Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹22.0 LAccepted-AOC | ₹22.0 L Quoted ₹2.2 L | L1 | Accepted-AOC Bein L1 Bidder |
| 2 | L2₹23.2 L+₹21.0 L (955.2%)Rejected-Finance 301 TULSI TOWER KHADAKPADA KALYAN THANE MAHARASHTRA 421301 | THANE | MAHARASHTRA | 421301 | ₹23.2 L+₹21.0 L (955.2%) | L2 | Rejected-Finance Being L2 |
| 3 | L3₹24.3 L+₹22.1 L (1002.8%)Rejected-Finance | ₹24.3 L+₹22.1 L (1002.8%) | L3 | Rejected-Finance Being L3 |
| Sl No | Description | Qty | Unit | Diamond Electric Co. L2 | K R GUPTA AND SONS L1 | Success PEB and Infra Consultants L3 |
|---|---|---|---|---|---|---|
| 1.00 | Supply, install, testing and commissioning of Diesel Engine driven generating set 100 KVA, 3 Phase, 4 wire, 415 Volts, 1500 RPM, 50 Hz power supply with power factor 0.8 coupled directly to alternator mounted on a common base plate complete with integral acoustic enclosure having silent features such as modular bolted construction with fabrication on imported CNC torret punch machines, nine tank treatment process with pure polyster based powder coating to ensure long life in all weather conditions and for out door application/ installation, integrated design there by facilitating / easy handling installation & shifting of the equipment at site. Compliance standard of DG set should be confirming to IS- 8728. The design of integral acoustic enclosure should be any type approved by national Physical laboratory as per Central Pollution Control Board (CPCB-IV) latest norms/ regulation with fuel tank, battery,AMF panel and standard accessories, acoustic enclosure, vibration pad, tools and spare, as provided by manufacturer, PCC foundation as per OEM to be paid under srl item no1 above all as specified and as directed with the following specifications :-
A) ENGINE:- Greaves make or equivelant model from make specified in Appx B, direct injection,04 Cylinder , water cooled, compression ignited, turbo charged and charged water cooled diseal engine 107.23 HP at 1500 RPM and compling with BS 5514/ISO 3046 standard :- | 1 | Each | 17,00,000 ₹17,00,000 | 16,00,000 ₹16,00,000 Lowest | 17,64,064 ₹17,64,064 |
| 1.01(i) 12V electrical starting system consisting of starter motor, charging alternator and 01 nos, 12V, 180 AH battery. (ii) Dry type Air cleaner with restriction indicator (iii) In-line Fuel injection system with Electronic Governor (iv) Spin-on Lube oil filter elements (iv) Radiator, Air-to- Air after cooler, pusher fan & fan drive arrangement, Gear driven water pump (v) Sensor for oil pressure, Coolant temperature & level (iv) First fill of Lube oil. (API CF4 grade, Greaves Maxtherm Lube or equivalent) ( B) ALTERNATOR:- Single bearing alternator suitable for continuous operation generating 100 KVA at 1500 RPM, 415 Volts, 0.8 power factor (lag) suitable for 50 Hz, 3 phase, 4 wire system confirming to BS 5000/ IS 4722, brushless type, screen protected revolving field, self excited, self regulated through an AVR. The alternator has the following features: (a) ± 1.0% voltage regulation (max) in static conditions (b) IP: 23 protection with insulated class H (c) Permissible overload of 10% for one hour in 12 hours of operation. Features, Functions, Protections (a) 16 character x 2 line alphanumeric LCD display with LED backlight (b) Operator Interface (c) Provide a record of most recent fault conditions, Fault history stored in the control non volatile memory (d) Provide Alternator data frequency. Provide Engine data- Starting (a) Battery Voltage (b) Engine Temp | ||||||
| 1.02(c) Oil pressured (d) Engine Hrs run Control includes provision for service adjustment and calibration of DG control function (a) Voltage, frequency selection (b) Meter calibration (c) Configurable input and output set up Power start operates on 24 V DC batteries Auto start mode accepts a ground signal from remote devices to automatically start the DG set. The remote start will also wake up the control system from sleep mode. Engine Starting The control system supports automatic engine starting, Primary and back up start disconnects are achieved by battery charging feedback or main alternator output frequency. Controller provide configurable time delay of 0-300 sec to start after remote start signal and time delay of 0-600 secs prior to shutdown after stop signal. Sleep mode increase battery life. Configurable current setting from low to minimize current draw when genset is not working. Engine Protective Functions includes :- Configurable alarm output emergency stop: Annunciated whenever an emergency stop signal is received by the control (a) Low Lube oil pressure warning and shutdown (b) High engine water temperature warning / shutdown (c) Low coolant temp warning (d) sensor failure indication (e) Low and high battery voltage warning (f) Weak battery warning (g) Fail to start shut down (h) Cranking lockout: Control will not allow the starter to engage or to crank the running engine (j) Cyclic cranking: Configurable for the number of starting cycle (1 to 7) and duration of crank and rest periods | ||||||
| 1.03(k) Alternator Protective functions includes (1) High and Low AC voltage shutdown (m) Under and over frequency shutdown/warning (n) Loss of sensing voltage input shutdown. Fuel tank( In built fuel tank) from remote devices to automatically start the DG set. The remote start will also wake up the control system from sleep mode. Engine Starting The control system supports automatic engine starting, Primary and back up start disconnects are achieved by battery charging feedback or main alternator output frequency. Controller provide configurable time delay of 0-300 sec to start after remote start signal and time delay of 0-600 secs prior to shutdown after stop signal. Sleep mode increase battery life. Configurable current setting from low to minimize current draw when genset is not working. Engine Protective Functions includes :- Configurable alarm output emergency stop: Annunciated whenever an emergency stop signal is received by the control (a) Low Lube oil pressure warning and shutdown (b) High engine water temperature warning / shutdown (c) Low coolant temp warning (d) sensor failure indication (e) Low and high battery voltage warning (f) Weak battery warning (g) Fail to start shut down (h) Cranking lockout: Control will not allow the starter to engage or to crank the running engine (j) Cyclic cranking: Configurable for the number of starting cycle (1 to 7) and duration of crank and rest periods (k) Alternator Protective functions includes (1) High and Low AC voltage shutdown (m) Under and over frequency shutdown/warning (n) Loss of sensing voltage input shutdown. Fuel tank( In built fuel tank) complete all as specified and directed by Engr-in-Charge. | ||||||
| 2.00 | Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 120 sq mm 3.5 core complete all as specified and directed by Engr-in-Charge. | 300 | Rm | 965 ₹2,89,500 Lowest | 1,000 ₹3,00,000 | 1,000 ₹3,00,000 |
| 3.00 | Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 150 sq mm 3.5 core complete all as specified and directed by Engr-in-Charge. | 23 | Rm | 1,140 ₹26,220 Lowest | 1,150 ₹26,450 | 1,300 ₹29,900 |
| 4.00 | Excavation in trenches not exc 1.5 m wide and not exc 1.5 m in depth and getting it out for laying of cable / pole in hard/dense soil complete all as specified and directed by Engr-in-Charge. | 65 | Cum | 150 ₹9,750 | 100 ₹6,500 Lowest | 110 ₹7,150 |
| 5.00 | Returnning,fillingin,including spreading, levelling, watering and well ramming in layers not exc 25 cm in hard/dense soil complete all as specified and directed by Engr-in-Charge. | 39 | Cum | 50 ₹1,950 Lowest | 50 ₹1,950 Lowest | 60 ₹2,340 |
| 6.00 | Removing excavated material n.exc 50 m and depositing where directed at a level exc. 1.5 cm above the starting point complete all as specified and directed by Engr-in-Charge. | 26 | Cum | 75 ₹1,950 | 50 ₹1,300 Lowest | 100 ₹2,600 |
| 7.00 | M&L for crushed stone sand cushioning to UG cable, provide with the layer 8 cm before and 15 cm after laying and stretching jointing and testing the cable complete all as specified and directed by Engr-in-Charge. | 20 | Cum | 450 ₹9,000 Lowest | 600 ₹12,000 | 1,500 ₹30,000 |
Tender Value
₹24.3 L
EMD Value
₹48,520
Closing Date
6 Aug 2026, 6:00 pmClosed
CWE(AF) BAMRAULI
CWE (AF) BAMRAULI
PROVN OF STAND BY POWER SUPPLY IN STATION ARMOURY AND BLDG NO P-730 AT AF STATION BAMRAULI
2026_MES_777349_1
87614/C/E8
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
GE(AF) BAMRAULI
AS PER NIT
7 documents required · 7 mandatory
₹500
GE(AF) BAMRAULI
₹48,520
Yes
14 Sept 2026
9 Jul 2026
13 Aug 2026
9 Jul 2026
6 Aug 2026
23 Jul 2026
9 Jul 2026 - 16 Jul 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | Supply, install, testing and commissioning of Diesel Engine driven generating set 100 KVA, 3 Phase, 4 wire, 415 Volts, 1500 RPM, 50 Hz power supply with power factor 0.8 coupled directly to alternator mounted on a common base plate complete with integral acoustic enclosure having silent features such as modular bolted construction with fabrication on imported CNC torret punch machines, nine tank treatment process with pure polyster based powder coating to ensure long life in all weather conditions and for out door application/ installation, integrated design there by facilitating / easy handling installation & shifting of the equipment at site. Compliance standard of DG set should be confirming to IS- 8728. The design of integral acoustic enclosure should be any type approved by national Physical laboratory as per Central Pollution Control Board (CPCB-IV) latest norms/ regulation with fuel tank, battery,AMF panel and standard accessories, acoustic enclosure, vibration pad, tools and spare, as provided by manufacturer, PCC foundation as per OEM to be paid under srl item no1 above all as specified and as directed with the following specifications :-
A) ENGINE:- Greaves make or equivelant model from make specified in Appx B, direct injection,04 Cylinder , water cooled, compression ignited, turbo charged and charged water cooled diseal engine 107.23 HP at 1500 RPM and compling with BS 5514/ISO 3046 standard :- | 1 | Each | - | - |
| 1.01 | (i) 12V electrical starting system consisting of starter motor, charging alternator and 01 nos, 12V, 180 AH battery. (ii) Dry type Air cleaner with restriction indicator (iii) In-line Fuel injection system with Electronic Governor (iv) Spin-on Lube oil filter elements (iv) Radiator, Air-to- Air after cooler, pusher fan & fan drive arrangement, Gear driven water pump (v) Sensor for oil pressure, Coolant temperature & level (iv) First fill of Lube oil. (API CF4 grade, Greaves Maxtherm Lube or equivalent)
( B) ALTERNATOR:- Single bearing alternator suitable for continuous operation generating 100 KVA at 1500 RPM, 415 Volts, 0.8 power factor (lag) suitable for 50 Hz, 3 phase, 4 wire system confirming to BS 5000/ IS 4722, brushless type, screen protected revolving field, self excited, self regulated through an AVR. The alternator has the following features: (a) ± 1.0% voltage regulation (max) in static conditions (b) IP: 23 protection with insulated class H (c) Permissible overload of 10% for one hour in 12 hours of operation. Features, Functions, Protections (a) 16 character x 2 line alphanumeric LCD display with LED backlight (b) Operator Interface (c) Provide a record of most recent fault conditions, Fault history stored in the control non volatile memory (d) Provide Alternator data frequency.
Provide Engine data- Starting (a) Battery Voltage (b) Engine Temp | - | - | - | - |
| 1.02 | (c) Oil pressured (d) Engine Hrs run Control includes provision for service adjustment and calibration of DG control function (a) Voltage, frequency selection (b) Meter calibration
(c) Configurable input and output set up Power start operates on 24 V DC batteries Auto start mode accepts a ground signal from remote devices to automatically start the DG set. The remote start will also wake up the control system from sleep mode. Engine Starting The control system supports automatic engine starting, Primary and back up start disconnects are achieved by battery charging feedback or main alternator output frequency.
Controller provide configurable time delay of 0-300 sec to start after remote start signal and time delay of 0-600 secs prior to shutdown after stop signal.
Sleep mode increase battery life. Configurable current setting from low to minimize current draw when genset is not working.
Engine Protective Functions includes :- Configurable alarm output emergency stop: Annunciated whenever an emergency stop signal is received by the control (a) Low Lube oil pressure warning and shutdown (b) High engine water temperature warning / shutdown (c) Low coolant temp warning (d) sensor failure indication (e) Low and high battery voltage warning (f) Weak battery warning (g) Fail to start shut down (h) Cranking lockout: Control will not allow the starter to engage or to crank the running engine (j) Cyclic cranking: Configurable for the number of starting cycle (1 to 7) and duration of crank and rest periods | - | - | - | - |
| 1.03 | (k) Alternator Protective functions includes (1) High and Low AC voltage shutdown (m) Under and over frequency shutdown/warning (n) Loss of sensing voltage input shutdown. Fuel tank( In built fuel tank)
from remote devices to automatically start the DG set. The remote start will also wake up the control system from sleep mode. Engine Starting The control system supports automatic engine starting, Primary and back up start disconnects are achieved by battery charging feedback or main alternator output frequency. Controller provide configurable time delay of 0-300 sec to start after remote start signal and time delay of 0-600 secs prior to shutdown after stop signal. Sleep mode increase battery life. Configurable current setting from low to minimize current draw when genset is not working. Engine Protective Functions includes :- Configurable alarm output emergency stop: Annunciated whenever an emergency stop signal is received by the control (a) Low Lube oil pressure warning and shutdown (b) High engine water temperature warning / shutdown (c) Low coolant temp warning (d) sensor failure indication (e) Low and high battery voltage warning (f) Weak battery warning (g) Fail to start shut down (h) Cranking lockout: Control will not allow the starter to engage or to crank the running engine (j) Cyclic cranking: Configurable for the number of starting cycle (1 to 7) and duration of crank and rest periods (k) Alternator Protective functions includes (1) High and Low AC voltage shutdown (m) Under and over frequency shutdown/warning (n) Loss of sensing voltage input shutdown. Fuel tank( In built fuel tank) complete all as specified and directed by Engr-in-Charge. | - | - | - | - |
| 2 | Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 120 sq mm 3.5 core complete all as specified and directed by Engr-in-Charge. | 300 | Rm | - | - |
| 3 | Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 150 sq mm 3.5 core complete all as specified and directed by Engr-in-Charge. | 23 | Rm | - | - |
| 4 | Excavation in trenches not exc 1.5 m wide and not exc 1.5 m in depth and getting it out for laying of cable / pole in hard/dense soil complete all as specified and directed by Engr-in-Charge. | 65 | Cum | - | - |
| 5 | Returnning,fillingin,including spreading, levelling, watering and well ramming in layers not exc 25 cm in hard/dense soil complete all as specified and directed by Engr-in-Charge. | 39 | Cum | - | - |
| 6 | Removing excavated material n.exc 50 m and depositing where directed at a level exc. 1.5 cm above the starting point complete all as specified and directed by Engr-in-Charge. | 26 | Cum | - | - |
| 7 | M&L for crushed stone sand cushioning to UG cable, provide with the layer 8 cm before and 15 cm after laying and stretching jointing and testing the cable complete all as specified and directed by Engr-in-Charge. | 20 | Cum | - | - |
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.31 MB
BOQ_870598.xls
BOQ • 0.27 MB
tender.pdf
Tender Documents • 0.73 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .