| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹37.6 LAccepted-AOC A 93 SECTOR 36 GREATER NOIDA GAUTAM BUDDHA NAGAR UTTAR PRADESH 201308 | GAUTAM BUDDHA NAGAR | UTTAR PRADESH | 201308 | ₹37.6 L Quoted ₹38.3 L | L1 | Accepted-AOC L1 |
| 2 | L2₹39.3 L+₹99,850 (2.61%)Rejected-Finance | ₹39.3 L+₹99,850 (2.61%) | L2 | Rejected-Finance Being not lowest tenderer |
| 3 | L3₹42.5 L+₹4.2 L (10.9%)Rejected-Finance | ₹42.5 L+₹4.2 L (10.9%) | L3 | Rejected-Finance Being not lowest tenderer |
| 4 | Rejected-Technical | - | - | Rejected-Technical Not enlisted in requisite category |
| 5 | Rejected-Technical 1 225 5 6 SADAR BAZAR DELHI CANTT 110010 | NEW DELHI | DELHI | 110010 | - | - | Rejected-Technical contractor requested recd vide letter No nil dated 11 Jul 2025, not open financial bid |
| Sl No | Description | Qty | Unit | M/S Delhi Engineering Co. L2 | M/S S.K.Electricals L3 | Deepak Electricals L1 |
|---|---|---|---|---|---|---|
| 1.00 | M & L HT 11 KV for under ground (high tension) cable fault finding for exact location by using HT fault locating equipment and trace out the fault complete all as specified and directed
Note :- The rate quoted by the contractor shall include the rate for excavating the cable at the fault location & pinpoint the fault, repairing the cable using cable jointing kits and by adding extra HT cable if required at site, jointing the cables as before to the panel and testing complete all as earth work and necessary T&P etc. | 20 | Per fault | 8,500 ₹1,70,000 | 7,500 ₹1,50,000 Lowest | 8,000 ₹1,60,000 |
| 2.00 | Supply and fix in replacement of cable route indicator made out of 15x15x6mm GI plate welded with 8 mm x 45cm long GI rod grouted in PCC block 1:2:4 type B1 using 20mm graded stone aggregate of size 15x15x10cm and writing the words 'HT cable' as directed with synthetic enamel paint of two coats over a coat of primer including excavation and earth work all as directed. | 35 | Each | 100 ₹3,500 Lowest | 100 ₹3,500 Lowest | 100 ₹3,500 Lowest |
| 3.00 | M & L for PCC (1:3:6) type C2 (using 40mm graded aggregate) as in foundation for stay set / Pole / feeder pillar lean concrete etc including fair finish even and fair to exposed surfaces without using extra cement complete all as specified and as directed. | 3.5 | Cum | 4,000 ₹14,000 Lowest | 4,500 ₹15,750 | 5,000 ₹17,500 |
| 4.00 | Supply and fixing in replacement space heater suitable for VCB panel 100 watt 240 AC 50 HZ AC Supply complete all as specified and as directed. | 18 | Each | 1,400 ₹25,200 Lowest | 1,500 ₹27,000 | 1,500 ₹27,000 |
| 5.00 | Supply and fixing in replacement Thermostat 30 to 70 degree centigrade suitable for controlling space heater inside VCB panel 240 AC 50 HZ AC Supply complete all as specified and as directed. | 10 | Each | 1,200 ₹12,000 | 1,000 ₹10,000 Lowest | 1,650 ₹16,500 |
| 6.00 | Supply, laying in replacement of testing and commissioning in replacement trenches /passing through pipes/ on poles etc cable XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured, electric power cables (heavyduty) with stranded aluminium conductor, 11000 volts, grade of size of cable 300 sq mm 3 core ISI marked suitable for earthed system including taking out unserviceable cable complete all as specified and directed by Engineer-in-Charge. | 120 | RM | 2,600 ₹3,12,000 | 2,450 ₹2,94,000 | 1,450 ₹1,74,000 Lowest |
| 7.00 | All as per item No.6 here-in-above but size 185 sqmm 3 core ISI marked complete all as specified and directed by Engineer-in-Charge. | 150 | RM | 1,800 ₹2,70,000 | 1,950 ₹2,92,500 | 1,250 ₹1,87,500 Lowest |
| 8.00 | All as per item No.6 here-in-above but size 120 sqmm 3 core ISI marked complete all as specified and directed by Engineer-in-Charge. | 160 | RM | 1,600 ₹2,56,000 | 1,550 ₹2,48,000 | 1,000 ₹1,60,000 Lowest |
| 9.00 | M&L cable jointing kit for 11 KV grade cable for indoor termination heat shrink type joint compelete with jointing material and accessories suitable for 3 core XLPE armoured conductor cable of size 50 to 95 Sqmm ISI marked complete all as specified and directed by Engineer-in-Charge. | 9 | Each | 4,500 ₹40,500 | 7,000 ₹63,000 | 3,600 ₹32,400 Lowest |
| 10.00 | M&L cable jointing kit for 11 KV grade cable for indoor termination heat shrink type joint compelete with jointing material and accessories suitable for 3 core XLPE armoured conductor cable of size 120 Sqmm to 185 Sqmm ISI marked complete all as specified and directed by Engineer-in-Charge. | 8 | Each | 8,500 ₹68,000 | 9,000 ₹72,000 | 5,000 ₹40,000 Lowest |
Tender Value
₹50 L
EMD Value
₹1 L
Closing Date
4 Jul 2025, 6:00 pmClosed
CWE AF TUGHLAKABAD
HQ CWE AF TUGHLAKABAD AF STATION, TUGHLAKABAD PO SANGAM VIHAR NEWDELHI-110080
REPAIR/MAINT OF RING MAIN UNIT, VCB AND CONNECTED ACCESSORIES IN TECH AREA 7 BRD UNDER GE (AF) TUGHLAKABAD
2025_MES_714275_1
CWE/TKD/TOKEN-27 OF 2025-26
Open Tender
Electrical and Maintenance Works
Item Rate
270 days
GE (AF) TUGHLAKABAD
AS PER NIT DOCUS
7 documents required · 7 mandatory
₹0
₹1 L
17 Oct 2025
13 Jun 2025
7 Jul 2025
13 Jun 2025
4 Jul 2025
27 Jun 2025
Amount
M & L HT 11 KV for under ground (high tension) cable fault finding for exact location by using HT fault locating equipment and trace out the fault complete all as specified and directed Note :- The rate quoted by the contractor shall include the rate for excavating the cable at the fault location & pinpoint the fault, repairing the cable using cable jointing kits and by adding extra HT cable if required at site, jointing the cables as before to the panel and testing complete all as earth work and necessary T&P etc.
Supply and fix in replacement of cable route indicator made out of 15x15x6mm GI plate welded with 8 mm x 45cm long GI rod grouted in PCC block 1:2:4 type B1 using 20mm graded stone aggregate of size 15x15x10cm and writing the words 'HT cable' as directed with synthetic enamel paint of two coats over a coat of primer including excavation and earth work all as directed.
M & L for PCC (1:3:6) type C2 (using 40mm graded aggregate) as in foundation for stay set / Pole / feeder pillar lean concrete etc including fair finish even and fair to exposed surfaces without using extra cement complete all as specified and as directed.
Supply and fixing in replacement space heater suitable for VCB panel 100 watt 240 AC 50 HZ AC Supply complete all as specified and as directed.
Supply and fixing in replacement Thermostat 30 to 70 degree centigrade suitable for controlling space heater inside VCB panel 240 AC 50 HZ AC Supply complete all as specified and as directed.
Supply, laying in replacement of testing and commissioning in replacement trenches /passing through pipes/ on poles etc cable XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured, electric power cables (heavyduty) with stranded aluminium conductor, 11000 volts, grade of size of cable 300 sq mm 3 core ISI marked suitable for earthed system including taking out unserviceable cable complete all as specified and directed by Engineer-in-Charge.
All as per item No.6 here-in-above but size 185 sqmm 3 core ISI marked complete all as specified and directed by Engineer-in-Charge.
All as per item No.6 here-in-above but size 120 sqmm 3 core ISI marked complete all as specified and directed by Engineer-in-Charge.
M&L cable jointing kit for 11 KV grade cable for indoor termination heat shrink type joint compelete with jointing material and accessories suitable for 3 core XLPE armoured conductor cable of size 50 to 95 Sqmm ISI marked complete all as specified and directed by Engineer-in-Charge.
M&L cable jointing kit for 11 KV grade cable for indoor termination heat shrink type joint compelete with jointing material and accessories suitable for 3 core XLPE armoured conductor cable of size 120 Sqmm to 185 Sqmm ISI marked complete all as specified and directed by Engineer-in-Charge.
M&L cable jointing kit for 11 KV grade cable for Straight through heat shrink type joint compelete with jointing material and accessories suitable for 3 core XLPE armoured conductor cable of size 120 Sqmm to 185 Sqmm ISI marked complete all as specified and directed by Engineer-in-Charge.
M&L cable jointing kit for 11 KV grade cable for Straight through heat shrink type joint compelete with jointing material and accessories suitable for 3 core XLPE armoured conductor cable of size 50 Sqmm to 95 Sqmm ISI marked complete all as specified and directed by Engineer-in-Charge.
Supply and jointing heat shrinkable straight through joint with jointing material suitable for HT 11 KV XLPE cable of size 240-300 sqmm 3 core ISI marked complete all as specified and as directed by Engineer-in-Charge.
Supply and jointing outdoor termination heat shrinkable joint with jointing material suitable for HT 11KV XLPE cable of size 240 to 300 Sq mm 3 core ISI marked complete all as specified and as directed by Engineer-in-Charge.
Excavation in trenches in soft/loose soil not exc 1.50 mtrs wide and not exc. 1.5 mtr deep and getting out for taking out/laying cable pole &stay etc including taking out old precast concrete cover complete all as specified and directed by Engineer-in-Charge.
Returning, filling in, including spreading levelling, watering and well ramming in layers not exc. 25 cm thick complete all as specified and directed by Engineer-in-Charge.
Removal of excavated surplus soil to a distance not exc. 50 mtr away and depositing where directed at a level not exc 1.5 mtr above the starting point complete all as specified and directed by Engineer-in-Charge.
M&L for sand cushioning to under ground cable provided with layer of sand (8cm deep before laying the cable and 15 cm deep after laying the cable ie total 23 cm and after punning down sand cushioning will be 18 cm complete all as specified and directed by Engineer-in-Charge. Note : Sand cushioning 18 cm thick only will be considered for payment purpose.
M&L in replacement of for precast concrete cover class HV type 1, flat size 300mmx180mmx40mm laid in trenches for cable protection complete all as specified and directed.
Supply and jointing kit for 11 KV grade cold shrinkable straight through joint with jointing material suitable for HT 11KV XLPE cable of size 240 to 400 Sq mm 3 core ISI marked complete all as specified and directed.
Supply and jointing kit for 11 KV grade cold shrinkable straight through joint with jointing material suitable for cable size 120 to 185 Sq mm ISI marked complete all as specified and directed.
M&L cable jointing kit for 11 KV grade cable for indoor termination heat shrink type joint compelete with jointing material and accessories suitable for 3 core XLPE armoured conductor cable of size 240 Sqmm to 300 Sqmm ISI marked complete all as specified and directed.
Supply and fix in replacement Motor assembly 110 volt / 220 volt AC/DC suitable for HT 11 KV VCB/Load brak switch complete all as specified and as directed by Engr In Charge. Make:- ABB/Siemens/Areva/CG/Schneider/Megawin
S&F in replacement of fixed contact block complete suitable for 630/800 Amps, 11 KV HT VCBs all as specified and directed
S&F in replacement of moving contact block complete suitable for 630/800 Amps 11 KV HT RMU/OCB all as specified and directed by Engineer-in-Charge.
S&F in replacement mechanical castle interlock assembly with key suitable for HT 11 KV VCB of rating 630 Amps complete all as specified and directed by Engineer-in-Charge.
S&F in replacement of closing coil assembly 230 volts AC/ 24 volts DC, CAT Part No 598/SP all as specified and directed by Engineer-in-Charge.
S&F in replacement Tripping coil with plunger assembly 230 volts AC/24V DC, CAT Part No 599/SP all as specified and directed by Engineer-in-Charge.
S&F in replacement closing coil plunger with 24 volts DC, CAT Part No 604/SP all as specified and directed by Engineer-in-Charge.
S&F in replacement spout bushing 11 KV for VCB all as specified and directed by Engineer-in-Charge.
S&F in replacement HT 11 KV PT HRC Fuse all as specified and directed by Engineer-in-Charge.
Calibration/mechanism of HT 11 KV VCB 800Amp to 630 Amp, with highly skilled mechanic specialist in electric HT breakers line, by taking out trolley, decarbonizing of all parts using CRC-2-26 spray, checking of all fixed and moving parts, tightening of all nuts & bolts, dressing, cleaning of contacts by using emery paper for fine/smooth contact, tightening of all connections, checking of alignment for easy moving of breaker, checking of ON/ OFF operation with setting of buffer gap adjustment, inspecting the wiring of IDMT relays contact travel contact alignments, roller gap, hard or light setting of breaker greasing of all moving mechanism complete all as specified and as directed. Note ; Calibration will be carried out by auth contractor/ Tech and test certificate will be kept on record.complete all as specified and directed by Engr-in-charge.
S&F in replacement in replacment of Vaccum interruptor type WL-33379 (4 inch dia) suitable for HT VCB 630/800 Amps all as specified and directed by Engineer-in-Charge.
S & F in replacement Push button for trip and hold of 11 KV 400 A RMU/ VCB complete all as specified and as directed.
S&F in replacement of indicator lamp LED with holder (R/Y/B in colour) complete all as specified and as directed by Engr-in-Charge.
S&F in replacement of shunt trip coil 30 volts DC for HT 11KV OCB/VCB all as specified and directed by Engineer-in-Charge.
Supply & Fix in replacement motor and gear assembly 11KV AC/24V DC UMG-14 type all as specified and directed by Engineer-in-Charge.
Supply & Fix in replacement of isolating contact assembly suitable for 630 Amps HT VCB or equivalent all as specified and directed
S&F in replacment of Power pack with battery backup 11KV AC/30V DC &nconnected to HT PT secondary circuit including testing for triping complete. all as specified and directed by Engineer-in-Charge. Make :- Areva/Electromotive/Power pack
Supply & Fix in replacement of Digital protective 3 phase earth fault relay with high set with CT rating 5A 2 NO+2NC model MC61A complete for HT 11 KV OCB/VCB panel and connection and testing on full load, all as specified and directed by Engineer-in-Charge. Make :-AREVA/L&T/C&G
Supplly & Fix in replacement of Master trip relay suitable for working voltage 30 Volt DC and connecting the circuit with existing over current and earth fault relas complete all as specified and directed by Engr-in-charge. Make:Areva/Alstom/crompton
S&F in replacement of maintenance free fully charged Nickle cadmium battery 60 Ah, 12 volts complete all as specified and as directed by Engineer-in-Charge.
Opening the front and rear cabinate of the HT 11KV RMU 3 way/5 way 630/800 Amps de-carbonizing moving and fixed contacts if required, lubricating, checking the pressure of SF-6 gas, inspecting the wiring of micro processor EF/OC relay, tripping coil electrical and checking for manual/auto tripping system complete and placing the SF-6 VCB and isolating unit in its original position all as specified and as directed by Engr-in-Charge
HT 11 KV RMU Callibration of microproccessor Eaeth fault and over current relay of RMU decarbonizing of all parts using CRC-2-26 spray, checking of all fixed and moving parts, tightening of all nuts & bolts, dressing, cleaning of contacts by using emery paper for fine/smooth contact, tightening of all connections, checking of alignment relay test kit to set time and fault level and adjustment of setting with according to load & time with main Tech area power house incl replacement of relay battery for proper functioning complete all as specified and directed by Engr-in-Charge.
S&F in replacement SF-6 Ring Main unit fuse 11 KV by opening fuse canisters of RMU positioned behind interlocking cover complete all as specified and directed by Engineer-in-Charge.
S & F in replacement Primary copper wound type HT resin cast CTs, dual current 3.0 VA of ratio 300/150/5+5A including making all, connection for relay meter indicator etc. and including connecting testing conforming complete all as specified and as directed.
S & F in replacement of dry type potential transformer of 11 KV single phase indoor resin cast CT of ratio 11 KV /v3/110V/v3/110V/v3 class 0.5-3, Bus bar 50 VA-50 VA, insulation level 28/75 KV voltage factor 1.2 Cont and 1.9 for 30 Sec conforming to IS-3156 complete all as specified and as directed.
S & F in replacement Primary copper wound type HT resin cast CTs, dual current 3.0 VA, of ratio 60/30/5+5A including making all, connection for relay meter indicator etc. and including connecting testing conforming complete all as specified and as directed.
S & F in replacement Primary copper wound type HT resin cast CTs, dual current 3.0 VA,of ratio 50/25/5+5A including making all, connection for relay meter indicator etc. and including connecting testing conforming complete all as specified and as directed.
S & F in replacement Primary copper wound type HT resin cast CTs, dual current 3.0 VA, of ratio 40/20/5+5A including making all, connection for relay meter indicator etc. and including connecting testing conforming complete all as specified and as directed.
S & F in replacement Primary copper wound type HT resin cast CTs, dual current 3.0 VA, ratio 30/5A including making all, connection for relay meter indicator etc. and including connecting testing conforming complete all as specified and as directed.
Supply and fix in replacement of digital type voltmeter for HT 11 KV VCB including taking out unserviceable one connectiong testing and commissioning all as specified and directed by Engineer-in-Charge.
Supply and fix in replacement of digital type Ammeter for HT 11 KV VCB as that of existing range model to suit to existing CT ratio 150/1A including taking out unserviceable one connectiong testing and commissioning all as specified and directed by Engineer-in-Charge.
Supply and fix in replacement of analog type voltmeter for HT 11 KV VCB including taking out unserviceable one connectiong testing and commissioning all as specified and directed by Engineer-in-Charge.
Supply and fix in replacement of analog type Ammeter on HT panel as that of existing range model to suit to existing CT ratio 150/1A including taking out unserviceable one connectiong testing and commissioning all as specified and directed by Engineer-in-Charge.
S&F in replacement terminal contact piece with silicone coupling for SF-6 Ring Main unit 11 KV by opening the terminal cover complete all as specified and directed by Engineer-in-Charge.
S&F in replacement pressure indicator manometer for SF-6 Ring Main unit 11 KV by opening the front cover complete all as specified and directed by Engineer-in-Charge.
S&F in replacement ring type current transformer 100/1 Amps for SF-6 Ring Main unit 11 KV by opening the cable compartment cover of fixed the CT on cable elbow plug/T plug complete all as specified and directed by Engineer-in-Charge.
S&F in replacement ring type current transformer 50/1 Amps for SF-6 Ring Main unit 11 KV by opening the cable compartment cover of fixed the CT on cable elbow plug/T plug complete all as specified and directed by Engineer-in-Charge.
S&F in replacement SF-6 gas in safe ring/safe plus by SF-6 gas bottle by removing front cover and on screw manometer and reduction valve and maintained the pressure 14 bar obslute complete all as specified and directed by Engineer-in-Charge.
M & L in replacement for mild steel plates/ duct cover Fe-410-W (Gde -E-250) plain or chequered as in duct covers including cutting , fabricate, cut to existing sizes including taking out the rusted plates all as specified and as directed.
Cutting removing the vegetation growth and surface dressing all around the installation, including apply white wash of installation bldg both side all as specified and as directed .
Supply & Fix in replacement of earth fault protection and indicator relay for Ring main unit including callibrating the relay with existing load and tripping timming complete all as specified and directed by Engr-in-Charge.
S&F in replacement Trifurcation boot 11 KV capacity for cable termination joint of RMU incoming and outgoing terminals including taking out old defective trifurcation boot complete all as specified and directed by Engineer-in-Charge.
S&F in replacement HT bushing with gaskit for SF-6 Ring main unit 11 KV complete all as specified and directed by Engineer-in-Charge.
M & L in replacement GI tubing 'Light' grade for cable protection fixed in poles/walls/laid under roads/crossing etc including taking out the rusted pipes of size 100mm dia ISI marked all as specified and directed
M & L for boring of holes under road, pavement, hard standing by trenchless technology using ultra sound technique and necessary machine including HDPE pipe of 110mm dia suitable for 0.4mpa working pressure complete all as specified and directed.
Supply and fix replacement Bushes suitable for RMU complete all as specified and as directed.
M&L in replacement of Maintenance free battery 12 Volt, 120AH complete all as specified and as directed.
Supply, laying in replacement of and pasting on floor suitable for HV 11KV synthetic insulating rubber mat of size 2m x1m x 19mm class A complete with ISI marked complete all as specified and as directed.
Mild in replacement of steel plates, plain or chequered, 5mm thick or over in thickness in available sizees Fe 410-W (Gde-E-250) quality-A complete all as specified and as directed by Engr-in-charge
M&L in replacement of Dehydrating breather assembly upto 750 KVA aluminium/CI body of standard size filled with silica-gel for transformer of any capacity complete all as specified and as directed.
M&L in replacement of temperature gauge circular dia type of standard size for transformer of any capacity in repairs complete all as specified and directed
S&F in replacement of MCCB 400 Amps 4 pole alongwith spreader/link 415 volts 3 phase 50 HZ with Adjustable Thermal & adjustable Magnetic setting of rapturing capacity 36 KA complete all as specified and as directed.
S&F in replacement of MCCB 250 Amps 4 pole alongwith spreader/link 415 volts 3 phase 50 HZ with Adjustable Thermal & adjustable Magnetic setting of rapturing capacity 35 KA complete all as specified and as directed.
S&F in replacement of MCCB 200 Amps 4 pole alongwith spreader/link 415 volts 3 phase 50 HZ with Adjustable Thermal & adjustable Magnetic setting of rapturing capacity 35 KA complete all as specified and as directed.
M&L cement concrete type B- 1, 1:2:4 (using 20mm grade aggregate) in mass concrete, complete all as specified and directed.
Supply & Fix in replacement K-mechanism for 11 KV Ring Main unit ABB Make, including taking out old unserviceable mechanism and testing complete all as specified and as directed.
Supply & Fix in replacement of Digital protective 3 phase over current relay with high set with CT rating 5A 2 NO+2NC model MC61A complete for HT 11 KV OCB/VCB panel and connection and testing on full load, all as specified and directed by Engineer-in-Charge.
Supply & Fix in replacement of Spring charging geared motor 230V AC/DC all as specified and directed by Engineer-in-Charge
M&L cable jointing kit for 11 KV grade cable for indoor termination heat shrink type joint compelete with jointing material and accessories suitable for 3 core XLPE armoured conductor cable of size 240 Sqmm to 300 Sqmm ISI marked complete all as specified and as directed. .
Supply & Fixing in replacement Motorized Aluminiun rolling shutter, Size 4090x4673 mm with chain drive System & key operater with 1 pair infrared beam Safety sensor & Hazard notification Led Siren Light, Specially make 1.2 mm thick double wall aluminium shutter curtain, jointless T-shaped specially design Specially Designed side guide with epdm lip seal, mild steel bottom bar with Epdm rubber seal & manual lock provision and attached angel, Galvalume 0.7mm thick Top cover & motor cover,mild steel 5 mm thick top support plate 7 round shaft, MS frame 3 mm thick rectanular pipe for shutter installation, complete shutter poder coated bottom top in blue colour.
Schedule of Credit
M/S Delhi Engineering Co. (BID ID -3338979)
M/S S.K.Electricals (BID ID -3346875)
stage.html
html • 0.07 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .