Loading…
Tenderkart now works inside Claude and ChatGPT: search and analyse tenders right from your chat
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Status |
|---|---|---|
| 1 | Admitted-Finance 12 GURU NANK AUTO MARKET KASHMERE GATE DELHI 110006 | NORTH | DELHI | 110006 | Admitted-Finance |
| 2 | Admitted-Finance | Admitted-Finance |
| 3 | Admitted-Finance 1008 A PREMIER ENGINEERING COMPANY PURVI RITHANI MEERUT DELHI ROAD MEERUT UTTAR PRADESH 250103 INDIA | MEERUT | UTTAR PRADESH | 250103 | Admitted-Finance |
| 4 | Not Admitted-Fee/PreQual/Technical B 70 43 DSIIDC COMPLEX LAWRENCE ROAD INDUSTRIAL AREA NORTH WEST DELHI DELHI 110035 | NORTH WEST DELHI | DELHI | 110035 | Not Admitted-Fee/PreQual/Technical Not Complied with technical specification |
Tender Value
Refer Docs
EMD Value
₹7,500
Closing Date
24 Mar 2021, 11:00 amClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
OFFICE OF THE EXECUTIVE ENGINEER (E and M) WS-NE
POCKET-A, DILSHAD GARDEN, DELHI-110095
Improvement of Power Factor at Kanti Nagar BPS. (Re-invite)
2021_DJB_201732_7
NIT No. 15 (20-21)
Open Tender
Miscellaneous Works
Works
30 days
Kanti Nagar BPS.
Please refer Tender documents.
3 documents required · 3 mandatory
₹500
Ac No. 50448339804
₹7,500
Yes
3 Apr 2021
17 Mar 2021
24 Mar 2021
17 Mar 2021
24 Mar 2021
17 Mar 2021
90 days
Dismantling of all damaged switchgears, capacitors, measurement instrument, indicating lights, relay and removing of complete wiring and connection at site and cleaning of APFC Panel by CRC.
Shunt capacitors power 3 phase, 415V AC 50Hz MPP type Make: Epcos/L&T/any DJB Approved.
PVC insulated flexible copper wire 16sq mm 1.1 KV Make: Havells/ Finolex/Any DJB Approved.
Automatic power factor correction relay 14 stage 415V digital type with display of power factor. Make: L&T/Siemen/Entes/DJB Approved.
MCB 3 pole 50Hz 415V 32Amp. Make: L&T/Siemens/ABB/any DJB Approved.
MCB 3 pole 50Hz 415V 63Amp. Make: L&T/Siemens/any DJB Approved.
MCCB TP 250 Amp. 3 Phase 50 kA 415V with spreader. Make: L&T/Siemens/Schineder/Any DJB Approved.
Power Contactor 220V AC 32Amp Make: L&T/Siemens/Any DJB Approved.
Power Contactor 220V AC 50Amp Make: L&T/Siemens/Any DJB Approved.
Power Contactor 220V AC 70Amp Make: L&T/Siemens/Any DJB Approved.
Indicating lights R.Y.B. & ON 415V Make: Siemens/Havells/Any DJB Approved.
Sensing current transformer of suitable ratio of incomer for current sensing at site
Banking of capacitor as per site requirement
Fixing of following components of APFC panel i.e. contactor, A.P.F.C. Relay, fuse, capacitors and all measurement components, indicating lights, in their respective space in existing APFC panels duly wired, tapping, thumbling, ferruling and connection with main bus bar both in outgoing incoming part.
Replacement of static capacitor bank installed across motors and repairing of switch fuse unite fitted in capacitor bank enclosure, replacement of fuse/MCB as required, changing of control wiring with ferrule, thimble etc. (Total 120 KVAR for 3 motors)
Static capacitor panel across transformer shunt capacitors power 3 phase, 415V AC 50 Hz MPP type heavy duty 30 KVAR X2 Make: Escos/L&T/Any DJB Approved.
MCCB 100 Amp 3phase, 415V with high breaking capacity as incomer. Make: -L&T/ Schineder/Any DJB Approved
MCB 6-32 Amp. 3phase, 415V. Make: - L&T/ Schineder/ Seimens/ Any DJB Approved
Fabrication & supply of MS enclosure in 2mm CRCA sheet with base frame duly painted for fixing the capacitor unit & above mention switchgear with lockable door front opening and suitable to install at site.
Fixing of capacitor bank & above switch gears with control wiring, for ON status banking of each capacitor units as required duly connection with bus bar termination set fixed in MS enclosure connection of all terminals vice-versa.
Installation, commissioning, testing of the capacitor unit across the transformer with cable connection both incoming & outgoing with thimbling, required hardware & required civil work at site.
Testing & commissioning of the APFC Panels & setting of APFC relay to get target power factor on load & off load.
Agarwala Traders
Premier Engineering Company
stage.html
html • 0.03 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .