Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹8.3 LAccepted-AOC | L1 | Accepted-AOC Being L1 | |
| 2 | L2₹9.2 L+₹14,300 (1.58%)Rejected-Finance | L2 | Rejected-Finance Being other than L1 | |
| 3 | L3₹9.5 L+₹41,880 (4.62%)Rejected-Finance | L3 | Rejected-Finance Being other than L1 | |
| 4 | L4₹10.9 L+₹1.8 L (20.3%)Rejected-Finance 111 YADAV ELECRIC MARKET GB MARG LUCKNOW LUCKNOW UTTAR PRADESH 226018 | LUCKNOW | UTTAR PRADESH | 226018 | L4 | Rejected-Finance Being other than L1 |
Tender Value
₹8.3 L
EMD Value
₹16,700
Closing Date
28 Sept 2024, 6:00 pmClosed
AGE (I) AF MEMAURA
AGE (I) AF MEMAURA
SPECIAL REPAIR REPLACEMENT OF APFC PANEL AND MES INSTALLATION AT AF STN MEMAURA
2024_MES_670402_1
8368/E8
Open Tender
Civil Works
Works
183 days
AGE (I) AF MEMAURA
Please refer Tender documents.
8 documents required · 8 mandatory
₹500
AGE (I) AF MEMAURA
₹16,700
Yes
16 Nov 2024
2 Sept 2024
30 Sept 2024
2 Sept 2024
28 Sept 2024
16 Sept 2024
Amount
Supply, laying and testing of LT cable 1100 volt grade XLPE insulated underground electric cable PVC bedded and sheathed steel wire/strip armoured aluminum stranded conductor of size 95 Sq mm 3.5 core complete all as specified and directed.
Supply, laying and testing of LT cable 1100 volt grade XLPE insulated underground electric cable PVC bedded and sheathed steel wire/strip armoured aluminum stranded conductor of size 25 Sq mm 4 core complete all as specified and directed.
M&L in replacement earthing complete with galvanised steel earth plate electrode 600x600x6.00 mm thick, burried directly in ground vertically to a depth not less than 2.25 mtr deep below GL with top edge of the plate not less than 1.5 mtr below normal GL and connected to earth plate . Earth plate surrounded by 15 cm thick packed layers of charcoal/coke and common salt upto 0.90 meter depth all around the earth plate and connected to earth lead of GI strip 25x4 mm by means of bolts, nuts, check nuts and washers of GI or steel and thimbles and other end of the earth wire connected to equipments/panels and protected by galvanized iron or steel pipe light grade 40 mm bore and water pipe 20 mm bore GI medium grade with funnel and wire mesh, including all necessary excavation and earth work PCC chamber in cement concrete 1:3:6 type C-2 and RCC cover and all as shown in electrical plate No 3 of MES schedule Pt I of 2009 and also including making test point for testing of earthing complete all as specified and as directed. Note : 1. RCC pit cover shall be pre-cast of RCC (1:2:4) type B-I , 50mm thick reinforced with XPM weighting not less than 4 KG/sqmm in lieu of CI cover. 2. Charcoal/coke and common salt upto 0.90 meter depth shall be filled in layers of 15 centimeters all around the earth plate. 3. On testing after completion of earthing if desired earth resistance is not achieved , the earthing will be redone at no extra cost to obtain the desired earth values.
M/S SURYA ASSOCIATES (BID ID -3101817)
VIDYA TRADERS (BID ID -3101434)
Industrial Traders (BID ID -3104098)
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .