Loading…
Loading…
Tender Value
₹1.6 L
EMD Value
₹3,200
Closing Date
13 Mar 2026, 5:00 pmClosed
EE
Electrical Division No.II, HPPWD, U.S. Club, Shimla-01.
Providing special repair and upgradation of electrical installation in Auditorium and class room at top floor Science Block RKMV Shimla.
2026_PWD_130438_1
ED.II.TA.TENDER.25.26.3782 dt.03.03.2026
Open Tender
Electrical Works
Percentage
90 days
Shimla
Please refer to tender documents. Eligibility criteria is mentioned at page No. 6-7, 9-10 of GCC. Documents mentioned in eligibility criteria must be uploaded to qualify the bid.
7 documents required · 7 mandatory
₹350
₹3,200
22 Mar 2026
6 Mar 2026
16 Mar 2026
6 Mar 2026
13 Mar 2026
6 Mar 2026
Wiring for light point / fan point / exhaust fan / call bell point with 1.5 Sq. mm. PVC insulated heat resistant flame retardant (HRFR) and low smoke single core (flexible) copper conductor cable in surface/recessed steel conduit with 5 Amp Modular Plate And Switch and earthing the light point with 1.5 Sq.mm. HRFRLS/PVC insulated single core copper conductor cable as required.
Group C
Wiring for group controlled ( looped) light point / Fan point / Exhaust fan point/ call bell point ( without independent switch etc) with 1.5 sq mm FRLS PVC insulated copper conductor singal core cable in surface/ recessed PVC conduit and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc as required.
supplying and fixing of suitable size GI box with modular plate and cover in front on surface/recess including providing and fixing 6 pin 5/6 amp &15/16 amp moduler socket and 15/16 amps modular switch connection As required
supplying and fixing following modular base & cover plate on existing modular mattal boxes ect. As required
8 module
supplying and fixing following modular switch & socketon the exising modular plate & switch box incuding connection but excluding modular plate ect. As required.
5/6 amps switch
3 pin 5/6 a socket outlet
Supplying and erection of 6 amps. to 32 amps. rating, 10 KA breaking capacity, 240 volts, 'C' curves, miniature circuit breaker of following poles in the existing MCB DB complete with connections etc. as required:-supplying and fixing of suitable size GI box with modular plate and cover in front on surface/recess including providing and fixing
Single pole. Cat-A.
Wiring for circuit/sub-main along with earth wire following size.HRFRLS/PVC insulated single core copper conductor cable surface/recessed steel conduit in medium class steel conduit as required
2x1.5 Sq. mm.+1x 1.5 sq mm earth wire
2x4.0 Sq. mm.+1x 4 sq mm earth wire
4x4 Sq. mm +2x 4 sq mm earth wire
Wiring for circuit/sub-main along with earth wire following size .HRFRLS/PVC insulated single core copper conductor cable surface/recessed medium class steel conduit as required.2X6 sq mm +1X6 Sq mm earth wire
Providing and installation of exhaust fan of following sizes in the existing opening, including making the hole to suit the size of the above fan, making good the damages, connections, testing and commissioning etc. as required:-
Exhaust Fan, Light 300 mm sweep
40/63 Amp 4 Pole
Supplying and fixing TP&N copper bus-bar chamber suitable for 415 volts capacity with 4 No. copper strip bus-bar each of length and x-section suitable for following current carrying capacities, enclosure made of sheet steel having thickness of 1.6mm dust protected duly powder painted with detachable gland plate and other accessories including drilling holes on the board making connection earthing etc. as required.
63 Amp. Copper Busbar Chambers 15" ( Enclosure)
Supplying and erection of 40/50/63 amps rating, 10 KA breaking capacity, 240 volts, 'C' curves, miniature circuit breaker of following poles in the existing MCB DB complete with connections etc. as required:-
Double pole. Cat-A.
Supplying and fixing of following way, single pole and neutral sheet steel MCB distribution board, 240 volts, on surface / recess, complete with tinned copper bus- bar, wire-set, neutral link, earth bar, din-bar, detachable gland plate, blanking plate, cable, identification labels interconnections, phosphatized and powder painted, including earthing etc. as required:-
Double door-16way
Double door-6way
S/E of LED Batten with polycarboante body and diffuser The fitting should be installed on existing surface/recess The job includes carriage, erection, making connections testing and commissioning of the fittings.
Specification of LED fittings:
Wattage of LED fittings - As per following parameter.
Total lumens of the fittings - as per wattage
Diffuser - Polycarbonate diffuser/PMMA
Operating voltage - 140 V to 270 V, AC supply or better.
Input frequency - 50 Hz + 1 Hz
Power factor - Minimum 0.90
Luminaire efficacy - ≥100 lm/w
Color rendering index - CRI shall be greater than 80
Working/ operating temperature - 00 to + 450c or better
Color temperature - 60000K + 10%
Electronic Driver
Drive current (LED) - As per OEM.
Operating voltage - 140 V to 270 V, AC supply or better.
Type of driver - Constant current output driver
THD - Less than 10%
Surge Protection - 2.5 KV minimum
Efficiency Driver - ≥85%
Protection - Shall have under voltage and over voltage protection.
Guarantee of LED fittings including LED driver - 2 years against manufacturing defect.
Fixture - Should comply with LM 79 test from UL/NABL lab.
LED Type/ Make/ Model - Power CREE/ OSRAM/ NICHIA/ Philips LUMILED with life more than 25,000 burning hours @70% lumen maintenance complying with LM 80 test report from the manufacturer.
Life of LED - 25000 burning hours at 70% lumen maintenance
Lumen output of the fitting
LED Batten Light ≥2000Lumens.
LED Batten Light ≥1000Lumens.
S/E of LED Downlighter round type surface with CRCA/PDC body and diffuser The fitting should be installed on existing surface The job includes carriage, erection, making connections testing and commissioning of the fittings.
Wattage of LED fittings - As per following parameter.
Total lumens of the fittings - as per wattage
Diffuser - Polycarbonate diffuser/PMMA
Operating voltage - 140 V to 270 V, AC supply or better.
Input frequency - 50 Hz + 1 Hz
Power factor - Minimum 0.90
Luminaire efficacy - ≥100 lm/w
Color rendering index - CRI shall be greater than 80
Working/ operating temperature - 00 to + 450c or better
Color temperature - 60000K + 10%
Electronic Driver
Drive current (LED) - As per OEM.
Operating voltage - 140 V to 270 V, AC supply or better.
Type of driver - Constant current output driver
THD - Less than 10%
Surge Protection - 2.5 KV minimum
Efficiency Driver - ≥85%
Protection - Shall have under voltage and over voltage protection.
Guarantee of LED fittings including LED driver - 2 years against manufacturing defect.
Fixture - Should comply with LM 79 test from UL/NABL lab.
LED Type/ Make/ Model - Power CREE/ OSRAM/ NICHIA/ Philips LUMILED with life more than 50,000 burning hours @70% lumen maintenance complying with LM 80 test report from the manufacturer.
Life of LED - 50000 burning hours at 70% lumen maintenance
Lumen output of the fitting
LED Down Light ≥2400Lumens.
S/E of LED Track Light with CRCA/PDC body and diffuser The fitting should be installed on existing surface. The job includes carriage, erection, making connections testing and commissioning of the fittings.
Wattage of LED fittings - As per following parameter.
Total lumens of the fittings - as per wattage
Diffuser - Polycarbonate diffuser/PMMA
Operating voltage - 140 V to 270 V, AC supply or better.
Input frequency - 50 Hz + 1 Hz
Power factor - Minimum 0.90
Luminaire efficacy - ≥100 lm/w
Color rendering index - CRI shall be greater than 80
Working/ operating temperature - 00 to + 450c or better
Color temperature - 60000K + 10%
Electronic Driver
Drive current (LED) - As per OEM.
Operating voltage - 140 V to 270 V, AC supply or better.
Type of driver - Constant current output driver
THD - Less than 10%
Surge Protection - 2.5 KV minimum
Efficiency Driver - ≥85%
Protection - Shall have under voltage and over voltage protection.
Guarantee of LED fittings including LED driver - 2 years against manufacturing defect.
Fixture - Should comply with LM 79 test from UL/NABL lab.
LED Type/ Make/ Model - Power CREE/ OSRAM/ NICHIA/ Philips LUMILED with life more than 50,000 burning hours @70% lumen maintenance complying with LM 80 test report from the manufacturer.
Life of LED - 50000 burning hours at 70% lumen maintenance
LED Track Light 30 Watt
Supplying and Fixing PVC batten/ angle holder including connection etc as required.
stage.html
html • 0.03 MB
tech_eval.pdf
fin_eval.pdf
finance_192848.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 1.29 MB
GCC.pdf
Tender Documents • 4.51 MB
BOQ_192848.xls
BOQ • 0.41 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .