EEE-II
MUNICIPAL CORPORATION OF DELHI OFFICE OF THE Ex. ENGINEER (ELECT)-II/SSZ 2 nd Floor Technical Laboratory Near NH-24 Ghazipur Delhi
Provision of Flood lights at Various MC(P) School Of AC-60 Krishna nagar and AC-61 Gandhi Nagar Under EEE-II/SSZ
2026_MCD_268036_1
EEE-II/2025-26/64.3
Open Tender
Electrical Works
Percentage
90 days
work
Please refer to tender document
4 documents required · 4 mandatory
₹590
₹20,000
24 Jul 2026
20 Feb 2026
26 Feb 2026
20 Feb 2026
26 Feb 2026
20 Feb 2026
This is a percentage-rate BOQ. The schedule below shows estimated quantities and rates. Bidders quote a single percentage above or below the total estimated cost.
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | Supplying, installation, Testing & Commissioning of Flood Light, powder coated pressure die cast aluminum body with built in or separate driver as per the requirement with Driver efficiency >85%, Input voltage: Input voltage: 140-270 Volt AC, freq 50/60 hz, Operating temp range -15 deg to 50deg centigrade, internal surge protection of 5 KV L,N,E as per IEC 61000-4-5, Driver efficiency >85%,THD < 10% as per IEC 61000-3-2 , P. F.≥0.95, IP- 66,IK-10, CRI >80 , under voltage and over voltage protection, EMIEMC as per CISPR -15 , lenses for beam angle 30 deg-120deg as per the application and the (LED,Driver & electrical circuitary) of minimum 50000 Burning Hours with project requirement deg., suitable tilt able fitting, life time 70% of initial Lumen maintained till life ends as per LM80 extrapolation IES TM-21-11 report, CCT 3000°K / 4000°K / 5700°K /6000°K/6500°K (As per ANSI Bin) , SDCM(Standard Deviation Color Matching) <5, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard complete in all respect i/c connections with 1.5 sq mm FRLS, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥120 and
<135 lm/Watt output . LM79 & LM80 Test report from NABL lab for all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-inCharge as per requirement. (Thermal management: heat sink ofaluminum housing such that LED junction temperature shall not rise above 90°C).150 WATT | - | each | 3,457 | - |
| 2 | Supply of XLPE insulated PVC sheathed Al. Conductor Armoured Cable 1.1KV grade conforming to IS-7098 of following size:-2C*6 sqmm | - | meter | 95 | - |
| 3 | Laying of one number PVC insulated PVC sheathed power cable of 1.1 KV grade of following size in the existing masonary open duct etc as reqd.(a) up to 35 Sqmm | - | meter | 36 | - |
| 4 | Laying of one number PVC insulated PVC sheathed power cable of 1.1 KV grade of following size on the Wall surface as reqd.(a)Upto 35 sq. mm (clamped with 1mm thick saddle) | - | meter | 64 | - |
| 5 | Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 meter long etc. with charcoal/ coke and salt as required. | - | each | 8,351 | - |
| 6 | Providing and fixing 25 mm X 5 mm G.I. strip on surface or in recess for connections etc. as required. | - | meter | 287 | - |
| 7 | Providing and fixing 25 mm X 5 mm G.I. strip in 40 mm dia G.I. pipe from earth electrode including connection with G.I. nut, bolt, spring, washer excavation and re-filling etc. as required. | - | each | 755 | - |
| 8 | Providing and fixing following rating and breaking capacity and pole MCCB with thermomagnetic release and terminal spreaders in existing cubicle release and terminal spreaders in existing cubicle panel board including drilling holes in cubicle panel,making connections, Ics=100% Icu and Operational Voltage 690V etc. as required.100 A, 16 KA,TPMCCB | - | each | 4,003 | - |
| 9 | Supplying and fixing following rating, double pole, 240 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.63 amps | - | each | 569 | - |
| 10 | Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, "C"curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. (a) Single pole | - | each | 285 | - |
stage.html
html • 0.05 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.48 MB
condition.pdf
Tender Documents • 0.34 MB
BOQ_311860.xls
BOQ • 0.29 MB
viewsbd.pdf
Additional Documents • 15.52 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .