| 1 | L1₹17.8 LAccepted-AOC 58 CHANDRALOK BLDG MAYO HOSPITAL ROAD NAGPUR 440018 | NAGPUR | NAGPUR | MAHARASHTRA | 440018 | ₹17.8 L Quoted ₹18.3 L | L1 | Accepted-AOC LOWEST BIDDER. |
| 2 | L2₹27.5 L+₹9.2 L (50.2%)Rejected-AOC 58 CHANDRALOK BUILDING MAYO HOSPITAL ROAD NAGPUR 440 018 | NAGPUR | MAHARASHTRA | 440018 | ₹27.5 L+₹9.2 L (50.2%) | L2 | Rejected-AOC NOT LOWEST BIDDER. |
Tender Value
₹20.0 L
EMD Value
₹40,000
Closing Date
10 Jan 2024, 6:00 pmClosed
LT COL SANDEEP BENIWAL, GE
OFFICE OF GARRISON ENGINEER AIR FORCE VAYUSENA NAGAR NAGPUR- 440007
REPAIR MAINT REPLACEMENT OF LT DISTRIBUTION SYSTEM, LT PANEL AND FEEDER PILLAR BOX AT VSN NAGPUR
2023_MES_625444_2
8643
Open Tender
Civil Works
Item Rate
180 days
GE AF NAGPUR
As per tender documents
7 documents required · 7 mandatory
₹500
GE AF NAGPUR
₹40,000
26 Feb 2024
15 Dec 2023
17 Jan 2024
15 Dec 2023
10 Jan 2024
22 Dec 2023
Amount
Comprehensive maintenance of LT panel boards, indoor/outdoor type after isolating the panel board from electric supply, opening all cover/doors, cleaning of all joints/contact points by using CRC, dismantling and taking out old unserviceable spares of panel board of any type and shape and fixing of new parts complete including tightening of all existing connections/screws/ nuts & bolts etc all as specified and directed. Note : Defective sapre parts required to be replaced will be measured and paid seperately as per relevent items as follows
Comprehensive maintenance of APFC panel boards, indoor/outdoor type after isolating the panel board from electric supply, opening all cover/doors, cleaning of all joints/contact points by using CRC, dismantling and taking out old unserviceable spares of panel board of any type and shape and fixing of new parts complete including tightening of all existing connections/screws/ nuts & bolts etc all as specified and directed. Note : Defective sapre parts required to be replaced will be measured and paid seperately as per relevent items as follows
(a) Digital 3 Ph multifunction meter, model A, 5A class 1 Make: L&T Cat part No WDM303FDWA1 or equivalent in Legrand/ Seimens
(b) CT up to 300/5 of class/burden 1.0/5 VA Make: L&T or equivalent in Legrand/ Seimens
(c) LED Indicator Lamp in three colours RYB
(d) Replacement of hinges, locking arrangements of each panel board by cutting/ welding etc all as specified and as directed
(e) Fabrication work of LT Panel with 3.00 mm thick MS Sheet (Outer cover), including cutting, welding, moulding all as specified and directed.
(f) Fabrication work of LT Panel with 2.00 mm thick MS Sheet (Inner sheets), including cutting, welding, moulding all as specified and directed.
(g) Aluminium busbar as per existing rating/size and colour coding
Supply only power factor correction capacitor cylindrical type 1 KVAR
Supply only power factor correction capacitor cylindrical type 2 KVAR
Supply onlypower factor correction capacitor cylindrical type 3 KVAR
Supply only power factor correction capacitor cylindrical type 5 KVAR
Supply only power factor correction capacitor cylindrical type 7.5 KVAR
Supply only power factor correction capacitor cylindrical type 10 KVAR
Supply only power factor correction capacitor cylindrical type 15 KVAR
Supply only power factor correction capacitor cylindrical type 20 KVAR
Supply only power factor correction capacitor cylindrical type 25 KVAR
Supply only power factor correction capacitor box type type 1 KVAR
Supply onlypower factor correction capacitor box type 2 KVAR
Supply only power factor correction capacitor box type 3 KVAR
Supply only power factor correction capacitor box type 5 KVAR
Supply only power factor correction capacitor box type 7.5 KVAR
Supply only power factor correction capacitor box type 10 KVAR
Supply only power factor correction capacitor box type 15 KVAR
Supply only power factor correction capacitor box type 20 KVAR
Supply only power factor correction capacitor box type 25 KVAR
Material and labour for on load change over switch for 125 Amp, 4 pole with all arrangements for fixing including taking out old UNSV on load change over switch all as directed. Make : L&T/ Schneider/ Havells
All as per item No 28 above but 160 Amp 4 pole
All as per item No 28 above but 250 Amp 4 pole
All as per item No 28 above but 400 Amp 4 pole
Material & labour for MCCB 63 Amps 16 KA, 4 pole with thermal magnetic protection unit including dismantling of old MCCB complete all as specified and directed. Make: Legrand Cat No 4200 13 or equivalent in Siemens/ Schneider/ L&T
All as per item No 32 above but MCCB 100 Amps 16 KA, 4 Pole Make: Legrand Cat No 4200 15 or equivalent in Siemens/ Schneider/ L&T
All as per item No 32 above but MCCB 125 Amps 16 KA, 4 Pole Make: Legrand Cat No 4200 16 or equivalent in Siemens/ Schneider/ L&T
All as per item No 32 above but MCCB 160 Amps 16 KA, 4 Pole Make: Legrand Cat No 4200 17 or equivalent in Siemens/ Schneider/ L&T
All as per item No 32 above but MCCB 250 Amps 25 KA, 4 Pole Make: Legrand Cat No 4202 19 or equivalent in Siemens/ Schneider/ L&T
Material and labour for new MCB 400 Amp 4 Pole 36 KA in the existing feeder Pillar box/ LT panel with new bolts and nuts including connecting the incoming and out going cables etc. Make: Legrand Cat No 4220 07 or equivalent in Siemens/ Schneider/ L&T
All as per item No 32 above but MCB TPN 63 amps of 10 KA, C curve Make : Legrand 4086 83 or equivalent in Siemens/ Schneider/ L&T
Supply & fixing MCB TPN 32 amps of 10 KA, Ccurve with enclosure in existing panel with incoming and outgoing connection complete all as directed Make : Legrand 4086 80 or equivalent in Siemens/ Schneider/ L&T
Supply and fixing thermoplastic cable junction boxes IP 55/IP 65 with metric knockout for cable entry including connector of size 295x255x120 mm on pole with MS clamps, nut bolts, washers and glands suitable for 10 to 25 sq mm 04 core cable incl dismantling and taking out old unserviceable cable junction boxes all as specified and directed . Make: Sintex catpart No GSJB 2520 or equivalent in Hensel/ Neptune.
Material and labour for roughing old painting from the LT panels by paint removers, cleaning with scrapes and preparing the surface and applying two coats painting complete with synthetic enameld paint of existing colour and writing incoming and outgoing feeder/ area with stencil complete all as directed.
Material & labour for cement concrete in foundation, filling and mass concrete type B2 1:2:4 (40mm graded aggregate). Not exceeding 15 CM in deapth for plinth protaction for path including dismentling of old surface.
Material & labour for PCC 1:2:4 for coping of existing LT pole of size 45X45X30cm with 20mm graded aggregate type B-1 including dismantling of old broken coping complete and also including finishing work with plaster 15 mm thick CM (1:4) and necessary cleaning of surronding Pole of 1 Mtr distance complete all as specified and directed.
Cutting / trimming of tree branches which are touching of street light/ perimeter pole and disposal of timber complete all as specified and directed.
Taking out existing LT cable of sizes up to 95 Sqmm 2 to 4 core from duct/wall/floor/trenches and re-laying the same serviceable cable after fault rectification in existing position with supply and fixing connecting materials such as thimbles, lugs, nuts, bolts and washers as required at site all as specified and directed.
All as per item No 45 above but LT cable of sizes from 120 Sqmm to 300 Sqmm 2 to 4 core
Taking down the unserviceable LT cable of any size from tranches/ walls /floor etc complete all as specified and as directed.
Material & labour for LT UG XLPE insulated, armored heavy duty electric cables with aluminum conductor, 1100 volts grade, cross sectional area 10 sq mm 2 core with suitable size of aluminum lugs, gland, nut, bolt and washers etc complete all as specified and directed.
All as per item No 48 above but cross sectional area 16 sq mm 4 core
All as per item No 48 above but cross sectional area 25 sq mm 3.5 core
All as per item No 48 above but cross sectional area 35 sq mm 3.5 core
All as per item No 48 above but cross sectional area 50 sq mm 3.5 core
All as per item No 48 above but cross sectional area 120 sq mm 3.5 core
All as per item No 48 above but cross sectional area 240 sq mm 3.5 core
Material and labour for aluminium lugs for upto 25 Sqmm E-bolt hole 8.4 to 13 upto 4 core complete all as specified and directed.
All as per item No 55 above but aluminium lugs for 35 Sqmm E-bolt hole 8.4 to 10.5 upto 4 core
All as per item No 55 above but aluminium lugs for 50 Sqmm E-bolt hole 8.4 to 13 upto 4 core
All as per item No 55 above but aluminium lugs for 70 Sqmm E-bolt hole 8.4 to 13 upto 4 core
All as per item No 55 above but aluminium lugs for 95 Sqmm E-bolt hole 10.5 to 17 upto 4 core
All as per item No 55 above but aluminium lugs for 120 Sqmm E-bolt hole 10.5 to 17 upto 4 core
All as per item No 55 above but aluminium lugs for 150 Sqmm E-bolt hole 10.5 to 17 upto 4 core
All as per item No 55 above but aluminium lugs for 185 Sqmm E-bolt hole 10.5 to 17 upto 4 core
All as per item No 55 above but aluminium lugs for 240 Sqmm E-bolt hole 13 to 17 upto 4 core
All as per item No 55 above but aluminium lugs for 300 Sqmm E-bolt hole 17 to 20.3 upto 4 core
Material and labour for copper lugs for upto 25 Sqmm E-bolt hole 8.4 to 13 upto 4 core complete all as specified and directed.
Material and labour for copper sector connector upto 25 Sqmm upto 4 core complete all as specified and directed.
Material and labour for aluminium sector connector barrel type upto 25 Sqmm upto 4 core complete all as specified and directed.
All as per item No 55 above but aluminium sector connector barrel type upto 35 Sqmm upto 4 core
All as per item No 55 above but aluminium sector connector barrel type upto 50 Sqmm upto 4 core
All as per item No 55 above but aluminium sector connector barrel type upto 70 Sqmm upto 4 core
All as per item No 55 above but aluminium sector connector barrel type upto 95 Sqmm upto 4 core
All as per item No 55 above but aluminium sector connector barrel type upto 120 Sqmm upto 4 core
All as per item No 55 above but aluminium sector connector barrel type upto 150 Sqmm upto 4 core
All as per item No 55 above but aluminium sector connector barrel type upto 240 Sqmm upto 4 core
All as per item No 55 above but aluminium sector connector barrel type upto 300 Sqmm upto 4 core
Material and labour for straight through joint kit Heat shrinkable type suitable for 1.1 KV XLPE under ground cable of size 6 sqmm to 16 Sqmm 3.5 core all as directed. Make : Denson/ 3M/ Raychem
All as per item No 76 above but cable of size 25 Sqmm to 50 sqmm 3.5 core
All as per item No 76 above but cable of size 70-120 sqmm 3.5 core
All as per item No 76 above but cable of size 150-185 sqmm 3.5 core
All as per item No 76 above but cable of size 240 to 300 sqmm 3.5 core
Surface excavation n.exc 30 cm deep and averaging 15 cm deep and getting out hard/dense soil including cleaning away all grass vegetation saplings, brush wood under grouting, roots & tree and not exceeding 30 cm girth and removing rubbish to a distance of 50 mtr outside the periphery of area as directed.
Excavation in trenches in hard/dense soil not exceeding 1.5 meter wide and not exceeding 1.5M in depth for laying of cables and getting out of excavated material complete all as specified and directed.
Returning, filling in, including spreading, leveling, watering and well ramming in layers not exceeding 25cm thick each, excavated soil in trenches after the cables have been laid and tested complete all as specified and directed.
Removing excavated soil to a distance not exceeding 50 meter and depositing where directed at a level not exceeding 1.50 meter above the starting point complete all as specified and directed.
Material and labour for cutting of PCC/Hard standing/WBM road not exceeding 20 cm in width not exceeding 30 cm in depth for passing of LT cable and making good of disturbed surface to match with the existing surfaces by using old and new material i.e bitumen/PCC (1:3:6) type C-1 complete all as specified and directed .
Material and labour for DWC pipe of 50 mm internal dia for cable protection complete all as specified and as directed. Make : Rex/ Gemini/ Duraline
All as per item no 86 above but 75 mm internal dia.
Supply and laying in trenches/ floor or fixed to pole/ wall GI pipe light grade with fitting of size 100 mm bore for protection of cable complete all as specified and directed by the Engineer-in-Charge.
Supply and laying in trenches/ floor or fixed to pole/ wall GI pipe light grade with fitting of size 40 mm bore for protection of cable complete all as specified and directed by the Engineer-in-Charge.
All as per item No 89 above but 15 mm bore.
Supply and fix 2 core 2.5 sqmm PVC insulated PVC sheathed weather proof multistranded copper conductor cable 1100 volts grade drawn through in GI conduit, pole etc from junction box to street light fitting all as specified and directed.
Material and labour for PCC cable route indicator in mix of 1:2:4 type B1of size 450x200x100 mm with ovel shapeand writing the letter LT cable with synthtic ennamel paint over a coat of yellow paint and embedded with PCC foundation type D2 1:4:8 of size minimum 250mm depth including necessary earth work complete all as specified and directed.
Dismantling /taking down and Re-fixing/ erecting of old steel tubular swaged poles any type with accessories/ fittings at other location as directed including necessary excavation, removal of soil, refilling of soil, PCC (1:3:6) type C-2 using 40 mm graded stone aggregate for foundation of pole and coping with PCC (1:2:4) type B-1 using 20 mm graded stone aggregate all as per SSR part I complete all as specified and directed.
Material and labour for preparing surfaces of LT/HT electric poles of any type size including street light brackets, bracket clamps, cable protection pipe, terminal box, stay etc of any sizes and shape & dusting, cleaning the surface complete and applying one coat of aluminium paint completely including painting strips on poles with one coats of sky blue and white synthetic enamel paint complete all as specified and as directed by Engineer-in-Charge.
Taking out old UNSV earthing and Material and labour for for new earthing complete with galvanised steel plate earth electrode 600X600X6mm thick buried directly in ground (earth pit not less than 2.25 meter below ground level) with top edge of the plate not less than 1.5 metre below normal ground level connected to GI strip 25X4mm at two points by means of bolts and nut, check nut and washers including charcoal dust, common salt, necessary excavation in hard/dense soil, returning filling in and removal of surplus soil to a distance up to 50metres, PCC pit in 1:3:6 type CI (using 20mm grade stone aggregate) RCC 1:2:4 type B-1 (using 20mm grade stone aggregate ) 50mm thick pit cover, reinforced with 8mm dia TMT bars 75mm c/c, both ways MS handle 12mm dia, GI funnel, wire mesh and GI watering pipe of 20mm bore GI (light grade) and earth lead protection pipe 40mm bore (light grade) all as specified, directed and shown in electrical plate No 3 of SSR Part-I including testing complete. Note : GI strip and protection pipes 40 mm GI light grade up to 7.5 metre is included in quoted rate and beyond that the same will be measured separately.
Material and labour for earth continuty conductor or main earthing lead as 25x4 mm GI strip fixed to wall on batten or recess or chasses or burried in ground or drawn in conduit /pipe or fixed to pole or any other situation for loop earthing etc all as directed .
Material and labour for detection of fault through cable fault locator machine by giving high voltage surge and to find out exact location with in minimum time all as directed. Note : The item includes transportation, charging machine upto detecting fault at a time and fault should be immediately located after intimation of JE/ Engr-in-charge.
Material and labour for air termination, single pointed aluminium rod 12mm dia and 300mm long complete all as specified and as directed
Material and labour for aluminium strip 25 x 3.15mm with saddles and fixing screws etc. for roof conductors and down conductors above ground all as directed
Material and labour for perforated GI cable tray of size 150 X75X 1.5 mm fixed to wall by using suitable nuts/bolts/coupler plates etc complete all as specified and as directed.
Supply & fixing in replacement power factor controller relay 8 step 415 Volts, AC,50 Hz to automation to power capacitor including replacement of control wring as required at site including addition/alteration if required. Make: L&T etaCON L8 Cat No ERPML08D500 or equivalent in Legrand/ seimens
M/S. ELECTROPOWER TECHNOLOGIES
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .