| Sl No | Description | Qty | Unit | ST ENTERPRISES L1 |
|---|---|---|---|---|
| 1.00Supply & Installation of the following capacity ceiling mounted clean agent Modular Fire Suppression system as per the Technical specifications as provided. | ||||
| 1.01Conditions: 1.The vendor should attach the Technical datasheet of the proposed ceiling mounted clean agent Modular Fire Suppression system. 2.If the vendor is not a OEM, they should attach OEM authorization certificate. 3.The proposed Ceiling Mounted modular fire extinguisher model should be tested from BSI for Class A (Polymer) and class B (N Heptane) fires and test certificate should be enclosed. 4.The proposed Ceiling Mounted modular fire extinguisher model should be PED certified con to PED 2014/68/EU, ANNEXIII (MODULE H) and copy of the certificate to be enclosed. 5.The agency should be ready to start the work on the next day of release of purchase order and shall be completed within 14 days. It is the responsibility of the vendor to bring all required tools, ladders and other accessories to complete the work. 6. No advance payment and the payment shall be made on receipt of invoice after effecting the supply and installation. | ||||
| 1.02 | 10 kg ceiling mounted clean agent Modular Fire Suppression system as per the Technical specifications. Capacity : 10 KG Agent : HFC 227ea Storage : Stored Pressure Working Pressure : 10 Bar Hydrostatic Test Pressure : 35 Bar Body Material : Steel CR2(DC01) Body Thickness : 2 mm Body Construction : Deep Drawn & Mig Welded Valve / Cap Construction : Forging And Machining Operating Temperature : -30°C To +60°C External Coating : Epoxy Polyester Powder Having Min.Thickness 50 Micron Shade Color Red Operating Mechanism : Automatic Pressure Gauge : Magnetic Bourdon Tube Type Discharge Fitting : Quartzoid Bulb Discharge Time : 6 To 10 Sec Coverage Volume : 20 M3 Fire Applicability : A, B, C, & Electrical Started Fire Helium Leak Detection Testing : Yes Warranty : Min 6 Years. | 4 | Nos | 76,200 ₹3,04,800 Lowest |
| 1.03 | 5 kg ceiling mounted clean agent Modular Fire Suppression system as per the Technical specifications. Capacity : 5 KG Agent : HFC 227ea Storage : Stored Pressure Working Pressure : 10 Bar Hydrostatic Test Pressure : 35 Bar Body Material : Steel CR2(DC01) Body Thickness : 1.6 mm Body Construction : Deep Drawn & Mig Welded Valve / Cap Construction : Forging And Machining Operating Temperature : -30°C To +60°C External Coating : Epoxy Polyester Powder Having Min.Thickness 50 Micron Shade Color Red Operating Mechanism : Automatic Pressure Gauge : Magnetic Bourdon Tube Type Discharge Fitting : Quartzoid Bulb Discharge Time : 4 To 8 Sec Coverage Volume : 10 M3 Fire Applicability : A, B, C, & Electrical Started Fire Helium Leak Detection Testing : Yes Warranty : Min 6 Years | 4 | Nos | 48,500 ₹1,94,000 Lowest |
Tender Value
₹5 L
EMD Value
₹10,000
Closing Date
19 Jan 2026, 3:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
Executive Engineer (Electrical)
Engineering Unit, Admin Block 3rd Floor, IIT Madras CHENNAI-600036
Supply and Installation of ceiling mounted clean agent Modular Fire Suppression system at various locations at IIT Madras
2026_IITM_262607_1
Qn05/2025-26/ELDB
Open Tender
Electrical Works
Item Rate
14 days
IIT MADRAS CHENNAI
All required documents as mentioned in the quotation
2 documents required · 2 mandatory
₹0
₹10,000
2 Feb 2026
12 Jan 2026
20 Jan 2026
12 Jan 2026
19 Jan 2026
12 Jan 2026
12 Jan 2026 - 13 Jan 2026
Supply & Installation of the following capacity ceiling mounted clean agent Modular Fire Suppression system as per the Technical specifications as provided.
Conditions: 1.The vendor should attach the Technical datasheet of the proposed ceiling mounted clean agent Modular Fire Suppression system. 2.If the vendor is not a OEM, they should attach OEM authorization certificate. 3.The proposed Ceiling Mounted modular fire extinguisher model should be tested from BSI for Class A (Polymer) and class B (N Heptane) fires and test certificate should be enclosed. 4.The proposed Ceiling Mounted modular fire extinguisher model should be PED certified con to PED 2014/68/EU, ANNEXIII (MODULE H) and copy of the certificate to be enclosed. 5.The agency should be ready to start the work on the next day of release of purchase order and shall be completed within 14 days. It is the responsibility of the vendor to bring all required tools, ladders and other accessories to complete the work. 6. No advance payment and the payment shall be made on receipt of invoice after effecting the supply and installation.
10 kg ceiling mounted clean agent Modular Fire Suppression system as per the Technical specifications. Capacity : 10 KG Agent : HFC 227ea Storage : Stored Pressure Working Pressure : 10 Bar Hydrostatic Test Pressure : 35 Bar Body Material : Steel CR2(DC01) Body Thickness : 2 mm Body Construction : Deep Drawn & Mig Welded Valve / Cap Construction : Forging And Machining Operating Temperature : -30°C To +60°C External Coating : Epoxy Polyester Powder Having Min.Thickness 50 Micron Shade Color Red Operating Mechanism : Automatic Pressure Gauge : Magnetic Bourdon Tube Type Discharge Fitting : Quartzoid Bulb Discharge Time : 6 To 10 Sec Coverage Volume : 20 M3 Fire Applicability : A, B, C, & Electrical Started Fire Helium Leak Detection Testing : Yes Warranty : Min 6 Years.
5 kg ceiling mounted clean agent Modular Fire Suppression system as per the Technical specifications. Capacity : 5 KG Agent : HFC 227ea Storage : Stored Pressure Working Pressure : 10 Bar Hydrostatic Test Pressure : 35 Bar Body Material : Steel CR2(DC01) Body Thickness : 1.6 mm Body Construction : Deep Drawn & Mig Welded Valve / Cap Construction : Forging And Machining Operating Temperature : -30°C To +60°C External Coating : Epoxy Polyester Powder Having Min.Thickness 50 Micron Shade Color Red Operating Mechanism : Automatic Pressure Gauge : Magnetic Bourdon Tube Type Discharge Fitting : Quartzoid Bulb Discharge Time : 4 To 8 Sec Coverage Volume : 10 M3 Fire Applicability : A, B, C, & Electrical Started Fire Helium Leak Detection Testing : Yes Warranty : Min 6 Years
stage.html
html • 0.04 MB
technical_304284.pdf
techsummary_304284.pdf
finance_304284.pdf
BOQ Comparative Chart
xlsx
cancelled_1.pdf
pdf • 0.37 MB
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.37 MB
e-Quotation05.pdf
Tender Documents • 0.76 MB
PriceBidForViewQn05.pdf
Other Document • 0.57 MB
BOQ_304284.xls
BOQ • 0.39 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .