Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | 1₹22.4 LAccepted-AOC | 1 | Accepted-AOC Being lowest and reasonable | |
| 2 | 2₹27.3 L+₹3.9 L (16.8%)Rejected-Finance | 2 | Rejected-Finance Not being the lowest bidder | |
| 3 | 3₹28.0 L+₹4.6 L (19.6%)Rejected-Finance | 3 | Rejected-Finance Not being the lowest bidder | |
| 4 | 4₹29.9 L+₹6.5 L (27.7%)Rejected-Finance PLOT NO 28 SANTOSHIMA COLONY WEST MARREDPALLY SECUNDERABAD 500026 | HYDERABAD | TELANGANA | 500026 | 4 | Rejected-Finance Not being the lowest bidder | |
| 5 | 5₹30.9 L+₹7.5 L (32.2%)Rejected-Finance | 5 | Rejected-Finance Not being the lowest bidder |
Tender Value
Refer Docs
EMD Value
₹74,000
Closing Date
13 Jul 2021, 6:00 pmClosed
GE(I) R AND D RCI, HYDERABAD
GE(I) RND RCI, MILITARY ENGINEER SERVICES, VIGNYANAKANCHA, RCI, HYDERABAD
REPAIRS MAINTENANCE OF PUMPS FIRE ALARM FIRE FIGHTING SYSTEM AND ALLIED WORKS AT TECHNICAL AREA AND CPDC UNDER GE I RND RCI HYDERABAD
2021_MES_451228_1
8633
Open Tender
Civil Works - Water Works
Item Rate
300 days
GE(I) R AND D RCI
MES enlisted Class D category a ii or c vi Un enlisted Meeting enlistment criteria of D class in MES and having no recovery pending. For further details ref NIT
8 documents required · 8 mandatory
₹500
Yes
GE(I) R AND D RCI, HYDERABAD
₹74,000
Yes
8 Nov 2021
14 Jun 2021
19 Jul 2021
14 Jun 2021
13 Jul 2021
29 Jun 2021
Amount
S&F in repairs, weather proof Manual Call Point to match various Conventional Type Fire Alarm system, suitable for surface mounting or semi flush mounting, making necessary connection, testing and making good disturbed surfaces complete all as directed. Make: Apollo, Morley, Agni, Securico
S&F in repairs, weather proof Manual Call Point to match various Addressable Type Fire Alarm system, suitable for surface mounting or semi flush mounting, making necessary connection, testing and making good disturbed surfaces complete all as directed. Make: Apollo, Morley, EST
S&F in repairs, Electric siren single mounting, horizontal, single phase, AC supply, audible diametrical sound range of 1 KM, power 110 V including testing complete all as specified and as directed.
S&F in repairs, electrically operated horizontal double mounting siren, 220/250V, single phase, AC supply, audible diametrical sound range of 1.5 KM including testing complete all as specified and as directed. Make for item No 3&4: Kheraj, Jaykay, Perfect, National
S&F in repairs, photoelectric optical use internal pulsing Smoke Detector addressable type complete all as specified and directed. Make: Kartar, Apollo, Morley, GST 5000
S&F in repairs, Manual Call Point break glass required for Conventional type Fire Alarm System complete all as specified and directed.
S&F in repairs, Response Indicator with set of built in tools for indication of detectors, 6V, fixed on walls or within false ceiling with indication complete all as specified and directed. Make: Dekars, Ravel, Fire, Securico, Agni
S&F in repairs, 24Volts, 8PIN, 24VAC Potential Free Relay with socket in existing Fire Alarm Main Panel complete all as specified and directed.
S&F in repairs, speaker type electrical Hooter, 8"(20CM), 110V single phase complete all as specified and directed. Make: Kheraj, National, Securico or techno commercially equivalent as approved by GE
S&F in repairs, Transformer 24-0-24 Volts, 5Amp in existing Fire Alarm main panel complete all as specified and directed. Make: Manish Engineers or techno commercially equivalent as approved by GE
S&F in repairs, speech auto dialing system suitable for micro controller base, consisting of 13key onboard key pad, 3 message, 1 to 40 numbers storage capacity with provision for fire, special and special help complete all as specified and directed. Make: Securico, Falcon or techno commercially equivalent as approved by GE
S&F in repairs, Assorted fuse 3A, 5A in existing fire alarm panel complete all as specified and directed.
S&F in repairs, 2core 1.5Sqmm FR PVC insulated, PVC round sheathed, flexible copper conductor cable, 1100Volts, ISI marked complete all as specified and directed.
S&F in repairs, 2core 2.5Sqmm FR PVC insulated, PVC round sheathed, flexible copper conductor cable, 1100Volts, ISI marked complete all as specified and directed.
S&F in repairs, 2core 4Sqmm FR PVC insulated, PVC round sheathed, flexible copper conductor cable, 1100Volts, ISI marked including PVC casing & capping with fittings of size 20mm, ISI marked complete all as specified and directed.
Dismantling and Reprogramming Single loop Fire Alarm main panel/ repeater panel board of any make for correct indication of sensors, detectors as per present precise locations as per manufacturer's instructions convenient windows programming software, changing of detector/sensor location, name, address of room, testing for exact fault locations and reconnecting to entire satisfaction of Engineer in Charge complete all as directed.
All as per item No 16 above for Two loop Fire Alarm main panel board
Dismantling and Reprogramming microprocessor based Four loop addressable type Fire Alarm main panel/ repeater panel board of any make for correct indication of sensors, detectors as per present precise locations as per manufacturer's instructions convenient windows programming software, changing of detector/sensor location, name, address of room, testing for exact fault locations and reconnecting to entire satisfaction of Engineer in Charge complete all as specified and directed.
S&F in repairs, Isolator module used for installation where there is problem of Id connection and damage to devices output 16W/12W, voltage 1500VDC/1MA complete all as specified and directed. Make: Apollo, Morley, XP95
S&F in repairs, 8 Way Wago/Phone PCB terminal block connector in weather proof mild steel junction box including necessary painting and insulation material complete all as specified and directed.
S&F, in repairs, sealed lead acid battery 12Volts 7AH complete all as specified and as directed. Make: EXIDE, AMARON, FURKKAVA
S&F in repairs, single loop main control panel, microprocessor based addressable type fire alarm control panel with LCD display, event storage with real time clock communication for network/repeater one programmable form C relay for fire extensive built in transient protection lamp test facility common fire, supervisory, fault LED indication and battery 12V/7AH including testing complete all as specified and as directed.
S&F in repairs, two loop main control panel, microprocessor based addressable type fire alarm control panel with LCD display, event storage with real time clock communication for network/repeater one programmable form C relay for fire extensive built in transient protection lamp test facility common fire, supervisory, fault LED indication and battery 12V/7AH including testing complete all as specified and as directed. Make for item No 22 & 23: Apollo, Notifier, Tata Honeywell, FDX 5000 Make of battery for item No 22 & 23: EXIDE, AMARON, FURKKAVA
S&F in repairs, Four zone main control panel conventional type fire alarm control panel with LCD display, event storage with real time clock communication for network form C relay for fire extensive built in transient protection lamp test facility common fire, supervisory, fault LED indication and battery 12V/7AH including testing complete all as specified and as directed. Make: AGNI, RAVEL, DEKARS, MINIMAX
S&F in repairs, gun metal Hydrant landing valve of size 63mm, single head outlet with hose coupling adaptor of size 63mm size instantaneous spring locks arrangements and blank cap complete as per IS-5290 type 'A' all as specified and directed.
All as per item No 25 but for type 'B', double head outlet. Make for item No 25 & 26: ALLIED/ NEW AGE INDUSTRIES / SAFEX / NITIN /KARTAR/WINCO
S&F in repairs, stand post made out of mild steel pipe of size 80mm dia heavy grade of 1.2m height and providing necessary flanges at both ends suitable for fire hydrant single out let including flanged reducer and other fittings suitable for stand post with necessary welding to existing pipe including earthwork in any type of soil complete all as specified and directed.
S&F in repairs, cotton synthetic fibre reinforced rubber line of size 63mm dia 15m length conforming to IS 636 with male and female couplings conforming to IS 903 duly housed in fire hose box complete all as specified and directed.
S&F in repairs, hose box of size 750 x 600 x 250mm outdoor type made of 1.5mm thick mild steel sheet with frosted glass doors, lock and key arrangement including stand for the hose box made out of 80mm dia medium grade mild steel pipe, 1.50m height, welded at top and bottom with 6mm mild steel plate, duly embedded in PCC 1:2:4 type B1 using 20mm graded stone aggregate and painted as per fire code, the hose box shall be installed near the hydrant by providing 2 Nos of cotton synthetic fibre reinforced rubber line of size 63mm dia 15m length with male and female couplings duly housed in fire hose box complete all as specified and directed.
S&F in repairs, 63mm dia water monitor with gun metal nozzle conforming to IS 8442 complete all as specified and directed.
Complete removal of existing paint from existing fire hydrant stand post of any size and type at various location of RCI and applying two coats of synthetic enamel paint over a coat of primer as per colour code including writing 8cm size letters in white colour (FIRE) complete all as specified and directed.
All as per item No 31 above but for Hose boxes
Supply, laying, welding, fixing, leak proof testing and commissioning of 200mm bore, medium grade mild steel ERW pipes conforming to IS 3589 with bitumen wrap coating over the external surface of the pipe including necessary specials/fittings and taking down old unserviceable pipe complete all as specified and directed.
All as per item No 33 above but for 150mm bore of pipe
All as per item No 33 above but for 100mm bore of pipe but conforming to IS 1239
All as per item No 33 above but for 80mm bore of pipe but conforming to IS 1239 Make for item No 33 to 36: TATA, JINDAL, PRAKASH Note for item No 33 to 36: Excavation and earthwork will be measured and paid separately.
Supply, install, test and commissioning of 200mm bore CI Sluice Valve in repairs, Class PN-1.6, both ends flanged and drilled type with stainless steel spindle including wheel, suitable rubber gasket for flanged joints, ISI marked, including provision of necessary jointing materials nuts and bolts, washers etc., complete all as specified and directed.
All as per item No 37 above but 150mm bore Sluice Valve.
All as per item No 37 above but 100mm bore Sluice Valve. Make for item No 37 to 39: KIRLOSKAR, LEADER, L&T, ZOLOTO, KARTAR
S&F in repairs Danfoss Pressure switch Model No KP36 regulation range 2 to 14 bar complete all as specified and directed
Opening the Smoke detector complete and cleaning of its sensor completely with blower and refixing complete all as directed
Excavation in trenches not exceeding 1.50m wide and not exceeding 1.50m depth for foundation, for laying of pipes/cables/poles etc., forming bottom surfaces to required slope/gradient where pipe are laid and getting out in any type of soil complete all as specified and directed.
Returning, filling in, including spreading, leveling, watering and well ramming in layers not exceeding 25cm thick each layer as in soil complete all as specified and as directed.
Removing excavated material/soil to a distance not exceeding 50m and depositing where directed at a level not exceeding 1.5m above the starting point complete all as specified and as directed.
Re-Programming of speech auto dialing suitable for controller base 1 to 40 numbers storage capacity with provision for adding to automatic fire alarm system panel programming phone number, recording, cable etc., including testing complete all as specified and as directed.
S&F in repairs, PVC Fire Hydrant coupling ring including washers of size 63mm complete all as directed.
M&L for Bailing out the water from the semi underground static water tank of 1,35,000 litres capacity without causing any interruption to regular water supply system and cleaning the walls, roof and floor thoroughly by using scrapper and removing the deposited scales/ fungus/ sludge/dirt etc and removing the same out of site, cleaning thoroughly with water and bleaching powder and finally with chlorine solution for complete anti bacterial disinfections including writing date of cleaning on the black back ground with white synthetic enamel paint complete all as directed.
Supply, install, test and commissioning of DSM-80/36, 100mm suction, 80mm delivery, horizontal split casing, two stage centrifugal pump having discharge capacity of 85Cum/hour at 70m head, suitable for fire fighting and conforming to IS, CI casing and impeller, stainless steel shaft mounted on heavy duty bearing suitable for continuous operation with totally enclosed in fan cooled induction motor, 30KW/40HP capacity, squirrel cage operating on 3 phase, 415Volts, 50Hz, 1450RPM complete including demolition of old PCC foundation and provision of new PCC foundation as per manufacturers instructions, making connection with existing cable with new lugs and discharge ends with suitable gland packing, bolts, nuts and washers, taking down old unserviceable pump and depositing in MES Store yard of AGE E/M complete all as specified and directed. Make: Kirloskar, Crompton Greaves, Grundfos, KSB, Jyothi
Bismi Engineering
S.S.ENGINEERING CORPORATION
Universal refrigeration and Engineering Company
shyam engineerings
Richcon Engineers
UNITY ENGINEERING TRADERS
ELEVATORS MAINTENANCE ENGINEER WORKS
stage.html
html • 0.07 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .