| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹2.5 LAccepted-AOC A 111 JHILMIL COLONY EAST DELHI 110095 | SHAHDARA | DELHI | 110095 | L1 | Accepted-AOC work order has been awarded | |
| 2 | L2₹2.5 L+₹333.80 (0.13%)Rejected-Finance | L2 | Rejected-Finance Not L1 | |
| 3 | L3₹2.9 L+₹35,207.74 (13.9%)Rejected-Finance N A | L3 | Rejected-Finance Not L1 |
Tender Value
₹3.1 L
EMD Value
₹6,150
Closing Date
30 Jan 2023, 1:00 pmClosed
EEE-I Shah(S)
Office of the Executive Engineer (Elect)-I Room No.5 First Floor Vishwakarma Nagar Near Hanuman Mandir Jhilmil Colony Delhi-110095
P/O Electrical Installation and Fans at 02 nos. Fixed Compactor Transfer Station under Shahdara (South) Zone.
2023_EDMC_142184_1
EE (Elect)-I//2022-23/12.3
Open Tender
Electrical Works
Item Rate
60 days
work
Please refer to tender documents
4 documents required · 4 mandatory
₹500
₹6,150
23 Oct 2024
19 Jan 2023
31 Jan 2023
19 Jan 2023
30 Jan 2023
19 Jan 2023
Amount
Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required. Group C
Wiring for light/ power plug with 2X4 sq. mm FRLS PVC insulated copper conductor single core cable in surface/recessed medium class PVC conduit alongwith 1 No. 4 sq. mm FRLS PVC insulated copper conductor single core cable for loopearthing as required
Wiring for circuit / submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface / recessed medium class PVC conduit as required. 2x2.5 sq.mm + 1x2.5 sq.mm earth wire
2 X 6 sq. mm + 1 X 6 sq. mm earth wire
Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.5/6 amps switch
3 pin 5/6 A socket outlet
Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 5/6 & 15/16 A modular socket outlet and 15/16 A modular switch, connections etc. as required.
Supplying and fixing extra down rod of 20 cm length G.I. Pipe, 15 mm dia, heavy gauge including painting etc. as required. (Note : More than 5 cm length shall be rounded to the nearest 10 cm and 5 cm or less shall be ignored.)
Installation of exhaust fan in the existing opening, including making good the damage, connection, testing, commissioning etc. as required. Upto 450 mm sweep
Supplying and fixing following way, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 volts, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) 4 way (4 + 12), Double door
Supplying and fixing following rating, four pole, 415 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required. 63 amps
Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. Single pole
Supplying and fixing following rating, four pole, (three phase and neutral), 415 V, residual current circuit breaker (RCCB), having a sensitivity current 30 mA in the existing MCB DB complete with connections, testing and commissioning etc. as required.(a) 63 Amp.
Supplying and fixing 30 A, 415 V, TPN Industrial type socket outlet, with 4 pole and earth, metal enclosed plug top alongwith 30 A "C" curve, TPMCB, in sheet steel enclosure, on surface or in recess, with chained metal cover for the socket out let and complete with connections, testing and commissioning etc. as required. (5 pin)
Supply of following sizes of XLPE insulated PVC Sheathed Al conductor armoured cables 1.1 KV grade on surface etc. as reqd. as per IS7098 (Part-I) /1998 as required: 4x16sq.mm
Supply, Installation, Testing and Commissioning of 1200 mm sweep, BEE 5 star rated, ceiling fan with Brush Less Direct Current (BLDC) Motor, class of insulation: B, 3 nos. blades, 30 cm long down rod, 2 nos. canopies, shackle kit, safety rope, copper winding, Power Factor not less than 0.9, Service Value (CMM/W) minimum 6.85, Air delivery minimum 215 CMM, 350 RPM (tolerance as per IS : 374- 2019), THD less than 10%, remote or electronic regulator unit for speed control and all remaining accessories including safety pin, nut bolts, washers, temperature rise=75 degree C (max.), insulation resistance more than 2 mega ohm, suitable for 230 V, 50 Hz, single phase AC Supply, earthing etc. complete as required.
Supply of 18 inch(450mm) exhaust fan heavy duty complete with shutters, blades etc as reqd. 1400 RPM.
Earthing with G.I. earth pipe 4.5 metre long, 40 mm dia including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc. (but without charcoal/ coke and salt ) as required.
Providing and laying earth connection from earth electrode with 6 SWG dia G.I. Wire in 15 mm dia G.I. pipe from earth electrode including connection with G.I. thimble excavation and re-filling as required.
Providing and fixing 6 SWG dia G.I. wire on surface or in recess for loop earthing as required.
SITC of surface mounting LED luminaire suitable for 1X20 watt LED rating complete with extruded aluminium batten prewired with high efficient LEDs with the following: a) Total System Wattage 20 ±5% Watt b) Luminaries effucacy ≥ 100 lumens/watt c) Power factor ≥ 0.95
SITC of 60W LED Flood Light luminiare fitted with lense, made of pressure die cast aluminium housing & toughned glass cover complete with the following specification as reqd.. (b) Total system wattage =60 watt +/- 5% c) Luminaire Efficacy>=100 Lm/w d) Power Factor>=0.95s f) Protection IP-66
S& F of compartment cubical type panel board duly powder coated made out of16 SWG MS Sheet with insulated aluminium bus bar i/c interconncetion copper wiring arrangment for mounting for switch gears, change over swichtes, MCCB i/c making the foundation brick work/ angle iron frame on floor/wall with proper locking arrangement etc. complete as required at site. Depth 30 to 60 cm
Providing and fixing following rating and breaking capacity and pole MCCB with thermomagnetic release and terminal spreaders in existing cubicle panel board including drilling holes in cubicle panel, making connections, etc. as required 150 A, 16kA, TPMCCB
100A 16KA TPMCCB
Providing and fixing M.V. danger notice plate of 200 mm X 150 mm, made of mild steel, at least 2 mm thick, and vitreous enameled white on both sides, and with inscription in single red colour on front side as required.
Laying and fixing of one number PVC insulated and PVC sheathed/ XLPE power cable of 1.1 KV grade of following size on wall surface as required Upto 35 sq. mm (clamped with 1mm thick saddle)
Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing masonry open duct as required. Upto 35sqmm
M/s Priyanshi Electricals
CANTILEVER ENGINEERS
stage.html
html • 0.04 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .