EX. ENGINEER (E AND M) W-S (SOUTH-WEST)
D BLOCK OHT OPP DESU COLONY JANAKPURI NEW DELHI-58
Renovation of electrical supply source by replacement of LT panel at Sec-3 pkt-BandC under CT-3 Dwarka.
2021_DJB_208907_8
N.I.T. No. 08 (2021-22)/ E.E.(EnM) WS- SW
Open Tender
Civil Works
Works
30 days
OFFICE OF THE EX. ENGINEER (E AND M) W-S (SOUTH-WE
Please refer Tender documents.
3 documents required · 3 mandatory
₹500
DJB EMD Ac No. 50448339804
Exempted
30 Oct 2021
27 Sept 2021
4 Oct 2021
27 Sept 2021
4 Oct 2021
27 Sept 2021
Distribution panel sheet steel enclosure made out of 2mm CRCA sheet totally enclosed, powder coated free standing, floor mounted type, dust& vermin proof, outward opening, lockable doors having hidden hinges and a bolted back cover both using non-deteriorating neoprene rubber gaskets to provide protection .The each part of the fabricated panel will be strictly subjected to seven tank treatment and will include the following procedures. The various components, assemblies and sub equipments of the panel will be as per standard given in relevant IS. The bus bar of the panel will be shaped out of high conductivity, electrolytic conductor and shall be liberal sized. The control wiring of the panel will be done with PVC flexible copper wires of 1.5mm cross section. Each wire will be terminating with a copper ferule crimped to the wire panel size 1500X1000X300mm. Having following components of approved make
MCCB 415V, TP200- 250 Amp with spreader & handle. Make- L&T/Siemens/DJB approved make
MCCB 415V, TP 63Amp With Spreader & handle Make- L&T/Siemens/DJB approved make
MCB Single pole 6Amp. Make -L&T/ Schneider/ DJB approved make
MCB Triple pole 32Amp. Make -L&T/Schneider/ DJB approved make
MCB Triple pole 63Amp. Make- L&T/ Schneider/ DJB approved make
DOL starter for 7.5 HP Make: L&T/Siemens/DJB approved make
Amp. Meter.digital Type Make -AE/L&T
Volt Meter0-500V Digital Type -Make AE/L&T
MPP type power capacitor 10Kvar Unit 440V 3phase. Make- Epcos/DJB approved make
Motor protection relay MPR200 Make L&T/ Siemens/ DJB approved make
Power contactor 220V 3phase 25Amp. Make: L&T/Schneider
Power contactor 220V 3phase 70Amp. Make-L&T/ Schneider
Current Transformer 200/5 Make- AE/ Advance/ Saviour
Current Transformer 100/5. Make- AE /Advance/ Saviour
Over load relay 30-50A Make- L&T/siemens
Over load relay 9-15A Make- L&T/siemens
Indicating lights LED type RYB & On/OFF. Make- Havells/ L&T
Flush Head push button Make- Havells/ L&T
Star delta timer Make: L&T/Siemens
On load 4pole change over switch 200Amp. Make: Havells/Advance/DJB approved make
Fitting of the above components in panel enclosure with terminal blocks, channels, ferrules, thimble, support insulator on bus bar, required hardwares, control wiring in 1.5sq mm wire complete in all respect.
Dismantling of old panel, structure, damaged components and Installation of the panel at site by making foundation, termination of cable both incoming & out going side, mongering of complete panel, fitting of the starter star delta including cable connection, functional testing of components at no load and testing of panel on load at site with site in charge. This includes cartage, loading& unloading etc.
HYDROCON ENGINEERS
Avon Electricals
CHANDERA BUILDERS
GOGIA BROTHERS
Raj Engineering Co.
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .