Chief Manager Electrical Planning and Contract Section
Revamping of Electrical works at IT Building of Aircraft Division HAL BC
FM/NE-P/Advt./12/26-27 Date: 23.09.2026::HAL/FMD/ER-3011/26-27
FM/NE-P/Advt./12/26-27 Date: 23.09.2026
Open Tender
Works
8 Months
Electrical Planning and Contract Section-E and M Dept-FMD-Bangalore
As per Tender Notice
₹0
₹2.8 L
24 Sept 2026
24 Sept 2026
27 Oct 2026
27 Oct 2026
20 Oct 2026
Name of the Individual / Firm / Company: * (Mandatory)
Type of ownership / Legal Status [Attach copies of the original document defining the legal status]
Year of Establishment of Company/Business
Registered Office Address, Telegraphic Address, Telephone No., Website / email id, FAX No.
Correspondance Address, Telegraphic Address, Telephone No., Website / email id, FAX No.
PAN no
PF number (If any)
ESI number
GST registration number
Particulars of registration with various other Government bodies (Attach documentary proof)
Contact details
Please enter Contact person name
Valid Electrical contractor license of appropriate voltage (Minimum 650V) issued by any state Govt. under clause 45 of Indian Electricity Rules 1956 or as amended from time to time
I.T Returns for past 03 years
Value of works executed during the following 05 years and it should be certified by Chartered Accountant. (In Rs. Lakhs)
Please enter values of works (sum of all the works in the respective year) in Rs. Lakhs for all the years
DETAIL OF WORK ON HAND UPTO COMPLETION PERIOD OF SUBJECT WORK (N=completion period=8months=8/12= 0.67 year) [For Bid capacity calculation] NOTE : PROVISION for 10 works are given. If more, a separate similar sheet to be made showing all the works with all details as per this FORMAT and same to Uploaded. However, 10 works details to be provided and balance work value of other works to be added and to be provided in 10th row as OTHER works. Apart from filling the details in the below table, this statement duly verified by Chartered Accountant shall also be uploaded.
Name of Organization with address
Action plan / bar chart as to indicate the completion of work, within the scheduled time (contract period)]
Bank(s) details: [Copy of the cheque leaf to be uploaded]
Bank Account No.
Name of the Bank
Type of Account
Branch, Place
Bank Code No.
MICR No.
ECS No.
IFS Code
Bank Statement for past THREE months
Latest Over draft Facilities with Bankers
Latest Bankers Solvency Certificate Details:
Please enter Latest Solvency Details and upload the same
Experience of having successfully completed similar works during last 7 years ending on the previous day of submission of tender should be either of the following:. [i. Work completion certificates along with LOA/PO/WO should be uploaded.ii. In case of experience certificate obtained from organizations other than government, TDS certificate of work also to be uploaded] (i) THREE similar completed works each costing not less than the amount equal to 40% of the estimated amount put to tender. (ii) TWO similar completed works each costing not less than the amount equal to 50% of the estimated amount put to tender. (iii) ONE similar completed work costing not less than the amount equal to 80% of the estimated amount put to tender.
Type of Work [ Incase of private works the same shall be supported with TDS certificate]
Type of Work [ Incase of private works the same shall be supported with TDS certificate]
Type of Work [ Incase of private works the same shall be supported with TDS certificate]
DETAILS OF TECHNICAL PERSONNEL AVAILABLE( if space provided is insufficient separate sheet to be uploaded with the same format as below)
Name of members or technical personnel available in the organization
PLANT, MACHINERY AND EQUIPMENT AVAILABLE [The Plant, Machinery and equipment (either owned or leased) that can be made available for this work must be furnished below].
Name of Machinery
Works of similar nature successfully completed in addition to Sl. No. (21) of Applicant Particulars (1) during the last 07 years ending on the previous day of submission of tender .
Name of the work / project and location
Details of person holding the power of Attorney
Please enter Person holding the power of attorney
Tender Document EMD details
DD No. & Issue Date
Please enter Tender Document EMD Details
Average annual financial turn over during the last 3 years, ending 31st March 2025 (In Lakhs). The values provided to be supported by uploading Balance Sheet along with Profit & loss account statement.
DECLARATION I
Please Accept the Declaration I
DECLARATION II
Please Accept the Declaration II
Subject tender has been called on item rate basis. Basic Rate to be quoted for each item.
Subject work is a Works contract and prevailing GST of 18% has been added in the BOQ on overall total. Any revision on this GST rate is to HAL account.
Sucessful offer that is L-1 (Lowest offer) will be determined including GST.
The payment terms shall be governed as per the terms indicated in General conditions of contract.
The work has to be carried out in co-ordination with engineer-in-charge with minimum power interruption. The shutdown work has to be carreid out during Holidays/Sundays with proper co-ordination of Engineer-in-charge. In case any preparation works requried, same have to be carried out as directed by Engineer-in-charge without any additional cost during execution of work.
Amount towards GST will be paid along with RAR payment against invoice.
The tenderers are requested to abide by the rules of prevailing GST act.
This BOQ specification has to be read in conjunction with technical specifications and tender drawings. Any ambiguty in these have to be brought to the knowledge of contract section before submission of tender to avoid future claims/dispute.
Shop Drawings: Indicative layouts of lighting, power, LAN, telephone and DLP trunking are provided along with the tender documents. The successful agency shall prepare detailed Lighting, Power, LAN, Telephone and DLP Trunking Layout drawings in AutoCAD/suitable format, incorporating actual site conditions and requirements, and submit the same to the Engineer-in-Charge (EIC) for approval before commencement of the work.After approval, the agency shall submit two (2) hard copies of the approved drawings in appropriate size and suitable scale for site/reference purposes. The agency shall incorporate all necessary modifications as directed by the EIC. No extra/additional payment shall be made for preparation, modification, printing and submission of the shop drawings.
Specification of item
Supplying, installation, Testing & commissioning of 36W LED Panel light 2x2 ft., Recessed/surface as per site requirement of Powder coated die cast /Extruded aluminum (Thickness > 1.20mm) body material and construction as per IS:10322 with driver as per the requirement with Driver efficiency>85%, Operating voltage AC 140-270 Volt, freq 50/60 Hz, operating temp range-5 deg to 40 deg centigrade, internal surge protection of 2.5kV with Short circuit & Open circuit protection, THD <10%, P.F.≥0.95, IP20, CRI>80, UGR(unified Glare Rating) < 19, Flicker free, (flicker should be below 5%), life time (LED, Driver & electrical circuitry), of minimum 50000 Burning hours with , 70% of initial Lumen maintained till life ends , CCT 3000°K / 4000°K / 5700°K / 6000°K / 6500°K (As per ANSI Bin), SDCM(Standard deviation color Matching)<3, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard and trade mark certificate (T.C). Manufactures word mark/name Engraved/ Embossing/ Screen printing on housing. Complete in all respect i/c connections with 1.5 sq mm FRLS, PVC insulated copper conductor single core cable and earthing etc. as required with minimum 5 year OEM warranty. System lumen Efficacy ≥120<135 lm/watt output. LM79 & LM80 Test report from NABL lab for all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement.(Thermal management : heat sink of aluminum housing such that LED junction temperature shall not rise above 90° C)
Supply, fixing directly to the ceiling/wall using suitable mounting arrangements testing & commissioning of surface mounting Decorative type 10W LED mirror light fitting, including driver, the driver shall have PF >0.9 and Colour temprature shall be ≥5700K, THD <20% operating on single phase 230V voltage 50 Hz AC supply with voltage range 140-270V including necessary interconnections complete in all respect and as directed by EIC. The lighting fixture shall be Havells:LUMILINENXTBS10WLED830SPCHW/Equivalent make in other approved makes.
Supplying, installation, Testing & commissioning of 18W LED Recessed/surface Down lighter (Round/square/ Rectangular) SMD type Powder coated die cast /Extruded aluminum body material with PMMA and prismatic diffuser and construction as per IS : 10322 with driver as per the requirement with driver efficiency >85%, Operating voltage AC 140-270volt, freq 50/60 Hz, operating temp range-5 deg to 40 deg centigrade internal surge protection of 2.5KV with Short & Open circuit protection, THD <10%, P.F≥0.95, IP20, CRI>80, UGR (Unified Glare Rating)<19, Flicker free (flicker should be below 5%), life time (LED, Driver & electrical circuitry), life time of minimum 50000 Burning Hours with, 70% of initial Lumen maintained till life ends, CCT 3000°K/4000°K/ 5700CK/6000°K/6500°K (As per ANSI Bin), SDCM(Standard deviation color Matching)<3, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard and trade mark certificate (T.C). Manufactures word mark/name Engraved/ Embossing/ Screen printing on housing. OEM must have its own in house NABL lab setup for all testing facilities for LED fixtures. Complete in all respect i/c connections with 1.5 sq mm FRLS, PVC insulated copper conductor single core cable and earthing etc. As required with Minimum 5 year OEM warranty. System lumen efficacy ≥120 <135 lm/watt output. LM79 & LM80 Test report from NABL Lab for all testing required for all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-In–Charge as per requirement.(Thermal management: heat sink of aluminum housing such that LED junction temperature shall not rise above 90° C)
Supplying, installation, Testing & commissioning of 12W LED Recessed/surface Down lighter (Round) SMD type, Powder coated die cast /Extruded aluminum body material with PMMA and prismatic diffuser and construction as per IS : 10322 with driver as per the requirement with Driver efficiency>85%, Operating voltage AC 140-270 Volt, frequency 50/60 hz, Operating temp range -5 deg to 40 deg centigrade, internal surge protection of 2.5KV with Short & Open circuit protection, THD< 10%, P.F≥0.95, IP20, CRI >80, UGR(Unified Glare Rating)>19, Flicker free(flicker should be below 5%), life time (LED, Driver & electrical circuitary), of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends,CCT 3000°K / 4000°K/ 5700°K /6000°K/6500°K(As per ANSI Bin), SDCM(Standard Deviation Color Matching)<3, Maximum power consumption should not more than the specified rating and Fixture shall be confirming to relevant BIS standards and trade mark certificate(T.C). Manufactures Word Mark/Name Engraved /Embossing/Screen printing on housing Complete in all respect i/c connections with 1.5 sq mm FRLS,PVC insulated copper conductor single core cable and earthing etc.as required with minimum 5 year OEM warranty. System lumen efficacy ≥105 and <120 lm/Watt output. LM79 & LM 80 Test report from NABL lab for all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminium housing/Die cast aluminium housing such that LED junction temperature shall not rise above 90°C)
Supplying, installation, Testing & commissioning of 20W LED surface mounted Batten light, Powder coated die cast /Extruded aluminium (Thickness > 1.20 mm) body material and construction as per IS:10322 with driver (Replaceable) as per the requirement with Driver efficiency > 85%, Operating voltage AC 140-270 Volt, freq 50/60hz, Operating temp range-5 deg to 40 deg centigrade, internal surge protection of 2.5 KV with Short & Open circuit protection, THD<10%, P.F≥0.95, IP20, CRI>80, Flicker free, (flicker should be below 5%), life time (LED, Driver & electrical circuitary), of minimum 50000 Burning Hours with, 70% of initial Lumen maintained till life ends, CCT 3000◦K/4000◦K/5700◦K/6000◦K/6500◦K (As per ANSI Bin), SDCM (Standard Deviation Color Matching) <3, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard and trade mark certificate (T.C). Manufacturers Word Mark/Name Engraved/Embossing/Screen printing on housing. Complete in all respect i/c connections with 1.5 Sqmm FRLS PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥105<120 lm/Watt output. LM79 & LM80 Test report from NABL lab for all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90° C).
Supplying, installation, Testing & commissioning of 40W LED surface mounted Batten light, Powder coated die cast /Extruded aluminium (Thickness > 1.20 mm) body material and construction as per IS:10322 with driver (Replaceable) as per the requirement with Driver efficiency > 85%, Operating voltage AC 140-270 Volt, freq 50/60hz, Operating temp range-5 deg to 40 deg centigrade, internal surge protection of 2.5 KV with Short & Open circuit protection, THD<10%, P.F≥0.95, IP20, CRI>80, Flicker free, (flicker should be below 5%), life time (LED, Driver & electrical circuitary), of minimum 50000 Burning Hours with, 70% of initial Lumen maintained till life ends, CCT 3000◦K/4000◦K/5700◦K/6000◦K/6500◦K (As per ANSI Bin), SDCM (Standard Deviation Color Matching) <3, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard and trade mark certificate (T.C). Manufacturers Word Mark/Name Engraved/Embossing/Screen printing on housing. Complete in all respect i/c connections with 1.5 Sqmm FRLS PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥105<120 lm/Watt output. LM79 & LM80 Test report from NABL lab for all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90° C).
Supply, fixing, testing & commissioning of the following factory built powder coated Double door MCB/MCCB DB of any approved make fabricated out of M.S. sheet steel enclosure & necessary cutouts for operating the MCB knobs & comprising of 200 amps tinned copper busbars & earthing bus with tapped holes including internal wiring with stranded copper PVC wires or suitable size copper strips etc. & fixing the DB in flush with wall/ on wall as per site requirement with necessary M.S. angle supports, chipping the wall and replastering to smooth finish etc., wherever required as per site condition, complete in all respects, as directed by Engineer-in-charge and comprising the following as detailed below:
6 way (4 + 18), Horizontal Double door MCB DB
4 way (4 + 12), Horizontal Double door MCB DB
12 way SPN Double door MCB DB
8 way (4 + 24), Vertical Double door MCCB DB
12 way (4 + 36), Vertical Double door MCCB DB
125 A, 415V 36KA, FP MCCB
40-63 amps. ratings, FP MCB, "C" curve, 10 KA breaking capacity.
40-63 amps. ratings, TP MCB, "C" curve, 10 KA breaking capacity.
32 amps. ratings, DP MCB, "C" curve, 10 KA breaking capacity.
6-32 amps. ratings, SP MCB, "C" curve, 10 KA breaking capacity.
Wiring for light point / fan point / exhaust fan point/call bell point from nearest switch box with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, fan regulator, modular plate, ceiling rose, suitable GI box and earthing the point with 1.5 sq. mm FRLS PVC insulated copper conductor single core cable etc. as required. (as per detailed CPWD specifications for Group C wiring)
Wiring to single light point controlled by 1 No 6A, 250V gr. flush type modular SP switch complete in all respects.
Wiring to two light point controlled by 1 No 6A, 250V gr. flush type modular SP switch complete in all respects.
Wiring to three light point controlled by 1 No 6A, 250V gr. flush modular type SP switch complete in all respects.
Wiring to Staircase light point controlled by 2 way 6A, 250V gr. flush type modular SP switch.
Wiring to fan point controlled by 1 No. 6A, 250V gr. flush type modular SP switch including providing 2 module type electronic five stepped speed regulator etc., complete in all respects.
Wiring to exhaust/wall mounting fan point using 6A, 250V gr. flush type modular SP switch housed along with other lighting switches/separate switch box if required and 3pin 6A, 250V gr. modular type socket housed near the exhaust/wall mounting fan complete in all respects.
Wiring for 6A power point with 2.5sq.mm FRLSH PVC insulated copper conductor multi strand, single core wire/cable in recessed/opened as per site requirement medium class 25mm dia PVC conduit, with 6A modular switch, 6A modular socket outlet, modular plate, suitable GI box and earthing the point with 3R x 2.5sq.mm, with all accessories complete as required.
Wiring for 2X6A power point with 2.5sq.mm FRLSH PVC insulated copper conductor multi strand, single core wire/cable in recessed/opened as per site requirement medium class 25mm dia PVC conduit, with 2X6A modular switch, 2X6A modular socket outlet, modular plate, suitable GI box and earthing the point with 3R x 2.5sq.mm, with all accessories complete as required.
Wiring for 6/16A power point with 4sq.mm FRLSH PVC insulated copper conductor multi strand, single core wire/cable in recessed/opened as per site requirement medium class 25mm dia PVC conduit, with 16A modular switch, 16A modular socket outlet, modular plate, suitable GI box and earthing the point with 3R x 4sq.mm, with all accessories complete as required.
Supplying and drawing following sizes of FRLS/HFFR PVC insulated copper conductor, single core cable in the existing surface/ recessed PVC conduit as required.
3 x 2.5 sq. mm copper wire (for ltg ckts from DB to switch box & for 6A sockets at race way & cubicle table)
3 x 4 sq. mm copper wire( for 16A sockets at race way & cubicle table)
Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required. (On cubicle table)
6A Switch
3 pin 6A Socket outlet
16A Switch
6 pin 15/16A Socket outlet
Supplying and fixing following size/ modules, GI box along with modular base & cover plate for modular switches in recess etc. as required. (On cubicle table)
2 Module
3 Module
6 Module
Supplying and fixing following Modular base & cover plate on existing modular metal/PVC boxes etc. as required. (On cubicle table)
2 Module
3 Module
6 Module
Telephone
Supply, Fixing, in the existing GI /PVC box as per site requirement, testing & Commissioning of 1 No. Twin RJ-11 telephone socket outlets with shutter with necessary interconnections complete as directed by Engineer-in-charge.(On wall/cubicle table)
Supply & drawing of 0.5 mm dia copper conductor PVC insulated 4 pair colour coded and twisted unarmoured telecommunication cables in the existing PVC conduit as per standard practice including necessary inter connections & end terminations.
Supply, laying in the already excavated cable trench/existing duct/fixing on wall/cable tray/ steel structure using suitable clamps etc./ encasing in pipe, testing and commissioning of 50 pair jelly filled armoured copper conductor of 0.5mm dia polyethylene insulated cover, twisted into pairs, colour coded, pairs laid up, fully filled with petroleum jelly as a moisture barrier, core wrapped with non-hygroscopic polyester tape to contain the jelly, covered with aluminium poly-laminates screen, polyethylene sheath extruded over aluminium screen, polyethylene tape over the above sheath, armoured with galvanised steel tape and outer polyethylene sheath underground telecommunication cable including both end terminations on the existing krone type junction box complete in all respects and as directed by EIC.
Supply & fixing on wall/grouted to floor upto 1200mm above ground level as per site requirement using suitable size MS angle iron frame work finished with two coats of enamel spray paint over a good primer & providing 50 pair krone type telephone connector junction box including krone connector with necessary mounting frame housed in suitable size FRP box with hinged lockable cover complete in all respects.
IT Works
Supply & fixing in flush with existing GI/PVC Modular box as per site requirement, testing & Commissioning of 1 Module RJ-45 socket in Module plate for One number of Data point with necessary interconnections complete as directed by Engineer-in-charge. (On cubicle table/wall)
Supplying, drawing, Testing and commissioning of Cat6A UTP 4 pair, 23 AWG solid copper cable in existing conduit/ on surface, U/FTP, LSZH, Non-Plenum, Horizontal (solid) Cable suitable for high speed data networking application supporting upto 10Gbps over a 100 meter channel. The 4 Unshielded Twisted Pairs (UTP) cable with color coded insulation for easy indentification should have FLAME PROPERTIES i.e. Flammability Test - IEC 60332-1, Smoke Density - IEC 61034, LSZH standards compliance: ANSI/TIA-568 C.2, ISO/IEC 11801, IEEE 802.3an, RoHS. Delay Skew should be < 45NS. The outer Cable Diameter should be 7.5 + 2 mm. Cable should have been tested and verified by UL/ ETL etc. complete as required.
Supplying and fixing of following size Wall Mount Rack having Fixed Structure with 0.8mm CRCA Sheet, completely knocked-down condition (CKD) Shape, Vertical Mounting Rail 1.6 mm with 'U'Marking, Minimum 2 cable entry/exit provision at Top and bottom with rubber protection, Front 5mm Toughened Glass with lock, wall mounting kit, Powder coated Color- RAL- 7035, complied with UL & RoHS, 2 x 6 sockets 16A power distribution units, 3 numbers closed cable organizer, Hardware mounting screws packet of 20 x 1 number, etc. complete as required.red.
6U Rack
9U Rack
Supplying, installation, Testing and commissioning of 24 port Layer 2 Non PoE indoor Network Switch having features and specifications etc. as mentioned here under: At least 24 X RJ-45 Gigabit Ethernet Ports and additional 2 X 10G Base -T with 4 X SFP Ports with non-blocking architecture by having Switching capacity of min. 168Gbps and packet forwarding rate of 125Mpps or higher, 16K MAC table. Console Port, USB port, Stacking support of min. 8 units per stack. Internal dual AC Power supply, STP, RSTP, MSTP, BPDU Filter, BPDU Restriction, Min. 9K Jumbo Frame, LBD, IGMP Snooping V1/V2/V3, MLD Snopping V1/V2. IGMP /MLD Groups 1K or more, IPv4/IPv6 Loopback Interface, 16 L3 IP Interface, Ipv6ND, VRRPv3, UDP Helper, ECMP. VLAN: 802.1Ǫ, Port based, Ǫ-in-Ǫ, Multicast VLAN, Protocol VLAN, VLAN Trunking, DHCP Snopping, Server, server Screening. RADIUS, TACACS+ Authentication, ǪoS: 802.1P, 8 queues per port, ǪoS : WRR, Strict+WRR, WRED, 802.1p. ACL: MAC based, IPv4C IPv6, TCP/UDP Port number, time based ACL, TFTP Client, SNMP V1, v2c, v3, SNMP traps, RMON, DHCP server, relay, client, LLDP, LLDP-MED, OAM, Dying Gasp, 802.3ah, sflow, RIP, OSPF v2/v3, policy based route, SSL, SSH. 6 kV surge protection on all Gigabit Ethernet ports and on all GE RJ-45 access ports. Certifications: UL, CE, FCC, RoHS, MTCTE, OEM/Product must be on Trusted Telecom Portal of Department of Telecommunication, Government of India etc. complete as required.
Supplying, installation, Testing and commissioning of 8 port Layer 2 Non PoE indoor Network Switch having features and specifications etc. as mentioned here under: Minimum 8 X RJ-45 Gigabit Ethernet Ports and ditional 2 X 1G SFP Ports with non-blocking architecture by having Switching capacity of minimum 20Gbps and packet forwarding rate of 14Mpps or higher, 8K MAC table. Internal dual AC Power supply with operating temperature of -5 0C to +50 0C. Jumbo frame: 10KB or higher, IGMP Snooping, IGMP snooping querier and support for IGMP Snooping Fast Leave, Should create 250 or more MLD groups, MLD Snooping, Per VLAN MLD Snooping C MLD nooping Fast Leave, STP, RSTP, MSTP, Loopback detection, Multicast filtering, VLAN Tagging, ǪOS: 8 Ǫue per port, WRR, IPv4/IPv6 Interface : minimum 100 IPv4 static route entries and minimum 50 IPv6 static route entries, 700 cess Control entries, SSH CSSL for IPv4 and IPv6, 802.1x,ARP Spoofing, DHCP Snooping and server screening, IP+MAC+Port Binding, Per Port Bandwidth Control, 802.1X Authentication (Supports local/RADIUS database, Port-based Access Control and EAP, OTP, TLS, TTLS, PEAP Support) Cable Diagnostic feature, LLDP, LLDP-MED, SNTP/NTP, RMON, SNMP v1,v2c, v3 and SNMP Traps. Certifications: UL, CE, FCC, RoHS, MTCTE, OEM/Product must be on Trusted Telecom Portal of Department of Telecommunication, Government of India etc. complete as required.
Supplying Installation Testing and Commissioning of 24 port Cat6 Patch Panel loaded. Must be of 1U height with clear label holders and white label with the panel. 24 Ports Cat-6 Patch Panel should have ETL/UL verification rogram certificate for compliance with ANSI/TIA-568.2-D etc. complete as required
Supplying, Installation, Testing and commissioning of Copper Patch Cords of 1m length CAT6 Patch Cord should have ETL/UL verification program certificate for compliance with ANSI/TIA-568.2-D etc. complete as required.
Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required.
20MM PVC Conduit
25MM PVC Conduit
Supply & laying in the already excavated cable trench/cable tray/fixing on wall/duct wall with necessary M.S clamps / encasing in pipes etc., testing & commissioning of following size XLPE insulated Aluminium (Al) /Copper (cu) conductor 1.1 KV grade confirming to IS: 7098 ( part-I)/1998 with upto date amendment earthed Armoured (Arm)/Copper un armoured U.G cables and as per technical specification including stacking at site, proper storage complete etc. as required. (Note:- Excavation, sand & Brick Protection, concrete cutting, reconcreting, casing pipes will be measured separately.)
3.5CX 400 Sqmm Aluminium armoured conductor
3.5CX 300 Sqmm Aluminium armoured conductor
3.5CX 185 Sqmm Aluminium armoured conductor
3.5CX 95 Sqmm Aluminium armoured conductor
3.5CX 70 Sqmm Aluminium armoured conductor
3.5CX 50 Sqmm Aluminium armoured conductor
3.5CX35 Sqmm Aluminium armoured conductor
3.5CX 25 Sqmm Aluminium armoured conductor
4CX16 Sqmm Aluminium armoured conductor
4CX 10 Sqmm Aluminium armoured conductor
4CX 6 Sqmm Aluminium armoured conductor
4C X 10 Sqmm Copper un armoured conductor LT Cable
4C X 16 Sqmm Copper un armoured conductor LT Cable
Supplying and making end termination with brass compression gland and aluminium/Copper lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium/copper conductor cable of 1.1 KV grade as required
3.5C X 400 sq. mm Aluminium armoured cable
3.5C X 300 sq. mm Aluminium armoured cable
3.5C X 185 sq. mm Aluminium armoured cable
3.5C X 95 sq. mm Aluminium armoured cable
3.5C X 70 sq. mm Aluminium armoured cable
3.5C X 50 sq. mm Aluminium armoured cable
3.5C X 35 sq. mm Aluminium armoured cable
3.5 X 25 sq. mm Aluminium armoured cable
4C X 16 sq. mm Aluminium/Copper armoured/un armoured cable
4C X 10 sq. mm Aluminium/Copper armoured/un armoured cable
4C X 6 Sqmm Aluminium armoured cable
Supplying and making straight through joint with heatshrinkable kit including ferrules and other jointing materials for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.
3.5C X 400 sq. mm Aluminium armoured cable
3.5C X 300 sq. mm Aluminium armoured cable
3.5C X 185 sq. mm Aluminium armoured cable
3.5C X 95 sq. mm Aluminium armoured cable
3.5C X 70 sq. mm Aluminium armoured cable
3.5C X 50 sq. mm Aluminium armoured cable
3.5C X 35 sq. mm Aluminium armoured cable
3.5 X 25 sq. mm Aluminium armoured cable
4C X 16 sq. mm Aluminium armoured cable
Removing & re-routing of existing LT cables
MV Cable Laying ( up to 35 Sqmm)
MV Cable Laying ( above 35 sq. mm and upto 95 sq. mm)
MV Laying Above (95 Sq.mm and upto 185 Sq.mm)
Supply & fixing of PVC DLP Cable trunking with cover
Supply and fixing on wall/ partition wall using necessary mounting arrangements for 105/100x50mm size DLP-PVC adaptable trunking system with separation partition for laying power and Data/Telephone cables/wires with full top cover, necessary accessoires such as end caps, flat angle, T joints, external/internal angle, flat junction, Body joint, cover joint, required cabling accessories etc., complete in all respects as directed by Engineer-in-charge.
Supply and fixing on wall/ partition wall using necessary mounting arrangements for 80x50mm size DLP-PVC trunking system including cover for laying power and Data/Telephone cables/wires with full top cover, necessary accessories such as end caps, flat angle, T joints, external/internal angle, flat junction, Body joint, cover joint, required cabling accessories etc., complete in all respects as directed by Engineer-in-charge.
Supply & fixing in flush with the above DLP-PVC adaptable trunking/Modular table, testing & Commissioning 2Nos of 6A, 250V grade, 5pin flush type modular socket outlets & 2Nos 6A, 250V grade flush type modular switch for control with necessary inter connections, including supply of suitable size modular type clip on support with suitable finish plates etc., complete in all respects and complete in all respects as directed by Engineer-in-charge.
Supply & fixing in flush with the above DLP-PVC adaptable trunking/Modular table, testing & Commissioning 1No of 6A, 250V grade, 5pin flush type modular socket outlets & 1No 6A, 250V grade flush type modular switch for control with necessary inter connections, including supply of suitable size modular type clip on support with suitable finish plates etc., complete in all respects and complete in all respects as directed by Engineer-in-charge.
Supply & fixing in flush with the above DLP-PVC adaptable trunking, testing & Commissioning 1No of 16A, 250V grade, Universal flush type modular socket outlet & 1No 16A, 250V grade flush type modular switch with neon indicator for control with necessary inter connections, including supply of suitable size modular type clip on support with suitable finish plates etc., complete in all respects as directed by Engineer-in-charge.
Supply, fixing in flush with the above DLP-PVC adaptable trunking/Modular table, testing & Commissioning of 1 no 1 Module RJ-45 socket in Module plate for One number of Data point including supply of suitable size modular type clip on support with finish plates etc., with necessary interconnections / crimping complete and as directed by Engineer-in-charge.
Supply, fixing in flush with the above DLP-PVC adaptable trunking/Modular table, testing & Commissioning of Modular type Twin RJ-11 telephone socket outlets for Two numbers of Telephone point including supply of suitable size modular type clip on support with finish plates etc., with necessary interconnections/crimping complete and as directed by Engineer-in-charge.
Supply & drawing/laying of 2C X 6 Sqmm PVC insulated 1100V gr. flexible multi stranded Copper cable with ISI mark for DB's earting using suitable copper lugs including necessary interconnections, clamps & hardwares complete as directed by Engineer -in-charge.
Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray (Galvanisation thickness not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with two numbers GI Suspenders i/c base of suitable size GI angle, GI bolts & nuts, fastner etc as required.
150 mm width X 50 mm depth X 1.6 mm thickness
225 mm width X 50 mm depth X 1.6 mm thickness
Design, Fabrication, Supply and fixing/grouting/welding on wall/ceiling/ truss of suitable size MS angle iron supports/ flat/ brackets for cable tray supports, as per site requirement and painting the same with two coats of synthetic enamel paint over a coat of zinc chromite primer complete in all respects and as directed by EIC/OIC.
Design, fabrication, Supply, erection, testing & commissioning of following Indoor Type LT Panel (PTTA)
Supply, Installation, Testing & commiissioning of LT Panel-1.(PTTA) at Aircraft Division
Incoming
1No - 400A 415V gr. 4P 36KA MCCB.
Lot-600A, 3Phase and 300A neutral 415V, short circuit rated 36KA for 1sec, TPN Aluminium bus bars with busbar insulators, heat shrinkable PVC sleeves etc.
1Nos- Multi function meter (MFM/MDM) suitable for 3ph, 4 wire, 240V(L-N), 5A, CL-1, RS 485 Port Digital MFM/MDM of EM6400NG of Schneider or any equivalent make meeting technical specification of above MFM complete in all respect.
1Set-400/5A current transformers of suitable class and VA burden for metering.
1Set - RYB indicating lamps of LED module with 6A, 230V,10KA, SP MCB.
1Set- 6A, 230V, 10KA SP MCB for the protection of measuring instruments.
Outgoing
6Nos - 125A 415V gr. 4P 25KA MCCB
20Nos - 63A 415V gr. 4P 10KA MCB
Supply, erection, testing & commissioning of Indoor Type Change Over Panel LT Panel (PTTA) at Aircraft Division
Incoming
1No - 630A 415V gr. 4P 50KA MCCB.
1No - 630A 415V gr. 4P Change Over switch (COS).
Lot-800A, 3Phase and 400A neutral 415V, short circuit rated 50KA for 1sec, TPN Aluminium bus bars with busbar insulators, heat shrinkable PVC sleeves etc.
1Set-630/5A current transformers of suitable class and VA burden for metering.
1Set - RYB indicating lamps of LED module with 6A, 230V,10KA, SP MCB.
1Set- 6A, 230V, 10KA SP MCB for the protection of measuring instruments.
1Nos- Multi function meter (MFM/MDM) suitable for 3ph, 4 wire, 240V(L-N), 5A, CL-1, RS 485 Port Digital MFM/MDM of EM6400NG of Schneider or any equivalent make meeting technical specification of above MFM complete in all respect.
2 Nos- Source-1 On /Source-2 On LED indicating Lamps
Outgoing
4Nos - 250A 415V gr. 4P 36KA MCCB
Supply, installation, testing & commissioning of Movement detector with coverage area of 3m dia. & detecting angle adjustable with standard mounting height of 2.5-4mtr.- (Make & Model No.Philips SES LCM 1061 Occ PIR WH/ Equivalent) all complete in all respects and as directed by Engineer-in-charge.(for Toilet area lighting control)
Earthing
Supply, providing and Fixing Cast Iron Pipe earth station confirming to IS 3043 complete with 2750mm long, 100 mm Inner Dia(ID),13mm thickness CI Pipe, with 2 part clamp made out of G I flat 50 x 6 mm continously welded around the pipe using cast iron welding electrodes as per drawing. The cost also incudes excavation for earth pit, providing & laying homogenous mixture of charcoal lumps, salt & sand all around the pipe as per specification, supplying and fixing of RCC Collar of size 450 mm dia, 450 mm height and 50 mm thick over Cement concrete base of minimum size 150mm width & 100mm thick all around below collar shall be provided using 1:2:6 CC after necessary excavation, refilling of soil, consolidating, ramming, leveling of soil etc., supplying & fixing the label board(MS Plate of size 300mmx200mmX2mm) welding to the elctrode complete as per specification, std drawing, instructions of EIC.
Supplying & laying 25 mm X 5 mm GI strip at 0.50 metre below ground as strip earth electrode, including connection/ terminating with G.I nut, bolt, spring, washer etc. as required. (Jointing shall be done by overlapping and with 2 sets of GI nut bolt & spring washer spaced at 50mm)
Dismantling & Removal of following items:
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
detail.html
html • 0.05 MB
TenderNoticeER3011.pdf
pdf • 0.45 MB
TechnicalBidER3011.pdf
pdf • 4.82 MB
TenderdrawingNo1to8ER3011.pdf
pdf • 11.32 MB
TenderdrawingNo9to13ER3011.pdf
pdf • 6.00 MB
PQFreeviewER3011.pdf
pdf • 0.21 MB
PBFreeviewER3011.pdf
pdf • 0.37 MB
ECSFormatER3011.pdf
pdf • 0.20 MB
UndertakingLetterER3011.pdf
pdf • 0.28 MB
ChecklistER3011.pdf
pdf • 0.11 MB
PQER3011.xlsm
xlsm • 0.03 MB
PriceBidER3011.xlsm
xlsm • 0.05 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .