pole & termination block (as applicable) and the civil works required for Street Lighting pole foundation is included in the bidder's scope and payment for the same will be made seperately
Supply of 9.0 meter height (from Finished ground level) G.I. Street lighting pole (octagonal/polygonal) single arm section; Galvanisation of 610gms/sq. mtr for ground mounting , complete with foundation bolts, all accessories, weather proof JBs at the foot of the pole & termination block (as applicable) Zinc passivated hardware for fixtures support and pole support , GI pipe for cable (class B) protection , clamp, nuts, bolts,etc. including supply of commissioning spares, as required. (Specific requirement : Bottom dia : 150mm, Top dia-70mm , sheet thickness - 3mm relevant standard for section - Hot rolled MS plate equivalent to BS EN-10025:2004,Gr.5355JO, IS-2026 (latest updated) , Gr.E350A, for base plate & foundation bolt as per IS:2026:(latest updated), Gr.E250A) NOTE - The civil works required for Street Lighting pole foundation is included in the bidder's scope subjected to IOCL approval and payment for the same will be made seperately
Supply of 2.5 mtr height Swan neck GI Lighting pole (50mm as per IS 1239 - Medium duty ; Galvanisation of 610 Gms/sqm) for structural mounting , complete with all clamping arrangements for cables including accessories , flameproof proof JBs inside the pole or at the foot of the pole & termination block (as applicable), zinc passivated hardware for fixtures support & pole support , clamps, nuts, bolts, etc. including supply of commissioning spares , as required. NOTE - The civil works required for Street Lighting pole foundation is included in the bidder's scope and payment for the same will be made seperately .
FLAMEPROOF AND NON FLP JUNCTION BOXES- supply
Supply of Flameproof 16A, 415V, Ph-N, 6-way ,Cast Aluminium (LM-6 )Junction boxes; Junction boxes with terminals block with additional earthing terminals and end clamps etc. including 3 Nos. Ex’d’ double compression stainless steel cable glands with PVC shrouds suitable for 2nos.-3.5cx50sq.mm (Al) and 4 nos- 3cx2.5 sq. mm (cu.) XLPE, FRLS cables, 2mm thick Alu canopy shall be provided.
Supply of Weather proof 16A, 415V, Ph-N, 6-way ,Cast Aluminium (LM-6 )Junction boxes; Junction boxes with terminals block with additional earthing terminals and end clamps etc. including 3 Nos. double compression stainless steel cable glands with PVC shrouds suitable for 2nos.-3.5cx50sq.mm (Al) and 4 nos- 3cx2.5 sq. mm (cu.) XLPE, FRLS cables, 2mm thick Alu canopy shall be provided.
Supply of Flame proof 16A, 240V 4-way, 125 mm (minimum) internal dimensions junction boxes with terminals block with additional earthing terminals and end clamps etc. including 4 Nos. Ex’d’ double compression Ni plated brass cable glands with PVC shrouds suitable for 3x2.5 sq. mm (cu.) XLPE, FRLS cable,canopy as per attached specifications.
Supply of Weather proof 16A, 240V 4-way, 125 mm (minimum) internal dimensions junction boxes with terminals block with additional earthing terminals and end clamps etc. including 4 Nos. W.P. double compression Ni plated brass cable glands suitable for 3x2.5 sq. mm (cu.) XLPE, FRLS cable ,canopy as per attached specifications.
CABLE TRAY
Supply of Cable Tray 100x30x3mm thick runners, Rungs at 300mm spacing, Min.2400mm length along with required Coupler Plate with stainless Hard-ware ,Hold on clamps With stainless Hard- ware , Horizontal /Vertical - Inside / Outside bends etc. suitable for following G.I.Cable Tray and Tray cover.
750 wide G.I. ladder type cable tray (for sub station)
600 wide G.I. ladder type cable tray (for plant area)
300 wide G.I. ladder type cable tray (for plant area)
1.5mm Thick cover for 750 wide G.I. ladder type cable tray
1.5mm Thick Cover for 600 wide G.I. ladder type cable tray
1.5mm Thick Cover for 300 wide G.I. ladder type cable tray
Supply of 150 mm x 50mm x 2 mm thick GI perforated cable trays
Supply of 100 mm x 25mm x 2 mm thick GI perforated cable trays
Supply of 1.5mm Thick G.I.Cover(155mm wide) for 150mm G.I. perforated cable trays
Supply of 1.5mm Thick G.I.Cover(105 wide) for 100mm G.I. perforated cable trays
HIGH MAST LIGHTING TOWERS
Supply of 30 Mtr. height High Mast complete with accessories as per specifications. The cost also includes supplying and providing trailing cable of suitable size from Switch Plug & Socket at the foot of high mast to the junction box at the top, FLP Motor, suitable size double compression, cable glands. Note: a) The civil works required for high mast foundations are excluded from scope of this item and shall be paid separately. b) The item includes the S/I of raising lowering system comprising double drum winch, 6mm diameter SS wire rope, trailing cable, connector, integral power tool motor, manual handle, junction box, lightening finial (Lightening arrestor), including low intensity LED type double dome aviation obstruction light. c) Tenderers should note that junction box shall be provided at the top of the high mast as per specifications.Rates for lighting fixtures and earth pits shall be paid separately. d) Bidder to provide design and drawing for foundation of high mast tower. e) The high Mast system shall be suitable for 55m/sec wind speed (as per IS-875), with head frame, winch mounting bracket, luminaries carriage suitable to install 16 nos. 350W LED FLD in Symmetrical arrangement (0-360Deg). e) The scope includes the supply foundation bolts manufactured from EN 8 grade galvanised steel along with nuts, washers, anchor plate and common template. f) Lightning arrestor(1000mm long 20mm dia.) & aviation obstruction lamp ( 2 x 15 W LED ultrabight ( RED) colour ) shall also be provided as a part of supply ofhigh mast. g) High mast lantern Carraige shall be designed for mounting 16/9 Nos Luminiares ( 350 W LED) - BVP485 LED 427 CW FLNB PSU SPD GR/ BVP485 LED485 CW NB PSU SPD GR , PHILIPS make OR Equivalent. h) Scope includes supply of approved/ reputed make single dome aviationobstruction light with 2x15W LED ultrabright (RED) colour lamp, anintegral control gear, double compression stainless steel cable glandsand mounting accessories shall be provided.
Supply of flameproof outdoor, made of 14 SWG CRCA sheet, IP-65, stand mounted feeder pillar with 1 no. 32A TPN MCB incomer, single dial time switch, 22A TP contactor for the automatic switching of luminaries, power tool control with 2 no 9A contactors and raise lower push button, Incoming 35-70 sq. mm and out going 12 & 2.5 sq. mm terminals & 1 no. outgoing upto 35-70 sqm for looping. (Necessary Civil Works shall be paid seperately)
END TERMINATION KITS
Supply of raychem make 11KV (UE) grade of following type end termination kit suitable for 3Cx300 sq.mm (AL),Armoured,FRLS,Screened Cable.
11 KV grade outdoor type
11 KV grade indoor type
SUPPLY,OF 11KV HT CABLES- 11 kV (U E) grade HT Cable with stranded compact Aluminium conductor,conductor screened by extruded semi conducting compound, XLPE insulated,colour coded, insulation screened by extruded semi conducting compound followed by a layer of copper tape, cores laid up together suitably extruded PVC innersheathed, strip (for multi core) and overall extruded FRLS PVC outer sheathed cable conforming to IS 7098-2. The item also includes cable Tag 2mm thick Aluminium with No. punched on it and shall be securely attached to the cable by not less than two turns of 20 SWG GI wire conforming to IS 280.
11 KV Grade (UE),3Cx300Sqmm(AL), XLPE, Screened,Armoured , FRLS Power cables as per specification
3CX25 sq. mm (Al)
3CX35 sq. mm (Al)
3CX50 sq. mm (Al)
3CX70 sq. mm (Al)
3.5Cx400 sq. mm (Al)
3.5Cx240 sq. mm (Al)
3.5Cx185 sq. mm (Al)
3.5Cx150sq. mm (Al)
3.5Cx120sq. mm (Al)
3.5Cx95sq. mm (Al)
3.5Cx70 sq. mm (Al)
3.5Cx50 sq. mm (Al)
3.5Cx35 sq. mm (Al)
3.5Cx25 sq. mm (Al)
4Cx10 sq. mm (Cu)
4Cx6 sq. mm (Cu)
3Cx6 sq. mm (Cu)
3Cx6 sq. mm (Cu) FIRE SURVIVAL CABLE-Annealed electrolytic copper conductor, heat barrier, XLPE, LSZH inner sheath G.S. wire and LSZH outer sheath as per IS 7098-I/BS 7846 testing as per IEC 331 & BS 6387 DETAIL SPECIFICATION- Conductor - Solid/Stranded, Plain /Tinned Heat Barrier - Mica Tape Insulation - XLPE Innersheath - LSZH Compound Armoured - G.S. Round Wire/ Flat S
4Cx4 sq. mm (Cu)
3Cx2.5 sq.mm (Cu) - Power
2Cx95 sq.mm (Cu) - Power
2Cx16 sq.mm (Cu) - Power
CABLE GLAND Supply of weather proof double compression Ni plated brass cable gland of the following sizes of XLPE,Arm. FRLS cables.
3CX25 sq. mm (Al)
3CX35 sq. mm (Al)
3CX50 sq. mm (Al)
3CX70 sq. mm (Al)
3.5Cx400 sq. mm (Al)
3.5Cx240 sq. mm (Al)
3.5Cx185 sq. mm (Al)
3.5Cx150sq. mm (Al)
3.5Cx120sq. mm (Al)
3.5Cx95sq. mm (Al)
3.5Cx70 sq. mm (Al)
3.5Cx50 sq. mm (Al)
3.5Cx35 sq. mm (Al)
3.5Cx25 sq. mm (Al)
4Cx10 sq. mm (Cu)
4Cx6 sq. mm (Cu)
4Cx4 sq. mm (Cu)
3Cx2.5 sq.mm (Cu) - Power
2Cx95 sq.mm (Cu)
2Cx16 sq.mm (Cu)
CABLE GLAND Supply of Flameproof double compression nickel plated brass cable gland suitable for following XLPE , FRLS cable sizes & as per relevant IS for hazardous area Zone-1, Gas group ,IIA/IIB, Temp. Class T3.
3CX2.5 sq. mm (Cu)
3CX25 sq. mm (Al)
3CX35 sq. mm (Al)
3CX50 sq. mm (Al)
3CX70 sq. mm (Al)
3.5Cx400 sq. mm (Al)
3.5Cx240 sq. mm (Al)
3.5Cx185 sq. mm (Al)
3.5Cx150sq. mm (Al)
3.5Cx120sq. mm (Al)
3.5Cx95sq. mm (Al)
3.5Cx70 sq. mm (Al)
3.5Cx50 sq. mm (Al)
3.5Cx35 sq. mm (Al)
3.5Cx25 sq. mm (Al)
4Cx10 sq. mm (Cu)
3Cx6 sq. mm (Cu)
4Cx6 sq. mm (Cu)
4Cx4 sq. mm (Cu)
2Cx95 sq.mm (Cu) - Power
2Cx16 sq.mm (Cu) - Power
Supply of Flameproof Nickle plated brass stopper plugs of following size including supply of stopper plugs.
1/2 inch size
3/4 inch size
1 inch size
Supply of Hot dip galvanized GI earth bus bar of size 390 x 50 x 12 thick with fixing materials-
Supply of approved make second class red bricks of standard size for making layer inside cable buried trenches
Supply of Insulators for mounting air termination rods and down conductors
SUPPLY OF FOLLOWING GENERAL SAFETY EQUIPMENTS
Supply of 1.1 KV, 900 mm wide, electric grade floor rubber mat (in pieces of length not less than 2 mtrs.) conforming to IS:15652 & ISI marked.
Supply of 11 KV, 900 mm wide, electric grade floor rubber mat (in pieces of length not less than 2 mtrs.) conforming to IS:15652 & ISI marked.
Supply of Fire extinguishers CO2 type in 4.5kg capacity as per IS 2878/UL 154 complete with handle , fixing bracket etc.
Supply of Shock treatment chart ( laminated type) in bilingual language (Hindi , English & Telgu ).
Supply of 415 V , Danger notice plate / caution board as per IS:2551.
Supply of 11 KV , Danger notice plate / caution board as per IS:2551.
Supply of First aid box of GI, 18 swg sheet with necessary items.
Supply of G.I fire bucket set. (4 no. each of 9 litre) as per IS:2546 filled with sand, painted with red colour along with its stand for holding the sand bucket including rain hood for sand bucket.
Supply of Rubber hand glove of 11 KV grade as per IEC60903.
Supply of Rubber hand glove of 1.1KV grade as per IS:4770.
Supply of Fire extinguishers DCP type in 10kg / 9 kg capacity complete with handle , fixing bracket etc.
Supply of 11KV, 50A DOF fuse for HT yard, fuse shall be suitable for installation in 11KV H-pole.
SUPPLY OF LOCAL CONTROL STATION (FLP & NON FLP)
Supply of Weather proof Local control station provided with START STOP PB, Ammeter, 3 mm thick FRP Canopy with side cover, including double compression Ni plated brass cable glands & plugs as required as per attached specifications.(TYPE -A).
Supply of FLP (Zone-1, IIA/IIB, T3) Local control station provided with START STOP PB, Ammeter ( AUTO ,REMORE ,MANUAL ) 3 mm thick FRP Canopy with side cover, including flameproof double compression Ni plated brass cable glands & plugs as required as per attached specifications (TYPE -C).
Supply of FLP (Zone-1, IIA/IIB, T3) Local control station provided with START STOP PB, 3mm thick FRP Canopy with side cover, including flameproof double compression Ni plated brass cable glands & plugs as required as per attached specifications.(TYPE -D).
EPB: Supply of weather proof emergency stop push button(EPB) with ON-OFF LED indication, break glass type enclosure,3mm thick FRP canopy, weather proof double compression Nickel Plted Brass cable glands(2 nos.) and 1 NO+1 NC contact .
EPB: Supply of Flameproof proof emergency stop push button(EPB) with ON-OFF LED indication, break glass type enclosure,3mm thick FRP canopy, weather proof double compression Nickel Plted Brass cable glands(2 nos.) and 1 NO+1 NC contact .
Supply of Emergency stop push button (EPB) for Power transformer with break glass type weather proof enclosure, FRP canopy, cable glands etc.
63A/16A SWITCH SOCKET & PLUG (FLP & NON FLP)
Supply of flameproof Interlocking type switch sockets and plugs of following ratings as per attached specifications. All switch sockets shall be provided with 3mm thick FRP canopy with side cover and required no. of FLP double compression Ni plated brass cable glands and FLP stopping plug as per attached specification sheets.
Supply of 415V,3 phase 63A flame proof switch socket and plug
Supply of 240V, 3-pin, 16A/6A flame proof switch socket and plug
LIGHTING FIXTURES & ACCESSORIES
Supply of Weather proof/Flameproof LED Lighting Fixtures & Accessories as per attached specifications.(All Lighting fixtures shall be provided with required no. of double compression nickle plated brass cable glands and stopping plug.)
Supply of 240 Volt AC, 100W WELL GLASS FLAMEPROOF Ex'd ' LED lighting fixtures (LM-6) with integral control gear box, lamp, FLP Double compression Ni plated brass cable glands ,Lugs etc complete suitable for mounting to (octagonal/polygonal) lighting pole as per attached specification.
Supply of 110 Volt DC, 100W WELL GLASS FLAMEPROOF Ex'd ' LED lighting fixtures (LM-6) with integral control gear box,lamp, FLP Double compression Ni plated brass cable glands ,Lugs etc complete suitable for mounting to (octagonal/polygonal) lighting pole as per attached specification.
Supply of 240 Volt AC,200 W LED Flame proof flood lighting fixture with integral Control gear box,FLP Double compression Ni plated brass cable gland ,lugs etc complete suitable for mounting to lighting pole.
Supply of 110 Volt DC, 200W LED Flame proof flood lighting fixture with integral Control gear box,FLP Double compression Ni plated brass cable gland ,lugs etc complete suitable for mounting to lighting pole.
Supply of 240 Volt AC, 45W Well glass Flameproof Ex'd' LED lighting fixtures (LM-6) with integral control gear box,lamp ,FLP Double compression Ni plated brass cable glands ,Lugs and all other accessories.
Supply of 240V AC specially designed flood light luminaries 350W LED lamps( BVP485 LED 427 CW FLNB PSU SPD GR Philips make or equivalent) on High Masts(.The cost shall include supply and providing 3C x 2.5 mm² unarmoured copper cable from the junction box at the top of mast to each lighting fixtures including terminations with suitable glands, Lugs etc all complete.
Supply of 110V DC specially designed flood light luminaries 350W LED lamps( BVP485 LED 427 CW FLNB PSU SPD GR Philips make or equivalent) on High Masts(.The cost shall include supply and providing 3C x 2.5 mm² unarmoured copper cable from the junction box at the top of mast to each lighting fixtures including terminations with suitable glands, Lugs etc all complete.
Supply of 240V AC 90W LED Weather proof street lighting fixture with integral Control gear box,WP Double compression Ni plated brass cable gland ,lugs etc complete suitable for mounting to above lighting pole as per attached specification of the LED lighting fixture and accessories.
Multi Cable Transit (MCT) BLOCKS: Supply of MCT block with SS Frame with EPDM Modules, Stay plate, Compression wedge, Lubricant etc complete with all accessories for following area as per the respective cable schedule/sizes.
MCT-PMCC Building (for LT Power Cables- 24 incomer/outoging Cables + 30% Spare blocks )
MCT-Control room (for LT Power cables -12 incomer/outoging Cables + 30% Spare blocks)
Invoice Room (for LT Power cables - 3 incomer/outoging Cables + 30% Spare blocks)
Sample Room (for LT Power cables - 3 incomer/outoging Cables + 30% Spare blocks)
TT Crew Rest Room (for LT Power cables - 6 incomer/outoging Cables + 30% Spare blocks)
Storage Room (for LT Power cables - 3 incomer/outoging Cables + 30% Spare blocks)
(B) INSTALLATION, TESTING & COMMISSIONING OF FOLLOWING ITEMS:
General notes i) The supplied items are to be installed at various places as mentioned in the layout drawing ii) For all the items under Part B of this schedule, the rates to be quoted include:-(A) Charges towards materials/ equipment handling including loading/ unloading within the site. Installation, Laying, Fixing, Erection works including supply of all erection equipment, tools & tackles, labour, consumables/hardware etc required for installation / laying / fixing / erection, testing & commissioning of all the items shall also form part of the items.These items rates to be quoted for installation / laying / fixing / erection of supplied items under Part-A without the cost of supply of materials that is already covered in Part-A. (B) Cutting, aligning to plumb & levels, fabrication, welding etc as per site requirements ; Testing and Commissioning of all items/ equipment as per attached specifications, data sheets, codes and directions of site in charge and QAP; Chipping of walls, drilling, making holes, patching up works with plastering including bringing the surfaces to original condition etc; Unless otherwise specified, the civil/ structural works required for erection & installation of items under Part B shall be paid separately under respective items.
H POLE STRUCTURE
Installation of ground mounted 11 kV incoming and outgoing DP structure as per enclosed sketch No. PC159-MA-1222 including handling, transportation to erection site, inspection, aligning, leveling, making civil foundation, fixing in position by nut bolts welding etc, fixing of Gang operated isolator, HT D.O. fuse with base, bushings, lightning arrestor,earthing, padlocking etc. by nut bolts welding etc earthing of poles; supply of GI hardware; GI pipe sleeves etc., all work, labour, materials complete as per drg. and specifications, codes & standards and direction of engineer in- charge.
Installation,testing and commissioning of trivector meter.
POWER TRANSFORMER AND LIGHTING TRANSFORMER
Transporatation to the erection site, inspection at site, Installation, Testing & Commissioning of 1000 KVA, 33/0.433KV, Dyn11, ONAN type with OLTC + AVR Tap changer Power Transformer along with its accessories including handling , transportation of transformers and it’s accessories/ parts supplied loose from owner’s store to place of erection , unpacking and inspection ,required placing in position on base channels / flats / rails provided on foundation assembly of all loose accessories and parts , Operational and functional checking of all work,glanding and termination of power,control & interfacing cables, labour and materials complete as per drawing and documents, specification, codes and standard and direction of engineer in-charge .
1.0 MVA, 11/ 0.433 kV, Dyn11,Oil filled, ONAN with OLTC + AVR changer, POWER TRANSFORMER complete with all accessories.
Transporatation to the erection site, inspection at site, Installation, Testing & Commissioning of 150 KVA, 0.433/0.415KV, Dyn11, Dry type lighting Transformer along with its accessories including handling , transportation of transformers and it’s accessories/ parts supplied loose from owner’s store to place of erection , unpacking and inspection , Making of foundation, required placing in position on base channels / flats / rails provided on foundation assembly of all loose accessories and parts , Operational and functional checking of all work,glanding and termination of power,control & interfacing cables, labour and materials complete as per drawing and documents, specification, codes and standard and direction of engineer in-charge .
Transporatation to the erection site, inspection at site, Installation, Testing & Commissioning of 50 KVA, 0.433/0.415KV, Dyn11, Dry type lighting Transformer along with its accessories including handling , transportation of transformers and it’s accessories/ parts supplied loose from owner’s store to place of erection , unpacking and inspection , Making of foundation, required placing in position on base channels / flats / rails provided on foundation assembly of all loose accessories and parts , Operational and functional checking of all work,glanding and termination of power,control & interfacing cables, labour and materials complete as per drawing and documents, specification, codes and standard and direction of engineer in-charge .
DG SETS
INSTALLATION, TESTING & COMMISSIONING OF DG SETS: Receiving of 2x500 KVA ( 2 no. 500 KVA) DG SET from store, transporting to erection site including cable glanding & power / control cable termination ,handling, arrangement of transport vehicle, loading & unloading equipment like crane, slings etc., placing on foundation, fixing on foundation channels, aligning, levelling etc. assembling of all accessories / parts supplied loose,installation of exhaust pipe and its supports structure including foundation of supports structure, fuel tank, battery system,AVM pads,Silencer,fuel oil system,lube oil system ,Starting system,governing system, dehydration of windings (If required), plugging unused cable gland cutout in alternator terminal box, checking of bearing grease / lubricant, checking of IR values, checking of continuity of windings, checking of direction of rotation, installation of acoustic enclosure for DG set, necessary hardware’s, testing & commissioning of complete DG set together with synchronising panel, functional testing of synchronising panel with all accessories, all performance tests of DG Sets, all works, labour and materials complete as per drawings & documents, specifications, codes & standards and instructions / directions of ENGINEER IN CHARGE .(Note: Separate rate for supporting exhaust pipe shall be applicable as per structural rate quoted) Note: a) Separate rate for supporting structure shall be applicable as per structural rate. b) Foundation for DG is not in bidder's scope
INSTALLATION, TESTING & COMMISSIONING OF DG SET: Receiving of 415V,250KVA DG sets from store, transporting to erection site including including AMF Panel installation, cable glanding & termination of power,control & interfacing cables , handling, arrangement of transport vehicle, loading & unloading equipment like crane, slings etc., placing on foundation, fixing on foundation channels, aligning, leveling etc. assembling of all accessories / parts supplied loose,installation of exhaust pipe and its structure, fuel tank, battery system,AVM pads ,Silencer,fuel oil system,lube oil system,Starting system,governing system, dehydration of windings (If required), plugging unused cable gland cutout in alternator terminal box, checking of bearing grease / lubricant, checking of IR values, checking of continuity of windings, checking of direction of rotation, installation of acoustic enclosure for DG set, necessary hardware’s, checking, testing & commissioning of complete DG set together with control pane( MF Panel),functional testing of control panel with all accessories,all performance tests of DG Sets, all works, labour and materials complete as per drawings & documents, specifications, codes & standards and instructions / directions of engineer-in-charge. Note: a) Separate rate for supporting structure shall be applicable as per structural rate. b) Foundation for DG Set is not in bidder's scope
Installation of exhaust piping for 250 KVA DG set- Exhaust pipe {(a) Asbestos rope lagging from DG exhaust up to silencer for isulation(dia 250mm). (b) Glass wool insulation and cladding in aluminium sheeting (24 G) for 250kVA DG sets beyond silencer (dia 250mm) as per manufacturer's recommendation/CPCB -IE rules)} up to building height+3.5 Mtrs with bellows / bends insulation etc including civil foundation , Design of exhaust pipe support structure including it's foundation design ,inter connecting cables and cable accessories
Installation of Exhaust Pipe of suitable size as recommended by OEM including Asbestos rope, glass wool insulation &cladding in Aluminium sheeting. Exhaust pipe of suitable size as perIS:1239/3589 schedule 20 (a) Asbestosrope lagging from DG exhaust up to silencerfor insulation (dia 250mm or as per manufacturer) b) Glass wool insulation and cladding in Aluminiumsheeting (24 G) for DG sets beyond silencer (dia 350mm or as per manufacturer) as per manufacturer's recommendations/CPCB -CEARegulations}.Note: The measurement shall be done for the stack lengthbeyond the exhaust silencer.
INSTALLATION, TESTING & COMMISSIONING OF HT AND LT SWITCH BOARDS/PANEL
Receiving from store, transporting to erection site including cable glanding & power/ control cable termination, verification of bill of materials, handling, arrangement of transport vehicle, loading / unloading equipment like crane, slings etc., preparation of foundation including supply of foundation base material frame & its fixing by welding on foundation insert plates or angles embedded in the foundation, (The base frame supply cost shall be included in steel fabrication, however, fixing cost shall be included in this item cost.), checking of bill of materials ,placing on foundation channel, aligning, plumbing,leveling, positioning,bus bar bolting between transportation sections, bolting / tack welding with foundation channels, various shipping section of panels including supply of GI bolts, nuts and washers etc., assembling of shipping sections, connection of inner panel busbars, internal wiring, checking of terminal connection for tightness and proper wiring, leakage in vacuum bottle or air circuit breakers, internal cleaning of all panels, chambers, insulation etc., drying out the bus bar chambers in case of low insulation, vermin proofing of panel where cutout & openings have been made sealing, gaps between adjacent panels with gasket, carrying out minor modification in wiring, revisioning / removal & refixing of components such as CT, switches etc. ,installation and testing of protecting relay,auxiliary relay,thermal relay,relay setting,caliberation of meters etc., touch up painting, testing & commissioning of following SWITCHBOARDS together with all accessories, all works, labour & materials complete as per drawings & documents, specifications, codes & standards and instructions / directions of switchboard manufacturer and ENGINEER IN CHARGE.
11kV VCB PANEL: Installation, Testing & Commissioning of 1 No,11 KV, 630A HT VCB for incoming and out going transformer feeder Panel .
Power Control Centre (PCC) : Installation, Testing & Commissioning of 415V, 3Ph, 4-wire,50Hz, 1600A, 50KA for 1 sec Aluminium busbar , Double front fully draw out PCC shall comprise following feeders: 2 nos incomer 4P 1600A ACB feeders with 1 Nos.4P 1600 A ACB Busboupler outgoing-4 nos. 500 A4P ACB 1 NOS 500A 4P MCCB , 2 NOS 320A 4P MCCB MCCB 2 NOS 250A 4P MCCB Nos 5NOS 80 A 4P MCCB Nos 2 NOS 63A 4P MCCB Nos
Intelligent Motor Control Centre (IMCC) : Installation, Testing & Commissioning of 415V, 3Ph, 4-wire,50Hz, 320A, 50KA for 1 sec Aluminium busbar , Double front fully draw out MCC shall comprise following feeders: 1 no. incomer 320A ACB feeder, outgoing-5nos.100 A3P+N MCCB 5nos.80 A3P+N MCCCB 3nos.63 A3P+N MCCCB - 7nos.32 A3P+N MCCCB -
Emergency switch Board (ESB): Installation, Testing & Commissioning of 415V,3 phase 4 wire 50 Hz, 500 A,50 KA for 1 second, motor feeder (draw out ) and MCCB outgoing feeders are fixed type, double front Emergency Switch Board including 2nos 500 A, 4P ACB incomer feeders and outgoing- 3 NOS 250A 4P MCCB , 3 NOS 150 A 4P MCCB 8 NOS 63 A 4P MCCB Nos 7 NOS 100 A 4P MCCB Nos 15 NOS 32 A 4P MCCB Nos
Main Power Dist. Board (MPDB) : Installation, Testing & Commissioning of 415V,3 phase 4 wire 50 Hz,5 00 A, 50 KA for 1 second, fixed type, single front comprising of 1 no.500 A ACB incomer feeder outgoing- 2NOS 250A 4P MCCB , 9NOS 100 A 4P MCCB
Emergency Main Lighting Distribution Board (EMLDB) : Installation, Testing & Commissioning of 415V,3 phase 4 wire 50 Hz 100A, 25 KA for 1 second, fixed type, double front Emergency Main Lighting Distribution Board including clock/Timer comprising of 1 no. 500 A, 4P,100 A MCCB incomer feeder through 50 KVA Lighting Transformer 13 NOS 32 A 4P MCCB , 23 NOS 16 A 4P MCCB
Main Lighting Dist. Board (MLDB): Installation, Testing & Commissioning of 415V,3 phase 4 wire 50 Hz,250 A, 25 KA for 1 second, fixed type, double frontincluding clock/Timer comprising of 4P,250 A MCCB incomer feeder through 250 KVA Lighting Transformer 17 NOS 32 A 4P MCCB , 26 NOS 16 A 4P MCCB
CAPACITOR PANEL : Installation, Testing & Commissioning of 415V, 3Ph-N, 50Hz, 50KA 420 KVAR capacitor panel with capacitor bank (6x50,3x50 ,4x25 KVAR), APFC relay,protections,filters etc..
FIRE FIGHTING PANEL (FPP) : Installation, Testing & Commissioning of 415V, 3Ph-N, 50Hz, 50KA , for 1 second, fixed type, single front Fire Fighting Panel comprising of 1 no. 100A MCCB incomer feeder and 3nos motor feeders with soft starter , 9 nos. DOL motor starter feeders, 3 nos. outgoing MCCB feeders approx.
Installation, Testing & Commissioning of Flame Proof 80 A, 415V, 10KA ,3Ph & N, 50HZ sheet steel enclosure flush / surface mounting MOV sub distribuition board of the following incoming and outgoing feeders as per attached specifications - Aux. BD & Drg. No PC159-MA- 1224 (Sh. 1 of 11). i) 1no. - Incomer 80A, 4P MCCB ii) 36 nos.- O/G 16A , MPCB
Installation, Testing & Commissioning of Flame Proof 63A, 415V, 10KA, 3Ph & N, 50HZ sheet steel enclosure flush / surface mounting MOV Sub distribuition board of the following incoming and outgoing feeders as per attached specifications Aux. BD & Drg. No PC159-MA- 1224 (Sh. 4 of 11). i) 1no. - Incomer 63A, 4P MCCB ii) 24 nos.- O/G 16A , MPCB
BATTERY CHARGER AND BATTERY
Receiving from store, transporting to erection site excluding cable glanding & power/ control cable termination but including handling, arrangement of transport vehicle, loading & unloading equipment like crane, slings etc., preparation of foundation, supply & fixing of base frame by welding on plate insert / angle embedded in the foundation placing on foundation frame (cost for supply of base frame shall be included in steel fabrication item) positioning, levelling, aligning, interpanel bus connection, wiring, fixing in the panel parts separately supplied, fixing with base frame by welding/bolting including supply of GI hardware, touch up painting as required, testing & commissioning of following BATTERY CHARGER with all works, labour and materials complete as per drawings & documents, specifications, codes & standards and instructions / directions of ENGINEER IN CHARGE. NOTE: installation of battery corresponding to this battery charger is considered in this item.
Installation, Testing & Commissioning of 110V., BATTERY CHARGER consisting of dual float cum load cum boost charger with DCDB.and Ni-Cd batteries for half hour backup.
Battery for Engine Starting ( Fire water pump) :-Installation, Testing & Commissioning of of battery banks. The battery bank shall be suitable for Deisel Engine starting( fire water pump). Battery detail - Exide /Reputed Make( mddel no -MDH-1800) 12 V ,180 AH -4 NOS( 2Working +2 STANDBY)
Battery for Engine Starting ( 250 kvaDG :-Installation of complete set of battery banks. The battery bank shall be suitable for Deisel Engine starting( fire water pump). Battery detail - Exide /Reputed Make( mddel no -MDH-1800) 12 V ,180 AH -2 NOS( 1Working +1 STANDBY)
Marshalling Cabine
Installation of wall mounted type Marshalling Cabinet (Interphassing cabinet) having 200 terminals suitable for 2.5 mm2 / 1.5 mm2 (Cu.) with required Nos. of Cable Glands as per technical specification
Installation of wall mounted type Marshalling Cabinet (Interphassing cabinet) having 50 terminals suitable for 2.5 mm2 / 1.5 mm2 (Cu.) with required Nos. of Cable Glands as per technical specification (One for DG set at DG room and one for Fire Fighting Panel at FWPH)
LIGHTING FIXTURE & ACCESSORIES
Installation of 240 Volt AC, 100W WELL GLASS FLAMEPROOF Ex'd ' LED lighting fixtures (LM-6) with integral control gear box, lamp, FLP Double compression Ni plated brass cable glands ,Lugs etc complete suitable for mounting to (octagonal/polygonal) lighting pole as per attached specification.
Installation of 110 Volt DC, 100W WELL GLASS FLAMEPROOF Ex'd ' LED lighting fixtures (LM-6) with integral control gear box,lamp, FLP Double compression Ni plated brass cable glands ,Lugs etc complete suitable for mounting to (octagonal/polygonal) lighting pole as per attached specification.
Installation of 240 Volt AC,200 W LED Flame proof flood lighting fixture with integral Control gear box,FLP Double compression Ni plated brass cable gland ,lugs etc complete suitable for mounting to lighting pole.
Installation of 110 Volt DC, 200W LED Flame proof flood lighting fixture with integral Control gear box,FLP Double compression Ni plated brass cable gland ,lugs etc complete suitable for mounting to lighting pole.
Installation of 240 Volt AC, 45W Well glass Flameproof Ex'd' LED lighting fixtures (LM-6) with integral control gear box,lamp ,FLP Double compression Ni plated brass cable glands ,Lugs and all other accessories.
Installation of 240V AC specially designed flood light luminaries 350W LED lamps( BVP485 LED 427 CW FLNB PSU SPD GR Philips make or equivalent) on High Masts(.The cost shall include Installation and providing 3C x 2.5 mm² unarmoured copper cable from the junction box at the top of mast to each lighting fixtures including terminations with suitable glands, Lugs etc all complete.
Installation of 110V DC specially designed flood light luminaries 350W LED lamps( BVP485 LED 427 CW FLNB PSU SPD GR Philips make or equivalent) on High Masts(.The cost shall include Installation and providing 3C x 2.5 mm² unarmoured copper cable from the junction box at the top of mast to each lighting fixtures including terminations with suitable glands, Lugs etc all complete.
Installation of 240V AC 90W LED Weather proof street lighting fixture with integral Control gear box,WP Double compression Ni plated brass cable gland ,lugs etc complete suitable for mounting to above lighting pole as per attached specification of the LED lighting fixture and accessories.
GROUND MOUNTED STREET LIGHTING POLE
Installation of 9.0 meter height (from Finished ground level) G.I. Street lighting pole (octagonal/polygonal) double arm section; Galvanisation of 610gms/sq. mtr for ground with earthing arrangement as per IS:2713, mounting of Flameproof / Weatherproof LED street lighting fixture as mentioned below. Lighting pole shall be supplied along with all required hardwares for installation of lighting pole like foundation Nuts & bolts,Washers,WP JBs, WP Ni plated brass cable glands, Cable lugs ,stopping plug for un-used cable entries etc complete along with mounting hardwares for lighting fittings, wiring with 3x2.5 sq. mm (cu ) cable between LTG SUB DB to (JB/control gear box wherever applied) to fixtures also.
Installation of 9.0 meter height (from Finished ground level) G.I. Street lighting pole (octagonal/polygonal) single arm section; Galvanisation of 610gms/sq. mtr for ground with earthing arrangement as per IS:2713, mounting of Flameproof / Weatherproof LED street lighting fixture as mentioned below. Lighting pole shall be supplied along with all required hardwares for installation of lighting pole like foundation Nuts & bolts,Washers,WP JBs, WP Ni plated brass cable glands, Cable lugs ,stopping plug for un-used cable entries etc complete along with mounting hardwares for lighting fittings, wiring with 3x2.5 sq. mm (cu ) cable between LTG SUB DB to (JB/control gear box wherever applied) to fixtures also.
Installation of structure mounted type flameproof LED lighting poles (2.5 Mtr height ) at Brick/RCC/Steel structure including handling , transportation to erection site , inspection , aligning , leveling, fixing in position by nut bolts welding etc , earthing of poles , supply of GI hardware , GI pipe sleeves etc , all work , labour , materials complete as per drawing & specifications codes & standards & instructions / directions of ENGINEER IN CHARGE.
FLAMEPROOF AND NON FLP JUNCTION BOXES- INSTALLATION ,TESTING ,COMMISSIONING
Flameproof 16A, 415V, Ph-N, 6-way ,Cast Aluminium (LM-6 )Junction boxes; Junction boxes with terminals block with additional earthing terminals and end clamps etc. including 3 Nos. Ex’d’ double compression stainless steel cable glands with PVC shrouds suitable for 2nos.-3.5cx50sq.mm (Al) and 4 nos- 3cx2.5 sq. mm (cu.) XLPE, FRLS cables, 2mm thick Alu canopy shall be provided.
Weather proof 16A, 415V, Ph-N, 6-way ,Cast Aluminium (LM-6 )Junction boxes; Junction boxes with terminals block with additional earthing terminals and end clamps etc. including 3 Nos. double compression stainless steel cable glands with PVC shrouds suitable for 2nos.-3.5cx50sq.mm (Al) and 4 nos- 3cx2.5 sq. mm (cu.) XLPE, FRLS cables, 2mm thick Alu canopy shall be provided.
Installation, testing, commissioning of Flame proof 16A, 240V 4-way, 125 mm (minimum) internal dimensions junction boxes with terminals block with additional earthing terminals and end clamps etc. including 4 Nos. Ex’d’ double compression Ni plated brass cable glands with PVC shrouds suitable for 3x2.5 sq. mm (cu.) XLPE, FRLS cable,canopy as per attached specifications.
Installation, testing, commissioning of Weather proof 16A, 240V 4-way, 125 mm (minimum) internal dimensions junction boxes with terminals block with additional earthing terminals and end clamps etc. including 4 Nos. W.P. double compression Ni plated brass cable glands suitable for 3x2.5 sq. mm (cu.) XLPE, FRLS cable ,canopy as per attached specifications.
INSTALLATION OF G.I. LADDER TYPE CABLE TRAY AS PER ENCLOSED DRAWINGS AND SPECIFICATION.
Installation of Pre-Fabricated G.I. cable tray with accessories like: Coupler Plates,Hold on Clamps , bends etc. and supporting arrangement. The work includes transportation from owners store to erection site, unpacking, inspection; checking, Erection in position on supports, fixing, supply of all erection materials Including necessary hardware. All work, labour and materials complete as per drawings, specifications, codes and standards and directions of Engineer-in-Charge.
750 wide G.I. ladder type cable tray
600 wide G.I. ladder type cable tray
300 wide G.I. ladder type cable tray
laying of 150 mm x 50mm x 2 mm thick GI perforated cable trays
laying of 100 mm x 25mm x 2 mm thick GI perforated cable trays
1.5mm Thick cover for 750 wide G.I. ladder type cable tray
1.5mm Thick Cover for 600 wide G.I. ladder type cable tray
1.5mm Thick Cover for 300 wide G.I. ladder type cable tray
Installation of 1.5mm Thick G.I.Cover(155mm wide) for 150mm G.I. perforated cable trays
Installation of 1.5mm Thick G.I.Cover(105 wide) for 100mm G.I. perforated cable trays
HIGH MAST TOWERS
30M HIGH MAST: Installation , testing and commissioning of High Mast (30 Meter height) as per specifications including handling , transportation of high mast and it’s accessories/ parts supplied loose from owner’s store to place of erection , unpacking and inspection, required placing in position on foundation assembly of all loose accessories and parts connection of high mast, Operational and functional checking of all work, labour and materials complete as per drawing, standard and direction of engineer in-charge. For foundations refer scope under supply.
Installation & Commissioning of flameproof outdoor, made of 14 SWG CRCA sheet, IP-65, stand mounted feeder pillar with 1 no. 32A TPN MCB incomer, single dial time switch, 22A TP contactor for the automatic switching of luminaries, power tool control with 2 no 9A contactors and raise lower push button, Incoming 35-70 sq. mm and out going 12 & 2.5 sq. mm terminals & 1 no. outgoing upto 35-70 sqm for looping. (Necessary Civil Works shall be paid seperately)
Installation of Raychem make 11KV (UE) grade of following type end termination kit suitable 3Cx300 sq.mm (AL),Armoured,FRLS,Screened Cable.
11KV (UE) grade, outdoor type
11KV (UE) grade, indoor type
CABLE LAYING
Horizontal and Vertical Laying of FRLS , XLPE HT& LT cables of following sizes and particulars on cable racks, RCC trenches, Buried trench , floor slits, in G.I. conduit (including chipping of floor wherever required), on cable trays, cable racks, cable risers, supports, hangers, saddles etc., Sealing of wall openings and pipe sleeves after cable laying etc., Including handling, transportation from owner's store/storage yard to installation site of cables/cable drums, unpacking , inspection, cable dressing, fixing of cable clamps in vertical and if necessary, in horizontal runs, fixing of cable identification tags (At every 20 Mtr. interval all along the length); testing before and after laying; supply of Aluminum cable clamps and cable tags, GI saddles and GI saddle bars ,providing cable route marker for buried cable trenches, GI bolts, nuts and washer screws etc., Actual site measurement shall be taken before cutting the cable from drum to avoid cable joint / waste ,measurement of IR value, testing of cables before and after terminations for IR values, all work, labour and materials complete as per drawings, specifications, codes and standards and directions of Engineer-in-Charge.(Refer cable Route layout drawing C241135-DIM-EL-CAB-4002 for detail routing)
11 KV (UE) Grade ,3Cx300Sqmm(AL), XLPE, Screened,Armoured , FRLS Power cables
1.1 KV Grade XLPE,Armoured, FRLS power cable
3CX25 sq. mm (Al)
3CX35 sq. mm (Al)
3CX50 sq. mm (Al)
3CX70 sq. mm (Al)
3.5Cx400 sq. mm (Al)
3.5Cx240 sq. mm (Al)
3.5Cx185 sq. mm (Al)
3.5Cx150sq. mm (Al)
3.5Cx120sq. mm (Al)
3.5Cx95sq. mm (Al)
3.5Cx70 sq. mm (Al)
3.5Cx50 sq. mm (Al)
3.5Cx35 sq. mm (Al)
3.5Cx25 sq. mm (Al)
4Cx10 sq. mm (Cu)
4Cx6 sq. mm (Cu)
3Cx6 sq. mm (Cu)
4Cx4 sq. mm (Cu)
3Cx2.5 sq.mm (Cu) - Power
2Cx95 sq.mm (Cu) - Power
2Cx16 sq.mm (Cu) - Power
Cable termination, connections and testing of 11 kV (UE) /1.1kV grade, Al. OR Cu. conductor, XLPE insulated, GI strip/ round wire armoured, FRLS power,control & interfacing cables of following sizes and particulars including drilling / tapping of gland plate for cable entry OR enlarging existing cable entries as required, fixing of cable glands & terminals supplied loose at equipment end but excluding supply of cable glands. Cable termination also includes supply of cable lugs with stripping of insulation, taping, soldering OR crimping of tinned Cu. / Al. (as required), sockets OR lugs to conductors, connection of leads to equipment terminals etc., ferruling, supply of GI nuts, bolts, washer, screws, insulating tapes, compounds, solders, fluxes, ferrules etc. Closing of unused cable entries to make the equipment dust, moisture & vermin proof, all work, labour and materials complete as per drawings, specifications, codes & standards and instructions / directions of engineer-in-charge.
CABLE GLANDING with weather proof double compression Ni plated brass cable gland of the following sizes of XLPE,Arm. FRLS cables.
3CX25 sq. mm (Al)
3CX35 sq. mm (Al)
3CX50 sq. mm (Al)
3CX70 sq. mm (Al)
3.5Cx400 sq. mm (Al)
3.5Cx240 sq. mm (Al)
3.5Cx185 sq. mm (Al)
3.5Cx150sq. mm (Al)
3.5Cx120sq. mm (Al)
3.5Cx95sq. mm (Al)
3.5Cx70 sq. mm (Al)
3.5Cx50 sq. mm (Al)
3.5Cx35 sq. mm (Al)
3.5Cx25 sq. mm (Al)
4Cx10 sq. mm (Cu)
4Cx6 sq. mm (Cu)
4Cx4 sq. mm (Cu)
3Cx2.5 sq.mm (Cu)
2Cx95 sq.mm (Cu)
2Cx16 sq.mm (Cu)
CABLE GLANDING with Flameproof double compression nickel plated brass cable gland suitable for following XLPE , FRLS cable sizes & as per relevant IS for hazardous area Zone-1, Gas group ,IIA/IIB, Temp. Class T3.
3CX2.5 sq. mm (Cu)
3CX25 sq. mm (Al)
3CX35 sq. mm (Al)
3CX50 sq. mm (Al)
3CX70 sq. mm (Al)
3.5Cx400 sq. mm (Al)
3.5Cx240 sq. mm (Al)
3.5Cx185 sq. mm (Al)
3.5Cx150sq. mm (Al)
3.5Cx120sq. mm (Al)
3.5Cx95sq. mm (Al)
3.5Cx70 sq. mm (Al)
3.5Cx50 sq. mm (Al)
3.5Cx35 sq. mm (Al)
3.5Cx25 sq. mm (Al)
4Cx10 sq. mm (Cu)
4Cx6 sq. mm (Cu)
3Cx6 sq. mm (Cu)
4Cx4 sq. mm (Cu)
2Cx95 sq.mm (Cu)
2Cx16 sq.mm (Cu)
Plugging of spare cable entry with Flameproof Nickle plated brass stopper plugs of following size.
1/2 inch size
3/4 inch size
1 inch size
GI Earth Bus bars
Installation of GI Earth Bus bars (size: 390x50 x12mm thick) Including handling, transportation, drilling of necessary holes/enlargement existing holes as required; all associated work for fixing the Bus bars in position e.g. cutting, levelling, aligning, chipping, grouting, welding bolting etc.; making good of broken/chipped portion on walls /columns by cement plastering. supply of all necessary hardware (GI), paints, civil masonry materials etc. all work, labour complete as per drawings, specifications, codes and standards and directios of consultant /owner.
Excavation of all type of soil including breaking/chipping of concerete , removal of soil/concerete for construction of buried cable trench for laying of cables , laying of fine river sand before and after laying of cables, laying of brick,ramming of soil, back filling of soil, removal of extra soil, installation of cable route marker along the buried cable route as per drawings,codes standards, labour, materials and as per direction of engineer in-charge.
300 mm wide 950 mm deep buried cable trench.
Charges for preparation of drawings, obtaining drawing approval, arranging for inspection getting safety certificate of complete installation from CEA authorities/Statuary authority like energisation of HT Panel, Transformer, PCC / MCC room & Generator etc.The contractor shall give 5 sets of approved as built drawings. The charges shall also include painting of single line diagram at shed as approved by site engineer. Note: a) The statutory payment to be made to the CEA authorities will be reimbursed at actual on submission of the original receipt to the owner. b) The job also includes all liasoning to be carried out with State Electricity Board authorities for obtaining necessary approval for successful commissioning of the facilities.
GENERAL SAFETY EQUIPMENTS - Installation
Installation of 1.1 KV, 900 mm wide, electric grade floor rubber mat (in pieces of length not less than 2 mtrs.) conforming to IS:15652 & ISI marked.
Installation of 11 KV, 900 mm wide, electric grade floor rubber mat (in pieces of length not less than 2 mtrs.) conforming to IS:15652 & ISI marked.
Installation of Fire extinguishers CO2 type in 4.5kg capacity as per IS 2878/UL 154 complete with handle , fixing bracket etc.
Installation of Shock treatment chart ( laminated type) in bilingual language (Hindi , English & Telgu ).
Installation of 415 V , Danger notice plate / caution board as per IS:2551.
Installation of 11 KV , Danger notice plate / caution board as per IS:2551.
Installation of G.I fire bucket set. (4 no. each of 9 litre) as per IS:2546 filled with sand, painted with red colour along with its stand for holding the sand bucket including rain hood for sand bucket.
Installation of Fire extinguishers DCP type in 10kg / 9kg capacity complete with handle , fixing bracket etc.
Installation of First aid box of GI, 18 swg sheet with necessary items.
Installation, testing & commissioning of 11KV, 50A DOF fuse for HT yard, fuse shall be suitable for installation in 11KV H-pole.
INSTALLATION ,TESTING & COMMISSIONING OF LOCAL CONTROL STATION (FLP & NON FLP)
Installation, testing & commissioning of Weather proof Local control station provided with START STOP PB, Ammeter, 3 mm thick FRP Canopy with side cover, including double compression Ni plated brass cable glands & plugs as required as per attached specifications.(TYPE -A).
Installation, testing & commissioning of FLP (Zone-1, IIA/IIB, T3) Local control station provided with START STOP PB, Ammeter ( AUTO ,REMORE ,MANUAL ) 3 mm thick FRP Canopy with side cover, including flameproof double compression Ni plated brass cable glands & plugs as required as per attached specifications (TYPE -C).
Installation, testing & commissioning of FLP (Zone-1, IIA/IIB, T3) Local control station provided with START STOP PB, 3mm thick FRP Canopy with side cover, including flameproof double compression Ni plated brass cable glands & plugs as required as per attached specifications.(TYPE -D).
EPB: Installation, testing & commissioning of weather proof emergency stop push button(EPB) with ON-OFF LED indication, break glass type enclosure,3mm thick FRP canopy, weather proof double compression Nickel Plted Brass cable glands(2 nos.) and 1 NO+1 NC contact .
EPB: Installation, testing & commissioning of FLP emergency stop push button(EPB) with ON-OFF LED indication, break glass type enclosure,3mm thick FRP canopy, weather proof double compression Nickel Plted Brass cable glands(2 nos.) and 1 NO+1 NC contact .
Installation, testing & commissioning of Emergency stop push button (EPB) for Power transformer with break glass type weather proof enclosure, FRP canopy, cable glands etc.
INSTALLATION ,TESTING & COMMISSIONING OF 63A/16A SWITCH SOCKET & PLUG (FLP & NON FLP)
Installation of flameproof Interlocking type switch sockets and plugs of following ratings as per attached specifications. All switch sockets shall be provided with 3mm thick FRP canopy with side cover and required no. of FLP double compression Ni plated brass cable glands and FLP stopping plug as per attached specification sheets.
415V,3 phase 63A flame proof switch socket and plug
240V, 3-pin, 16A/6A flame proof switch socket and plug
Installation of Multi Cable Transit (MCT) BLOCKS with SS Frame with EPDM Modules, Stay plate, Compression wedge, Lubricant etc complete with all accessories for following area including necessary civil works such as dismantling the wall, fixing of the block and restoration of the wall.
MCT-PMCC Building (for LT Power Cables- 24 incomer/outoging Cables + 30% Spare blocks )
MCT-Control room (for LT Power cables -12 incomer/outoging Cables + 30% Spare blocks)
Invoice Room (for LT Power cables - 3 incomer/outoging Cables + 30% Spare blocks)
Sample Room (for LT Power cables - 3 incomer/outoging Cables + 30% Spare blocks)
TT Crew Rest Room (for LT Power cables - 6 incomer/outoging Cables + 30% Spare blocks)
Security Room (for LT Power cables - 3 incomer/outoging Cables + 30% Spare blocks)
(C ) COMPOSITE WORKS- ELECTRICAL
Supply & Fixing of B-class G.I. pipe conforming to IS: 1039 for cable protection burried in concrete/ PCC / Brick work or under Earth including cutting to size, threading, bending etc of following sizes
50 mm Dia. G.I. pipes
75 mm Dia. G.I. pipes
100 mm Dia G.I. Pipes
150 mm Dia G.I. Pipes
MS CHEQUERED PLATE
Supply and installation of 6 mm thick MS chequered plate conforming to IS: 3502 in flooring steps cover over cable trenches, earthing pits with painting by one coat of bitumen paint with 50% thinner & two coats of high built black bitumen paint including supply of all consumable and paint & lifting arrangement.
ANCHOR FASTENERS :Providing & fixing anchor fasteners of approved make like HILTI and any of size on the RCC slab, beam, columns etc. at any height including drilling the holes using drilling machine / tools having carbide tips, scaffolding (If required) for fixing the fasteners and its bolt as per the drawing or as directed by Engineer in charge with all labour, materials, tools and tackles.
Upto 1/4" (6 mm) BSW x 12 mm dia.
Between 1/4"(6 mm) BSW x 12 mm to 3/8" BSW x 25 mm dia.
Supply & laying of Heavy Duty type, High compression strength, IP 67 rated (DWC) Double wall corrugated HDPE Conduits as per IS:14930/ IS:16205. Laying includes with GI pull wires inside the conduits & necessary ends to be filled with sealants, of all complete and as per drawing & specification.
EARTHING & LIGHTNING
PIPE ELECTRODE EARTH PIT Supply, installation & testing of earth electrode with following sizes: 80 mm dia, 3.8 M long heavy duty perforated GI pipe electrode (Galvanisation is 610 gms/sq. mtr or as per IS-4759/ISO 1461.) as per IS:3043 providing suitable earth bus for interconnection, providing a mixture of salt & charcoal, making RCC/ Brick earth pit chamber and associated civil works with chequered plate cover as per standard Drwng. etc. all complete as per specification & direction of Site-In-charge. Item also includes Supply and fixing of Earth resistance display board of size 450 X 300 mm with 3mm thick Aluminium Composite Material (ACM)/ Aluminium Composite Panel (ACP) bolted to 25 X 25 X 5 mm (with 2 bolts MS angle section, 60 cm long (minmum 200 mm embedded in ground). The rate shall also include supply and pasting of UV resistant vinyl sticker having details as per Site-in-charge.
Supply & drawing/laying, jointing, connecting, testing and commissioning of Hot Dip Galvanized (Galvanisation is 610 gms/sq. mtr. or as per IS-4759/ISO 1461) earth strip/copper strip/GI wire for earthing and lightning protection under or aboveground complete as per specification for the following sizes as per direction of Site in-Charge.
75 mm x 8 mm GI Strip
50 mm x 6 mm GI Strip
40 x 6 mm GI Strip
40 x 5 mm GI Strip
25 mm x 6 mm GI Strip
25 x 3 mm GI Strip
1Cx25 mm2 PVC (Al) cable Green colour
1Cx16 mm2 PVC (Al) cable Green colour
1Cx4 mm2 PVC (CU) cable Green colour
Supply & installation of 1000mm long,20 dia. GI air termination rod (lightning rod) with all fixing material, accessories as per IS:2309 and as per drg.no. PDS:E 614.
Supply and Installation of Copper Jumpers of following Sizes
Jumper Length 127 mm (25mm x 3 mm )
Jumper Length 130.05 mm (25mm x 3 mm )
Jumper Length 132.08 mm (25mm x 3 mm )
Jumper Length 139.7 mm (25mm x 3 mm )
Jumper Length 166.88 mm (50mm x 3 mm )
Jumper Length 187.45 mm (50mm x 3 mm )
Jumper Length 198.63 mm (50mm x 3 mm )
Jumper Length 209.8 mm (50mm x 3 mm )
Jumper Length 220.47 mm (50mm x 3 mm )
Jumper Length 231.65 mm (50mm x 3 mm )
Jumper Length 264.92 mm (50mm x 3 mm )
Jumper Length 299.97 mm (50mm x 3 mm )
Jumper Length 314.45 mm (50mm x 3 mm )
Jumper Length 298.2 mm (50mm x 3 mm )
COMPOSITE WORKS- CIVIL AND STRUCTURAL WORK
Earthwork: Earth work
Clearing grass and removal of the rubbish outside site premises and at unobjectionable place.
Clearing jungle including uprooting of rank vegetation, grass, brush wood, trees and saplings of girth upto 30cm measured at a height of 1m above ground level and removal of rubbish outside the site and to unobjectionable place.
Earth work in surface excavation not exceeding 30 cm in depth but exceeding 1.5 m in width as well as 10 sqm on plan including disposal of excavated earth within site and lift upto 1.5 m, disposed soil to be levelled and neatly dressed
Earth work in excavation by mechanical means (Hydraulic excavator) / manual means over areas (exceeding 30 cm in depth, 1.5m in width as well as 10 sqm on plan) including taking out and disposal of excavated earth within or outside site to unobjectionable place and lift upto 1.5m, as directed by Engineer-in-charge. Disposed earth to be levelled and neatly dressed. Extra for levelling and neatly dressing of disposed soil completely to be paid separately as per relevant item. All kinds of Soil such as ordinary/hard soil, kankar, murrum, gravel, pebbles, bajri, removal of shrubs, uprooting the tree roots etc. and all types of material encountered in excavation including excavation of saturated soils, mud, sludge etc.
Note: a) The prices for all excavations are to include for removing and clearing away all shrubs, bushes, roots etc. including tank pad foundation. b) The prices are also to include for all leveling and ramming foundation beds, trimming of sides and bottom grading to proper level as required. c) Removal and carrying shall include for all loading, unloading and handling as may be necessary and also all necessary means of transport (Mechanical or manual as required). d) The prices are also to include removal of water accumulated due to subsoil seepage, rains or from any kind of sources, either by pumping or by bailing or by any suitable method like well point dewatering etc. if reqd. No extra payment shall be made for dewatering. This also includes for draining out the pumped water to nearby available drainage system. e) Normally payment of earth work shall be made according to the+B5 sizes of PCC for trenches/ pits as contemplated in the working drawings. Extra due to widening or deepening of trenches / pits shall not be paid for except for the cases where water / acid proofing would be accepted as per working drawings in such case the mode of measurement shall be as per IS : 1200. f) Nothing extra shall be paid for sorting /screening of excavated materials to obtain good earth for filling.
g) Nothing extra shall be paid on account of any lift for disposal of excavated materials. h) Where excavation are made in excess of the depth required, the contractor shall at his own expense fill up to the desired level with lean concrete of mix 1:5:10 (1 Cement: 5 Coarse sand: 10 Graded stone aggregate 40 mm nominal size. i) Rate shall include Royalty, Taxes, etc., levied by the local authorities, all transportation, loading and unloading, etc., and nothing extra will be paid on this account. j) Soft / loose soil also includes filled up earth / murrum. k) The filling for earth / murrum or sand shall be done in layers not exceeding 20 cm in thickness (consolidated) with Suitable means to achieve 95% dry density at Optimum Moisture Content corresponding to standard Proctor test compaction with vibroroller(8 to 10MT capacity) & vibro compactor in confined spaces. l) For other conditions please refer document.
i) All kinds of Soil
Extra for levelling & neatly dressing of disposed surplus soil completely as directed by engineer in charge
Extra for every additional lift of 1.5m or part thereof in excavation in all kinds of soil
Excavating trenches of required width for pipes, cables, etc including excavation for sockets & dressing of sides, ramming of bottoms, depth upto 1.5m including getting out excavated soil & then returning the soil as required, in layers not exceeding 20 cm in depth including consolidating each deposited layer by ramming, watering, etc. and disposing surplus excavated soil as directed, within or outside site at unobjectionable place IN ALL KIND OF SOILS
i) Pipes,cables etc. not exceeding 80mm dia
ii) For extra depth of >1.5m < 3m for dia upto 80mm
Filling available excavated earth (excluding rock) in trenches, plinth, sides of foundations etc. in layers not exceeding 20cm in depth, consolidation each deposited layer by ramming and watering, within premises and lift upto 1.5m
Filling low lying areas with available excavated surplus earth within station premises (excluding rock) in layers not exceeding 20cm in depth, consolidation each deposited layer by ramming and watering for all Lift and Lead as per direction of Engineer-in-Charge / Site in charge.
Supply & filling imported local earth (including royalty) of approved quality, in plot, trenches, plinth, sides of foundations etc. in layers not exceeding 20 cm in depth each deposited layer by ramming and watering. Item includes compaction using minium 15 ton capacity vibro-compactor with a adequate minimum of passes for earth work in under optimum moisture conditions to give at least 95% of the maximum dry density of the material. Note: a) Tenderer to note that initial & final level survey shall be undertaken jointly by the Contractor &/or representatives with IOC Site Engineer. b) Tenderers to note that approval from IOCL shall be obtained for the imported earth & quarry used for mass filling & necessary test reports from a Govt Engg Colleges/Universities or NABL acredited labs (As approved by IOCL/PMC Engineer) have to be submiited for the parameters specified by IOCL prior to undertaking filling in the site. c) Item rate is inclusive of applicable Royalty for the imported earth, charges for Specific approval to be obtained from concerned Statutory Authorities & Necessary Royalty receipts/ NOC to be submitted by the Contractor. d) Net quantity of compacted earth shall be paid & no compensation whatsoever on account of subsidence of soil etc shall be permitted. e) No extra cost shall be payable by IOCL on account of payment of any statutory fees and compliances sought by statuory authorities from tenderer both within & outisde the premises.
Supplying and filling coarse sand of Zone III as per IS Code, in plinth, under floors, under ground tanks & tank foundations etc. in layers not exceeding 200mm in depth, each deposited layer shall be compacted by mechanical vibration (Vibro-roller) and watering (consolidation) and dressing complete to as to attain relative density not below 90 to 95% of maximum laboratory density. Last layer of tank foundation to be prepared in desired slope as per drawing and as per technical specifications. Note:The rate quoted should include testing of compacted layers of sand with necessary equipment/laboratory tests etc in order to achieve desired relative density for the compacted layers.
Supplying and filling in plinth with sand within specified grading zone of fine aggregates specified in attached specifications under floors, etc. in layers not exceeding 20cm in depth, each deposited layer to be compacted by ramming including watering, consolidating and dressing complete.
i) Local Fine Sand within grading zone IV
CONCRETE WORK/ REINFORCED CONCRETE WORK
a) The prices for concrete in beds and slabs are to include for laying on any type of sub grade, laying to falls, or cambers and for preparing surfaces to receive concrete. b) All concrete surfaces shall be finished to a fair face to give a smooth and even surface. Nothing extra shall be paid on this account. c) The prices are to include leaving pockets, cut outs and holes and to provide wooden boxes or any other suitable arrangements in RCC for bolt holes in slab, beams, walls, foundation of equipments etc. as per approved working drawing. (Nothing extra shall be paid on this account). d) No deduction in RCC quantity shall be made for pockets and nothing extra shall be paid for providing pockets as mentioned in para 'C' above. e) Measurement of opening in concrete work/RCC work: For measurement of openings in concrete work / RCC works, shall be as per IS: 1200 Part-III. f) All pocket holes are to be properly covered by suitable means so that dirt, rain water etc. etc., should not enter the pockets/holes etc. (Nothing extra shall be paid on this account.)
g) Threads of bolts etc. which have already been fixed in the pockets are to be greased and polythene sheet properly covered with gunny bags to protect it from damages from all sources. (Nothing extra shall be paid on this account.) h) The prices shall include for all rebating, trotting, chamfering weathering, molding etc. to accord with the details shown on the approved working drawings. i) Nothing extra shall be paid for any intricate concrete work for foundations of equipments and machinery (dynamic/static), RCC wall and other superstructure works or any delay in concreting in small and thin sections in PCC or RCC works. j) The prices for concrete are to include for hoisting and / or lowering to any height and/or depth required and in any type of form work, packing around reinforcement where required and finishing the surfaces, to fair and even surface. k) The prices shall include working up or hacking of concrete surface for providing keys for further concrete work and shall also include all plane, rebated or grooved constructional and other joints. l) The design mixes of all controlled concrete of various grades shall be established by the contractor on the basis of weigh batching, at the beginning of work. In all concrete / RCC work graded coarse aggregate shall be used. Any concrete work with honey comb shall be rejected and the work has to be redone by the contractor at his own cost.
m) Concrete admixtures for workability if necessary, may be used in RCC if decided by Engineer-in-charge. No extra payment for mixing etc, shall be made on this account. n) Machine and equipment foundations shall mean all foundations including pedestals of vessels, towers, pumps, compressor motors, or any other equipment or machinery (both static and dynamic), pipe supports, etc. and the like. o) The prices are also to include the removal of water caused by rains/seepage etc. either pumping or by bailing out or by special means like well point dewatering etc. that may accumulate in the trenches and foundation pits etc. p) The prices are to include the supply of cement by the contractor. q) Anti shrinkage compound used in grouting shall be paid separately. r) The source of supply for sand and stone chips shall be approved by IOCL.
Following additional points to be noted for Ready Mix Concrete(RMC) a) Ready mix concrete (RMC) of approved vendor at the site of casting including coordinating with Engineer-in-charge, prior to casting, making all arrangement to unload the concrete so as to ensure that RMC is not detained for unloading, placing the concrete at site, vibrating, taking concrete cubes, testing, curing the concrete etc. complete in relevant items. b) Necessary schedule will have to be submitted by agency 3 days in advance so that proper coordination with Engineer-in-charge is done. c) It shall be ensured that shuttering done by contractor shall be adequate to withstand pumping pressure. d) Any loss of material shall be contractor’s responsibility. e) Submission of test results at RMC mixing plant site as well as casting site shall be contractors responsibility f) Desired design mix shall be got approved from Engineer-in charge before placing order for RMC. g) Any toll taxes applicable to be borne by the contractor. h) Any other taxes as levied by Govt. from time to time shall be deemed to be inclusive in the contract. i) Approved brand of 43 grade cement shall be used for preparing RMC & Cement shall be tested as per relevant IS Codes. Cement supply shall be in contractor’s scope.
PLAIN CEMENT CONCRETE: Providing and laying cement concrete in foundation, footings and base for columns/walls including proportioning, mixing in mechanical mixer, laying vibration by means of mechanical vibrators, curing etc. complete including the cost of shuttering:-
Plain Cement Concrete of mix 1:2:4 ( 1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size)
Plain Cement Concrete of mix 1:3:6 ( 1 cement : 3 coarse sand : 6 graded stone aggregate 20 mm nominal size)
Plain Cement Concrete of mix 1:4:8 ( 1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size)
REINFORCED CEMENT CONCRETE
Providing and laying in position specified grade of reinforced cement concrete excluding the cost of centering, shuttering, finishing and reinforcement - All work up to plinth level
i) RCC 1 Cement :1 Coarse Sand: 2 Graded Stone Aggregate 20mm
ii) RCC 1 Cement :1½ Coarse Sand: 3 Graded Stone Aggregate 20mm
iii) RCC 1 Cement :2 Coarse Sand: 4 Graded Stone Aggregate 20mm
IN FOUNDATION & PLINTH: Providing and laying in position, machine batched & machine mixed design mix M-25 grade reinforced cement concrete work, using cement content as per approved design mix, including pumping of concrete to site of laying but excluding the cost of centering, shuttering, finishing and reinforcement. Including admixtures in recommended proportions as per IS 9109 to accelerate, retard setting of concrete,improve workability without impairing strength and durability as per direction of Engineer-in-charge -- M-25 grade reinforced cement concrete UP TO PLINTH LEVEL Note :- a. Minimum Cement content considered in this item is @330 kg/cum and accordingly design mix to be done. Less cement used as per design mix (if any) will be recoverable separately. No extra payment against extra cement if used shall be payable. b. Batch mixing plant of capacity to be approved by Site Engineer for the works to be installed by the Contractor at site along with required NOCs from concerned Authorities. Alternatively, Contractor shall also be permitted to use RMC (if available) at no extra cost to IOC & after obtaining prior approval from Engineer In-Charge. c. For small quantities (up to 5 cum per day), mixing & placing of concrete of M25 (1:1:2) using mechanical mixer shall be permitted with the prior approval of IOC. d. Hacking of exposed surface of green concrete (wherever applicable) as Key to plaster shall be done at no extra cost to IOC.
IN SUPER-STRUCTURE: Providing and laying in position, machine batched & machine mixed design mix M-25 grade cement concrete for reinforced cement concrete work, using cement content as per approved design mix, including pumping of concrete to site of laying but excluding the cost of centering, shuttering, finishing and reinforcement. Including admixtures in recommended proportions as per IS 9109 to accelerate, retard setting of concrete,improve workability without impairing strength and durability as per direction of Engineer-in-charge -- M-25 grade reinforced cement concrete ABOVE PLINTH & UP TO FLOOR 5 LEVEL Note :- a. Minimum Cement content considered in this item is @330 kg/cum and accordingly design mix to be done. Less cement used as per design mix (if any) will be recoverable separately. No extra payment against extra cement if used shall be payable. b. Batch mixing plant of capacity to be approved by Site Engineer for the works to be installed by the Contractor at site along with required NOCs from concerned Authorities. Alternatively, Contractor shall also be permitted to use RMC (if available) at no extra cost to IOC & after obtaining prior approval from Engineer In-Charge. c. For small quantities (up to 5 cum per day), mixing & placing of concrete of M25 (1:1:2) using mechanical mixer shall be permitted with the prior approval of IOC. d. Hacking of exposed surface of green concrete (wherever applicable) as Key to plaster shall be done at no extra cost to IOC.
Providing M-30 grade concrete BMC/RMC. (Note:- Cement content considered in M-30 is @ 340 kg/cum) for All works UP TO PLINTH LEVEL. IN FOUNDATION & PLINTH: Providing and laying in position, machine batched & machine mixed design mix M-30 grade reinforced cement concrete work, using cement content as per approved design mix, including pumping of concrete to site of laying but excluding the cost of centering, shuttering, finishing and reinforcement. Including admixtures in recommended proportions as per IS 9109 to accelerate, retard setting of concrete,improve workability without impairing strength and durability as per direction of Engineer-in-charge -- M-30 grade reinforced cement concrete UP TO PLINTH LEVEL Note :- a. Minimum Cement content considered in this item is @340 kg/cum and accordingly design mix to be done. Less cement used as per design mix (if any) will be recoverable separately. No extra payment against extra cement if used shall be payable. b. Batch mixing plant of capacity to be approved by Site Engineer for the works to be installed by the Contractor at site along with required NOCs from concerned Authorities. Alternatively, Contractor shall also be permitted to use RMC (if available) at no extra cost to IOC & after obtaining prior approval from Engineer In-Charge. c. For small quantities (up to 5 cum per day), mixing & placing of concrete of M30 using mechanical mixer shall be permitted with the prior approval of IOC. d. Hacking of exposed surface of green concrete (wherever applicable) as Key to plaster shall be done at no extra cost to IOC.
Providing M-30 grade concrete grade BMC/RMC. (Note:- Cement content considered in M-30 is @ 340 kg/cum). for All works ABOVE PLINTH UPTO FLOOR 5 LEVEL IN SUPER-STRUCTURE: Providing and laying in position, machine batched & machine mixed design mix M-25 grade cement concrete for reinforced cement concrete work, using cement content as per approved design mix, including pumping of concrete to site of laying but excluding the cost of centering, shuttering, finishing and reinforcement. Including admixtures in recommended proportions as per IS 9109 to accelerate, retard setting of concrete,improve workability without impairing strength and durability as per direction of Engineer-in-charge -- M-30 grade reinforced cement concrete ABOVE PLINTH & UP TO FLOOR 5 LEVEL Note :- a. Minimum Cement content considered in this item is @340 kg/cum and accordingly design mix to be done. Less cement used as per design mix (if any) will be recoverable separately. No extra payment against extra cement if used shall be payable. b. Batch mixing plant of capacity to be approved by Site Engineer for the works to be installed by the Contractor at site along with required NOCs from concerned Authorities. Alternatively, Contractor shall also be permitted to use RMC (if available) at no extra cost to IOC & after obtaining prior approval from Engineer In-Charge. c. For small quantities (up to 5 cum per day), mixing & placing of concrete of M30 using mechanical mixer shall be permitted with the prior approval of IOC. d. Hacking of exposed surface of green concrete (wherever applicable) as Key to plaster shall be done at no extra cost to IOC.
REINFORCEMENT: Supplying, cutting, bending, hoisting, placing in position with proper precast concrete block cover and binding with 18 SWG annealed wire, high yield strength deformed bars Thermo Mechanically Treated Bars Fe-500 d grade or more, Conforming to as per IS: 1786 for all R.C.C works including all necessary handling at all heights and depths complete in all respects and as per direction of the Engineer-in-Charge.
Note: a) Wastage in cutting will not be paid. Only steel actually fixed in position will be paid by the linear measurement i/c hooks, chairs, dowels and laps. Only authorized hooks and laps approved in bar bending schedule shall be paid. Lapping of bars will be allowed only where the required bar length exceeds the standard lengths available unless otherwise approved. All other laps provided unless otherwise specified in the drawings shall not be measured and paid for. Weight of binding wire shall not be measured for payment. The prices are to include for the supply of all Reinforcement & Embedment at site by the Contractor. b) Reinforcement are to be tack welded in addition to binding by 18 SWG annealed wire wherever necessary to impart fixity. Bars of 28 mm dia & above shall also be provided with stitch weld in additions to binding with annealed iron wire and nothing extra will be paid for stitch welding. Stitch welding shall be done as per IS specifications. No extra claim shall be entertained on this account. c) Supplying, cutting, bending, hoisting, placing in position with proper precast concrete block cover and binding with 18 SWG annealed wire, high yield strength deformed bars as per IS: 1786 for all R.C.C works including all necessary handling at all heights and depths complete in all respects and as per direction of the Engineer-in-Charge.
SHUTTERING & CENTERING: Centering and shuttering including strutting, propping etc. with suitable materials as per Tender conditions & specifications and removal of form for: -
i) Foundations,footings,bases of columns, etc. for mass concrete
ii) RCC Walls (any thickness) including attached pilasters, buttress, plinth and string courses etc.
v) Columns, Pillars, Piers, Abutments, Posts and Struts.
STRUCTURAL STEEL
Supplying, transporting, de-rusting, fabricating, erecting, hoisting and fixing in position with necessary welding and/or bolting with MS bolts conforming to property class 4.6 or higher of I.S:1367 at all height as per approved fabrication drawings of all types of structural steel work in rolled steel joints, channels, angles, tees, flats, plates, lattice members built up / compound sections in columns, portals, girders, beams, bracings, trusses, purlins, rafters, staircase, steps, hand-railings, walkway, cat ladder with cages, toe plates, side walling, trestles, Conveyor gantries grating, chequred plate etc. including gusset plates, anchor plates etc., including site and shop fasteners, riveting, bolting, welding at shop or work site at all heights etc. & including applying approved coats of primers, undercoat and finish painting as per Technical specification. Complete as per drawing and direction of Owner / Consultant. (All material supply is in contractor’s scope including paints ) Providing and applying Anticorrosive treatment to structural steel surface as per below specifications. a) Surface preparation by shot blasting conforming to SA 2.5 b) Primer coat of INORGANIC ZINC ETHYL SILICATE (DFT 65 – 75 micron) c) Intermediate coat of TWO PACK EPOXY-POLYAMIDE MIO UNDERCOAT (DFT 100 – 125 micron) d) Final coat of TWO PACK ALIPHATIC POLYURETHANE (DFT40-50 micron) Total DFT shall be min 215 micron. Final paint shades shall be as approved by IOCL. Payment will be on the basis of weight of structural steel provided.
Supplying, providing, shop fabricated, steel pressed lock, erection of galvanised electro forged gratings comprising of shaped, grating and stair treads out of steel using 25x5mm/6mm flat bars and 6mm MS twisted Bars as per requirements duly welded/fixed/clamped to base frame and as shown in relevant drawings including galvanizing of gratings as per enclosed specifications. Note:- Finished size of grating laid shall be measured for the purpose of payment. Pitch of the main flat bars(25x5mm) shall be 33-35mm and the pitch of the 6mm twisted rod (cross members) shall be 100mm, the outer frame of grating of all sizes shall be 25x5mm/6mm FB or as per approved drawing.
Supplying and fixing MS foundation bolts with necessary GI nuts and washers of specified sizes,with suitable anchorage all conforming to relevant Indian Standards and as approved by Engineer-in-charge :
BRICK WORK
Providing and laying Brick work with bricks of class designation 75 Including Scaffolding :
i) Brick work in Cement mortar 1:4 (1 cement : 4 coarse sand) IN FOUNDATION UPTO PLINTH
ii) Brick work in Cement mortar 1:4 (1 cement: 4 coarse sand) in superstructure in all shapes & sizes in superstructure ABOVE PLINTH & UP TO FLOOR V LEVEL
Providing and fixing on wall face unplasticised Rigid PVC rain water pipes conforming to IS:13592 Type A including jointing with seal ring conforming to IS : 5382 leaving 10 mm gap for thermal expansion, Single socketed pipes.
ii) 110 mm diameter
Providing & fixing on wall face unplasticised - PVC moulded fittings/ accessories for unplasticised Rigid PVC rain water pipes conforming to IS : 13592 Type A including jointing with seal ring conforming to IS : 5382 leaving 10 mm gap for thermal expansion.
ii) 110mm Coupler
FINISHING
Providing and laying cement plaster on surfaces with fine sand including curing etc.
i) 6 mm cement plaster of mix 1:4 (1 cement: 4 coarse sand)
ii) 12 mm cement plaster of mix1:6 (1 cement: 4 fine sand)
Providing and laying cement plaster on surfaces in two coats including curing etc.
18 mm cement plaster in two coats under layer 12 mm thick cement plaster 1:5 (1 cement: 5 coarse sand) and a top layer 6mm thick cement plaster 1:3 (1 cement: 3 coarse sand) finished rough with sponge.
Note a) The prices are to include for work at any height / depth and for all necessary scaffolding etc. as required. b) The prices shall also include for making to form key for plaster and for all work in narrow width formed angles, chamfered external angles and for making good the faces. c) Plastering shall be measured in sq. meter area of the surface to be plastered, as per IS: 1200 (Part XII). The rate shall include erecting and removal of scaffolding all labour, all materials, equipment, plants, tools and all incidental expenses to complete plastering, pointing, rubbing out joints, cleaning, wetting, filling with cement mortar, troweling etc. and making of drip moulds, grooves, vattas, bands etc. including curing. d) The prices are to include the supply of cement at site by the contractor. e) Sand used for plastering shall be from approved sources.
Finishing walls with water proofing cement paint of required shade with Two or more coats applied @ 3.84 kg/10 sqm
White washing with 3 or more coats of lime to give an even shade
Distempering with 1st quality acrylic washable distemper (ready mixed) having VOC content less than 50gm/ltr of approved manufacturer, of required shade and colour complete as per manufacturer's specification with 2 or more coats
Providing and fixing 18mm thick gang saw cut mirror polished premoulded and prepolished, machine cut for kitchen platforms, vanity counters, sills, facias, Pump Island & similar locations of required size, approved shade, colour and texture laid over 20mm thick base cement mortar 1:4 (1 cement : 4 coarse sand), joints treated with white cement mixed with matching pigment, epoxy touch ups, including rubbing, curing, moulding & polishing to edge to give high gloss finish etc. complete at all levels.
iii) Granite of any colour and shade having Area of slab upto 0.50 sqm
iv) Granite of any colour and shade having Area of slab over 0.50 sqm
Extra for providing edge moulding to 18mm Granite/ marble stone counters,Vanities etc. including machine polishing to edge to give high gloss finish etc. complete as per design approved by Engineer-in- Charge.
ii) Granite work
Providing and laying non-pressure NP2 class (light duty) R.C.C. pipes with collars jointed with stiff mixture of cement mortar in the proportion of 1:2 (1 cement : 2 fine sand) including testing of joints etc. complete : Light Duty
i) 100 mm dia. R.C.C. pipe
ii) 150 mm dia. R.C.C. pipe
iii) 250 mm dia. R.C.C. pipe
iv) 300 mm dia. R.C.C. pipe
Providing and laying non-pressure NP3 class (Medium class) R.C.C. pipes with collars jointed with stiff mixture of cement mortar in the proportion of 1:2 (1 cement : 2 fine sand) including testing of joints etc.complete
i) 600 mm dia. R.C.C. pipe
GROUTING
Providing grouting under base plates with cement mortar 1:1 (1 cement : 1 coarse sand) including anti shrinkage compound with necessary finishing etc all complete as per directions of engineer-in-charge.
Providing grouting in pockets with cement concrete 1:1:2 (1 cement : 1 coarse sand : 2 coarse aggregate 10 mm nominal gauge) including approved anti shrinkage compound as per manufacturer’s specifications with necessary finishing etc all complete as per directions of engineer-in-charge.
EXHAUST FANS Supply and fixing of exhaust fan including electrical wiring all shall be with per specification and direction of site In charge. The fans shall be with louvers / shutters. (The job does not include making suitable cut out in the wall for fixing the fan).
i) 6" dia light duty, make Khaitan or equivalent
ii) 9" dia light duty, make Khaitan or equivalent
iii) 12" heavy duty, make GEC or equivalent
SFI OF COPPER LIGHTNING CONDUCTOR FINIA-LProviding and fixing of lightning conductor finial made of 25 mm dia 300 mm long GI tube having single prong at top with 85 mm dia 3 mm thick GI base plate including holes etc. complete as required.
GI LIGHTNING TAPE FOR HORIZONTAL RUN-Providing and fixing of GI strip of 25 x 3 mm thick on parapet or surface of wall for lightning conductor complete with joints and other accessories as required.(for horizental run).
GI LIGHTNING TAPE FOR Vertical RUN -Providing and fixing of GI Tape of 25 x 3 mm thick on parapet or surface of wall for lightning conductor complete with joints and other accessories as required.(for vertical run).
RIVERTING SWEATING SOLDERING LIGHTNING CONDUCTOR TAPE : Riverting, sweating and soldering of copper / GI tape (with another copper / GI tape, base of the finial or any other metallic object) as required.
TESTING JOINT FOR GI LIGHTNING STRIP : Providing and fixing testing joint, made of 20mm x 3mm thick, GI strip, 125mm long, with 4 nos. of GI bolts, nuts, check nuts and spring washers etc. complete as required.
Dismantling / Demolision
Demolishing cement concrete manually/ by mechanical means including disposal of material outside premises at unobjectionable and as per direction of Engineer - in - charge.
i) 1:3:6 or richer mix (i/c equivalent design mix)
ii) 1:4:8 or leaner mix (i/c equivalent design mix)
Demolishing R.C.C. work manually/ by mechanical means including stacking of steel bars & disposal of unserviceable material outside site at unobjectionable place& as per direction of Engineer-in-charge.
Extra for cutting reinforcement bars manually/ by mechanical means in R.C.C. or R.B. work (Payment shall be made on the cross sectional area of R.C.C. or R.B. work) as per direction of Engineer-in-charge.
Demolishing brick work manually/mechanical means including stacking of serviceable material & disposal of unserviceable material outside site at unobjectionable place & as/direction of Engineer-in-charge.
Demolishing stone masonry manually/ by mechanical means including stacking serviceable material & disposal of unserviceable material out of site at unobjectionable place and as per direction of Engineer-in-charge:
Dismantling Steel work in single sections including dismembering and stacking within premises
i) R.S Joists
ii) Channels, angles, tees and flats etc
Dismantling Steel work in built up sections in angles, tees, flats channels etc. including all gusset plates, bolts nuts, cutting rivets welding etc. including dismembering and stacking within premises
Dismantling manually/by mechanical means including stacking of serviceable material & disposal of unserviceable material outside site at unobjectionable place as per direction of Engineer-in-charge :
i) Water bound macadam road
ii) Bituminous road
Dismantling Metal pipes (external work) including excavation and refilling trenches after taking out the pipes, manually/ by mechanical means including stacking of pipes within premises as per direction of Engineer-in-charge :
i) 15 mm to 40 mm nominal bore
ii) Above 40 mm nominal bore upto 80mm
DISMANTLING Dismantling of following electrical fittings / fixtures with all leads and lifts.
i) Electrical cables of all sizes from under / above ground position
ii) DPS board all types with/ without stand
iii) 5 to 15A switches/MCBs/plugs
iv) 32/63/100A DP/TPN switches/ MCCBs /MCBs
v) Flourescent tube light fittings of all sizes
Dismantling of light poles
MISCELLANEOUS ITEMS
Dismantling & store of all existing Electrical 415 Volt Panels include the following activities at Dimapur depot. - 1) Disconnection of all Incoming and out going cables 2)Dismantling of LV panel section into movable pieces. 3)Transportation of OLD Panles( HV&LV) from existing control room/ electrical room to Owners Store 4) Re- arrange the dismantal parts Dismentling & store of all existing Electrical 11 KV & 415KV cables, Electrical motors, Lighting fixture with poles, Sub distribtion power Boards.
Dismantling of extsting transformer and shifting to the owner's storage yard
Dismantling, removal, shifting of existing 250kVA DG Set from old sub-station building to near new sub-station building. Job includes disconnection of cables, disconnection of fuel tank etc, relocation of the DG set to new location, reinstallation of DG set and dismantled accessories.
Dismantling of extsting DG Sets (125kVA) and shifting to the owner's storage yard
Dismantling, removal, shifting and reinstallation of existing solar power system from the existing sub-station building to new location as descided by IOCL.
Repair of existing high mast poles & fixing of new light by way of rectifying carriage pulley system or by refixing and aiming existing fixtures.
Roundoff
Please Enable Macros to View BoQ information
stage.html
html • 0.07 MB
tech_bid_open.pdf
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Tendernotice_1.pdf
PDF • 0.75 MB
PartA.pdf
Tender Documents • 3.66 MB
Tender-Acceptance-Format.pdf
Additional Documents • 0.08 MB
FAQs-IOCL-Online-EMD.pdf
Additional Documents • 0.55 MB
Bidders_help_Document_for_Preferencial_Bidding_20230207_v1.pdf
Additional Documents • 0.82 MB
Special_Instructions_to_the_Bidders_Version_5_dated_30_June_2025.pdf
Additional Documents • 2.80 MB
33_PartB.pdf
Tender Documents • 1.71 MB
BOQ_198501.xls
BOQ • 1.06 MB
TechSpecs1.rar
Additional Documents • 32.31 MB
TechSpecs2.rar
Additional Documents • 19.13 MB
TechSpecs3.rar
Additional Documents • 24.40 MB