Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | 1₹17.5 LAccepted-AOC K B ROAD WARD NO 11 NORTH LAKHIMPUR PIN 787001 ASSAM | LAKHIMPUR | ASSAM | 787001 | 1 | Accepted-AOC The lowest bidder. | |
| 2 | 2₹18.0 L+₹47,315 (2.70%)Rejected-Finance B 22 HQ ADG NEI GUWAHATI BABULAR BAZAAR TINSUKIA 786125 ASSAM | TINSUKIA | ASSAM | 786125 | 2 | Rejected-Finance Not the lowest bidder. | |
| 3 | 3₹18.0 L+₹48,575 (2.77%)Rejected-Finance BORBHETA JAIL ROAD NEW CHRISTIAN PATTY JAIL ROAD JORHAT ASSAM 785001 | JORHAT | ASSAM | 785001 | 3 | Rejected-Finance Not the lowest bidder. | |
| 4 | 4₹18.3 L+₹79,565 (4.54%)Rejected-Finance 16 BAITHAKKHANA ROAD 16 BAITHAKKHANA ROAD SEALDAH BAITHAKKHANA ROAD SEALDAH BAITHAKKHANA ROAD SEALDAH KOLKATA | 4 | Rejected-Finance Not the lowest bidder. |
Tender Value
₹21 L
EMD Value
₹42,000
Closing Date
21 Mar 2020, 6:00 pmClosed
Commander Works Engineer Dinjan
Headquarters Commander Works Engineer Dinjan Military Engineer Services Post - Panitola, Dist - Dibrugarh Pin Code - 786 183 (Assam)
SPECIAL REPAIR/ REPLACEMENT OF STANDBY DG SET AGAINST BER AT OUT POCKETS OF DINJAN MIL STN UNDER GE DINJAN
2020_MES_327591_1
83002/e8
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
Dinjan
As per tender documents
7 documents required · 7 mandatory
₹500
GE Dinjan
₹42,000
Yes
22 Apr 2020
22 Feb 2020
23 Mar 2020
22 Feb 2020
21 Mar 2020
9 Mar 2020
22 Feb 2020 - 14 Mar 2020
Amount
Supplying, installing, testing and commissioning diesel engine driven generating set 35 kVA /28 kW (prime power), 415 volt, 50 Hz, 3 phase, 4 wire, at 1500 rpm, 0.8 lagging power factor including diesel engine, alternator, coupling, common base plate, acoustic enclosure, 12 V DC battery, AMF Panel. Exhaust system, foundation etc. complete all as specified and as directed.
Supplying, installing, testing and commissioning diesel engine driven generating set 25 kVA /20 kW (prime power), 415 volt, 50 Hz, 3 phase, 4 wire, at 1500 rpm, 0.8 lagging power factor including diesel engine, alternator, coupling, common base plate, acoustic enclosure, 12 V DC battery, AMF Panel. Exhaust system, foundation etc. complete all as specified and as directed.
Supplying, installing, testing and commissioning diesel engine driven generating set 15 kVA /12 kW (prime power), 415 volt, 50 Hz, 3 phase, 4 wire, at 1500 rpm, 0.8 lagging power factor including diesel engine, alternator, coupling, common base plate, acoustic enclosure, 12 V DC battery, AMF Panel. Exhaust system, foundation etc. complete all as specified and as directed.
Excavating in trenches not exceeding 1.5 m wide and not exceeding 1.5 m in depth; for foundation, etc. or for shafts, wells, cesspits, manholes, pier holes, etc. or for cable laying or not exceeding 10 sqm on plan and not exceeding 1.5 m in depth and getting out in soft/ loose soil complete all as specified and as directed.
M & L for laying of bricks locally available sub class 'B' bricks (old size) for cable protection cover laid flat and dry in trenches over the cable perpendicular to the direction of cable all as directed.
Supply & spreading in trenches dry river sand cushioning to underground cable in trenches including spreading, levelling hand punning down complete all as specified and directed Note:- Depth of sand cushioning will be measured after punning down and levelling the sand properly.
Returning, filling in, including spreading, levelling, watering and well ramming in layers not exceeding 25 cm in soft/ loose/ hard/ dense soil complete all as specified and as directed.
Removing excavated material (soils) not exceeding 50 m and depositing where directed at a level n exc. 1.5 m above the starting point
Supply, laying, jointing, testing and commissioning cross-linked polyethylene (XLPE) insulated cable for working voltages of 1100 V, PVC sheathed, armoured, 3 core with reduced neutral conductors (3½ core), nominal cross sectional area of main conductor 70 sqmm, stranded aluminium conductor, ISI marked as per IS 7098(Part-I): 1988 including cable glands, lugs etc. to suit the cable size and to be laid in trenches, fixed along pole, under floors, through GI pipe laid under floors/roads, through concealed GI pipe along wall etc. complete all as specified and as directed.
Supply, laying, jointing, testing and commissioning cross-linked polyethylene (XLPE) insulated cable for working voltages of 1100 V, PVC sheathed, armoured, 3 core with reduced neutral conductors (3½ core), nominal cross sectional area of main conductor 50 sqmm, stranded aluminium conductor, ISI marked as per IS 7098(Part-I): 1988 including cable glands, lugs etc. to suit the cable size and to be laid in trenches, fixed along pole, under floors, through GI pipe laid under floors/roads, through concealed GI pipe along wall etc. complete all as specified and as directed.
M & L for earthing complete with galvanised steel plate earth electrode 600 mm X 600 mm X 6 mm thick, buried directly in ground (earth pit not less than 2.25 metres deep below ground level) with top edge of the plate not less than 1.5 metres below normal ground level, connected to earthing lead of 32 mm X 6 mm galvanised mild steel strip by means of bolts, nuts, check nuts and washers of galvanised iron from earth plate to test point upto 7.5 metre including all as shown in electrical plate No. 3 of SSR Part I (2009) including necessary concrete chamber in cement concrete M15 (Nominal Mix) using 20 mm nominal size coarse aggregate, precast RCC cover slab in cement concrete M15 (Nominal mix) using 20 mm nominal size coarse aggregate of size 40 cm X 40 cm X 5 cm reinforced with 8 mm dia TMT bars @ 150 mm c/c with one handle for lifting made out of 8 mm dia bar, GI funnel, GI wire mesh filter, 20 mm dia GI pipe medium grade for watering, 40 mm dia GI pipe medium grade for protection of earthing lead, charcoal or coke and salt in alternate layers including necessary excavation and earth work in any type of soil/ strata and testing complete all as specified and as directed by the Engineer-in-charge.
S & F earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc. as required 32 mm X 6 mm galvanised mild steel strip complete all as specified and as directed.
Garg Brothers
ANIL RAI AND COMPANY
M/s HALDER ENTERPRISE
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .