| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹18.4 LAccepted-AOC NO 9 BYRAVESHWARA INDUSTRIAL ESTATE ANDRAHALLI MAIN ROAD NEAR PEENYA 2ND STAGE BENGALURU 560 091 | BENGALURU URBAN | KARNATAKA | 560091 | ₹18.4 L Quoted ₹20.2 L | L1 | Accepted-AOC BEING LOWEST |
| 2 | L2₹20.7 L+₹58,550.48 (2.90%)Rejected-Finance | ₹20.7 L+₹58,550.48 (2.90%) | L2 | Rejected-Finance BEING NOT LOWEST |
| 3 | L3₹24.9 L+₹4.7 L (23.5%)Rejected-Finance | ₹24.9 L+₹4.7 L (23.5%) | L3 | Rejected-Finance BEING NOT LOWEST |
| 4 | L4₹25.0 L+₹4.9 L (24.2%)Rejected-Finance RZ 212F D BLOCK RAJ NAGAR PART II PALAM COLONY NEW DELHI 110077 | SOUTH WEST | DELHI | 110077 | ₹25.0 L+₹4.9 L (24.2%) | L4 | Rejected-Finance BEING NOT LOWEST |
| 5 | L5₹27.5 L+₹7.4 L (36.5%)Rejected-Finance | ₹27.5 L+₹7.4 L (36.5%) | L5 | Rejected-Finance BEING NOT LOWEST |
Tender Value
₹45.2 L
EMD Value
₹90,400
Closing Date
6 Jul 2021, 6:00 pmClosed
ARJUN PATRO,IDSE
GE U ELECTRIC SUPPLY,DELHI CANTT
REPAIR AND MAINTENANCE OF 11 KV HT CABLE RMU LT PANEL AND MAINTENANCE OF ELECTRICAL BREAKDOWN INCL FAULT DETECTION LOCALIZATION AND RECTIFICATION IN HTLT UNDERGROUND NETWORK AT ARJAN VIHAR NEW PRATAP CHOWK PRATAP CHOWASS, AHPU RRRC, AEPTA AND ADJ
2021_MES_449828_1
GE ELECT/D-32/2021-2022
Open Tender
Electrical and Maintenance Works
Item Rate
270 days
GE U ELECTRIC SUPPLY
Please refer Tender documents.
8 documents required · 8 mandatory
₹500
GE U ELECTRIC SUPPLY
₹90,400
Yes
14 Sept 2021
17 Jun 2021
8 Jul 2021
18 Jun 2021
6 Jul 2021
1 Jul 2021
Amount
Excavation in trenches not exc. 1.5 m wide and not exc 1.5 mtr deep in soft/loose soil for laying / taking up/ taking down of cables and getting out and levelling of bottom suface to required level all as specified and directed by Engineer- in- Charge.
Returning filling Including spreading, levelling,watering and well ramming soil in layers not exceeding 25 cm thick all as specified and directed.
Removing excavated material (ie soil) from site to a distance n. exc 50 mtrs away and depositing where directed at a level n. exc. 1.5 mtr above the starting point all as specified and directed by Engineer-in-Charge.
Material and labour for river washed and screened, dry sand for filling in trenches below and around underground cables for cushioning of cables etc, complete all as specified. Note : Measurement shall be taken after punning down.
S&F sub class B bricks having minimum compressive strength 75 Kg/ Sqcm laid in trenches for cable protection etc complete all as directed by Engineer-in-Charge.
All as per srl item No 5 here-in-before but using old bricks obtained under srl item No1 here in before.
Supplying and laying un-reinforced precast concrete cable cover, class HV, type 1, flat size 300mmx 180mm x 40mm.
All as per srl item No 7 here-in-before but using old un-reinforced precast concrete cable cover obtained under srl item No 1
Supply, laying, jointing, testing and commissioning in replacment LT underground cables 1100 volts grade, PVC insulated XLPE and PVC sheathed, heavy duty armoured, with multistranded aluminium conductors, IS-1554 marked, laid in trenches complete all as specified and directed. Cables of the following sizes:- Note Excavation, earth work ,cable protection , sand fillings , cable joint shall be measured and paid separately.
16 Sqmm 4 core
25 Sqmm 4 core
35 Sq mm 3.5 core.
50 Sq mm 3.5 core.
70 Sqmm 3.5 core
95 Sqmm 3.5 core
120 Sqmm 3.5 core
185 Sqmm 3.5 core
240 Sqmm 3.5 core
300 Sqmm 3.5 core
Supplying, laying, jointing testing and connecting in replacement XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured, electric power cable (heavy duty) with multistranded aluminum conductors, 11 KV grade, IS 7098 marked, suitable for HT 11 KV(E) system, laid in trenches fixed to pole, including jointing & testing complete all as specified and directed of following sizes Note :- Excavation, earth work ,cable protection , sand fillings , cable joint shall be measured and paid separately.
95 sqmm 3 core.
120 sqmm 3 core.
185 sqmm 3 core
240 sqmm 3 core
300 sqmm 3 core
Testing the cables with high voltage DC testing machine and locating the fault in the cables by fault locating machine to pin point exact position of fault, disconnecting faulty 11 KV HT cables of different sizes from both ends, removal of Fault, Re-connections and testing of cables after removal of fault complete all as specified and directed. Note: (a) 11 KV HT cable & joints shall be measured and paid for seperately under respective items of schedule. (b) Retrieved old serviceable cable cover/bricks will be laid in trenches for cable protection. If extra PCC cover/bricks and sand required at site shall be measured and paid separately under respective items of BOQs. (c) Excavation and earth work will be measured and paid for seperately under respective items of schedule.
All as per item Ser No 11above but 1100 Volt LT cables complete all as specified and as directed.
Taking out faulty underground 1100 Volt LT cable of different sizes by excavation and removing bricks of any size and relaying in the same trenches or re routing after rectification of fault or replacing faulty portion of cable with new cable and removing of surplus soil and using new bricks as required. Note: (a) 1100 Volt LT cable & joints shall be measured and paid for seperately under respective items of schedule. (b) Retrieved old serviceable bricks will be laid in trenches for cable protection. If extra bricks and sand required at site shall be measured and paid separately under respective items of BOQs. (c) Excavation and earth work will be measured and paid for seperately under respective items of schedule.
All as per item Ser No 13 above but 11000 Volt HT cables complete all as specified and as directed..
Material and labour disconnecting faulty /burnt end or portion of cable by removing the cable from loop including necessary excavation & earth work , suitable size of thimble LT tap , relaying and reconnecting the cable by removing faulty/burnt portion of cable and preparing fresh terminals for 25 Sqmm 3.5/4 core to 240 Sqmm 3.5 core of LT cable to LT Panel/pole/main switch complete all as directed.
Supply, fixing and testing LT straight through joint heat shrinkable type with jointing kit suitable for cable PVC/XLPE insulated armoured heavy duty aluminium conductor 1100 Volts grade complete all as directed for the following sizes :-
16-50 Sqmm x 3.5 core/ 4 core
70-150 Sqmm x 3.5 core
185 -240 Sqmm x 3.5 core
Supply and fix Cable jointing kit for 11 KV (Earthed) grade cable for indoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of following size :-
95 Sqmm 3 core.
120 Sqmm to 185 Sqmm, 3 core.
240 Sqmm to 300 Sqmm 3 core
Supply and fix Cable jointing kit for 11 KV (Earthed) grade cable for outdoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of following size :-
95 Sqmm 3 core.
120 Sqmm to 185 Sqmm, 3 core.
240 Sqmm to 300 Sqmm, 3 core.
Supply and fix Cable jointing kit for 11 KV (Earthed) grade cable for straight through heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of following size :-
95 Sqmm 3 core.
120 Sqmm to 185 Sqmm, 3 core.
240 Sqmm to 300 Sqmm 3 core
Boring of hole under road/pavement/hard standing or any other situation by mannual means and including GI pipe 100 mm bore (medium grade) and making good both ends all specified and directed
Supply and lay GI pipe light grade in replacement as cable protection laid on trench/floor, fixed on pole/wall etc of following sizes all as specified of sizes
100 mm dia
80 mm dia
50 mm dia
Supply and laying as replacement in sub station fixing 3.3 KV to 11 KV insulating mat of size 5mtr x 1 mtr x 2.5 mm thick specification as per IS-15652 2006
M&L in Earthing complete with galvanized steel earth plate electrode of size 60cmx60cmx6 mm thick, buried directly in ground (earth pit not less than 2.25 m below normal ground level) with top edge of earth plate not less than 1.5m below normal ground level, connected to galvanized strip 32mm by means of bolts, nuts, check nuts and washers of galvanised iron or steel as shown in electrical plate No 3 of SSR Part I,2009 connected to earth test point and the equipment on the other nuts and washers of galvanised iron side complete all as specified, including testing and commissioning complete all as directed. Note :- (a) The unit rates quoted against this item shall be deemed to include the cost of excavation and earth work in soft/loose soil, common salt & charcoal dust in alternate layers, PCC 1:3:6 type C2 as in pit, precast RCC 1:2:4 type B-1 with necessary reinforcement 6mm dia both ways as in cover & frame for pit, funnel, watering pipe 20 mm bore GI pipe light grade, protection pipe 40 mm bore GI pipe medium grade etc. (b) The quoted rates shall also deemed to include the cost of earth test point and earth strip/GI lead wire and protection pipe upto 7.5 meter beyond the earth plates electrode.
M&L Brick work with sub-class 'B' bricks, straight or curved on plan exc 6 m mean radius, built in cement mortar 1:6 complete as specified and directed.
M&L Rendering 15mm thick on fair faces of brick work or concrete surfaces in cement mortar (1:4) finished fair and even without using extra cement complete as specified and directed.
M & L for PCC 1:3:6 type C-2 (using 40 mm gradded aggregate) for foundation, filling and mass concrete etc complete all as specified and directed .
M & L for cement concrete type B-2, 1:2:4, 75 mm thick (using 40 mm gradded aggregate) for floors and paving etc complete all as specified and directed.
S&F Cross arms, bracings, supports, clamps and back plates fabricated from structural steel sections including nuts, bolts, washers,welding, bending cold or hot,drilling holes for bolts, in any shape or size as indicated or directed and inclusive of one primer coat, one under coat and one finishing coat of paint.
Dismantling of fencing wire mesh of any type and S&F 4 mm dia mild steel wire 75x75 mm mesh,made up into mattresses or cages ,lapped wired and liad in position including welding for fencing in grid complete all as specified and as directed.
M & L for 2 coatS of synthetic enamel painting over a coat of red oxide PRIMER to steel surfaces including preparation of newly surface complete all as specified.
Dismantling of HT insulators any type, any size complete all as specified..
Dismantling of air break gang operated switches vertical/horizontal mounted including insulators and operating mechanism.
Dismantling of cross-arms or M.S. channel or angle sections etc complete all as specified.
Dismantling of GI pipe 80mm/100 dia complete all as specified..
Dismantaling of existing 4 pole structure complete all as specified..
Supply, installing, testing and commissioning in replacement of factory made and tested (including CPRI type tested certified panel) LT Panel board ,cubical compartmentalized , out door type double door , mounted on angle iron legs 50x50x6mm thick, suitable for 415 volts, 3 phase, 4 wire, 50 HZ AC supply system accomodated with 01 No ACB 4 pole, 800 Amp, 50 KA, 415 Volt AC Horizontal draw out type motorized, front operated with Micro processor based LCD protection release for adjustable over current, short circuit and earth fault protection fitted with aluminium bus bar link 1200 Amps for incomming and outgoing cable connection. The panel shall be dust and vermin proof. IP-65 class protection and shell be made of 3.15 mm CRCA MS sheet, and 50x50x6mm thick MS angle iron frame work, powder coated finish over one coat of red oxide primer on outside surface and painted inside with two coats of red oxide primer, front and rear opening type, with apron for cable entry closing locking arrangement . including excavation, earth work and platform for the panel with PCC 1:4:8 type D-2 with 40 mm graded crushed stone, 15 cm thick in foundation, brick work in CM 1:6 with sub class 'B', old size bricks, rendering 15 mm thick in CM 1:6 on exposed surfaces and 100 mm thick PCC padding 1:3:6, type C-1 using 20 mm graded crushed sotne aggregate on top and grouting bolts etc for panel. The platform shall be such that it is of a height 45 cm above the nearest road level. (Location : New Pratap Chowk Sub Stn. )
Note : (i)contractor should provide 50 % of the material as listed above within 15 days of the placing of work order and shall be verified by the Eng-in-charge.
Buddham Builders
Water Power Engg. Enterprises
MV Engineers And Contractors
Rajindera Enterprises
mayur enterprises
Ridhi engineers and builders
DS CONSTRUCTION
stage.html
html • 0.07 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .