Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹5.8 CrAccepted-Finance 545 G T ROAD HOWRAH WEST BENGAL 711101 | HOWRAH | HOWRAH | WEST BENGAL | 711101 | ₹5.8 Cr | L1 | Accepted-Finance L1 |
| 2 | L2₹6.0 Cr+₹24.0 L (4.17%)Rejected-Finance 159 KAILASH GHOSHI ROAD KOLKATA WEST BENGAL 700008 | KOLKATA | KOLKATA | WEST BENGAL | 700008 | ₹6.0 Cr+₹24.0 L (4.17%) | L2 | Rejected-Finance HIGH BID VALUE |
| 3 | L3₹6.3 Cr+₹54.0 L (9.38%)Rejected-Finance | ₹6.3 Cr+₹54.0 L (9.38%) | L3 | Rejected-Finance HIGH BID VALUE |
Tender Value
Refer Docs
EMD Value
₹10.9 L
Closing Date
29 Nov 2019, 5:00 pmClosed
EXECUTIVE ENGINEER, HMC
4, Mahatma Gandhi Road. Howrah-711 101
Design, Supply, Erection, Commissioning and 3 months trial run of Pumps, Motors etc. of total capacity 3000 cu-mtr/hr and Electrical sub-station, switch gears etc for 3.6 M.G. U.G.R. cum Boosting Pumping station located at Olabibitala, H.I.T. Park,
2019_MAD_250430_1
05-TN/EE/PandD/19-20
Open Tender
CIVIL AND ELECTRICAL WORKS
Item Rate
365 days
WITHIN HMC AREA
Ward No. 25, of Howrah Municipal Corporation.
5 documents required · 5 mandatory
₹5,500
MUNICIPAL AFFAIRS DEPARTMENT// URBAN LOCAL BODIES
₹10.9 L
Yes
OFFICE OF THE EXECUTIVE ENGINEER, HMC
7 Jan 2020
26 Oct 2019
2 Dec 2019
26 Oct 2019
29 Nov 2019
26 Nov 2019
19 Nov 2019
Amount
PART A1, Supply, Delivery and Storage at Site (Design, Supply, Erection, Commissioning of Pumps, Motors etc. of total capacity 3000 cu-mtr/hr)
Supply, delivery, at site and storage of vertical turbine pumps with column assembly, discharge head, sole plate, motor stool, stainer, cassion pipes and all other accessories all complete, of capacity 1500 m3/hr. as per specification. Maximum allowable speed of pump will be 1000 R.P.M.
Supply, delivery, at site and storage of pipes, specials, joints, flanges, & common manifold, for 500 mm delivery line & 750 mm common manifold with extended pipe line as per Specification.
Supply, delivery at site and storage of valves Complete with fixture as per specification & as follows.
Butterfly valve 500 mm dia for delivery side of pumps fitted with electrical actuator suitable for local and control desk operation and display system for the individual pump delivery pipe lines.
Non Return Valve 500 mm dia for the individual pump delivery pipe lines
c. Butterfly valve 750 mm dia. fitted with electrical actuator suitable for local and control desk operation and display system for the individual pump delivery pipe lines after common manifold.
Supply, delivery at site and storage of M.S. Dismantling joint assembly 750 mm dia for common delivery line as per specification.
Supply, delivery at site and storage of M.S. Dismantling joint assembly 500 mm dia for delivery side of pump as per specification.
Supply delivery at site and storage of M.S. Puddle collar for common delivery line as per specification.
Supply, delivery at site and storage of Flow Meter, Recorder, Totaliser as per specification.
Supply, delivery at site and storage of pressure gauges complete with fittings and fixture as per specification & as follows.
Pressure gauge (0-5kg/cm2) delivery side
Pressure gauge for deliver side and common manifold (0-5kg/cm2)
Supply, delivery at site and storage of pressure transmitter complete with fitting and fixture as per specification & as follows.
Pressure transmitter for pump delivery side (0-5kg/cm2)
Pressure transmitter for delivery (0-5kg/cm2) at common manifold
Supply, delivery at site and storage of Vertical Squirrel cage induction motor rated at 415V ±10%, 50Hz ±5%, 3Ph, 1000 R.P.M.(syn) of adequate capacity to match the pump in sl. no. 1 complete with coupling hub and all other accessories and spares as mentioned in the technical specification. (Rating shall not be less than 200K.W. + at least 15% margin)
Supply, delivery at site and storage of multi panel M.V switch board of 1000A suitable for operation at 415Volt, ±10%, 3phase, 50Hz ±5%, AC system as per specification.
Supply, delivery at site and storage of Remote control Desk and instrument panel for motor control system as per specification.
Supply, delivery at site and storage of pure sine wave, 1450VA inverter with 180AH battery backup as per Specification.
Supply, delivery at site and storage of Double throat air valve at common delivery manifold as per Specification.
Supply, Delivery at site and storage of M.V Cable as per specification & as follows. i) M.V. Cable
a) From MV Switch Board to respective Motor Terminal, 1.1KV, grade, 3C, 2 X 185 sq mm. Al conductor, XLPE insulated armoured cable.
b) From MV Switch Board to Ventilation System 1.1KV, 4C, 6 sq.mm. Multi Strand Cu conductor, XLPE insulated.
c) From MV Switch Board to Valve Actuators 1.1KV, 4C, 2.5 sq.mm. Multi Strand Cu conductor, XLPE insulated.
d) From MV Switch Board to Inverter , 1.1KV, 4C, 2.5 sq.mm. Multi Strand Cu conductor, XLPE insulated.
e) From MV Switch Board to Flow Sensor 1.1KV, 4C, 2.5 sq.mm. Multi Strand Cu conductor, XLPE insulated.
f) From MV Switch Board to Space Heater 1.1KV, 4C, 2.5 sq.mm. Multi Strand Cu conductor, XLPE insulated.
g) From MV Switch Board to E.O.T. Crane 1.1KV, 4C, 6 sq.mm. Multi Strand Cu conductor, XLPE insulated.
h) From MV Switch Board to Control Desk, 1.1KV, 4C, 2.5 sq.mm. Multi Strand Cu conductor, XLPE insulated.
i) From MV Switch Board to LDB, 1.1KV, 4C, 2.5s sq.mm. Multi Strand Cu conductor, XLPE insulated.
iii) Control Cable Control cable of copper conductors of various sizes & grade and of suitable length as per specification for all remote control circuit and interlocking circuits.
Supply, delivery at site and storage of Jointing Materials as per specification & as follows :
a) All H.T. Cables jointing materials (dry type).
b) All M.V. Cables jointing materials (dry type)
c)All control & signal Cables jointing materials
N.B. – No extra payment would be made if the type, variety, length and dia. of the different sizes of cable varies on the higher side to meet up the requirement of the specification and site condition. Rates must be quoted carefully. This is also applicable for all type of cable joints.
Supply & delivery at site and storage of Earthing equipment as per current I.E. Rule & specification.
Supply & delivery at site & storage of fire extinguishers as follows :
Dry Powder (5Kg. each)
CO2 (4.5Kg. each)
A-B-C Type (5Kg. each)
Supply & delivery at site and storage of ring ventilation system of pump house with 12 air changes per hour all complete as per specification.
Supply & delivery at site and storage of air conditioners for control room cum office all complete as per specification.
Supply of Misc. item such as rubber mats, Shock Treatment chart etc. and storage as per specification.
Supply & delivery at site and storage of M.S. Structural Works for cable tray/ rack, panel installation supports, Pipe & valve supports, fabricated stairs & all other fabrication works.
Supply and delivery at site and storage of all luminaries, fittings, fixtures complete with necessary cables for inside and outside lighting of pump house as per specification.
Supply and delivery at site and storage of E.O.T. Crane along with it’s structural members & accessories for 7 M.T. main hoist and 1 M.T. auxiliary hoist, all complete with gear box, brakes, as per I.S. and technical specification. (Calculation Should be soon)
Supply and delivery at site and storage of illuminaries, light fittings and allied accessories for area illumination.
Supply and delivery at site and storage of spare parts as per specification
PART A2 (Installation)
Installation at site of the vertical turbine pumps with column assembly, discharge head, sole plate, motor stool, stainer,cassion pipes and all other accessories all complete, of capacity 1500 m3/hr. as per specification. Maximum allowable speed of pump will be 1000 R.P.M.
Installation at site of the pipes, specials, joints, flanges, & common manifold, for 500 mm delivery line & 750 mm common manifold with extended pipe line as per Specification.
Installation at site of the valves Complete with fixture as per specification & as follows.
a. Butterfly valve 500 mm dia for delivery side of pumps fitted with electrical actuator suitable for local and control desk operation and display system for the individual pump delivery pipe lines.
b. Non Return Valve 500 mm dia for the individual pump delivery pipe lines.
c. Butterfly valve 750 mm dia. fitted with electrical actuator suitable for local and control desk operation and display system for the individual pump delivery pipe lines after common manifold.
Installation at site of the M.S. Dismantling joint assembly 750 mm dia for common delivery line as per specification.
Installation at site of the M.S. Dismantling joint assembly 550 mm dia for delivery side of pump as per specification.
Installation at site of the M.S.Puddle collar for common delivery line as per specification.
Installation at site of the Flow Meter, Recorder, Totaliser as per specification.
Installation at site of the pressure gauges complete with fittings and fixture as per specification & as follows.
a) Pressure gauge (0-5kg/cm2) delivery side
b) Pressure gauge for deliver side and common manifold (0-5kg/cm2)
Installation at site of the pressure transmitter complete with fitting and fixture as per specification & as follows.
a) Pressure transmitter for pump delivery side (0-5kg/cm2)
b) Pressure transmitter for delivery (0-5kg/cm2) at common manifold
Installation at site of the Vertical Squirrel cage induction motor rated at 415V ±10%, 50Hz ±5%, 3Ph, 1000 R.P.M.(syn) of adequate capacity to match the pump in sl. no. 1 complete with coupling hub and all other accessories and spares as mentioned in the technical specification. (Rating shall not be less than 200K.W. + at least 15% margin)
Installation at site of the multi panel M.V switch board of 1000A suitable for operation at 415Volt, ±10%, 3phase, 50Hz ±5%, AC system as per specification.
Installation at site of the Remote control Desk and instrument panel for motor control system as per specification.
Installation at site of the pure sine wave, 1450VA inverter with 180AH battery backup as per Specification.
Installation at site of the Double throat air valve at common delivery manifold as per Specification.
Laying of M.V Cable as per specification & as follows. i) M.V. Cable
a) From MV Switch Board to respective Motor Terminal, 1.1KV, grade, 3C, 2 X 185 ssq mm. Al conductor, XLPE insulated armoured cable.
b) From MV Switch Board to Ventilation System 1.1KV, 4C, 6 sq.mm. Multi Strand Cu conductor, XLPE insulated.
c) From MV Switch Board to Valve Actuators 1.1KV, 4C, 2.5 sq.mm. Multi Strand Cu conductor, XLPE insulated.
d) From MV Switch Board to Inverter , 1.1KV, 4C, 2.5 sq.mm. Multi Strand Cu conductor, XLPE insulated
e) From MV Switch Board to Flow Sensor 1.1KV, 4C, 2.5 sq.mm. Multi Strand Cu conductor, XLPE insulated.
f) From MV Switch Board to Space Heater 1.1KV, 4C, 2.5 sq.mm. Multi Strand Cu conductor, XLPE insulated.
g) From MV Switch Board to E.O.T. Crane 1.1KV, 4C, 6 sq.mm. Multi Strand Cu conductor, XLPE insulated.
h) From MV Switch Board to Control Desk, 1.1KV, 4C, 2.5 sq.mm. Multi Strand Cu conductor, XLPE insulated.
i) From MV Switch Board to LDB, 1.1KV, 4C, 2.5 sq.mm. Multi Strand Cu conductor, XLPE insulated.
iii) Control Cable Control cable of copper conductors of various sizes & grade and of suitable length as per specification for all remote control circuit and interlocking circuits.
Installation at site of the Jointing Materials as per specification & as follows :
a) All H.T. Cables jointing materials (dry type).
b) All M.V. Cables jointing materials (dry type)
c) All control & signal Cables jointing materials.
N.B. – No extra payment would be made if the type, variety, length and dia. of the different sizes of cable varies on the higher side to meet up the requirement of the specification and site condition. Rates must be quoted carefully. This is also applicable for all type of cable joints.
Installation at site of the Earthing equipment as per current I.E. Rule & specification.
Installation at site of the fire extinguishers as follows :
Dry Powder (5Kg. each)
CO2 (4.5Kg. each)
A-B-C Type (5Kg. each)
Installation at site of the ring ventilation system of pump house with 12 air changes per hour all complete as per specification.
Installation at site of the air conditioners for control room cum office all complete as per specification.
Installation at site of the Misc. item such as rubber mats, Shock Treatment chart etc. and storage as per specification.
Installation at site of the M.S. Structural Works for cable tray/ rack, panel installation supports, Pipe & valve supports, fabricated stairs & all other fabrication works.
Installation at site of the all luminaries, fittings, fixtures complete with necessary cables for inside and outside lighting of pump house as per specification.
Installation at site of the E.O.T. Crane along with it’s structural members & accessories for 7 M.T. main hoist and 1 M.T. auxiliary hoist, all complete with gear box, brakes, as per I.S. and technical specification.
Area Illuination
Carrying out heat run of H.T & M.V equipments, dehydration of both switches & Transformer oil, and making ready all H.T./M.V. equipment for High/Medium pressure testing as per rule.
Carrying out Statutory High pressure testing on all H.T. equipment & medium pressure testing on M.V. Equipments as per specification including charges of Govt. Inspector.
Charges for Diesel Generator set/Temporary power connection from CESC for construction purpose.
Testing the whole installation & submission of test reports as per specification & direction of E.I.C.
Commissioning the whole installation including Trial Run of Pumps for 72 hours on load operation and 8 hrs. at a stretch operation as per specification & direction of E.I.C.
Trial Run of pumping machinery and all electrical appliances installed in the pumping station for a period of 3 months with adequate number of working personnel for round the clock operation as per requirement & as per specification & direction of E.I.C.
PART - B1 (Sub-Station) Supply, delivery and storage at site of Power Transformer along with Allied Electrical Equipments of 6/11 KV Electrical Power Distribution Sub-station for 3.6 M.G. Capacity UGR cum Boosting Station at Olabibitala H.I.T. Park under Ward No. 25 of H.M.C
Supply, delivery at site and storage of not less than 750 KVA (Calculation has to be shown considering load of motor, battery charger, light and exhaust fan etc.), 11 or 6 KV / 433 V indoor type Transformers with neutral brought out as per technical specification and all accessories complete
Supply, delivery at site and storage of 3 panel,not less than 800A indoor type H.T. Vacuum Circuit Breaker as per specification with all inter connection
Supply, delivery at site and storage of multi panel 1200A MV Switch board connected with the secondary side of transformers suitable for operation at 415 volt, 3 phase, 50 Hz AC system with all interconnection complete as per specification
Supply, delivery at site and storage of multi panel 1200 A MV Switch board connected with the secondary side of transformers suitable for operation at 415 volt, 3 phase, 50 Hz AC system with all interconnection complete as per specification
Supply, delivery at site and storage of H.T., M.V. & Control Cable as per specification & as follows
H.T.Cable
From CESC’s summation panel to incoming panel of HT Switch gear of 11 KV grade, 300 sq mm dia ( to withstand maximum fault current for 1 sec. ) Al. conductor, XLPE cable armoured as per specification
From HT Switchgear to two numbers of Transformer HV side terminal of 11 KV grade, 300 sq mm dia, Al conductor, XLPE insulated, armoured cable as per specification
M.V. Cables
From two numbers of transformer secondary side to the two number of 1200A incomers of MV Switchboard at sub-station 1.1 KV grade, 3.5C x 300 sq mm Al. conductor, XLPE insulated armoured cable, 3 lengths each per incomer i.e. total 6 lengths
From each of the 630 A outgoing ACB of 1200 A Sub-station MV Switchboard to respective incoming ACB of MV Panel at Pump House, 1.1 KV grade, 3.5 C, 300 sq mm, Al. conductor, XLPE insulated armoured cable, 3 lengths each i.e. total 6 lengths
From Battery Charger / DCDB to MV Panel Switch board at Pump House, 1.1 KV grade, 4 C X 6 sq mm stranded Cu. Conductor XLPE insulated armoured cable
From 1200 A Sub-station MV Switchboard to ventilation system, 1.1 KV grade, 3 C x 2.5 sq mm stranded Cu. Conductor, XLPE insulated armoured cable
From 1200A Substation MV Switchboard to Lighting DB, 1.1 KV grade 4 C x 6 sq mm stranded Cu. Conductor, XLPE insulated armoured cable
From 1200 A MV Switch board to H.T. Switch gear 1.1 KV grade, 3 C X 2.5 sq mm stranded Cu. Conductor, XLPE insulated armoured cable
Stranded copper conductor of various ratings and of suitable sizes as per specification for all control circuit and interlocking circuits at Substation
Supply, delivery at site and storage of Jointing Materials as per specification & as follows:
All H.T Cables jointing materials ( Dry type, Heat Shrink Joint )
All MV Cables jointing materials for different Cross sections ( Dry type )
All copper control & power Cables jointing materials for different cross sections (Dry Type)
N.B :- No extra payment would be made if the length and diameter of the different sizes of cable varies on the higher side to meet up the requirement of the specification and site condition. Rates must be quoted carefully. This is also applicable for all type of cable joints
Supply & delivery at site and storage of earthing equipment as per specification and all the other equipments required to comply with latest I.E. Rules
Supply, delivery at site and storage of fire extinguishers as follows:
Dry Powder ( 5 Kg each )
CO2 ( 4.5 Kg each )
Supply & delivery at site and storage of Misc. items such as rubber mats, Shock Treatment Chart, danger boards, sand buckets, Glow sign board etc. as per specification
Supply & delivery at site and storage of all luminaries, fittings, fixtures complete with necessary multi-strand copper wires for inside lighting of Substation as per specification
Supply & delivery at site and storage of Lightning arrestor alongwith earth strip and earth electrodes all complete as per specification and all other equipment required to comply with latest I.E. Rules
Supply & delivery at site and spare parts as per specification
PART - B2 (Installation at site of Power Transformer along with Allied Electrical Equipments of 6/11 KV Electrical Power Distribution Sub-station for 3.6 M.G. Capacity UGR cum Boosting Station at Olabibitala H.I.T. Park under Ward No. 25 of H.M.C)
Installatiion of transformar site of not less than 750 KVA, 11 or 6 KV / 433 V indoor type Transformers with neutral brought out as per technical specification and all accessories complete
Installation at site of 3 panel, not less than 800 MVA indoor type H.T. Vacuum Circuit Breaker as per specification with all inter connection
Installation at site of multi panel 1200 A (at least) MV Switch board connected with the secondary side of 750 KVA transformers suitable for operation at 415 volt, 3 phase, 50 Hz AC system with all interconnection complete as per specification
Installation at site of 110 V, 80Ah, sealed maintenance free battery comprising of 55 nos., 2 Volts cells with float and boost charger cum DCDB
Laying at site of H.T., M.V. & Control Cable as per specification & as follows
H.T.Cable
From CESC’s summation panel to incoming panel of HT Switch gear of 11 KV grade, 300 sq mm dia ( to withstand maximum fault current for 1 sec. ) Al. conductor, XLPE cable armoured as per specification
M.V.Cable
From two numbers of transformer secondary side to the two number of 1200A (at least) incomers of MV Switchboard at sub-station 1.1 KV grade, 3.5C x 300 sq mm Al. conductor, XLPE insulated armoured cable, 3 lengths each per incomer i.e. total 6 lengths
From each of the 630 A outgoing ACB of 1200 A (at least) Sub-station MV Switchboard to respective incoming ACB of MV Panel at Pump House, 1.1 KV grade, 3.5 C, 300 sq mm, Al. conductor, XLPE insulated armoured cable, 3 lengths each i.e. total 6 lengths
From 1200 A (at least) Substation MV Switchboard to Battery Charger, 1.1 KV grade, 4 C, 6 sq mm, stranded Cu conductor, XLPE insulated armoured cable
From Battery Charger / DCDB to MV Panel Switch board at Pump House, 1.1 KV grade, 4 C X 6 sq mm stranded Cu. Conductor XLPE insulated armoured cable
From 1200 A Sub-station MV Switchboard to ventilation system, 1.1 KV grade, 3 C x 2.5 sq mm stranded Cu. Conductor, XLPE insulated armoured cable
From 1200 A Substation MV Switchboard to Lighting DB, 1.1 KV grade 4 C x 6 sq mm stranded Cu. Conductor, XLPE insulated armoured cable
From 1200 A MV Switch board to H.T. Switch gear 1.1 KV grade, 3 C X 2.5 sq mm stranded Cu. Conductor, XLPE insulated armoured cable
Control Cable
Stranded copper conductor of various ratings and of suitable sizes as per specification for all control circuit and interlocking circuits at Substation
Installation at site of Jointing Materials as per specification & as follows:
All H.T Cables jointing materials ( Dry type, Heat Shrink Joint )
All MV Cables jointing materials for different Cross sections ( Dry type )
All copper control & power Cables jointing materials for different cross sections ( Dry type )
N.B :- No extra payment would be made if the length and diameter of the different sizes of cable varies on the higher side to meet up the requirement of the specification and site condition. Rates must be quoted carefully. This is also applicable for all type of cable joints.
Installation at site of earthing equipment as per specification and all the other equipments required to comply with latest I.E. Rule
Installation at site of fire extinguishers as follows:
Dry Powder ( 5 Kg each )
CO2 ( 4.5 Kg each )
Installation at site of Misc. items such as rubber mats, Shock Treatment Chart, danger boards, sand buckets, Glow sign board etc. as per specification
Installation at site of all luminaries, fittings, fixtures complete with necessary multi-strand copper wires for inside lighting of Substation as per specification
Installation at site of Lightning arrestor alongwith earth strip and earth electrodes all complete as per specification and all other equipment required to comply with latest I.E. Rules
Carrying out heat run of HT & MV equipments, dehydration of Transformer oil and making ready all HT / MV equipment for High / Medium pressure testing as per rule
Carrying out statutory high pressure testing on all HT equipment & medium pressure testing on MV equipments as per specification including charges of Govt. Inspector
Charges for Diesel Generator set / Temporary power connection from CESC for construction purposes
Testing the whole installation & submission of test reports as per specification & direction of EIC
Commissioning the whole installation including trial run for 72 hours on load operation as per specification & direction of EIC
Trial run of all electrical appliances installed in the substation for a period of 3 monthswith adequate number of working personnel for round the clock operation as per requirement and as per specification & direction of EIC
POWER INDIA
LOGIC NODES
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .