Loading…
Loading…
| # | Company | Amount |
|---|---|---|
| 1 | ₹100 | ₹100 |
Tender Value
₹82.4 Cr
EMD Value
₹82.4 L
Closing Date
4 Aug 2022, 11:00 amClosed
Carrying out Part Work/ Incomplete work at Risk and Cost of previous agency for the works of construction of various buildings in Phase-1(b) for IIT Bhubaneswar at Bhubaneswar and its extended campus
NBCC/CPG/IIT/BBSR/Phase_1b/2022/334
NBCC/CPG/IIT/BBSR/Phase_1b/2022/334
Open Tender-Domestic
Civil Works General
Khordha, Odisha
₹1.2 L
₹82.4 L
11 Jul 2022
11 Jul 2022
4 Aug 2022
4 Aug 2022
12 Sept 2022
S.No. Description of item Unit DSR Amount MR Amount
4 LTC Corridor
5 LTC External development
Boys Hostel External development
ANUJ NAVNEET Digitally signed by ANUJ
CHACHA Date: 2022.07.11
IIT Bhubaneswar
NBCC (INDIA) LIMITED
(A Govt. of India Enterprise)
NAME OF WORK -Carrying out Part work of Various buildings of Phase-1(b) under risk and cost of previous agency at
IIT Bhubaneswar, Argul Campus
ABSTRACT OF BOQs
Sr. No Sub Head Unit DSR-Amount NON DSR-Amount
C ELETRICAL (Internal) Rs. 3,125,295.17 63,975,434.96
D FIRE FIGHTING Rs. 25,312,566.82 7,371,869.42
G PRESENTATION & UNIFIED CONFERENCING Rs. - 113,074,896.03
LECTURE THEATRE IIT Bhubaneswar
NBCC (INDIA) LIMITED
(A Govt. of India Enterprise)
BOQ for Construction of Lecture Theater for IIT Bhubaneswar at Argul, Khurda, Odisha
DSR- DSR- NON DSR- TOTAL NON DSR-
Sr. No Sub Head Unit NON DSR-Amount DSR-Amount NON DSR-Amount NON DSR-Amount DSR-Amount NON DSR-Amount DSR-Amount TOTAL DSR-Amount
Amount Amount Amount Amount
Block-1 Block-2 Block-3 Corridor External Devlopment Total for Block -1, 2 & 3
GST / Service tax shall be extra as applicable 525,478,583.47
LECTURE THEATRE IIT Bhubaneswar
NBCC (INDIA) LIMITED
(A Govt. of India Enterprise)
BOQ for Construction of Lecture Theater Complex-2 for IIT Bhubaneswar at Argul, Khurda,
Sr. No Sub Head Unit DSR-Amount NON DSR-Amount
C ELETRICAL (Internal) Rs. 2,067,090.03 33,936,953.62
D FIRE FIGHTING Rs. - 949,619.97
PRESENTATION & UNIFIED
LECTURE THEATER BLOCK-2-CIVIL IIT Bhubaneswar
NBCC (I) LIMITED
A GOVERNMENT OF INDIA ENTERPRISE
NAME OF WORKS -CIVIL WORKS FOR IIT BHUBANESWAR,ODISHA
Summary (LECTURE THEATRE BLOCK-2)
Sno Sub Head Unit DSR-Amount NON DSR-Amount
1 SUBHEAD I-EARTH WORK Rs. 6,321,348.02 390,532.21
2 SUB HEAD II- CONCRETE WORK Rs. 3,824,094.89 -
3 SUB HEAD III- R.C.C WORK Rs. 20,118,781.15 -
4 SUB HEAD IV- BRICK WORK Rs. 11,566,269.01 -
5 SUB HEAD V- STEEL WORK Rs. 16,356,925.23 -
6 SUB HEAD VI- FLOORING WORK Rs. 61,222,603.65 35,202.97
7 SUB HEAD VII- FINISHING WORK Rs. 10,773,297.32 -
8 SUB HEAD-VIII- ALUMINIUM WORK Rs. 7,714,376.28 -
9 SUB HEAD IX- WATERPROOFING WORK Rs. 2,752,637.37 -
10 SUB HEAD X - WOOD WORK Rs. 1,056,913.71 -
11 SUB HEAD - XI-FALSE CEILING Rs. 11,024,499.84 -
SUB HEAD - X1II-GLAZING AND ALUMINIUM
12 COMPOSIT PANAL WORKS
13 SUB HEAD-XII FIRE RESISTANT DOOR Rs. 1,453,465.58 -
14 SUB HEAD-XIII-WALL LINING WORKS Rs. 8,144,746.24 -
15 SUB HEAD XIV -MISCELLANEOUS WORKS Rs. - -
16 SUB HEAD-XV NON SCHEDULE ITEMS Rs. - 30,462,444.36
GRAND TOTAL (DSR+NON DSR) Rs. 206,692,180.32
GRAND TOTAL (DSR+NON DSR) Rs. 206,692,180.32
LECTURE THEATER BLOCK-2- CIVIL IIT Bhubaneswar
NBCC (I) LIMITED
A GOVERNMENT OF INDIA ENTERPRISE
NAME OF WORKS -CIVIL WORKS FOR IIT BHUBANESWAR,ODISHA
SCHEDULE OF QUANTITIES LECTURE THEATER BLOCK-2
SI.No. DSR Description of Item Unit Total Balance DSR Rate MR RATE DSR-AMOUNT MR-AMOUNT
2014- Quantity in Quantity at which at which
Code Original to be item was item was
Tender executed awarded awarded
at Risk & in original in original
Cost tender tender
SUBHEAD I-EARTH WORK
Carriage of material by mechanical transport including loading,
unloading and stacking
Earth work in excavation by mechanical means (Hydraulic excavator)
/ manual means over areas (exceeding 30cm in depth. 1.5m in width
2 2.6 as well as 10 sqm on plan) including disposal of excavated earth, lead
upto 50m and lift upto 1.5m, disposed earth to be levelled and neatly
Earth work in excavation by mechanical means (Hydraulic excavator)
/ manual means over areas (exceeding 30 cm in depth, 1.5m in width
3 2.7 as well as 10 sqm on plan) including disposal of excavated earth, lead
upto 50 m and lift upto 1.5 m, disposed earth to be levelled and
neatly dressed.
Earth work in excavation by mechanical means (Hydraulic excavator)
/ manual means in foundation trenches or drains (not exceeding 1.5
m in width or 10 sqm on plan) including dressing of sides and
ramming of bottoms, lift up to 1.5 m, including getting out the
excavated soil and disposal of surplus excavated soil as directed,
within a lead of 50 m.
Excavation work by mechanical means (Hydraulic excavator)/ manual
means in foundation trenches or drains not exceeding 1.5m in width
or 10 sqm on plan including dressing of sides and ramming of
bottoms, lift up to 1.5 m, including getting out the excavated soil and
disposal of surplus excavated soils as directed, within a lead of 50m.
1 NBCC (I) Ltd.
LECTURE THEATER BLOCK-2- CIVIL IIT Bhubaneswar
SI.No. DSR Description of Item Unit Total Balance DSR Rate MR RATE DSR-AMOUNT MR-AMOUNT
2014- Quantity in Quantity at which at which
Code Original to be item was item was
Tender executed awarded awarded
at Risk & in original in original
Cost tender tender
Excavating trenches of required width for pipes, cables, etc including
excavation for sockets, and dressing of sides, ramming of bottoms,
depth up to 1.5 m including getting out the excavated soil, and then
6 2.10 returning the soil as required, inlayers not exceeding 20 cm in depth,
including consolidating each deposited layer by ramming, watering,
etc. and disposing of surplus excavated soil as directed, within a lead
2.10.1 All kinds of soil
2.10.1.1 Pipes, cables etc, not exceeding 80 mm dia. Mtr 475.00 475.00 134.14 63716.37
Pipes, cables etc, not exceeding 80 mm dia. Pipes, cables etc.
exceeding 80 mm dia. but not exceeding 300 mm dia.
Pipes, cables etc. exceeding 300 mm dia but not exceeding 600 mm.
Extra for excavating trenches for pipes, cables etc. in all kinds of soil
for depth exceeding 1.5 m, but not exceeding 3 m. (Rate is over
corresponding basic item for depth up to 1.5 metre).
a Pipes, cables etc, not exceeding 80 mm dia. Mtr 375.00 375.00 182.43 68411.26
Pipes, cables etc, not exceeding 80 mm dia. Pipes, cables etc.
b exceeding 80 mm dia. but not exceeding 300 mm dia. Mtr 305.00 305.00 297.69 90795.56
Pipes, cables etc. exceeding 300 mm dia but not exceeding 600 mm.
Extra for excavating trenches for pipes, cables, etc, in all kinds of soil
for depth exceeding 3 m in depth, but not exceeding 4.5 m. (Rate is
over corresponding basic item for depth up to 1.5 metre.)
a Pipes, cables etc, not exceeding 80 mm dia. Mtr 395.00 395.00 468.15 184918.32
Pipes, cables etc, not exceeding 80 mm dia. Pipes, cables etc.
exceeding 80 mm dia. but not exceeding 300 mm dia.
Pipes, cables etc. exceeding 300 mm dia but not exceeding 600 mm.
Excavating trenches of required width for pipes, cables, etc, including
excavation for sockets, depth up to 1.5 m including getting out the
excavated materials, returning the soil as required in layers not
9 2.13 exceeding 20 cm in depth, including consolidating each deposited
layers by ramming, watering etc., stacking serviceable material for
measurements and disposal of unserviceable material as directed,
within a lead of 50m :
2.13.1 Ordinary rock :
2.13.1.1 Pipes, cables etc, not exceeding 80 mm dia. Mtr 305.00 305.00 191.10 58284.05
Pipes, cables etc, not exceeding 80 mm dia. Pipes, cables etc.
exceeding 80 mm dia. but not exceeding 300 mm dia.
Pipes, cables etc. exceeding 300 mm dia but not exceeding 600 mm.
2 NBCC (I) Ltd.
LECTURE THEATER BLOCK-2- CIVIL IIT Bhubaneswar
SI.No. DSR Description of Item Unit Total Balance DSR Rate MR RATE DSR-AMOUNT MR-AMOUNT
2014- Quantity in Quantity at which at which
Code Original to be item was item was
Tender executed awarded awarded
at Risk & in original in original
Cost tender tender
Extra for excavating trenches for pipes, cables, etc. in ordinary/hard
rock exceeding 1.5 m in depth but not exceeding 3 m. (Rate is over
corresponding basic item for depth up to 1.5 metre.)
a Pipes, cables etc, not exceeding 80 mm dia. Mtr 205.00 205.00 202.56 41525.00
Pipes, cables etc, not exceeding 80 mm dia. Pipes, cables etc.
b exceeding 80 mm dia. but not exceeding 300 mm dia. Mtr 185.00 185.00 501.58 92793.20
c Pipes, cables etc. exceeding 300 mm dia but not exceeding 600 mm. Mtr 165.00 165.00 577.16 95231.78
Extra for excavating trenches for pipes, cables, etc. in ordinary/hard
rock exceeding 3m in depth but not exceeding 4.5 m. (Rate is over
corresponding basic item for depth up to 1.5 metre.)
a Pipes, cables etc, not exceeding 80 mm dia. Mtr 180.00 180.00 504.49 90808.46
Pipes, cables etc, not exceeding 80 mm dia. Pipes, cables etc.
exceeding 80 mm dia. but not exceeding 300 mm dia.
Pipes, cables etc. exceeding 300 mm dia but not exceeding 600 mm.
Close timbering over areas including strutting,shoring and
12 2.18 packing,cavities (whereaver required) etc.complete. (Measurements
to be taken of the area timbered) :
2.18.1 Depth not exceeding 1.5 m. Sqm 90.00 90.00 100.99 9088.72
2.18.2 Depth not exceeding 1.5 m but not exceeding 3m. Sqm 85.00 85.00 108.29 9204.57
2.18.3 Depth not exceeding 3 m but not exceeding 4.5m. Sqm 105.00 105.00 116.12 12192.37
Filling available excavated earth (excluding rock) in trenches, plinth,
sides of foundations etc. in layers not exceeding 20cm in depth,
consolidated each deposited layer by ramming and watering, lead up
to 50m and lift upto 1.5m.
Extra for every additional lift of 1.5m or part thereof in excavation/
banking excavated or stacked materials.
Supplying and filling in plinth with Jamuna sand under floors,
watering, ramming, consolidating and dressing complete.
Surface dressing of the ground including removing vegetation and
16 2.28 inequalities not exceeding 15 cm deep and disposal of rubbish, lead
upto 50 m and lift upto 1.5 m.
2.28.1 All kinds of soil 100 sqm 10.00
Ploughing the existing ground to a depth of 15 cm to 25 cm and
watering the same.
2.29.1 All kinds of soil 100 sqm
3 NBCC (I) Ltd.
LECTURE THEATER BLOCK-2- CIVIL IIT Bhubaneswar
SI.No. DSR Description of Item Unit Total Balance DSR Rate MR RATE DSR-AMOUNT MR-AMOUNT
2014- Quantity in Quantity at which at which
Code Original to be item was item was
Tender executed awarded awarded
at Risk & in original in original
Cost tender tender
Felling trees of the girth (measured at a height of 1 m above ground
level) including cutting of trunks and branches, removing the roots
and stacking of serviceable material and disposal of unserviceable
2.33.1 Beyond 30 cm girth upto and including 60 cm girth each 8.00 8.00 206.70 1653.60
2.33.2 Beyond 60 cm girth upto and including 120 cm girth each 6.00 6.00 915.39 5492.32
2.33.3 Beyond 120 cm girth upto and including 240 cm girth each 4.00 4.00 4233.89 16935.55
Supplying chemical emulsion in sealed containers including delivery
19 2.34 as specified.
2.34.1 Chlorpyriphos/ Lindane emulsifiable concentrate of 20% litre 7120.00 7120.00 195.40 1391274.33
Diluting and injecting chemical emulsion for PRE/POST
20 CONSTRUCTIONAL anti-termite treatment (excluding the cost of
chemical emulsion) :
Along external wall where the apron is not provided using chemical
emulsion @ 7.5 litres / sqm of the vertical surface of the substructure
(i) to a depth of 300 mm including excavation channel along the wall &
rodding etc. complete:
With Chlorpyriphos/ Lindane E.C. 20% with 1% concentration
Treatment of soil under floors using chemical emulsion @ one litre
Rate per hole, 300 mm apart including making 12 mm diameter holes and
Analysis channels etc. complete as per specification and as per the direction of
engineer-in-charge.
(i) With Chlorpyriphos/Lindane E.C. 20% with 1% concentration Sqm 4825.00 4825.00 80.08 386407.79
Treatment at points of contact of wood work by chemical emulsion
Chlorpyriphos/ Lindane (in oil or kerosene based solution) @ 0.5litres
22 2.35.5 per hole by drilling 6 mm dia holes at downward angle of 45degree at Sqm 3312.00 3312.00 210.90 698512.68
150 mm centre to centre and sealing the same.
TOTAL FOR SUB HEAD - I 6321348.02 390532.21
SUB HEAD II- CONCRETE WORK
Providing and laying in position cement concrete of specified grade
1 4.1 excluding the cost of centering and shuttering - All work up to plinth
1:2:4(1 Cement : 2 coarse sand : 4 graded stone aggregate 20mm
1:4:8 (1 Cement : 4 coarse sand : 8 graded stone aggregate 40 mm
4 NBCC (I) Ltd.
LECTURE THEATER BLOCK-2- CIVIL IIT Bhubaneswar
SI.No. DSR Description of Item Unit Total Balance DSR Rate MR RATE DSR-AMOUNT MR-AMOUNT
2014- Quantity in Quantity at which at which
Code Original to be item was item was
Tender executed awarded awarded
at Risk & in original in original
Cost tender tender
Providing and laying cement concrete in retaining walls, return walls,
walls (any thickness) including attached pilasters, columns, piers,
abutments, pillars, posts, struts, buttresses, string or lacing courses,
2 4.2 parapets, coping, bed blocks, anchor blocks, plain windowsills, fillets,
sunken floor, etc., up to floor five level, excluding the cost of
centering, shuttering and finishing :
1:2:4 (1 cement:2coarse sand:4 graded stone aggregate 20 mm
Providing and laying damp-proof course 40 mm thick with cement
3 4.10 concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate sqm 315.00 315.00 270.91 85335.56
12.5 mm nominal size).
Extra for providing and mixing water proofing material in cement
concrete work in doses by weight of cement as per manufacturer’s
Applying a coat of residual petroleum bitumen of grade of VG-10 of
approved quality using 1.7 kg per square metre on damp proof course
after cleaning the surface with brushes and finally with a piece of
cloth lightly soaked in kerosene oil.
Making plinth protection 50 mm thick of cement concrete 1:3:6 (1
coarse sand : 6 graded stone aggregate 20 mm nominal size) over
75mm thick bed of dry brick ballast 40 mm nominal size, well
rammed and consolidated and grouted with fine sand, including
finishing the top
Extra for addition of synthetic Polyester triangular fibre of length
12mm,effective diameter 10-40 microns and specific gravity of 1.34
to 1.40 in cement. concrete/RCC/Flooring/water retaining
7 4.18 structures by using Per Bag of 125gms of synthetic Polyester 1390.00 1390.00 55.69 77415.38
triangular fibre for 50 Kg cement used 50 Kg of as per directions of
Engineer-in-Charge.(For water retaining structures only)
TOTAL FOR SUB HEAD II 3824094.89
SUB HEAD III- R.C.C WORK
Reinforced cement concrete work in beams, suspended floors, roofs
having slope up to 15° landings, balconies, shelves, chajjas, lintels,
bands, plain window sills, staircases and spiral stair cases up to floor
1 5.3 five level excluding the cost of centering, shuttering, finishing and Cum 175.00 175.00 7122.80 1246490.65
reinforcement with 1:2:4 (1 cement : 2 coarse sand : 4 graded stone
aggregate 20 mm nominal size).
5 NBCC (I) Ltd.
LECTURE THEATER BLOCK-2- CIVIL IIT Bhubaneswar
SI.No. DSR Description of Item Unit Total Balance DSR Rate MR RATE DSR-AMOUNT MR-AMOUNT
2014- Quantity in Quantity at which at which
Code Original to be item was item was
Tender executed awarded awarded
at Risk & in original in original
Cost tender tender
Centering and shuttering including strutting, propping etc. and
2 5.9 removal of form for : Foundations, footings, bases of columns, etc. for
Foundations, footings, bases of columns, etc. for mass concrete.
Walls (any thickness) including attached pilasters, butteresses, plinth
and string courses etc.
Suspended floors, roofs, landings, balconies and access platform.
5.9.4 Shelves (Cast in situ) Sqm 20.15 20.15 422.07 8504.71
Lintels, beams, plinth beams, girders, bressumers and cantilevers.
5.9.6 Columns, Pillars, Piers, Abutments, Posts and Struts. Sqm 3343.00 500.00 476.40 238199.16
5.9.7 Stairs, (excluding landings) except spiral-staircases. Sqm 130.60 46.71 415.76 19422.04
Extra for shuttering in circular work (20% of respective centering and
shuttering items).
Suspended floors, roofs, landings, balconies and access platform.
Lintels, beams, plinth beams, girders, bressumers and cantilevers.
c Columns, Pillars, Piers, Abutments, Posts and Struts. Sqm 1008.65 158.82 95.28 15131.84
Small lintels not exceeding 1.5m clear span, moulding as in cornices,
5.9.15 window sills, string courses, bands, copings, bed plates, anchor Sqm 265.00 265.00 206.44 54705.94
blocks and the like.
5.9.16 Edges of slabs and breaks in floors and walls.
5.9.17 Cornices and mouldings Sqm 284.00 284.00 577.12 163902.46
Small surfaces such as cantilever ends, brackets and ends of steps,
caps and bases to pilasters and columns and the like.
5.9.19 Weather shade, Chajjas, corbels etc., including edges. Sqm 250.00 134.94 517.38 69813.85
Providing and fixing tie bolt, spring coil and plastic cone in wall
shuttering complete as per the directions if engineer-in charge
20mm dia & 225 mm length
Extra for additional height in centering, shuttering where ever
required with adequate bracing, propping etc. including cost of de-
4 5.11 shuttering and decentering at all levels, over a height of 3.5 m, for
every additional height of 1 metre or part thereof
(Plan area to be measured)
Suspended floors, roofs, landing, beams and balconies (Plan area to
6 NBCC (I) Ltd.
LECTURE THEATER BLOCK-2- CIVIL IIT Bhubaneswar
SI.No. DSR Description of Item Unit Total Balance DSR Rate MR RATE DSR-AMOUNT MR-AMOUNT
2014- Quantity in Quantity at which at which
Code Original to be item was item was
Tender executed awarded awarded
at Risk & in original in original
Cost tender tender
Steel reinforcement for R.C.C. work including straightening, cutting,
6 5.22 bending, placing in position and binding all complete up to plinth
5.22.6 Thermo-Mechanically Treated bars. Kg 162500.00 54236.30 71.56 3881269.27
Steel reinforcement for R.C.C. work including straightening, cutting,
5.22A bending, placing in position and binding all complete above plinth
5.22A.6 Thermo-Mechanically Treated bars. Kg 383000.00 15000.00 71.56 1073433.06
Add for plaster drip course/ groove in plastered surface or moulding
to R.C.C. projections.
Providing and laying in position machine batched and machine mixed
design mix M-25 grade cement concrete for reinforced cement
concrete work, using cement content as per approved design mix,
including pumping of concrete to site of laying but excluding the cost
of centering, shuttering, finishing and reinforcement, including
admixtures in recommended proportions as per IS: 9103 to
8 5.33 accelerate, retard setting of concrete, improve workability without
impairing strength and durability as per direction of Engineer-in-
charge. (Note :- Cement content considered in this item is @ 330
kg/cum.“Excess/ less cement used as per design mix is
payable/recoverable separately).
5.33.1 All works up to plinth level. cum 759.60 50.00 6616.25 330812.31
5.33.2 All works above plinth level up to floor V level. cum 3320.97 1028.33 7371.17 7579963.91
Extra for providing richer mixes at all floor levels. (Note :- Cement
content considered in this item is @ 330 kg/cum.“Excess/ less
cement used as per design mix is payable/recoverable separately).
Providing M-30 grade concrete instead of M-25 grade BMC/RMC.
5.34.1 (Note:- Cement content considered in M-30 is @340 kg/cum). cum 4080.57 1028.33 80.39 82666.69
Add for using extra cement in the items of design mix over and above
the specified cement content therein.
TOTAL FOR SUB HEAD III 20118781.15
SUB HEAD IV- BRICK WORK
Brick work with common burnt clay F.P.S. (non modular) bricks of
class designation 7.5 in foundation and plinth in:
6.1.2 Cement mortar 1:6 (1 cement : 6 coarse sand) Cum 84.00 84.00 4915.04 412863.48
7 NBCC (I) Ltd.
LECTURE THEATER BLOCK-2- CIVIL IIT Bhubaneswar
SI.No. DSR Description of Item Unit Total Balance DSR Rate MR RATE DSR-AMOUNT MR-AMOUNT
2014- Quantity in Quantity at which at which
Code Original to be item was item was
Tender executed awarded awarded
at Risk & in original in original
Cost tender tender
Extra for providing and placing in position 2 Nos. 6mm dia. M.S. bars
at every third course of half brick masonry.
Brick work with clay fly ash F.P.S. (non modular) brick of class
3 6.32 designation 7.5 in superstructure above plinth level up to floor five
6.32.2 Cement mortar 1:6 (1 cement : 6 coarse sand) Cum 68.50 68.50 5733.23 392725.94
Providing and laying autoclaved aerated cement blocks masonry with
100mm thick AAC blocks in super structure above plinth level up to
4 6.38 floor V level in cement mortar 1:4 (1 cement : 4 coarse sand ) The cum 2051.50 1489.90 6711.66 9999682.81
rate includes providing and placing in position 2 Nos. 6 mm dia M.S.
bars at every third course of masonry work.
Half brick masonry with non modular fly ash bricks class designation
5 6.45 10, conforming to IS : 12894, in super structure above plinth and sqm 882.50 882.50 789.29 696544.83
upto floor V level.
6.45.2 Cement mortar 1:4 (1 cement :4 coarse sand)
TOTAL FOR SUB HEAD IV 11566269.01
SUB HEAD V- STEEL WORK
Structural steel work in single section, fixed with or without
connecting plate, including cutting, hoisting, fixing in position and
applying a priming coat of approved steel primer all complete.
Structural steel work riveted, bolted or welded in built up sections,
trusses and framed work, including cutting, hoisting, fixing in
position and applying a priming coat of approved steel primer all
Providing and fixing 1mm thick M.S. sheet door with frame of
40x40x6mm angle iron and 3mm M.S. gusset plates at the junctions
3 10.5 and corners, all necessary fittings complete, including applying a
priming coat of approved steel primer.
10.5.1 Using M.S. angels 40x40x6 mm for diagonal braces. sqm 2.35 2.35 3230.12 7590.79
Providing and fixing pressed steel door frames conforming to IS:
4351 manufactured from commercial mild steel sheet of 1.60 mm
thickness including hinges, jamb, lock jamb, bead and if required
angle threshold of mild steel angle of section 50x25mm, or base ties
of 1.60 mm pressed mild steel welded or rigidly fixed together by
mechanical means, including M.S. pressed butt hinges, 2.5mm thick
with mortar guards, lock strike-plate and shock absorbers as specified
and applying a coat of approved steel primer after pre-treatment of
the surface as directed by Engineer-in-charge:
10.14.3 Profile E
8 NBCC (I) Ltd.
LECTURE THEATER BLOCK-2- CIVIL IIT Bhubaneswar
SI.No. DSR Description of Item Unit Total Balance DSR Rate MR RATE DSR-AMOUNT MR-AMOUNT
2014- Quantity in Quantity at which at which
Code Original to be item was item was
Tender executed awarded awarded
at Risk & in original in original
Cost tender tender
Fixing with carbon steel galvanised dash fastener of required dia and
10.14.3.2 size (to be paid for separately). Mtr 128.00 128.00 437.04 55941.68
Steel work in built up tubular (round, square or rectangular hollow
tubes etc.) trusses etc., including cutting, hoisting, fixing in position
5 10.16 and applying a priming coat of approved steel primer, including
welding and bolted with special shaped washers etc. complete.
10.16.1 Hot finished welded type tubes Kg 95500.00 94089.13 108.13 10173992.74
Providing and fixing M.S. fan clamp type I or II of 16 mm dia M.S. bar
bent to shape with hooked ends in R.C.C. slabs, beams during laying
including painting the exposed portion of loop, all as per standard
design complete.
7 10.20 Providing and fixing bolts including nuts and washers complete. kg 4775.00 4775.00 103.25 492995.02
Steel work welded in built up sections/ framed work including cutting,
8 10.25 hoisting, fixing in position and applying a priming coat of approved
steel primer using structural steel etc. as required.
In gratings, frames, guard bar, ladder, railings, brackets, gates and
Providing and fixing carbon steel galvanised ( minimum coating 5
micron) dash fastener of 10 mm dia double threaded 6.8 grade (yield
8 10.27 480 N/mm2), counter sunk head, comprising of 10 m dia polyamide
PA 6 grade sleeve, including drilling of hole in frame , concrete/
masonry, etc.as per direction of Engineer-in-Charge
Providing and fixing stainless steel ( Grade 304) railing made of
Hollow tubes, channels, plates etc. including welding, grinding,
buffing, polishing and making curvature (wherever required) and
fitting the same with necessary stainless steel nuts and bolts
complete i/c fixing the railing with necessary accessories & stainless
9 10.28 steel dash fasteners , stainless steel bolts etc., of required size, on Kg 5028.00 5028.00 650.89 3272676.41
the top of the floor or the side of waist slab with suitable arrangement
as per approval of Engineer-in-charge.( for payment purpose only
weight of stainless steel members shall be considered excluding fixing
accessories such as nuts, bolts, fasteners etc.)
TOTAL FOR SUB HEAD V 16356925.23
SUB HEAD VI- FLOORING WORK
9 NBCC (I) Ltd.
LECTURE THEATER BLOCK-2- CIVIL IIT Bhubaneswar
SI.No. DSR Description of Item Unit Total Balance DSR Rate MR RATE DSR-AMOUNT MR-AMOUNT
2014- Quantity in Quantity at which at which
Code Original to be item was item was
Tender executed awarded awarded
at Risk & in original in original
Cost tender tender
Stone work (machine cut edges) for wall lining etc. (veneer work)
upto 10 metre height, backing filled with a grout of average 12 mm
thick cement mortar 1:3 (1 cement : 3 coarse sand) including
1 7.23 pointing in white cement mortar 1:2 (1 white cement : 2 stone dust)
with an admixture of pigment matching the stone shade : (To be
secured to the backing and the sides by means of cramps and pins
sand be paid- for
stone separately)
face machine cut and table rubbed with
Providing and fixing stainless steel cramps of required size and shape
for anchoring stone wall lining to the backing or securing adjacent
2 7.25 stones in stone wall lining in cement mortar 1:2 (1 cement : 2 coarse Kg 285.00 285.00 603.87 172101.58
sand) including making the necessary chases in stone and holes in
walls wherever required.
Providing and fixing copper pins 7.5 cm long 6 mm diameter for
securing adjacent stones in stone wall lining in cement mortar 1:2
(1cement : 2 coarse sand) including making the necessary chases.
Extra for stone work for wall lining on exterior walls of height more
4 7.39 than 10 m from ground level for every additional height of 3 m or sqm 1050.00 1050.00 87.59 91966.89
Providing and fixing structural steel frame (for dry cladding with 30
mm thick gang saw cut with machine cut edges sand stone) on walls
at all heights using M.S. square / rectangular tube in the required
pattern as per architectural drawing, including cost of cutting,
bending, welding etc. The frame work shall be fixed to the wall with
the help of MS brackets / lugs of angle iron / flats etc. which shall
be welded to the frame and mbedded in brick wall with cement
concrete block 1:2:4 (1 cement : 2 coarse sand : 4 graded stone
aggregate 20 mm nominal size) of size 300x230x300 mm, including
cost of necessary centring and shuttering and with approved
expansion hold fasteners on CC/RCC surface, including drilling
necessary holes. Approved cramps / pins etc. shall be welded to the
frame work to support stone cladding, the steel work will be given a
priming coat of Zinc primer as approved by Engineer-in-Charge and
painted with two or more coats of epoxy paint (Shop drawings shall
be submitted by the contractor to the Engineer-in-Charge for
approval before execution). The frame work shall be fixed in true
horizontal & vertical lines/planes. (Only structural steel frame work
shall be measured for the purpose of payment, stainless steel cramps
shall be paid for separately and nothing extra shall be paid.)
10 NBCC (I) Ltd.
LECTURE THEATER BLOCK-2- CIVIL IIT Bhubaneswar
SI.No. DSR Description of Item Unit Total Balance DSR Rate MR RATE DSR-AMOUNT MR-AMOUNT
2014- Quantity in Quantity at which at which
Code Original to be item was item was
Tender executed awarded awarded
at Risk & in original in original
Cost tender tender
Providing & Fixing adjustable stainless steel cramps of approved
quality ,required shap & size ,adjustable with stainless steel nuts
,bolts and washer (total wieght less then 260 gms )for dry stone fixed
5 7.42 on frame work at suitaable lacation , including making necessary each 33910.00 33910.00 216.63 7345945.88
recesses in stone slab ,drilling reqired holes ect complete as per
direction of the Engineer-in-charge.with stainless steel nuts and bolts
Providing and fixing 18mm thick gang saw cut mirror polished
premoulded and prepolished) machine cut for kitchen platforms,
vanity counters, window sills , facias and similar locations of required
size of approved shade, colour and texture laid over 20mm thick base
6 8.2 cement mortar 1:4 (1 cement : 4 coarse sand) with joints treated
with white cement, mixed with matching pigment, epoxy touch ups,
including rubbing, curing, moulding and polishing to edges to give
high gloss finish etc. complete at all levels.
8.2.2 Granite of any colour and shade
Providing edge moulding to 18mm thick marble/Granite stone
counters, Vanities etc. including machine polishing to edge to give
7 8.3 high gloss finish etc. complete as per design approved by Engineer-in-
Extra for fixing marble /granite stone over and above corresponding
basic item, in facia and drops of width upto 150 mm with epoxy resin
based adhesive including cleaning etc. complete.
Extra for providing opening of required size & shape for wash basins/
kitchen sink in kitchen platform, vanity counters and similar location
9 8.5 in marble/Granite/stone work including necessary holes for pillar taps Each 40.00 40.00 406.25 16250.19
etc. including moulding, rubbing and polishing of cut edges etc.
Providing and fixing stone slab table rubbed, edges rounded and
polished of size 75x50 cm deep and 1.8 cm thick fixed in urinal
partitions by cutting a chase of appropriate width with chase cutter
10 8.10 and embedding the stone in the chase with epoxy grout or with
cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone
aggregate 6mm nominal size) as per direction of Engineer-in-charge
8.10.2 Granite Stone of approved shade. Sqm 48.50 48.50 3429.42 166326.69
11 NBCC (I) Ltd.
LECTURE THEATER BLOCK-2- CIVIL IIT Bhubaneswar
SI.No. DSR Description of Item Unit Total Balance DSR Rate MR RATE DSR-AMOUNT MR-AMOUNT
2014- Quantity in Quantity at which at which
Code Original to be item was item was
Tender executed awarded awarded
at Risk & in original in original
Cost tender tender
Providing and laying flamed finish Granite stone flooring in required
design and patterns, in linear as well as curvilinear portions of the
building all complete as per the architectural drawings with 18 mm
11 8.12 thick stone slab over 20 mm (average) thick base of cement mortar
1:4 (1 cement : 4 coarse sand) laid and jointed with cement slurry
and pointing with white cement slurry admixed with pigment of
matching shade including rubbing, curing and polishing etc. all
complete as specified
Flamed finish granite and as slab
stone directed by the Cherry
Jet Black, Engineer-in-Charge :
Red, Elite Brown,
Cat Eye or equivalent.
Kota stone slab flooring over 20 mm (average) thick base laid over
and jointed with grey cement slurry mixed with pigment to match the
shade of the slab including rubbing and polishing complete with base
of cement mortar 1 : 4 (1 cement : 4 coarse sand) :
Kota stone slabs 20 mm thick in risers of steps, skirting, dado and
pillars laid on 12 mm (average) thick cement mortar 1:3 (1 cement
13 11.27 3coarse sand) and jointed with grey cement slurry mixed with Sqm 99.60 99.60 1251.81 124680.59
pigment to match the shade of the slabs, including rubbing and
polishing complete.
Extra for pre finished nosing in treads of steps of Kota stone/ sand
Rate Extra for Kota stone/ sand stone in treads of steps and risers
15 using single length up to 1500 mm completed as per drawing. Sqm 182.65 182.65 192.73 35202.97
Providing and fixing Ist quality ceramic glazed wall tiles conforming
to IS : 15622 (thickness to be specified by the manufacturer ) of
approved make in all colours, shades except burgundy, bottle green,
black of any size as approved by Engineer-in-Charge, in skirting,
16 11.36 risers of steps and dados over 12 mm thick bed of cement Mortar 1:3 Sqm 821.00 821.00 879.19 721811.12
(1 cement : 3 coarse sand) and jointing with grey cement slurry @
3.3kg per sqm including pointing in white cement mixed with pigment
of matching shade complete.
Providing and laying rectified Glazed Ceramic floor tiles 300x300 mm
or more (thickness to be specified by the manufacturer) of 1st quality
conforming to IS : 15622 of approved make in all colours, shades,
except White, Ivory, Grey, Fume Red Brown, laid on 20 mm thick
Cement Mortar 1:4 (1 Cement : 4 Coarse sand) including pointing the
joints with white cement and matching pigments etc., complete.
12 NBCC (I) Ltd.
LECTURE THEATER BLOCK-2- CIVIL IIT Bhubaneswar
SI.No. DSR Description of Item Unit Total Balance DSR Rate MR RATE DSR-AMOUNT MR-AMOUNT
2014- Quantity in Quantity at which at which
Code Original to be item was item was
Tender executed awarded awarded
at Risk & in original in original
Cost tender tender
Providing and laying vitrified floor tiles in different sizes (thickness to
be specified by the manufacturer) with water absorption's less than
0.08%and conforming to IS : 15622 of approved make in all colours
and shades, laid on 20mm thick cement mortar 1:4 (1 cement : 4
coarse sand) including grouting the joints with white cement and
matching pigments etc., complete.
Providing and laying Vitrified tiles in different sizes (thickness to be
specified by manufacturer) with water absorption less than 0.08 %
and conforming to I.S. 15622, of approved make in all colours &
19 11.46 shade in skirting, riser of steps, over 12 mm thick bed of cement
mortar 1:3 (1cement: 3 coarse sand), including grouting the joint
with white cement &matching pigments etc. complete.
20 16.30 Supplying and stacking at site.
16.3.4 Over burnt (Jhama) brick aggregate 120 mm to 40 mm. Cum 25.00 25.00 690.51 17262.67
16.3.5 Over burnt (Jhama) brick aggregate 90 mm to 45 mm. Cum 27.53 27.53 714.94 19685.13
Laying water bound macadam sub-base with brick aggregate and
blinding material, earth etc. including screening, sorting and
16.5 spreading to template and consolidation with light power road-roller
etc. complete.(payment for brick aggregate and moorum etc. to be
made separately)
16.5.1 Over burnt (Jhama) brick aggregate 120 mm to 40 mm. Cum 41.50 41.50 345.31 14330.20
16.5.2 Over burnt (Jhama) brick aggregate 90 mm to 45 mm. Cum 45.00 45.00 345.31 15538.77
Supplying, stacking and Spreading 6 mm thick red bajri, watering
21 16.6 and rolling complete including preparation of the surface and rolling.
16.6.1 With road roller/ hand roller. Sqm 1935.00 1935.00 15.66 30297.29
TOTAL FOR SUB HEAD VI 61222603.65 35202.97
SUB HEAD VII- FINISHING WORK
1 13.1 12 mm cement plaster of mix :
15 mm cement plaster on the rough side of single or half brick wall of
18 mm cement plaster in two coats under layer 12 mm thick cement
plaster 1:5 (1 cement: 5 coarse sand) and a top layer 6mm thick
cement plaster 1:3 (1 cement: 3 coarse sand) finished rough with
13 NBCC (I) Ltd.
LECTURE THEATER BLOCK-2- CIVIL IIT Bhubaneswar
SI.No. DSR Description of Item Unit Total Balance DSR Rate MR RATE DSR-AMOUNT MR-AMOUNT
2014- Quantity in Quantity at which at which
Code Original to be item was item was
Tender executed awarded awarded
at Risk & in original in original
Cost tender tender
4 13.16 6 mm cement plaster of mix :
Extra for plastering exterior walls of height more than 10 m from
level for every additional height of 3 m or part thereof.
Extra for plastering on circular work not exceeding 6 m in radius:
White washing with lime to give an even shade: (For lift shaft
,Electrical room , Store Rooms& machine Room)
13.37.1 New work (three or more coats) Sqm 450.00 450.00 17.02 7660.62
Distempering with oil bound washable distemper of approved brand
and manufacture to give an even shade
New work (two or more coats) over and including water thinnable
priming coat with cement primer.
13.45 Finishing walls with textured exterior paint of required shade :
New work (Two or more coats applied @ 3.28 ltr/10 sqm) over and
9 13.45.1 including priming coat of exterior primer applied @2.20kg/10 sqm. Sqm 3485.00 3485.00 153.90 536325.88
Finishing with Deluxe Multi surface paint system for interiors and
exteriors using Primer as per manufacturers specifications :
Painting wood work with Deluxe Multi Surface Paint of required
shade. Two or more coat applied @ 0.90 ltr/10 sqm over an under
coat of primer applied @0.75 ltr/ 10 sqm of approved brand or
Finishing with Epoxy paint (two or more coats) at all locations
prepared and applied as per manufacturer's specifications including
appropriate priming coat, preparation of surface, etc. complete.
Painting (two or more coats) on rain water, soil, waste and vent pipes
and fittings with synthetic enamel paint of approved brand and
manufacture and required colour over a priming coat of approved
steel primer on new work.
Painting with synthetic enamel paint of approved brand and
manufacture of required colour to give an even shade :
Two or more coats on new work over an under coat of suitable shade
13.62.1 with ordinary paint of approved brand and manufacture sqm 56.00 56.00 111.65 6252.50
14 NBCC (I) Ltd.
LECTURE THEATER BLOCK-2- CIVIL IIT Bhubaneswar
SI.No. DSR Description of Item Unit Total Balance DSR Rate MR RATE DSR-AMOUNT MR-AMOUNT
2014- Quantity in Quantity at which at which
Code Original to be item was item was
Tender executed awarded awarded
at Risk & in original in original
Cost tender tender
Lettering with black Japan paint of approved brand and manufacture per
Extra for addition of synthetic Polyester triangular fibre of length
6mm, effective diameter 10-40 microns and specific gravity of 1.34 to Per bag
12 13.79 1.40 in cement plaster/mortar by using 125gms. of synthetic of 50 kg 1920.00 1920.00 61.00 117122.42
Polyester triangular fibre for 50 Kgs. cement used in cement mortar cement
as per directions of Engineer-in-Charge
Providing and applying white cement based putty of average
thickness 1 mm, of approved brand and manufacturer, over the
plastered wall surface to prepare the surface even and smooth
TOTAL FOR SUB HEAD VII 10773297.32
SUB HEAD-VIII- ALUMINIUM WORK
Providing and fixing aluminium work for doors, windows, ventilators
and partitions with extruded built up standard tubular
sections/appropriate Z sections and other sections of approved make
conforming to IS: 733 and IS: 1285, fixing with dash fasteners of
required dia and size, including necessary filling up the gaps at
junctions, i.e. at top, bottom and sides with required EPDM
1 21.1 rubber/neoprene gasket etc. Aluminium sections shall be smooth,
rust free, straight, mitred and jointed mechanically wherever required
including cleat angle, Aluminium snap beading for glazing / paneling,
C.P. brass/ stainless steel screws, all complete as per architectural
drawings and the directions of Engineer-in-charge. (Glazing, paneling
and dash fasteners to be paid for separately) :
21.1.1 For fixed portion
Anodised aluminium (anodised transparent or dyed to required shade
21.1.1.1 according to IS: 1868, Minimum anodic coating of grade AC 15) Kg 3620.00 3620.00 366.22 1325708.22
For shutters of doors, windows & ventilators including providing and
fixing hinges/ pivots and making provision for fixing of fittings
wherever required including the cost of EPDM rubber / neoprene
gasket required (Fittings shall be paid for separately).
Anodised aluminium (anodised transparent or dyed to required shade
21.1.2.1 according to IS: 1868, Minimum anodic coating of grade AC 15) kg 1715.70 1715.70 426.54 731807.74
15 NBCC (I) Ltd.
LECTURE THEATER BLOCK-2- CIVIL IIT Bhubaneswar
SI.No. DSR Description of Item Unit Total Balance DSR Rate MR RATE DSR-AMOUNT MR-AMOUNT
2014- Quantity in Quantity at which at which
Code Original to be item was item was
Tender executed awarded awarded
at Risk & in original in original
Cost tender tender
Providing and fixing glazing in aluminium door, window, ventilator
shutters and partitions etc. with EPDM rubber / neoprene gasket etc.
3 21.3 complete as per the architectural drawings and the directions of
engineer-in-charge . (Cost of aluminium snap beading shall be paid in
21.3.1 With float glass panes of 4.0 mm thickness Sqm 25.00 25.00 870.88 21772.09
Providing and fixing double action hydraulic floor spring of approved
brand and manufacture conforming to IS : 6315, having brand logo
embossed on the body / plate with double spring mechanism and
door weight upto 125 kg, for doors, including cost of cutting floors,
21.4 embedding in floors as required and making good the same matching
to the existing floor finishing and cover plates with brass pivot and
single piece M.S. sheet outer box with slide plate etc. complete as per
the direction of Engineer-in-charge.
21.4.1 With stainless steel cover plate minimum 1.25 mm thickness each 10.00 10.00 2142.66 21426.63
Filling the gap in between aluminium frame & adjacent RCC/ Brick/
Stone work by providing weather silicon sealant over backer rod of
approved quality as per architectural drawings and direction of
Engineer-in-charge complete.
21.8.1 Upto 5mm depth and 5 mm width Rmt 1947.00 1947.00 93.26 181581.21
Providing and fixing aluminium tubular handle bar 32 mm outer dia,
5 21.12 3.0 mm thick & 2100 mm long with SS screws etc .complete as per
direction of Engineer-in-Charge.
21.12.1 Anodized (AC 15 ) aluminium tubular handle bar Each 4.00 4.00 486.54 1946.16
Providing and fixing 100mm brass locks (best make of approved
6 21.13 quality) for aluminium doors including necessary cutting and making Each 2.00 2.00 439.93 879.87
good etc. complete.
Providing and fixing anodised aluminium (anodised transparent or
dyed to required shade according to IS: 1868. Minimum anodic
coating of grade AC 15) sub frame work for windows and ventilators
7 21.14 with extruded built up standard tubular sections of approved make Kg 3068.00 3068.00 328.07 1006525.66
conforming to IS: 733 and IS: 1285, fixed with dash fastener of
required dia and size (Dash fastener to be paid for separately).
(Aluminium section 50x25*3.2)
16 NBCC (I) Ltd.
LECTURE THEATER BLOCK-2- CIVIL IIT Bhubaneswar
SI.No. DSR Description of Item Unit Total Balance DSR Rate MR RATE DSR-AMOUNT MR-AMOUNT
2014- Quantity in Quantity at which at which
Code Original to be item was item was
Tender executed awarded awarded
at Risk & in original in original
Cost tender tender
Providing and fixing anodised aluminium grill /louver (anodised
transparent or dyed to required shade according to IS: 1868 with
minimum anodic coating of grade AC 15) of approved design/pattern,
with approved standard section and fixed to the existing window
frame with C.P brass/ stainless steel screws @ 200mm centre to
8 21.17 centre, including cutting the grill to proper opening size for fixing and Kg 10434.50 10434.50 423.86 4422728.71
operation of handles and fixing approved anodised aluminium
standard section around the opening, all complete as per requirement
and direction of Engineer-in-charge. (Only weight of grill to be
measured for payment).
TOTAL FOR SUB HEAD VIII 7714376.28
SUB HEAD IX- WATERPROOFING WORK
Providing and fixing of expansion joint system related with floor
location as per drawings and direction of Engineer-In-Charge. The
joints system will be of extruded aluminum base members, self
aligning / self centering arrangement and support plates etc. as per
ASTM B221-02. The system system for various vertical localtion in
load application areas that accommodates multi directional seismic
movement without stress to it's components. System shall consist of
metal profiles with a universal aluminum base member designed to
accommodate various project conditions and finish floor treatments.
1 5.44 The cover plate shall be designed of width and thickness required to
satisfy projects movement and loading requirements and secured to
base members by utilizing manufacturer's pre-engineered self-
centering arrangement that freely rotates / moves in all directions.
The Self -centering arrangement shall exhibit circular sphere all
directions. The Self -centering arrangement shall exhibit circular
sphere vertical displacement. Provision of Moisture Barrier Membrane
in the Joint System to have watertight joint is mandatory requirement
all as per the manufactures design and as approved by Engineer -in-
Charge (Material shall confirm to ASTM 6063.) .
Providing and fixing of expansion joint system related with wall
joints(internal/External location as per drawings and direction of
Engineer-In-Charge. The joints shall be of extruded aluminum base
members, self aligning / self centering arrangement and support
plates etc. as per ASTM B221-02. The Materail shall be such that it
provides an Expansion joints system suitable for vertical wall /wall to
2 5.45 corner application ,both new &Exiting construction in buildings with
no slipping dwon tendency amongst the components of the joints
systems. the joint system shall utilize light weight aluminum profiles
Extibting minimal Exposed Aluminium Surface mechanically snap
locking the multicellular to facilitate movement .(Materail shall
coffime to ASTM 6063) (Material shall confirm to ASTM 6063.) .
17 NBCC (I) Ltd.
LECTURE THEATER BLOCK-2- CIVIL IIT Bhubaneswar
SI.No. DSR Description of Item Unit Total Balance DSR Rate MR RATE DSR-AMOUNT MR-AMOUNT
2014- Quantity in Quantity at which at which
Code Original to be item was item was
Tender executed awarded awarded
at Risk & in original in original
Cost tender tender
Providing and fixing of expansion joint system of approved make and
manufacturers for various roof location as per approved drawing and
direction of engineer in charge . The joint shall be of extruded
aluminium base members with, self align and self centering
arrangement support plates as per ASTMB221-02.The system shall be
such that it provides water tank roof to roof / roof to corner joint
cover expansion control system that is capable of accomodating
multidirectional siesmic movement without stress to its component.
System shall consist of metal profile that incorporates a universal
aluminium based member designed to accomodate various project
condition and roof treatments. The cover plate shall be designed of
width and thickness required to satisfy movement and loading
3 5.46 requirements and screwed to badse embers by utilizing
manufacturers pre engineered self centering arrangement that freely
rotates/ moves in all directions. The self centering arrangement shall
exhibit circular sphere ends that lock and slide inside the
corresponding aluminium extrusion cavity to allow freedom of
movement and flexure in all directions including vertical
displacement. The jointts system shall resists damages in all
directions from the impact of falling ice, exposure to UV, airborne
contaminants and occasional foot traffic from maintenance personnel
. Provision of moisture barrier memberane in the joint system to have
water tank jointing mandatory requirements. Material shall confirm to
Providing gola 75X75 mm in cement mortar 1:2:4 (1 cement : 2
Coarse sand : 4 stone aggregates 10 mm down ) including finishing
4 12.21 with cement mortar 1:3 (1 cement : 3 fine sand ) as per standard Rmt 554.00 554.00 150.38 83307.86
design :in75x75 mm deep chase.
Making khurras 45x45 cm with average minimum thickness of 5 cm
cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone
aggregate of 20 mm nominal size) over P.V.C.
5 12.22 sheet1mx1mx400micron, finished with 12mm cement plaster 1:3 (1 Each 22.00 22.00 196.14 4315.06
cement :3 coarse sand) and a coat of neat cement, rounding the
edges and making and finishing the outlet complete.
18 NBCC (I) Ltd.
LECTURE THEATER BLOCK-2- CIVIL IIT Bhubaneswar
SI.No. DSR Description of Item Unit Total Balance DSR Rate MR RATE DSR-AMOUNT MR-AMOUNT
2014- Quantity in Quantity at which at which
Code Original to be item was item was
Tender executed awarded awarded
at Risk & in original in original
Cost tender tender
Providing and fixing on wall face unplasticised Rigid PVC rain water
pipes conforming to IS : 13592 Type A, including jointing with seal
6 12.41 ring conforming to IS : 5382, leaving 10 mm gap for thermal Mtr 585.00 585.00 243.43 142404.85
expansion, (i) Single socketed pipes.
12.41.2 110 mm diameter
Providing and fixing on wall face unplasticised - PVC moulded fittings/
accessories for unplasticised Rigid PVC rain water pipes conforming to
6 12.42 IS : 13592 Type A, including jointing with seal ring conforming to IS :
5382, leaving 10 mm gap for thermal expansion.
12.42.1 Coupler
12.42.3 Single tee with door
12.42.4 Single tee without door
12.42.6 Shoe (Plain)
Providing and fixing unplasticised -PVC pipe clips of approved design
to unplasticised - PVC rain water pipes by means of 50x50x50 mm
7 12.43 hard wood plugs, screwed with M.S. screws of required length,
including cutting brick work and fixing in cement mortar 1:4 (1
cement : 4 coarse sand) and making good the wall etc. complete.
Providing and fixing to the inlet mouth of rain water pipe cast iron
8 12.44 grating 15 cm diameter and weighing not less than 440 grams. Each 22.00 22.00 43.19 950.17
Providing and Placing in position suitable PVC water stops conforming
to IS:12200 for construction/ expansion joints between two RCC
9 22.4 members and fixed to the reinforcement with binding wire before
pouring concrete etc. complete : for Over headwater tank)
22.4.2 Dumb bell with central bulb (180mm wide, 8mm thick). Mtr 40.00 40.00 484.59 19383.79
19 NBCC (I) Ltd.
LECTURE THEATER BLOCK-2- CIVIL IIT Bhubaneswar
SI.No. DSR Description of Item Unit Total Balance DSR Rate MR RATE DSR-AMOUNT MR-AMOUNT
2014- Quantity in Quantity at which at which
Code Original to be item was item was
Tender executed awarded awarded
at Risk & in original in original
Cost tender tender
Providing and laying water proofing treatment in sunken portion of
WCs, bathroom etc., by applying cement slurry mixed with water
proofing cement compound consisting of applying : a) First layer of
slurry of cement @ 0.488 kg/sqm mixed with water proofing cement
compound@ 0.253 kg/sqm. This layer will be allowed to air cure for 4
10 22.5 hours. b)Second layer of slurry of cement @ 0.242 kg/sqm mixed sqm 410.00 410.00 297.49 121972.05
with waterproofing cement compound @ 0.126 kg/sqm. This layer will
be allowed to air cure for 4 hours followed with water curing for 48
hours. The rate includes preparation of surface, treatment and sealing
of all joints, corners, junctions of pipes and masonry with polymer
Providing and laying water proofing treatment on roofs of slabs by
applying cement slurry mixed with water proofing cement compound
consisting of applying: a) after surface preparation, first layer of
slurry of cement @ 0.488 kg/sqm mixed with water proofing cement
compound@ 0.253 kg/sqm. b) laying second layer of Fibre glass cloth
when the first layer is still green. Overlaps of joints of fibre cloth
should not be less than 10 cm. c) third layer of 1.5 mm thickness
11 22.6 consisting of slurry of cement @ 1.289 kg/sqm mixed with water Sqm 1292.50 1292.50 410.20 530177.55
proofing cement compound@ 0.670 kg/sqm and coarse sand @ 1.289
kg/sqm. This will be allowed to air cure for 4 hours followed by water
curing for 48 hours. The entire treatment will be taken upto 30cm on
parapet wall and tucked into groove in parapet all around. d) fourth
and final layer of brick tiling with cement mortar (which will be paid
for separately For the purpose of measurement the entire treated
surface will be measured.
TOTAL SUB HEAD IX- WATERPROOFING WORK 2752637.37
SUB HEAD X - WOOD WORK
Providing and fixing ISI marked flush door shutters conforming to IS:
2202 (Part I) non-decorative type, core of block board construction
1 9.21 with frame of 1stclass hard wood and well matched commercial 3 ply
veneering with vertical grains or cross bands and face veneers on
both faces of shutters :
35 mm thick including ISI marked Stainless Steel butt hinges with
Extra for providing lipping with 2nd class teak wood battens 25 mm
2 9.23 minimum depth on all edges of flush door shutters (over all area of Sqm 126.85 126.85 384.45 48767.46
door shutter to be measured).
Extra for providing vision panel not exceeding 0.1 sqm in all type of
3 9.24 flush doors (cost of glass excluded) (overall area of door shutter to be
9.24.1 Rectangular or square. Sqm 126.85 126.85 146.49 18581.89
20 NBCC (I) Ltd.
LECTURE THEATER BLOCK-2- CIVIL IIT Bhubaneswar
SI.No. DSR Description of Item Unit Total Balance DSR Rate MR RATE DSR-AMOUNT MR-AMOUNT
2014- Quantity in Quantity at which at which
Code Original to be item was item was
Tender executed awarded awarded
at Risk & in original in original
Cost tender tender
Extra for cutting rebate in flush door shutters (Total area of the
shutter to be measured).
Providing and fixing wooden Architrave /moulded beading to door and
5 9.40 window frames with iron screws, plugs and priming coat on
unexposed surface etc. complete :
9.40.1 Second class teak wood
Providing and fixing IS : 12817 marked stainless steel butt hinges
with stainless steel screws etc. complete :
Providing and fixing aluminium extruded section body tubular type
universal hydraulic door closer (having brand logo with ISI, IS :
7 9.84 3564, embossed on the body, door weight upto 36 kg to 80 kg and Each 60.00 60.00 1096.66 65799.40
door width from 701 mm to 1000mm) with double speed adjustment
with necessary accessories and screws etc. complete.
Providing and fixing factory made P.V.C. door frame of size 50x47mm
with a wall thickness of 5mm, made out of extruded 5mm rigid PVC
foam sheet, mitred at corners and joined with 2 Nos. of 150mm long
brackets of 15x15mmM.S. square tube, the vertical door frame
8 9.119 profiles to be reinforced with19x19mm M.S. square tube of 19 gauge, Mtr 124.15 124.15 482.28 59875.44
EPDM rubber gasket weather seal to be provided through out the
frame. The door frame to be fixed to the wall using M.S. screws of
65/100mm size, complete as per manufacturers specification and
direction of Engineer-in-Charge.
21 NBCC (I) Ltd.
LECTURE THEATER BLOCK-2- CIVIL IIT Bhubaneswar
SI.No. DSR Description of Item Unit Total Balance DSR Rate MR RATE DSR-AMOUNT MR-AMOUNT
2014- Quantity in Quantity at which at which
Code Original to be item was item was
Tender executed awarded awarded
at Risk & in original in original
Cost tender tender
Providing and fixing factory made panel PVC door shutter consisting
of frame made out of M.S. tubes of 19 gauge thickness and size of
19mm x 19mm for styles and 15x15mm for top & bottom rails. M.S.
frame shall have a coat of steel primers of approved make and
manufacture . M.S. frame covered with5mm thick heat moulded PVC
'C' channel of size 30mm thickness, 70mmwidth out of which 50mm
shall be flat and 20mm shall be tapered in 45degreeangle on both
side forming styles; and 5mm thick, 95mm wide PVC sheet out of
which 75mm shall be flat and 20mm shall be tapered in 45 degree on
the inner side to form top and bottom rail and 115mm wide PVC sheet
9 9.120 out of which 75mm shall be flat and 20mm shall be tapered on both
sides to form lock rail. Top, bottom and lock rails shall be provided
both side of the panel.10mm (5mm x 2 ) thick, 20mm wide cross PVC
sheet be provided as gap insert for top rail & bottom rail. paneling of
5mm thick both side PVC sheet to be fitted in the M.S. frame welded/
sealed to the styles & rails with 7mm(5mm+2mm) thick x 15mm
wide PVC sheet beading on inner side, and joined together with
solvent cement adhesive. An additional 5mm thick PVC strip of20mm
width is to be stuck on the interior side of the 'C' Channel using PVC
solvent adhesive etc. complete as per direction of Engineer-in-charge.
Manufacturer’s specification & drawing
9.120.1 30 mm thick plain PVC door shutters. Sqm 60.85 60.85 2889.39 175819.36
Providing & Fixing decorative high pressure laminated sheet of plain /
wood grain in gloss / matt / suede finish with high density protective
10 9.127 surface layer and reverse side of adhesive bonding quality conforming
to IS : 2046 Type Including cost of adhesive of approved quality
TOTAL FOR SUB HEAD - X
SUB HEAD - XI-FALSE CEILING
Providing and fixing thermal insulation of ceiling (under deck
insulation) with Resin Bonded Fibre glass wool conforming to IS :
8183, density24kg / m3, 50mm thick, wrapped in 200 G Virgin
Polythene bags, fixed to ceiling with metallic cleats (50x50x3 mm) @
60 cm and wire mesh of12.5 mm x 24 gauge wire mesh, for top most
ceiling of building.
22 NBCC (I) Ltd.
LECTURE THEATER BLOCK-2- CIVIL IIT Bhubaneswar
SI.No. DSR Description of Item Unit Total Balance DSR Rate MR RATE DSR-AMOUNT MR-AMOUNT
2014- Quantity in Quantity at which at which
Code Original to be item was item was
Tender executed awarded awarded
at Risk & in original in original
Cost tender tender
Providing and fixing false ceiling at all height including providing and
fixing of frame work made of special sections, power pressed from
M.S. sheets and galvanized with zinc coating of 120 gms/sqm (both
side inclusive) as per IS : 277 and consisting of angle cleats of size
25 mm wide x 1.6 mm thick with flanges of 27 mm and 37mm, at
1200 mm centre to centre, one flange fixed to the ceiling with dash
fastener 12.5mm dia x 50mm long with 6mm dia bolts other flange of
cleat fixed to the angle hangers of 25x10x0.50 mm of required length
with nuts &bolts of required size and other end of angle hanger fixed
with intermediate G.I. channels 45x15x0.9 mm running at the rate of
1200mm centre to centre to which the ceiling section 0.5 mm thick
bottom wedge of 80 mm with tapered flanges of 26 mm each having
lips of10.5 mm, at 450 mm centre to centre, shall be fixed in a
2 12.45 direction perpendicular to G.I. intermediate channel with connecting
clips made out of 2.64 mm dia x 230 mm long G.I. wire at every
junction, including fixing perimeter channels 0.5 mm thick 27 mm
high having flanges of 20mm and 30 mm long, the perimeter of
ceiling fixed to wall/partition with the help of rawl plugs at 450 mm
centre, with 25mm long dry wall screws @ 230 mm interval, including
fixing of gypsum board to ceiling section and perimeter channel with
the help of dry wall screws of size3.5 x 25 mm at 230 mm c/c,
including jointing and finishing to a flush finish of tapered and square
edges of the board with recommended jointing compound , jointing
tapes , finishing with jointing compound in 3layers covering upto 150
mm or both sides of joint and two coats of primer suitable for board,
all as per manufacture's specification and also including the cost of
making openings for light fittings, grills, diffusers, cutouts made with
frame of perimeter channels suitably fixed, all complete as per
12.45.3 12.5 mm thick tapered edge gypsum moisture resistant board. Sqm 3645.00 3645.00 1113.36 4058215.35
23 NBCC (I) Ltd.
LECTURE THEATER BLOCK-2- CIVIL IIT Bhubaneswar
SI.No. DSR Description of Item Unit Total Balance DSR Rate MR RATE DSR-AMOUNT MR-AMOUNT
2014- Quantity in Quantity at which at which
Code Original to be item was item was
Tender executed awarded awarded
at Risk & in original in original
Cost tender tender
Providing and fixing tiled false ceiling of approved materials of size
595x595 mm in true horizontal level suspended on inter locking
metal grid of hot dipped galvanized steel sections ( galvanized @
120gsm/sqm, both side inclusive) consisting of main "T" runner with
suitably spaced joints to get required length and of size
24x38mmmade from 0.30mm thick (minimum) sheet, spaced at
1200mm center to center and cross "T" of size 24x25mm made of
0.30mm thick(minimum) sheet, 1200mm long spaced between main
"T" at 600mmcenter to center to form a grid of 1200x600 mm and
secondary cross T of length 600mm and size 24x25mm made of 0.30
mm thick(minimum) sheet to be interlocked at middle of the
1200x600mm panel to form grids of 600x600mm and wall angle of
size 24x24x0.3 mm and laying false ceiling tiles of approved texture
3 12.52 in the grid including, wherever, required, cutting/making, opening for
services like diffusers, grills, light fittings, fixtures, smoke detectors
etc. Main "T" runners to be suspended from ceiling using GI slotted
cleats of size 27 x 37 x 25 x1.6x mm fixed to ceiling with 12.5 mm
dia and 50 mm long dash fasteners,4mm GI adjustable rods with
galvanised butterfly level clips of size 85 x30 x 0.8 mm spaced at
1200mm center to center along main T, bottom exposed width of 24
mm of all T-sections shall be pre-painted with polyester paint, all
complete at all heights as per specifications drawings and as directed
by Engineer-in-charge.12.52.1 GI Metal Ceiling Lay in plain Tegular
edge Global white color tiles of size 595x595 mm, and 0.5mm thick
with 8mmdrop; made of G I sheet having galvanizing of 100
gms/sqm(both sides inclusive) and electro statically polyester powder
coated of thickness 60 microns (minimum), including factory painted
GI Metal Ceiling Lay in perforated Tegular edge global white color
tiles of size 595x595 mm and 0.5mm thick with 8mmdrop; made of
GI sheet having galvanizing of 100 gms/sqm(both sides inclusive)
12.52.2 and 20% perforation area with 1.8mmdia holes and having NRC Sqm 370.00 370.00 1758.58 650674.87
(Noise Reduction Coefficient ) of0.5, electro statically polyester
powder coated of thickness60 microns (minimum), including factory
painted after bending and perforation, and backed with a black Glass
Providing and laying roof insulation with 40 mm thick impervious
sprayed, closed cell free Rigid Polyurethane foam over deck insulation
conforming to IS - 12432 Pt. III (density of foam being 40-45
kg/cum),over a coat of polyurethane primer applied @ 6-8 sqm per
4 12.56 litre, laying400 G polythene sheet over PUF spray and providing a Sqm 3645.00 3645.00 1226.54 4470739.93
wearing course of 40 mm thick cement screed 1: 2 : 4 (1 cement : 2
coarse sand : 4stone aggregate 20 mm nominal size) in chequered
rough finish, in panels of 2.5 m x 2.5 m and embedding with 24 G
wire netting and sealing the joints with polymerized mastic, all
complete as per direction of Engineer-in-Charge.
TOTAL SUB HEAD - XII-FALSE CEILING
24 NBCC (I) Ltd.
LECTURE THEATER BLOCK-2- CIVIL IIT Bhubaneswar
SI.No. DSR Description of Item Unit Total Balance DSR Rate MR RATE DSR-AMOUNT MR-AMOUNT
2014- Quantity in Quantity at which at which
Code Original to be item was item was
Tender executed awarded awarded
at Risk & in original in original
Cost tender tender
SUB HEAD - XII-GLAZING AND ALUMINIUM COMPOSIT PANAL
Providing and fixing 12 mm thick frameless toughened glass door
shutter of approved brand and manufacture, including providing and
fixing top & bottom pivot & spring type fixing arrangement and
making necessary holes etc. for fixing required door fittings, all
complete as per direction of Engineer-in-charge (Door handle, lock
Providing and supplying aluminium extruded tubular and other
aluminium sections as per the architectural drawings and approved
shop drawings , the aluminium quality as per grade 6063 T5 or T6 as
per BS 1474,including super durable powder coating of 60-80 microns
conforming to AAMA 2604 of required colour and shade as approved
by the Engineer-in-Charge
Designing, fabricating, testing, protection, installing and fixing in
position semi (grid) unitized system of structural glazing (with open
3 26.2 joints) for linear as well as curvilinear portions of the building for all
heights and all levels including:
:(a) Structural analysis, design and preparation of shop drawings for
the specified design loads conforming to IS 875 part III (the system
must passed the proof test at 1.5 times design wind pressure without
any failure), including functional design of the aluminum sections for
fixing glazing panels of various thicknesses, aluminium cleats,
sleeves and splice plates etc. gaskets, screws, toggles, nuts, bolts,
clamps etc., structural and weather silicone sealants, flashings, fire
stop (barrier)-cum-smoke seals, microwave cured EPDM gaskets for
water tightness, pressure equalisation & drainage and protection
against fire hazard including
(b) Fabricating and supplying serrated M.S. hot dip galvanised
/Aluminium alloy of 6005 T5 brackets of required sizes, sections and
profiles etc. to accommodate 3 Dimentional movement for achieving
perfect verticality and proper fixing of structural glazing system with
the RCC/ masonry/structural steel framework of building structure,
using stainless steel anchor fasteners/ bolts, nylon seperator to
prevent bimetallic contacts with nuts and washers etc. of stainless
steel grade 316, of the required capacity and in required numbers.
(c) Providing and filling, two part pump filled, structural silicone
sealant and one part weather silicone sealant compatible with the
structural silicone sealant of required bite size in a clean and
controlled factory / work shop environment , including double sided
spacer tape, setting blocks and backer rod, all of approved
grade,brand and manufacturer, as per the approved sealant design,
within and all around the perimeter for holding glass
25 NBCC (I) Ltd.
LECTURE THEATER BLOCK-2- CIVIL IIT Bhubaneswar
SI.No. DSR Description of Item Unit Total Balance DSR Rate MR RATE DSR-AMOUNT MR-AMOUNT
2014- Quantity in Quantity at which at which
Code Original to be item was item was
Tender executed awarded awarded
at Risk & in original in original
Cost tender tender
.(d) Providing and fixing in position flashings of solid aluminium sheet
1 mm thick and of sizes, shapes and profiles, as required as per the
site conditions, to seal the gap between the building structure and all
its interfaces with curtain glazing to make it watertight
(e) Making provision for drainage of moisture/ water that enters the
curtain glazing system to make it watertight, by incorporating
principles of pressure equalization, providing suitable gutter profilesat
bottom (if required), making necessary holes of required sizes and of
required numbers etc. complete This item includes cost of all inputs
of designing, labour for fabricating and installation of aluminium grid,
installation of glazed units, T&P,scaffolding and other incidental
charges including wastages etc.,enabling temporary structures and
services, cranes or cradles etc. as described above and as specified.
The item includes the cost of getting all the structural and functional
design checked and all the shop drawings vetted by the Principals of
the structural glazing system.The item also includes the cost of all
mock ups at site, cost of all samples of the individual components for
testing in an approved laboratory, field tests on the assembled
working structural glazing as specified, cleaning and protection till the
handing over of the building for occupation. In the end, the
Contractor shall provide a water tight structural glazing having all the
performancecharacteristics etc. all complete as required, as per the
Architectural drawings, as per item description, as specified, as per
the approved shop drawings and as directed by the Engineer-in-
Note:- 1. The cost of providing extruded aluminium frames, shadow
boxes, extruded aluminium section capping for fixing in the grooves
of the curtain glazing and vermin proof stainless steel wire mesh shall
be paid for separately under relevant items under this subhead.
However, for the purpose of payment, only the actual area of
structural glazing (including width of grooves ) on the external face
shall be measured in sqm. up to two decimal places.
Note:-2. The following performance test are to be conducted on
glazing system if area of structural glazing exceeds 2500 Sqm from
certified laboratories accreditated by NABL(National Accreditation
for Testing and Calibration Laboratories), Department of Science &
Technologies, India. Cost of testing is payable separately. The NIT
approving authority will decide the necessity of testing on the basis of
cost of the work, cost of the test and importance of the work.
Performance Testing of Structural glazing system Tests to be
conducted in the NBL Certified laboratories
26 NBCC (I) Ltd.
LECTURE THEATER BLOCK-2- CIVIL IIT Bhubaneswar
SI.No. DSR Description of Item Unit Total Balance DSR Rate MR RATE DSR-AMOUNT MR-AMOUNT
2014- Quantity in Quantity at which at which
Code Original to be item was item was
Tender executed awarded awarded
at Risk & in original in original
Cost tender tender
Performance Laboratory Test for Air Leakage Test (-50pa to – 300pa)
(+50pa to +300pa) as per ASTM E-283-04 testing method for a range
of testing limit 1 to 200 mVhr”
Static Water Penetration Test. (50pa to 1500pa) as per ASTME- 331-
2 09 testing method for a range up to 2000 ml.”
Dynamic Water Penetration (50pa to 1500pa) as per AAMA 501.01- 05
3 testing method for a range upto 2000 ml”
Structural Performance Deflection and deformation by static air
4 test (1.5 times desing wind pressure without any failure) as per
330-10 testing method for a range upto 50 mm”
Seismic Movement Test (upto 30 mm) as per AAMA 501.4-09 testing
method for Qualitative test” Tests to be conducted on site 6. Onsite
Test for Water Leakage for a pressure range 50 kpa to 240 kpa (35psi)
Providing, assembling and supplying vision glass panels (IGUs)
comprising of hermetically-sealed 6-12-6 mm insulated glass (double
glazed) vision panel units of size and shape as required and specified,
comprising of an outer high performance heat strengthened float
glass 6mm thick, of approved colour and shade with reflective soft
coating on surface # 2 of approved colour and shade, an inner Heat
strengthned clear float glass 6mm thick, spacer tube 12mm
wide,dessicants, including primary seal and secondary seal
(structural silicone sealant) etc. all complete for the required
performances, as per the Architectural drawings, as per the approved
shop drawings,as specified and as directed by the Engineer-in-
4 26.3 Charge. The IGUs shall be assembled in the factory/ workshop of the Sqm 190.00 190.00 4298.93 816797.44
glass processor.(Payment for fixing of IGU Panels in the curtain
glazing is included in cost of item No.1) For payment, only the actual
area of glass on face # 1 of the glass panels (excluding the areas of
the grooves and weather silicone sealant) provided and fixed in
position, shall be measured in sqm. (i) Coloured tinted float glass
6mm thick substrate with reflective soft coating on face # 2, + 12mm
Airgap + 6mm Heat Strengthened clear Glass of approved make
having properties as visible Light transmittance (VLT) of 25 to 35 %,
Light reflection internal 10 to 15%, light reflection external 10 to 20
%, shading coefficient (0.25- 0.28) and U value of 3.0 to 3.3 W/m2
degree K etc. (Glass Make Saint gobain,Asahi,Pilkington,Glod Plus)
27 NBCC (I) Ltd.
LECTURE THEATER BLOCK-2- CIVIL IIT Bhubaneswar
SI.No. DSR Description of Item Unit Total Balance DSR Rate MR RATE DSR-AMOUNT MR-AMOUNT
2014- Quantity in Quantity at which at which
Code Original to be item was item was
Tender executed awarded awarded
at Risk & in original in original
Cost tender tender
Extra for openable side / top hung vision glass panels (IGUs)
including providing and supplying at site all accessories and
hardwares for the openable panels as specified and of the approved
make such as heavy duty stainless steel friction hinges, min 4 -point
5 26.4 cremonelocking sets with stainless steel plates, handles, buffers etc. Sqm 1.20 1.20 3217.93 3861.52
including necessary stainless steel screws/ fasteners, nuts, bolts,
washers etc. all complete as per the Architectural drawings, as per
the approved shop drawings, as specified and as directed by the
Engineerin-in-Charge.
Providing and supplying Spandrel Glass Panels comprising of 6 mm
thick heat strengthened monolithic float glass of approved colour and
shade with reflective soft coating on surface # 2 of approved colour
and shade so as to match the colour and shade of the IGUs in the
vision panels etc. ,all complete for the required performances as
specified, as per the Architectural drawings, as per the approved shop
drawings, as specified, and as directed by the Engineer- in-
Charge.“For payment, only the actual area of glass on face # 1 of the
glass panels (but excluding the area of grooves and weather silicone
sealant) provided and fixed in position, shall be measured in sqm.
(Payment for fixing of Spandrel Glass Panels in the curtain glazing is
included in cost of relevent Item*). (i) Coloured tinted float glass
6mm thick substrate with reflective soft coating on face # 2, having
properties as visible Light transmittance (VLT) of 25 to 35 %, Light
reflection internal 10 to 15%, light reflection external 10 to 20 %,
shading coefficient (0.25- 0.28) and U value of 3.0 to 3.3 W/m2 K
etc. The properties of performance glass shall be decided by
technical sanctioning authority as per the site requirement.
28 NBCC (I) Ltd.
LECTURE THEATER BLOCK-2- CIVIL IIT Bhubaneswar
SI.No. DSR Description of Item Unit Total Balance DSR Rate MR RATE DSR-AMOUNT MR-AMOUNT
2014- Quantity in Quantity at which at which
Code Original to be item was item was
Tender executed awarded awarded
at Risk & in original in original
Cost tender tender
Designing, fabricating, testing, installing and fixing in position Curtain
Wall with Aluminium Composite Panel Cladding, with open grooves
for linear as well as curvilinear portions of the building, for all
heights and all levels etc. including:
a) Structural analysis & design and preparation of shop drawings for
pressure equalisation or rain screen principle as required, proper
drainage of water to make it watertight including checking of all the
structural and functional design.
b) Providing, fabricating and supplying and fixing panels of
aluminium composite panel cladding in pan shape in metalic colour
of approved shades made out of 4mm thick aluminium composite
panel material consisting of 3mm thick FR grade mineral core
sandwiched between two Aluminium sheets (each 0.5mm thick).
The aluminium composite panel cladding sheet shall be coil coated,
with Kynar 500 based PVDF / Lumiflon based fluoropolymer resin
coating of approved colour and shade on face # 1 and polymer
(Service) coating on face # 2 as specified using stainless steel
screws, nuts, bolts, washers, cleats, weather silicone sealant, backer
c) The fastening brackets of Aluminium alloy 6005 T5 / MS with Hot
Dip Galvanised with serrations and serrated washers to arrest the
wind load movement, fasteners, SS 316 Pins and anchor bolts of
approved make in SS 316, Nylon separators to prevent bi-metallic
contacts all complete required to perform as per specification and
drawing The item includes cost of all material & labour component,
the cost of all mock ups at site,
cost of all samples of the individual components for testing in an
approved laboratory, field tests on the assembled working curtain
wall with aluminium composite panel cladding, cleaning and
protection of the curtain wall with aluminium composite panel sqm 1750.00 1750.00 3967.24 6942663.44
cladding till the handing over of the building for occupation. Base
frame work for ACP cladding is payable under the relevant aluminium
item.s The Contractor shall provide curtain wall with aluminium
composite panel cladding, having all the performance characteristics
all complete , as per the Architectural drawings, as per item
description, as specified, as per the approved shop drawings and as
directed by the Engineer-in-Charge. However, for the purpose of
payment, only the actual area on the external face of the curtain
wall with Aluminum Composite Panel Cladding (including width of
groove) shall be measured in sqm. up to two decimal places.
TOTAL FOR SUB HEAD XI 13474042.50
SUB HEAD-XIII FIRE RESISTANT DOOR
29 NBCC (I) Ltd.
LECTURE THEATER BLOCK-2- CIVIL IIT Bhubaneswar
SI.No. DSR Description of Item Unit Total Balance DSR Rate MR RATE DSR-AMOUNT MR-AMOUNT
2014- Quantity in Quantity at which at which
Code Original to be item was item was
Tender executed awarded awarded
at Risk & in original in original
Cost tender tender
Providing and fixing fire resistant door frame of section 143 x 57 mm
having built in rebate made out of 16 SWG G.I.sheet (zinc coating not
less than 120gm/sqm) duly filled with vermuculite based concrete
mix, suitable for mounting60 minutes fire rated door shutters. The
frame is fitted with intumuscent fire seal strip of size 10x4 mm
(minimum) alround the frame and fixing with dash fastener of
approved size and make, including applying a coat of approved brand
fire resistant primer etc. complete as per direction of Engineer-in-
charge(Dash fastener to be paid for separately).
Providing and fixing 50 mm thick glazed fire resistant door shutters of
60 minutes fire rating conforming to IS:3614 (Part-II) tested and
certified as per laboratory approved by Engineer-in-charge with
suitable mounting on doorframe, consisting of vertical styles, lock
rail, top rail 100mm wide, bottom rail200mm wide, made out of 16
2 9.137 SWG G.I.sheet (zinc coating not less than 120 gm/sqm duly filled FR Sqm 39.60 39.60 6586.88 260840.26
insulation material and fixing with necessary stainless steel ball
bearing hinges of approved make, including applying a coat of
approved fire resistant primer etc. all complete as per direction of
Engineer-in charge(pannelling to be paid for separately).
Providing and fixing glazing in fire resistant door shutters, fixed
panels, ventilators and partitions etc., with G.I. beading of
appropriate size made out of 20 SWG G.I.sheet (zinc coating not less
3 9.138 than 120 gm/sqm sealant, including applying a coat of approved fire
resistant primer on G.I. beading etc. complete all as per direction of
Engineer-in-charge.
With clear fire resistant glass panes 6mm thick of approved brand,
9.138.1 having minimum 60 minutes fire resistance. sqm 31.00 31.00 29064.87 901010.92
Providing and fixing panic bar / latch (Double point) fitted with a
single body, Trim Latch & Lock on back side of the Panic Latch of
4 9.139 reputed brand and manufacture to be approved by the Engineer- in- Each 16.00 16.00 6445.01 103120.19
charge, all complete.
Providing and applying two coats of fire retardant paint on cleaned
wood/ply surface @ 3.5 sqm per litre per coat including preparation
5 13.58 of base surface as per recommendations of manufacturer to make the Sqm 215.00 215.00 260.24 55951.71
surface fire retardant.
TOTAL SUB HEAD-XIII FIRE RESISTANT DOOR 1453465.58
SUB HEAD-XIV-WALL LINING WORKS
30 NBCC (I) Ltd.
LECTURE THEATER BLOCK-2- CIVIL IIT Bhubaneswar
SI.No. DSR Description of Item Unit Total Balance DSR Rate MR RATE DSR-AMOUNT MR-AMOUNT
2014- Quantity in Quantity at which at which
Code Original to be item was item was
Tender executed awarded awarded
at Risk & in original in original
Cost tender tender
Providing 50x50x50mm 2nd class teak wood plugs including cutting
brick work and fixing in cement mortar 1:3 (1 cement : 3 fine sand)
and making good the walls etc.
Providing and fixing expandable fasteners of specified size with
necessary plastic sleeves and galvanised M.S. screws including
drilling holes in masonry work /CC/ R.C.C. and making good etc.
Providing and fixing in wall lining flat pressed three layer (medium
density) particle board or graded wood Pre-laminated one side
3 9.35 decorative lamination on other side balancing lamination Grade I,
Type II, IS : 12823 marked, including priming coat on unexposed
surface, with necessary fixing arrangement and screws etc. complete :
Providing and fixing specified wood frame work consisting of battens
50x25 mm fixed with rawl plug and drilling necessary holes for rawl
plug etc. including priming coat complete.
Kiln seasoned and chemically treated hollock wood.
Providing and fixing thermal insulation with Resin Bonded Fibre glass
wool conforming to IS: 8183 having density 24 kg/cum , 50 mm
5 12.57 thick, wrapped in 200G Virgin Polythene Bags fixed to wall with sqm 3312.00 3312.00 336.16 1113374.23
screw, rawl plug & washers and held in position by criss crossing GI
wire etc. complete as per directions of Engineer-in-Charge.
TOTAL SUB HEAD-XIV-WALL LINING WORKS 8144746.24
SUB HEAD XV -MISCELLANEOUS WORKS
31 NBCC (I) Ltd.
LECTURE THEATER BLOCK-2- CIVIL IIT Bhubaneswar
SI.No. DSR Description of Item Unit Total Balance DSR Rate MR RATE DSR-AMOUNT MR-AMOUNT
2014- Quantity in Quantity at which at which
Code Original to be item was item was
Tender executed awarded awarded
at Risk & in original in original
Cost tender tender
Providing and erecting 2.00 metre high temporary barricading at site
as per drawing/ direction of Engineer-in-Charge which includes
writing and painting, arrangement for traffic diversion such as traffic
signals during construction at site for day and night, glow lamps,
reflective signs, marking, flags, caution tape as directed by the
Engineer-in-Charge. The barricading provided shall be retained in
position at site continuously i/c shifting of barricading from one
1 16.81 location to another location as many times as required during the Mtr
execution of the entire work till its completion. Rate include its
maintenance for damages, painting, all incidentals, labour materials,
equipments and works required to execute the job. The barricading
shall not be removed without prior approval of Engineer-in-Charge.
(Note :- One time payment shall be made for providing barricading
from start of work till completion of work i/c shifting. The barricading
provided shall remain to be the property of the contractor on
completion of the work).
TOTAL SUB HEAD XV -MISCELLANEOUS WORKS
SUB HEAD-XVI NON SCHEDULE ITEMS
Sealing the core of different diameter pipes in the slabs of varying
thickness after fixing of sanitary / S.S. Pipes and fitting in the cut
areas and making it water proof and leak proof by following
Cutting 25 mm deep V-groove around the periphery of the pipe, and
sealing it with polymer modified mortar using 1 part acrylic polymer
: 2 part Cement : 5 Sand, applying three coats of acrylic polymer
Rate admixed with cement (as 1 part ShaliCrete: 2 part cement) over
1 concrete slab as well as on the pipe surface upto 150 mm height, Rmt 433.00 433.00 1071.79 464086.69
After first coat of acrylic polymer a layer of fibre glass mesh shall
be placed as centre core, This coating shall cover minimum 150 mm
around the periphery. moist cure for one day , then once the coating
is completely bone dry after about two days apply two coats of PU
modified liquid membrane by brush application , protection be
provided as per good engineering practice. (Perimeter of the sealed
area shall be measured for payment).
Core cutting in existing RCC slabs / walls of depth thickness in
required size including making arrangement for scaffolding, diamond
cutter, labour for all purpose, and all necessary equipment and
2 accessories like fixing dash fastener to fix machine complete as per Sqcm 638335.00 638335.00 1.51 965934.65
the directions of Engineer-in-charge. (Total cut surface area
(Perimeter and depth) will be measured to nearest cm for payment)
Providing Stainless Steel 20x20 mm square bar . foot rests including
3 fixing in water tank as per standard design : all complete as per Each 20.00 20.00 450.68 9013.69
Engineer in charge.
32 NBCC (I) Ltd.
LECTURE THEATER BLOCK-2- CIVIL IIT Bhubaneswar
SI.No. DSR Description of Item Unit Total Balance DSR Rate MR RATE DSR-AMOUNT MR-AMOUNT
2014- Quantity in Quantity at which at which
Code Original to be item was item was
Tender executed awarded awarded
at Risk & in original in original
Cost tender tender
Puddle flange of following dia. M.S/G.I pipe by providing 6mm thk
M.S plate minimum 100mm wide from the M.S/G.I pipe including
Rate welding , priming and bitumastic painting and necessary fixing
Analysis arrangement by welding or threading on both and as per
standard/requirement at site etc. complete as directed by engineer-in-
Providing & Fixing 150 mm Dia Each 2.00 2.00 1658.60 3317.21
(ii) Providing & Fixing 100 mm dia Each 4.00 4.00 1374.41 5497.66
(iii) Providing & Fixing 80 mm dia Each 4.00 4.00 1297.61 5190.44
(iv) Providing & Fixing 65 mm dia Each 6.00 6.00 1176.66 7059.94
(v) Providing & Fixing 50mm dia Each 6.00 6.00 1099.89 6599.36
EPDM Rubbergard Membrane.Water proofing :-Horizontal area:
Providing and laying a layer of 200 gsm Geotextile is loose laid on
Lean concrete substrate. The geotextile membrane must be
overlapped for 75mm. The overlapping joint may be secured by
Stitching or Bonding Adhesive or hot air gun as convenient to the
waterproofing applicator. EPDM Rubbergard : Prividing & Laying 1.1
mm EPDM membrane confirming to above mentioned technical values
Rate is loose laid over the geotextile layer. The width of EPDM sheet should
5 be minimum 9 meter or large as possible to minimize the number of
joints. Adjacent sheet shall be laid in similar fashion with an overlap
of minimum 100 mm . Min 75mm wide rubber polymers butyl splice
tape having 100% solid content together with synthetic-rubber
polymer primer having 16-18% solids, Specific Gravity 0.793 and
Flash point-17.8 degree centigrade, should be used to make
watertight QuickSeam between 2 EPDM membranes.
Vertical wall:The surface of wall shall be smooth, hard , dry and free
from dust before applying treatment. 1.1mm thick EPDM Rubbergard
confirming to above standards is fully bonded to the RCC substrate
using FM approved solvent based Neoprene Bonding adhesive.
having following parameters : A blend of Polychloroprene and SBR
rubbers Solvents: A blend of Acetone, Hexane, Toluene and Xylene;
Viscosity: 3,300-3,800 cps, with R.V.F. #3 spindle @ 10
rpm,Weight/Gallon:6.6-7.4 lb/gal, Specific Gravity: 0.7909-0.8868;
V.O.C. Content: 5.282 lb/gal (633 g/L). All the insertions shall be
treated with uncured EPDM. The treatment to be terminated atleast at Sqm 3645.00 3645.00 801.60 2921838.45
the height of 300mm above the roof floor level using termination bar
and appropriate fasteners. Water block sealant should be used on top
edge behind membrane and lap sealant should be applied on the
edges of termination detail.
Uncured EPDM flashing
material factory laminated to splice tape should be used to flash
inside and outside corners, pipes, drain outlets, scuppers and other
penetrations or unusually shaped walls/details where the use of cured
membrane flashing is not practical.
33 NBCC (I) Ltd.
LECTURE THEATER BLOCK-2- CIVIL IIT Bhubaneswar
SI.No. DSR Description of Item Unit Total Balance DSR Rate MR RATE DSR-AMOUNT MR-AMOUNT
2014- Quantity in Quantity at which at which
Code Original to be item was item was
Tender executed awarded awarded
at Risk & in original in original
Cost tender tender
Rate Providing and fixing Stain finished Stainless Steel tower bolts Round
6 (barrel type) with necessary screws etc. complete :
Rate Providing and fixing Stain finished Stainless Steel 304 handles with
Analysis screws etc. complete :
Providing and fixing Stain finished Stainless Steel with Rubber
8 hanging type floor door stopper with necessary screws, etc. complete. Each 70.00 70.00 98.22 6875.54
Providing and fixing 304 Grade Stain less Steel Stain Finish Aldrop
9 with double lock hook size 200x16 mm with Screws etc. all Complete Each 74.00 74.00 387.93 28706.68
as per Engineer in charge.
Rate Providing & fixing wiremesh at juction of Brick works & RCC Works
Analysis all Complete as per direction of Engineer -in-charge.
Rate Extra for providing 5x3 mm Groove to 25 mm thick Kota & Granite
Analysis stone staircase Traed etc.
34 NBCC (I) Ltd.
LECTURE THEATER BLOCK-2- CIVIL IIT Bhubaneswar
SI.No. DSR Description of Item Unit Total Balance DSR Rate MR RATE DSR-AMOUNT MR-AMOUNT
2014- Quantity in Quantity at which at which
Code Original to be item was item was
Tender executed awarded awarded
at Risk & in original in original
Cost tender tender
Design, Manufacture, Supply and Installation of Poly carbonate panel
system, a complete assembly of extruded cellular structure UV
protected polycarbonate panels incorporated into a complete system.
Co-extruded UV protected polycarbonate panel system of minimum
16 mm thickness with panel width of 1050 - 1250 mm to ensure best
performance for wind uplift, vibration, oil canning and visual
appearance. Panels shall be manufactured with vertical standing
seam with standing seam height of 10 - 15mm at both sides of the
panel. Panels shall be of Softlite / Antiglare type to prevent glare.
Panels shall be fixed on Purlins with continuous twin wall aluminum
spacer and HD polycarbonate U connectors. Continuous twin wall
aluminum spacer will be secured on MS Structure with self-drilling
Rate screws to ensure a pull-out load of min. 21000N (21KN) tested as per
Analysis ISO 6892:1998 and IS 1608:2005. Polycarbonate panels also shall
not have Yellowness Index as per ASTM D 1925 of 15 units when
tested on a sample exposed to UV for 500 Hours as per ASTM G 155.
The polycarbonate panels must satisfy Dart drop impact test as per IS
14443-97 shall show no sign of breakage on Polycarbonate sheets
which have been exposed to UV for a min. of 500 Hours as per ASTM
G 155.Panel shall be with additional End cap/Aluminum U / F Profile /
Glazing Bar (mill finish) for ends as required. Panel shall be fixed over
M S structural steel / MS purlin (paid separately) conforming to the
detail technical specifications as per approved architectural
drawings.Trained and factory authorized labor with supervision to
complete the entire panel installation as per drawing & direction of
the engineer in charge.Color: As per Approval
Granite work gang saw cut (polished and machine cut) of thickness
30 mm for wall lining (veneer work), backing filled with a grout of
average 12 mm thick in cement mortar 1:3 (1 cement : 3 coarse
Rate sand)including pointing with white cement mortar 1:2 (1 white
Analysis cement : 2marble dust) with an admixture of pigment to match the
Granite shade:(To be secured to the backing by means of cramps,
which shall be paid for separately).
Providing and fixing double glazed hermetically sealed glazing in
aluminium windows, ventilators and partition etc. with 6 mm thick
Tempered glass both side(SKN 440Saint Gobain India & Exceed
Rate Green Vision Asahi india glass), having 12 mm air gap, including
Analysis providing EPDM gasket, perforated aluminium spacers, desiccants,
sealant (Both primary and secondary sealant) etc. as per
specifications, drawings and direction of Engineer-in-charge complete.
Rate Providing and fixing Stain finished Stainless Steel 316 glass door
15 Floor Lock with screws etc. complete : PF14S kich make or equivalent Each 10.00 10.00 3148.88 31488.84
35 NBCC (I) Ltd.
LECTURE THEATER BLOCK-2- CIVIL IIT Bhubaneswar
SI.No. DSR Description of Item Unit Total Balance DSR Rate MR RATE DSR-AMOUNT MR-AMOUNT
2014- Quantity in Quantity at which at which
Code Original to be item was item was
Tender executed awarded awarded
at Risk & in original in original
Cost tender tender
Providing and fixing Combi. finished Stainless Steel 316 glass door
16 pull handles 450x25mm (pair of handle) dia with screws etc. Each 10.00 10.00 4547.91 45479.09
complete : PHH2518 kich make or equivalent
Supply & fixing Fresh Color Restroom(Toilet) Cubicle made out of
Thickness of Compact Laminate : 18 mm. Size of Cubicle : 1000mm
(W) X 1550mm (D) X 2100mm (H),Door Size : 1995mm (H) x
Rate 610mm (W),Overall Height of Cubicle : 2100 mm (Including bottom 1No
Analysis Gap of 100mm) all Including Stainless Steel - 304 Grade Cubical
accessories,Occupancy Indicator , Rubber Lining for Groove. all
complete as per direction of Engineer-in-charge.
Providing and laying M-20 grade foam concrete filling in sunken
portion of W.C. & kitchen/Terrace with approved quality of foam
18 concrete including pumping of concrete to site of laying but excluding cum 991.75 991.75 4611.57 4573523.86
the cost of centering, shuttering.as per direction of Engineer-in-
Providing and fixing Romanhuse blinds non blockout with chain
19 Mechanism all complete Make.Vista,Hunter Duglus,fabindia Sqm 359.55 359.55 2074.74 745971.50
Extra Providing and Double Charge vitrified floor/wall tiles in different
20 sizes (thickness to be specified by the manufacturer) sqm 2086.50 2086.50 162.68 339432.95
SUBHEAD XVI TOTAL NON SCHEDULE ITEMS 30462444.36
36 NBCC (I) Ltd.
LECTURE COMPLEX - 2- Plumbing IIT Bhubneswar
NAME OF PROJECT :- LECTURE -2 BOQ FOR IIT BHUBNESWAR
B. SUMMARY OF PLUMBING WORKS
Sl. No. Description of Item DSR Amount M.R. Amount
1 SUB HEAD - I - (SANITARY FIXTURES & INTERNAL PLUMBING) 898965.14 3310888.99
2 SUB HEAD - II - (SOIL, WASTE, RAIN WATER AND VENT PIPES) 1484245.63 902493.59
3 SUB HEAD - III - (WATER SUPPLY) 803566.31 232168.90
4 SUB HEAD - IV - (SEWERAGE AND DRAINAGE) 1234879.09 385565.11
5 SUB HEAD - V - EXTERNAL WATER SUPPLY 97188.78 52432.09
6 SUBHEAD - VI - SUBMERSIBLE TRANSFER PUMPS 0.00 310031.41
7 SUB HEAD - VII - (RAIN WATER HARVESTING) 1023429.35 0.00
TOTAL DSR + MR 10735854.40
LECTURE COMPLEX- 2 - Plumbing IIT Bhubneswar
NAME OF PROJECT :- LECTURE -2 BOQ FOR IIT BHUBNESWAR
DETAILED ESTIMATE - PLUMBING WORK
Ite DSR - Description of Item Unit Total Balance DSR Rate MR RATE at DSR-Amount MR-Amount
m 2014 Quantity Quantity at which which item
No Code No. in to be item was was awarded
Original executed awarded in in original
Tender at Risk & original tender
SUB HEAD - I - (SANITARY FIXTURES & INTERNAL PLUMBING)
17.5 Providing and fixing white vitreous china flat back half stall urinal of size
580x380x350 mm with white PVC automatic flushing cistern, with fittings,
standard size C.P. brass flush pipe, spreaders with unions and clamps (all in
1 C.P. brass) with waste fitting as per IS : 2556, C.I. trap with outlet grating
and other couplings in C.P. brass, including painting of fittings and cutting
and making good the walls and floors wherever required
17.5.1 Single half stall urinal with 5 litre P.V.C. automatic flushing cistern Each 36.00 36.00 6926.19 249342.89
17.10 Providing and fixing Stainless Steel A ISI 304 (18/8) kitchen sink as per IS:
2 13983 with C.I. brackets and stainless steel plug 40 mm, including painting
of fittings and brackets, cutting and making good the walls wherever
17.10.1.3 510x1040 mm bowl depth 200 mm
17.31 Providing and fixing 900 x 600 mm beveled edge mirror of
superior glass (of approved quality) complete with 6 mm thick hard
board ground fixed to wooden cleats with C.P. brass screws and
washers complete.
4 17.34 Providing and fixing toilet paper holder.
17.78 Providing and fixing white vitreous china extended wall mounting water
closet of size 780x370x690 mm of approved shape including providing &
5 fixing white vitreous china cistern with dual flush fitting, of flushing capacity Each 54.00 54.00 10614.43 573179.21
3 litre/6 litre (adjustable to 4 litre/8 litres), including seat cover, and cistern
fittings, nuts, bolts and gasket etc complete.
6 18.21 Providing and fixing uplasticised PVC connection pipe with brass unions
18.21.2 45 cm length
18.21.2.1 15 mm dia nominal bore
18.51 Providing and fixing C.P. brass long body bib cock of approved quality
conforming to IS standards and weighing not less than 690 gms.
M.R. Providing and fixing CP brass bottle trap with wall connection pipe for
8 wash basins and urinals. Jaquar make cat. ALD-769L250x190 or
1 NBCC (I) Ltd.
LECTURE COMPLEX- 2 - Plumbing IIT Bhubneswar
Ite DSR - Description of Item Unit Total Balance DSR Rate MR RATE at DSR-Amount MR-Amount
m 2014 Quantity Quantity at which which item
No Code No. in to be item was was awarded
Original executed awarded in in original
Tender at Risk & original tender
M.R. Providing and fixing C.P. brass liquid soap container with C.P. brass
lid and brackets fixed to wall with wooden cleats and C.P. brass
9 screws, including cutting and making good the walls wherever Each 54.00 54.00 1083.57 58512.98
required. Jaquar make cat. ACN-1135N or EQUIVALENT
M.R. Providing and fixing C.P. brass towel ring with C.P. brass wall brackets
10 & C.P brass screws complete as required. Jaquar make cat. ACN- Each 54.00 54.00 793.11 42827.99
1121BN or EQUIVALENT
M.R. Providing, fixing, testing and commissioning of star white colour
vitreous china below / over counter Oval Wash Basin / circular
basin (Size 560 x 410 mm) with CP brass waste assembly complete Each 54.00 54.00 3743.95 202173.50
including CI / MS brackets duly painted, cutting and making good the
walls floors wherever jaquar make cat.no. FLS-WHT-0401 ,ALD-
709 or equivalent
M.R. Providing and fixing CP brass twin coat hooks fixed on toilet door/wall
12 with CP brass screws. Jaquar Make Cat. No ACN-1161N or Each 54.00 54.00 514.91 27805.23
M.R. Providing, fixing, testing and commissioning of C.P. brass single hole
sink mixer with CP wall flange, swinging spout complete as required
and making good. Jaquar Make Cat. No. KUB-35179B or
M.R. Supplying, Fixing , testing & commissioning of two way CP brass Bib
Cock with CP brass stop cock and ABS Heath Faucet (complete with
14 hook and flexible SS tube min. Length 1.0 m) as required. Jaquar Nos. 54.00 54.00 2743.36 148141.71
Make Cat. No. VGP-81041 , ALD-CHR-583 , LYR-38083 or
M.R. Providing, fixing, testing & commissioning of C.P. brass eurometic
15 self closing pillar tap. Jaquar Make Cat. No. 031] or EQUIVALENT Nos. 54.00 54.00 1809.74 97725.72
2 NBCC (I) Ltd.
LECTURE COMPLEX- 2 - Plumbing IIT Bhubneswar
Ite DSR - Description of Item Unit Total Balance DSR Rate MR RATE at DSR-Amount MR-Amount
m 2014 Quantity Quantity at which which item
No Code No. in to be item was was awarded
Original executed awarded in in original
Tender at Risk & original tender
M.R. Supply, Installation, Testing and commissioning of wall hanging drinking
online water cooler with bottle filler facility, made by stainless steel top and
heavy duty galvanized steel frame. With cooling capacity, ADA Compliant,
size 472 mm Depth X 447mm width, flexible bubbler guard , operated
between 50 to 120 PSI, Chiller unit Suitable to R134a Refrigerant, Adjustable
thermostat control, suitable for 220-230v/50-60 hz A/C Supply Complete
16 with all accessories which include MD-CU29, which is an EPA registered
antimicrobial copper that fights off microorganisms which include MRSA and
e-coli. The water Fountain shall possess NSF-USA, Green building, energy
star saving certification, and to be placed at different location of buidling.
Agency has to execute all civil work for installing the Water Fountain for
proper functioning and aesthetic view as directed by the engineer-in-charge
without any extra cost. (Oasis or Equivalent)
WITH 50 LPH RO System with 60 ltr HTP Storage tank Each 6.00 6.00 101773.29 610639.72
50 Lph RO System including with, RAW WATER PUMP, MICRON FILTER,
MEMBRANE HOUSING, Membrane Boosting Pump, RO Membranes, CONTROL Each 6.00 6.00 53228.26 319369.57
INSTRUMENTS, SKID Hanging with Pressure tank of capacity of 60 Ltr.
M.R. Providing and fixing in position storage type automatic electric water
heater pressure/ non pressure type thermostratically controlled, single
phase, vertical wall mounted of approved make ( to the approval of
Engineer-in-charge) with thermostats, inner container of stainless steel
17 complete with 1 Mtr three core flexible cord with plug, non return valve
and pressure release valve complete including fixing and testing complete
in all respect. Venus Make Model No. MAGMA-VERTICAL Allied
Jaquar Cat. No. ALD-805B or EQUIVALENT
50 litre capacity water heater Each 3.00 3.00 13735.69 41207.06
M.R. Providing & fixing of C.P. brass single hole basin mixer of approved quality:
(jaquar Or Equivalent)
M.R. Providing, fixing, testing and commissioning of shower including necessary
19 wall chases and making good. Make Cat. No. 281 KN] [Make Cat. No.
OHS-1985] [Make Cat. No. SHA-479 L450] or EQUIVALENT
Single lever wall mixer with spout, adjustable OH shower with arm and wall
flange complete with wall flange diverter assembly with Non-return Valves. Each 4.00 4.00 9337.25 37349.00
M.R. Providing and fixing lab sink for OTS, CONSULTANTS & OTHER AREAS of
20 approved quality complete will all respect as required and approved by Each 1.00 1.00 18377.44 18377.44
Engineer-in-charge. NAVELI OR EQUIVALENT
3 NBCC (I) Ltd.
LECTURE COMPLEX- 2 - Plumbing IIT Bhubneswar
Ite DSR - Description of Item Unit Total Balance DSR Rate MR RATE at DSR-Amount MR-Amount
m 2014 Quantity Quantity at which which item
No Code No. in to be item was was awarded
Original executed awarded in in original
Tender at Risk & original tender
M.R. Providing and fixing single bay SS janitor sink of approved quality complete
21 will all respect as required and approved by Engineer-in-charge. NAVELI Each 6.00 6.00 40044.27 240265.59
M.R. Providing and fixing adjustable type wash basin for handicap toilet complete
22 with brackets, tracks, waste pipes and other accessories complete as Each 6.00 6.00 50356.64 302139.85
required. [Presalit -Commander Make Cat. No. R4140]
M.R. Providing and fixing 2 Nos. support arms and backrest to mounted on the
23 track (vertically and laterally) for handicap toilet complete as required. Each 6.00 6.00 107448.63 644691.79
[Presalit -Commander Make Cat. No. R 3548 XXX & 6533]
M.R. Providing and fixing raised toilet seat with cover for handicap toilet [Presalit
-Commander Make Cat. No. R34000]
M.R. Providing and fixing ABS alloy steel grab bar. [Presalit -Commander Make
Cat. No. RT 100 XXX]
SUB HEAD - II - (SOIL, WASTE, RAIN WATER AND VENT PIPES)
4.1 Providing and laying in position cement concrete of specified grade excluding
1 the cost of centering and shuttering - All work up to plinth level:
4.1.3 1:2:4 (1 cement :2 coarse sand: 4 hard stone aggregate 20mm and
12.22 Making khurras 45x45 cm with average minimum thickness of 5 cm cement
concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate of 20
2 mm nominal size) over P.V.C. sheet 1 m x1 m x 400 micron, finished with 12 Each 28.00 28.00 196.14 5491.90
mm cement plaster 1:3 (1 cement : 3 coarse sand) and a coat of neat
cement, rounding the edges and making and finishing the outlet complete.
3 17. 35 Providing and fixing soil, waste and vent pipes.
17.35.1.2 Centrifugally cast (spun) iron socketed pipe as per IS:3989
17.35.2.2 Centrifugally cast (spun) iron socketed pipe as per IS:3989
17. 37 Providing and fixing M.S. holder-bat clamps of approved design to Sand Cast
iron/cast iron (spun) pipe embedded in and including cement concrete blocks
4 10x10x10 cm of 1:2:4 mix (1 cement : 2 coarse sand : 4 graded stone
aggregate 20 mm nominal size), including cost of cutting holes and making
good the walls etc.
4 NBCC (I) Ltd.
LECTURE COMPLEX- 2 - Plumbing IIT Bhubneswar
Ite DSR - Description of Item Unit Total Balance DSR Rate MR RATE at DSR-Amount MR-Amount
m 2014 Quantity Quantity at which which item
No Code No. in to be item was was awarded
Original executed awarded in in original
Tender at Risk & original tender
17. 38 Providing and fixing bend of required degree with access door, insertion
rubber washer 3 mm thick, bolts and nuts complete.
17.38.1.2 Sand cast iron S&S as per IS-3989
17.38.2.2 Sand cast iron S&S as per IS-3989
6 17. 39 Providing and fixing plain bend of required degree.
17.39.1.2 Sand cast iron S&S as per IS:3989
17.39.2. Sand cast iron S&S as per IS:3989
7 17. 40 Providing and fixing heel rest sanitary bend.
17.40.1.2 sand cast iron S&S as per IS-3989
17. 43 Providing and fixing single equal plain junction of required degree with
8 access door, insertion rubber washer 3mm thick, bolts and nuts complete.
17.43.1.2 sand cast iron S&S as per IS-3989
17.43.2. sand cast iron S&S as per IS-3989
9 17. 44 Providing and fixing single equal plain junction of required degree
17.44.1.2 sand cast iron S&S as per IS-3989
17.44.2. sand cast iron S&S as per IS-3989
17. 47 Providing and fixing single unequal junction of required degree with access
10 door, insertion rubber washer 3mm thick, bolts and nuts complete.
17.47.1.2 sand cast iron S&S as per IS-3989
5 NBCC (I) Ltd.
LECTURE COMPLEX- 2 - Plumbing IIT Bhubneswar
Ite DSR - Description of Item Unit Total Balance DSR Rate MR RATE at DSR-Amount MR-Amount
m 2014 Quantity Quantity at which which item
No Code No. in to be item was was awarded
Original executed awarded in in original
Tender at Risk & original tender
11 17. 56 Providing and fixing terminal guard.
17.56.1.2 sand cast iron S&S as per IS-3989
17.56.2.2 sand cast iron S&S as per IS-3989
12 17. 57 Providing and fixing collar
17.57.1.2 Sand cast iron S&S as per IS-3989
17.57.2. Sand cast iron S&S as per IS-3989
17. 58 Providing lead caulked joints to sand cast iron /centrifugally cast (spun) iron
pipes and fittings of diameter:
17. 59 Providing and fixing M.S. stays and clamps for sand cast iron / centrifugally
cast (spun) iron pipes of diameter :
17.60 Providing and fixing trap of self cleansing design with screwed down or
15 hinged grating with or without vent arm complete, including cost of cutting
and making good the walls and floors: (F.T. + U.T.)
17.60.1.1 100 mm inlet and 100 mm outlet (Sand cast iron S&S as per IS: 3989
17.65 Painting sand cast iron / centrifugally cast (spun) iron soil, waste vent
16 pipes and fittings with paint of any colour such as chocolate, grey, or buff
etc. over a coat of primer (of approved quality) for new work:
18.10 Providing and fixing G.I. pipes complete with G.I. fittings and clamps, i/c
17 cutting and making good the walls etc.
6 NBCC (I) Ltd.
LECTURE COMPLEX- 2 - Plumbing IIT Bhubneswar
Ite DSR - Description of Item Unit Total Balance DSR Rate MR RATE at DSR-Amount MR-Amount
m 2014 Quantity Quantity at which which item
No Code No. in to be item was was awarded
Original executed awarded in in original
Tender at Risk & original tender
M.R. Providing, fixing and jointing UV stabilized uPVC rain water pipes
conforming to IS:4985 (working pressure 6 kg/sqcm.) including all
18 fittings such as bends, clamps, tees, cowls, clean out plugs etc including
Fixing at wall / ceiling level supported by s SFMC OR EQUIVALENT
(I) Single socketed pipes
M.R. Providing & fixing 100mm x 50mm G.I. waste with reducing elbow &
19 nipple cutting chases, the floor / slab, repairs complete as required and Each 32.00 32.00 1290.11 41283.38
connection to GI / CI waste pipe. JINDAL OR EQUIVALENT
M.R. Providing and fixing Heavy Class SS grating with of approved design
20 including setting in floor with cement motor to match with floor finish as Each 32.00 32.00 227.28 7272.82
per architect requirement . SIZE - 100 X 100 MM Jayna OR
M.R. Providing and fixing Heavy Class SS grating with Cockroach proof SS
strainer of approved design including setting in floor with cement motor
20 to match with floor finish as per architect requirement suitable for waster Each 100.00 100.00 447.01 44700.63
and FT. SIZE - 100 MM
DIA Jayna (RRG 102) OR EQUIVALENT
M.R. Providing and fixing G.I. EXTENSION PIECE for 100 mm dia floor
trap formed out of main pipe (Type A) with multiple side inlets, suitable
21 for various dia pipes, side connections, including all fixtures and fittings Each 100.00 100.00 1320.29 132028.59
as per site conditions and as per standard details and water tight sealing
of joints and area surrounding the grating and as directed. Jindal OR
M.R. Providing and fixing clean out plug comprising of GI socket caulked to
pipe and cast brass plug with suitable inlet key for opening male threaded
22 joint with GI class 'C' pipe & socket. Including lead caulked to CI pipes
complete as required.Jayna OR EQUIVALENT
7 NBCC (I) Ltd.
LECTURE COMPLEX- 2 - Plumbing IIT Bhubneswar
Ite DSR - Description of Item Unit Total Balance DSR Rate MR RATE at DSR-Amount MR-Amount
m 2014 Quantity Quantity at which which item
No Code No. in to be item was was awarded
Original executed awarded in in original
Tender at Risk & original tender
M.R. Providing and fixing cleaning eye on horizontal CI soil & waste pipes of
300 mm long GI medium class pipe with one plain end lead caulked in to
the collar of CI pipe and the other end with flange which in covered by
23 neoprene rubber gasket and blank flange, complete with nuts, bolts etc
and hot dip galvanization after fabrication to the satisfaction of Engineer
in Charge GMGR OR EQUIVALENT
SUB HEAD - III - (WATER SUPPLY)
18.8 Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having
thermal stability for hot & cold water supply, including all CPVC plain & brass
threaded fittings, i/c fixing the pipe with clamps at 1.00 m spacing.This
1. includes jointing of pipes & fittings with one step CPVC solvent cement and
the cost of cutting chases and making good the same including testing of
joints complete as per direction of Engineer in Charge.
Concealed work, including cutting chases and making good the walls
18.8.1 15 mm nominal outer dia Pipes Mtr 750.00 750.00 283.73 212795.10
18.8.2 20 mm nominal outer dia Pipes Mtr 370.00 370.00 311.47 115243.52
18.8.3 25 mm nominal outer dia Pipes Mtr 250.00 250.00 369.16 92290.02
18.8.4 32 mm nominal outer dia Pipes Mtr 150.00 150.00 443.87 66581.22
MR 40 mm dia nominal bore Mtr 100.00 100.00 496.05 49604.90
MR 50 mm dia nominal bore Mtr 20.00 20.00 748.79 14975.73
18.10 Providing and fixing G.I. pipes complete with G.I. fittings and clamps, i/c
cutting and making good the walls etc.
Internal work - Exposed on wall
18.10.1 15 mm dia nominal bore Metre 25.00 25.00 226.04 5650.89
18.10.2 20 mm dia nominal bore Metre 25.00 25.00 261.97 6549.36
18.10.3 25 mm dia nominal bore Metre 40.00 40.00 319.61 12784.52
18.10.4 32 mm dia nominal bore Metre 35.00 35.00 360.65 12622.69
18.10.6 50 mm dia nominal bore Metre 80.00 80.00 554.00 44320.23
M.R. 65 mm dia nominal bore Metre 60.00 60.00 779.91 46794.75
M.R. 80 mm dia nominal bore Metre 30.00 30.00 984.55 29536.59
M.R. 100 mm dia nominal bore Metre 15.00 15.00 1304.25 19563.75
18.17 Providing and fixing gun metal gate valve with C.I. wheel of approved
(screwed end) :
8 NBCC (I) Ltd.
LECTURE COMPLEX- 2 - Plumbing IIT Bhubneswar
Ite DSR - Description of Item Unit Total Balance DSR Rate MR RATE at DSR-Amount MR-Amount
m 2014 Quantity Quantity at which which item
No Code No. in to be item was was awarded
Original executed awarded in in original
Tender at Risk & original tender
18.38 Painting G.I. pipes and fittings with synthetic enamel white paint with two
4 coats over a ready mixed priming coat, both of approved quality for new
18.38.1 15 mm dia nominal bore Metre 25.00 25.00 10.09 252.20
18.38.2 20 mm dia nominal bore Metre 25.00 25.00 11.93 298.18
18.38.3 25 mm dia nominal bore Metre 40.00 40.00 15.71 628.40
18.38.4 32 mm dia nominal bore Metre 35.00 35.00 18.60 651.00
18.38.5 40 mm dia nominal bore Metre 230.00 230.00 22.07 5075.56
18.38.6 50 mm dia nominal bore Metre 80.00 80.00 26.01 2080.66
Derived 65 mm dia nominal bore
Derived 80 mm dia nominal bore
Derived 100 mm dia nominal bore
18.40 Painting G.I. pipes and fittings with two coats of anti-corrosive bitumastic
5 paint of approved quality :
18.40.3 25 mm diameter pipe metre 30.00 30.00 9.19 275.85
18.53 Providing and fixing C.P. brass angle valve for basin mixer and geyser points
of approved quality conforming to IS:8931
M.R. BUTTERFLY VALVE WITH ON/OFF TYPE MOTORIZED ACTUATOR Single
phase 220V with limit switches, C I body & PN 16 pressure rating SS Disc
7 & shaft of Feedback, BMS Compatible for overhead tank filling as specified
duly insulated of following sizes as per specified AIP OR EQUIVALENT
M.R. 32 mm dia nominal bore Each 1.00 1.00 16368.71 16368.71
M.R. 40 mm dia nominal bore Each 1.00 1.00 16787.43 16787.43
9 NBCC (I) Ltd.
LECTURE COMPLEX- 2 - Plumbing IIT Bhubneswar
Ite DSR - Description of Item Unit Total Balance DSR Rate MR RATE at DSR-Amount MR-Amount
m 2014 Quantity Quantity at which which item
No Code No. in to be item was was awarded
Original executed awarded in in original
Tender at Risk & original tender
M.R. Providing and fixing Nitrile Rubber Insulation 9 mm thick on hot water
8 supply/return pipes without outer mechanical protection SUPREME OR
15 mm dia. (9 mm thickness) Metre 50.00 50.00 82.98 4149.24
20 mm dia. (9 mm thickness) Metre 20.00 20.00 89.59 1791.89
25 mm dia. (9 mm thickness) Metre 10.00 10.00 100.91 1009.12
M.R. Providing & fixing full way lever operated forged brass ball valve of
brass body with forged brass hard chrome plated steel ball tested to a
9 pressure not less than 10 Kg / sqcm with threaded / flanged joints
complete with nuts, bolts, gaskets, washers ZOLOTO OR
M.R. Providing and fixing Butter fly valve with nitrile seat and stainless steel
stem with lever operation and cast iron body in powder coated finish,
10 suitable for test pressure of 10Kg/sq.mm) with flanges, gaskets and
necessary pad locking arrangement complet ZOLOTO OR
SUB HEAD - IV - (SEWERAGE AND DRAINAGE)
2.6 Earth work in excavation by mechanical means (Hydraulic excavator)/manual
means over areas (exceeding 30 cm in depth 1.5m in width as well as 10
1 sqm on plan) including disposal of excavated earth, lead upto 50m and lift
upto 1.5m, disposed earth to be leveled and neatly dressed. (For Manholes)
2.10 Excavating trenches of required width for pipes, cables, etc including
excavation for sockets, and dressing of sides, ramming of bottoms, depth
upto 1.5 m, including getting out the excavated soil, and then returning the
2 soil as required, in layers not exceeding 20 cm in depth, including
consolidating each deposited layer by ramming, watering, etc. and disposing
of surplus excavated soil as directed, within a lead of 50 m.
2.10.1.2 Pipes, cables etc. exceeding 80mm dia. But not exceeding 300mm dia. Metre 540.00 540.00 218.89 118200.58
2.11 Extra over for item no. 1.1 excavating trenches for pipes, cables etc. in all
3 kinds of soil for depth exceeding 1.5 m, but not exceeding 3 m. (Rate is over Metre 40.00 40.00 297.69 11907.61
corresponding basic item for depth up to 1.5 metre)
10 NBCC (I) Ltd.
LECTURE COMPLEX- 2 - Plumbing IIT Bhubneswar
Ite DSR - Description of Item Unit Total Balance DSR Rate MR RATE at DSR-Amount MR-Amount
m 2014 Quantity Quantity at which which item
No Code No. in to be item was was awarded
Original executed awarded in in original
Tender at Risk & original tender
19.1 Providing, laying and jointing glazed stoneware pipes class SP-1 with stiff
4 mixture of cement mortar in the proportion of 1:1 (1 cement : 1 fine sand)
including testing of joints etc. complete:
19.2 Providing and laying cement concrete 1:5:10 (1 cement : 5 fine sand : 10
5 graded stone aggregate 40 mm nominal size) alround S.W. pipes including
bed concrete as per standard design:
19.3 Providing and laying cement concrete 1:5:10 (1 cement : 5 coarse sand : 10
6 graded stone aggregate 40 mm nominal size) up to haunches of RCC pipes
including bed concrete as per standard design :
19.4 Providing and fixing square-mouth S.W. gully trap class SP-1 complete with
C.I. grating brick masonry chamber with water tight C.I. cover with frame of
7 300 x300 mm size (inside) the weight of cover to be not less than 4.50 kg
and frame to be not less than 2.70 kg as per standard design:
19.4.1 100x100 mm size P type
19.4.1.1 With common burnt clay F.P.S. (non modular) bricks of class designation 7.5
19.6 Providing and laying non-pressure NP2 class (light duty) R.C.C. pipes with
8 collars jointed with stiff mixture of cement mortar in the proportion of 1:2 (1
cement : 2 fine sand) including testing of joints etc. complete.
19.7 Constructing brick masonry manhole cement mortar 1:4 (1 cement : 4
coarse sand) R.C.C. top slab with 1:2:4 mix ( 1cement : 2 coarse sand : 4
graded stone aggregate 20 mm nominal size ), foundation concrete 1:4:8
mix (1cement : 4 coarse sand : 8 graded stone aggregate 40 mm nominal
9 size) inside plastering 12mm thick with cement mortar 1:3 (1 cement : 3
coarse sand) finished with floating coat of neat cement and making
necessary channels in cement concrete 1:2:4 (1 cement : 2 coarse sand : 4
graded stone aggregate 20mm nominal size) finished with a floating coat of
neat cement complete as per standard design.
11 NBCC (I) Ltd.
LECTURE COMPLEX- 2 - Plumbing IIT Bhubneswar
Ite DSR - Description of Item Unit Total Balance DSR Rate MR RATE at DSR-Amount MR-Amount
m 2014 Quantity Quantity at which which item
No Code No. in to be item was was awarded
Original executed awarded in in original
Tender at Risk & original tender
19.7.1 Inside size 90 x 80 cm and 90 cm deep including C.I. cover with frame (light
duty) 455 x 610 mm internal dimensions total weight of cover and frame to
be not less than 38 kg (weight of cover 23 kg and weight of frame 15 kg)
19.7.1.1 With F.P.S. bricks with class designation 7.5 Each 14.00 14.00 8939.50 125152.94
19.7.2 Inside size 120 x 90 cm and 90 cm deep including C.I. cover with frame
(medium duty) 500 mm internal diameter, total weight of cover and frame to
be not less than 116 kg (weight of cover 58 kg and weight of frame 58 kg)
19.7.2.1 With F.P.S. bricks with class designation 7.5 Each 10.00 10.00 19235.05 192350.48
10 19.8 Extra depth for manholes
19.8.1.1 Size 90 x 80 cm (With With F.P.S. bricks with class designation 7.5) Metre 2.00 2.00 5924.85 11849.69
19.8.2.1 Size 120x 90 Cm (With F.P.S. bricks with class designation 7.5) Metre 2.00 2.00 7097.01 14194.01
19.16 Providing orange colour safety foot rest of minimum 6 mm thick plastic
encapsulated as per IS: 10910 on 12 mm dia steel bar conforming to IS :
1786 having minimum cross section as 23 mm x 25 mm and over all
minimum length 263 mm and width as 165 mm with minimum 112 mm
space between protruded legs having 2 mm tread on top surface by ribbing
or chequering besides necessary and adequate anchoring projections on tail
length on 138 mm as per standard drawing and suitable to with stand the
bend test and chemical resistance test as per specification and having
manufacture's permanent identification mark to be visible even after fixing,
including fixing in manholes with 30 x 20 x 15 cm cement concrete block
1:3:6 (1 cement : 3 coarse sand : 6 graded stone aggregate 20 mm
nominal size) complete as per design.
19.27 Constructing brick masonry road gully chamber 50x45x60 cm with bricks in
12 cement mortar 1:4 (1 cement : 4 coarse sand) including 500x450 mm pre-
cast R.C.C. horizontal grating with frame complete as per standard design :
19.27.1 With common burnt clay F.P.S. (non modular) bricks of class designation 7.5
M.R. Constructing brick masonry surface drain with bricks of class designation 7.5
in cement mortar 1:4 (1 cement : 4 coarse sand) including earth excavation,
10cm thick bed concrete 1:5:10 (1 cement : 5 coarse sand : 10 graded
stone aggregate 40 mm nominal size) and 25 mm thick cement concrete
1:2:4 (1 cement 2 coarse sand 4 graded stone aggregate 12.5 mm
13 nominal size) for filling haunches including 12 mm cement plaster 1:4 (1
cement : 4 coarse sand) with a floating coat of neat cement inside the
drain, its top and exposed side and 12mm thick external plaster with cement
mortar 1:6 (1 cement : 6 coarse sand) including connection to existing drain
and disposal of surplus earth.
30 cm drain 50cm average depth Metre 30.00 30.00 2068.14 62044.12
12 NBCC (I) Ltd.
LECTURE COMPLEX- 2 - Plumbing IIT Bhubneswar
Ite DSR - Description of Item Unit Total Balance DSR Rate MR RATE at DSR-Amount MR-Amount
m 2014 Quantity Quantity at which which item
No Code No. in to be item was was awarded
Original executed awarded in in original
Tender at Risk & original tender
14 M.R. Extra for additional depth for brick masonry surface drain.
30 cm drain 50cm average depth 1.00 1.00 682.77 682.77
M.R. Supplying and fixing of Ductile Iron grating of 350 x 750 x 40 mm
(LXW),Bar Design, with Drainlock to suit the above channel, with inlet
15 section 1673 cm²/weighing 28.0 kg/unit for D 400 Load class according Each 30.00 30.00 10761.27 322838.22
to DIN EN 1433 complete in all respects as per manufacturers
specifications. FOR DRAIN COVER
SUB HEAD - V - EXTERNAL WATER SUPPLY
4.1 Providing and laying in position cement concrete of specified grade excluding
1 the cost of centering and shuttering - All work up plinth level (for thrust
4.1.3 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal
18.12 Providing and fixing medium grade G.I. pipes complete with G.I. fittings
including trenching and refilling etc. (external work)
18.12.3 25 mm dia nominal bore Metre 5.00 5.00 270.38 1351.91
18.12.5 40 mm dia nominal bore Metre 60.00 60.00 351.14 21068.29
18.32 Constructing masonry Chamber 30 x 30 x 50 cm, inside with 75 class
designation brick work in cement mortar 1:4 (1 cement : 4 fine sand) for
sluice valve, with C.I. surface box 100mm top diameter, 160 mm bottom
diameter and180 mm deep (inside) with chain lid and RCC top slab 1:2:4
3 mix (1 cement : 2 coarse sand : 4 graded stone aggregate 20mm nominal
size) necessary excavation foundation concrete 1:5:10 (1 cement : 5 fine
sand : 10 graded stone aggregate 40 mm nominal size) and inside plastering
with cement mortar 1:3 (1 cement :3 coarse sand) 12 mm thick finished with
a floating coat of neat cement complete as per standard design.
18.32.1 With common burnt clay F.P.S.(non modular) bricks of class designation 7.5
18.33 Constructing masonry Chamber 60x60x75 cm inside, in brick work in cement
mortar 1:4 (1 cement : 4 coarse sand) for sluice valve, with C.I. surface box
100mm top diameter, 160 mm bottom diameter and 180 mm deep ( inside)
with chained lid and RCC top slab 1:2:4 mix (1 cement : 2 coarse sand : 4
4 graded stone aggregate 20mm
nominal size ) , i/c necessary excavation, foundation concrete 1:5:10 (1
cement : 5 fine sand : 10 graded stone aggregate 40 mm nominal size) and
inside plastering with cement mortar 1:3 (1 cement : 3 coarse sand) 12 mm
thick, finished with a floating coat of neat cement complete as per standard
18.33.1 With common burnt clay F.P.S.(non modular) bricks of class designation 7.5
13 NBCC (I) Ltd.
LECTURE COMPLEX- 2 - Plumbing IIT Bhubneswar
Ite DSR - Description of Item Unit Total Balance DSR Rate MR RATE at DSR-Amount MR-Amount
m 2014 Quantity Quantity at which which item
No Code No. in to be item was was awarded
Original executed awarded in in original
Tender at Risk & original tender
18.41 Providing and filling sand of grading zone V or coarser grade alround the G.I.
pipes in external work.
18.41.3 25 mm dia nominal bore Metre 5.00 5.00 72.56 362.80
18.41.5 40 mm dia nominal bore Metre 60.00 60.00 75.40 4523.87
MR Providing, fixing, joints and testing in position the following UPVC Pipe
conferming to IS:4985 of 6kg sqcm for garden irrigation system cut to
6 required length pipe to be laid below level in trenches up to required
depth, including excavation & backfilling etc. all complete. SFMC OR
MR Providing & fixing in position 25 mm dia lawn hydrants consisting of 25
7 mm dia Ball valve, GI nipple and threaded hose receiver complete as Each 6.00 6.00 969.46 5816.78
required. ZOLOTO OR EQUIVALENT
SUBHEAD - VI - SUBMERSIBLE TRANSFER PUMPS
MR Supply, assembly, erection, testing and commissioning of SS submersible
non-clog pumps, having the following capacities with vortex impeller /
grinder type, complete with 3 phase squirrel cage submersible motor of
required HP for 415 ± 10% volts, 3 phase, 50 Hz. A.C. supply cooled by
1 surrounding liquid, submersible cable upto main panel within the plant
room, dry running preventor, G.I. guide pulling chain, all the necessary
piping and accessories, valves, delivery header etc. as required complete
in all respects. The rate will include electrical panel with cyclic operation
as supplied by the manufacturers)
The above installation shall be complete with sump pump lifting
assembly, ready made electro – galvanized MS lifting chain, GI pipe
header complete with discharge manifold, flanges, tee, elbow etc.
complete including GI pipe upto the top of sump and including GI union.
Header shall be sized for both pump working under delivery velocity of
Capacity of 100 lpm against a total head of 50 m (solid handling 5-8 mm)
(Domestic water transfer from UGT to OHT) (1 Working + 1 Stand by) Set 1.00 1.00 134497.52 134497.52
(SS Body and SS Impeller and shaft)
Capacity of 100 lpm against a total head of 50m (solid handling 5-8 mm)
(Flushing water transfer from UGT to OHT) (1 Working + 1 Stand by) (SS Set 1.00 1.00 134497.52 134497.52
Body and SS Impeller and shaft)
14 NBCC (I) Ltd.
LECTURE COMPLEX- 2 - Plumbing IIT Bhubneswar
Ite DSR - Description of Item Unit Total Balance DSR Rate MR RATE at DSR-Amount MR-Amount
m 2014 Quantity Quantity at which which item
No Code No. in to be item was was awarded
Original executed awarded in in original
Tender at Risk & original tender
MR Supplying, assembly, erection, testing and commissioning of magnetic level
sensors and controllers, CPVC probe tube, PP actuating float and all other
equipment required for the performance of the system to the satisfaction of
2 the engineer in charge complete including providing and fixing wiring from
control junction box near the OH tank to probes of required length,
interconnection wiring between level controller and the concerned contactor
in the starter panel as required. The level controller will perform the following
To switch on the pumps of DOMESTIC TRANSFER PUMP AND FLUSHING
TRANSFER PUMP FOR OHT FILLING when the level of water in the supply
water tank is low and to cut off the pump when the level in the receiving
water tank is high and switch off the pumps when the level of water in the
supply water tank is low.
To indicate 5 levels of water in all tanks through a control panel with LEDs
To start the pumps in a cyclic order.
The system shall be complete to ensure automatic quotation of pump in
accordance to water level in respective tanks.
The Contractor will include all the over head tanks and all the pumps as
required for level control in this item
TOTAL CARRIED TO SUMMARY 310031.41
SUB HEAD - VII - (RAIN WATER HARVESTING)
2.8 Earth work in excavation by mechanical means (Hydraulic excavator)
/ manual means in foundation trenches or drains (not exceeding 1.5
m in width or 10 sqm on plan), including dressing of sides and
ramming of bottoms, lift upto 1.5 m, including getting out the
excavated soil and disposal of surplus excavated soil as directed,
within a lead of 50 m.
2.25 Filling available excavated earth (excluding rock) in trenches, plinth,
sides of foundations etc. in layers not exceeding 20cm in depth,
consolidating each deposited layer by ramming and watering, lead up
to 50 m and lift upto 1.5 m.
2.26 Extra for every additional lift of 1.5 m or part thereof in excavation /
banking excavated or stacked materials.
4.1 Providing and laying in position cement concrete of specified grade
4 excluding the cost of centering and shuttering - All work up to plinth
4.1.8 1:4:8 (1 Cement : 4 coarse sand : 8 graded stone aggregate 40 mm
5.1 Providing and laying in position specified grade of reinforced cement
5 concrete, excluding the cost of centering, shuttering, finishing and
reinforcement - All work up to plinth level :
15 NBCC (I) Ltd.
LECTURE COMPLEX- 2 - Plumbing IIT Bhubneswar
Ite DSR - Description of Item Unit Total Balance DSR Rate MR RATE at DSR-Amount MR-Amount
m 2014 Quantity Quantity at which which item
No Code No. in to be item was was awarded
Original executed awarded in in original
Tender at Risk & original tender
5.1.3 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm
5.9 Centering and shuttering including strutting, propping etc. and
removal of form for :
5.9.3 5.9.3 Suspended floors, roofs, landings, balconies and access platform
5.22 Steel reinforcement for R.C.C. work including straightening, cutting,
7 bending, placing in position and binding all complete upto plinth level.
5.22.6 Thermo-Mechanically Treated bars kg 3159.52 3159.52 71.56 226101.86
6.1 Brick work with common burnt clay F.P.S. (non modular) bricks of
class designation 7.5 in foundation and plinth in:
6.1.2 Cement mortar 1:6 (1 cement : 6 coarse sand) cum 50.00 50.00 4915.04 245752.07
9 13.1 12 mm cement plaster of mix :
19.16 Providing orange colour safety foot rest of minimum 6 mm thick
plastic encapsulated as per IS : 10910, on 12 mm dia steel bar
conforming to IS: 1786, having minimum cross section as 23 mmx25
mm and over all minimum length 263 mm and width as 165 mm with
minimum 112 mm space between protruded legs having 2 mm tread
on top surface by ribbing or chequering besides necessary and
adequate anchoring projections on tail length on 138 mm as per
10 standard drawing and suitable to with stand the bend test and each 27.00 27.00 327.44 8840.93
chemical resistance test as per specifications and having
manufacture’s permanent identification mark to be visible even after
fixing, including fixing in manholes with 30x20x15 cm cement
concrete block 1:3:6 (1 cement : 3 coarse sand : 6 graded stone
aggregate 20 mm nominal size) complete as per design.
19.19 Providing and fixing in position pre-cast R.C.C. manhole cover and
of required shape and approved quality 19.19.1 L D- 2.5
19.19.4. Circular shape 560 mm internal dia
16 NBCC (I) Ltd.
LECTURE COMPLEX- 2 - Plumbing IIT Bhubneswar
Ite DSR - Description of Item Unit Total Balance DSR Rate MR RATE at DSR-Amount MR-Amount
m 2014 Quantity Quantity at which which item
No Code No. in to be item was was awarded
Original executed awarded in in original
Tender at Risk & original tender
24.1 Boring/drilling bore well of required dia for casing/ strainer pipe, by
suitable method prescribed in IS: 2800 (part I), including collecting
samples from different strata, preparing and submitting strata chart/
12 bore log, including hire & running charges of all equipments, tools,
plants & machineries required for the job, all complete as per
direction of Engineer -in-charge, upto 90 metre depth below ground
24.1.1 All types of soil
24.1.1.1 300 mm dia metre 407.10
24.2 Boring/drilling bore well of required dia for casing/ strainer pipe, by
suitable method prescribed in IS: 2800 (part I), including collecting
samples from different strata, preparing and submitting strata chart/
13 bore log, including hire & running charges of all equipments, tools,
plants & machineries required for the job, all complete as per
direction of Engineer -in-charge, beyond 90 metre & upto 150 metre
depth below ground level.
24.2.1 All types of soil
24.3 Supplying, assembling, lowering and fixing in vertical position in bore
well, unplasticized PVC medium well casing (CM) pipe of required dia,
14 conforming to IS: 12818, including required hire and labour charges,
fittings & accessories etc. all complete, for all depths, as per direction
of Engineer-in-charge.
24.3.2 150 mm nominal size dia
24.4 Supplying, assembling, lowering and fixing in vertical position in bore
well unplasticized PVC medium well screen (RMS) pipes with ribs,
15 conforming to IS: 12818, including hire & labour charges, fittings &
accessories etc. all complete, for all depths, as per direction of
Engineer-in-charge.
24.4.2 24.4.2 150 mm nominal size dia metre 528.95
24.5 Supplying, filling, spreading & leveling stone boulders of size range 5
cm to 20 cm, in recharge pit, in the required thickness, for all leads &
lifts, all complete as per direction of Engineer-in-charge. cum 504.15
24.6 Supplying, filling, spreading & leveling gravels of size range 5 mm to
10 mm, in the recharge pit, over the existing layer of boulders, in
required thickness, for all leads & lifts, all complete as per direction of
Engineer-incharge.
17 NBCC (I) Ltd.
LECTURE COMPLEX- 2 - Plumbing IIT Bhubneswar
Ite DSR - Description of Item Unit Total Balance DSR Rate MR RATE at DSR-Amount MR-Amount
m 2014 Quantity Quantity at which which item
No Code No. in to be item was was awarded
Original executed awarded in in original
Tender at Risk & original tender
24.7 Supplying, filling, spreading & leveling coarse sand of size range 1.5
mm to 2 mm in recharge pit, in required thickness over gravel layer,
for all leads & lifts, all complete as per direction of Engineer -in-
24.8 Gravel packing in tubewell construction in accordance with IS: 4097,
including providing gravel fine/ medium/ coarse, in required grading
& sizes as per actual requirement, all complete as per direction of
Engineerin- charge.
24.9 Providing and fixing factory made precast RCC perforated drain
covers, having concrete of strength not less than M-25, of size 1000 x
450x50 mm, reinforced with 8 mm dia four nos longitudinal & 9 nos
20 cross sectional T.M.T. hoop bars, including providing 50 mm dia each 5.00 5.00 1009.02 5045.08
perforations @ 100 to 125 mm c/c, including providing edge binding
with M.S. flats of size 50 mm mm x 1.6 mm complete, all as per
direction of Engineer-in-charge.
24.13 24.13 Providing and fixing suitable size threaded mild steel cap or
spot welded plate to the top of bore well housing/ casing pipe,
removable as per requirement, all complete for borewell of:
24.14 24.14 Providing and fixing M.S. clamp of required dia to the top of
22 casing/housing pipe of tubewell as per IS: 2800 (part I), including
necessary bolts & nuts if required size complete.
24.14.2 150 mm clamp
24.15 Providing and fixing Bail plug/ Bottom plug of required dia to the
23 bottom of pipe assembly of tubewell as per IS:2800 (part I).
TOTAL CARRIED TO SUMMARY 1023429.35
18 NBCC (I) Ltd.
LECTURE COMPLEX-2-Electrical IIT, Bhubaneswar
SCHEDULE OF QUANTITIES FOR PROVIDING, INSTALLATION, TESTING & COMMISSIONING
OF DISTRIBUTION OF L.T. PANELS ETC. FOR LECTURE HALL-2, IIT BHUBNESWAR
SUMMARY OF COST
DSR Amount MR Amount
S. No. Item Description
1 SUB HEAD - I: MAIN PANEL - 774,109.04
2 SUB HEAD - II - UPS - 879,593.26
SUB HEAD - III- LT CABLES, RACE WAYS, CABEL TRAYS &
4 SUB HEAD - IV - Point Wiring 721,094.19 -
5 SUB HEAD - V -Distribution Board 257,637.60 -
6 SUB HEAD -VI - Light Fitting and Fans 151,439.70 13,854,168.48
7 SUB HEAD -VII - Data and TV points 123,903.91 24,121.21
8 SUB HEAD - VIII - EXTERNAL LIGHTING 18,494.78 909,049.00
9 SUB HEAD - IX - ADDRESSABLE FIRE ALARM SYSTEM - 7,025,768.05
10 SUB HEAD - X - CCTV SURVEILLANCE SYSTEM 386,629.99 10,265,532.00
11 SUB-HEAD - XII - LIGHTNING CONDUCTOR 29,684.13 -
TOTAL DSR + MR 36,004,043.65
LECTURE COMPLEX-2- Electrical IIT, Bhubaneswar
SCHEDULE OF QUANTITIES FOR PROVIDING, INSTALLATION, TESTING & COMMISSIONING OF DISTRIBUTION OF L.T. PANELS ETC. FOR LECTURE HALL-2, IIT BHUBNESWAR
S. DSR DESCRIPTION OF ITEM Total Balance DSR Rate MR RATE at DSR Amount MR Amount (Rs.)
NO. 2014 Quantity Quantity at which which item (Rs.)
in to be item was was
executed awarded awarded in
Tender at Risk & in original
Cost original tender
SUB HEAD - I: MAIN PANEL
Design, fabrication, supplying, assembling, erecting, connecting, testing and
commissioning of dust,damp and vermin proof free floor standing sheet steel
enclosed non-drawout moduler type LT Panel, fabricated out of suitable sized
angle iron and flats, base channel and covered with 2.0mm thick CRCA sheet,
duly painted complete with earth bus, aluminium bus bar, numbering & sign
writing, interconnection & including the cost of connection through bus bar /
copper conductor flexible connection with necessary interlocking with existing
panel as shown in drawing as per specification and mounted with the followings.
Trafo and DG incomers alongwith buscoupler shall be colour coded
compartment.The Panel shall have IP-54 rating of form-4.
1 Nos.630amps, 415V 4P MCCB '25ka' with overcurrent and short circuit TM
1 Set of three phase R,Y,B, ON indicating lamps, along with 2A SP MCB backup
Three phase and neutral Aluminium extensible type busbars rated at 415V, 800
amps capacity insulated with heat shrinkable coloured PVC sleeves.
Following rated 415V, MCCB's with overcurrent and short circuit releases, all
indication, front operating handle & door interlock with Multifunction Meter with
Volt, Amp and KWH etc. complete with RS Port in all respects as mentioned in
specifications and as required. For each outgoing:
160A, FP, 25KA, MCCB manually operated - 5 No.(1 for light power panel + 3
no. for Ventilation + 1 spare)
63A, FP, 25KA, MCCB manually operated - 10 No. ( 3 no. for AC +1 No. For Lift
Panel + 1 No. For Fire Fighting Panel + 1 external lighting + 1 UPS + 3 spare )
2 LIGHT POWER PANEL
1 NBCC (I) Ltd.
LECTURE COMPLEX-2- Electrical IIT, Bhubaneswar
S. DSR DESCRIPTION OF ITEM Total Balance DSR Rate MR RATE at DSR Amount MR Amount (Rs.)
NO. 2014 Quantity Quantity at which which item (Rs.)
in to be item was was
executed awarded awarded in
Tender at Risk & in original
Cost original tender
Design,fabrication,supplying, assembling, erecting, testing and commissioning of tender
wall mounted /floor mounted cubical type compartmentalised dust, damp &
vermin proof Light & power Panel fabricated out of suitable sized angle iron and
flats and covered with 2mm thick cold rolled CRCA sheet painting etc. complete
with Al. bus bars, interconnection with solid/stranded copper conductor wires
copper strips neutral links, etc. and mounted with with 1 No 0-500V, Voltmeter,
selector switch, 1 set (3 Nos) of phase indicating lamps, ammeter with CTs etc.
as required. The Panel shall have IP-42 rating .The Panel will also include
fabrication of dual energy meter box with space provision of single or three
phase Prepaid dual source type electronic energy Meter as per
Incoming/outgoing requirement or as per SLD with all necessary power wiring
for dual metering with MS support for meter fixing , windows for meter reading
inculding supply and fixing of MCB"s, main frame fabricated out of 2mm in
cubical formati Ho
1 Nos. 160amps, 415V 4P MCCB '25ka' with overcurrent and short circuit TM
1 Set of three phase R,Y,B, ON indicating lamps, along with 2A SP MCB backup
Three phase and neutral Aluminium extensible type busbars rated at 415V, 250
amps capacity insulated with heat shrinkable coloured PVC sleeves.
Following rated 415V, MCCB's with overcurrent and short circuit releases, all
indication, front operating handle & door interlock with Multifunction Meter with
Volt, Amp and KWH etc. complete with RS Port in all respects as mentioned in
specifications and as required. For each outgoing:
All outgoing feeders shall be provided with On indicating lamp with 2 A SP MCB
13 Nos. 63A 4P MCB with 10kA Breaking Capacity ( 12Nos. for Light & Power
4 Nos. 40A 4P MCB with 10kA Breaking Capacity ( 3 Nos. for Light & power DB
Metering Panel Described as above. Set 1.00 1.00 112256.36 112256.36
3 Lift Panel (2 lifts)
Supplying, assembling, erecting, connecting, testing and commissioning of dust,
damp and vermin proof wall mounting factory built sheet steel enclosed non-
drawout modular type Panel fabricated out of suitable sized angle iron and flats,
base channel and covered with 2.0mm thick PCRC sheet, duly painted complete
with earth bus, aluminium bus bar, numbering & sign writing, interconnection &
including the cost of connection through bus bar / copper conductor flexible
connection with necessary interlocking with existing panel as shown in drawing
as per specification and mounted with the followings.
2 NBCC (I) Ltd.
LECTURE COMPLEX-2- Electrical IIT, Bhubaneswar
S. DSR DESCRIPTION OF ITEM Total Balance DSR Rate MR RATE at DSR Amount MR Amount (Rs.)
NO. 2014 Quantity Quantity at which which item (Rs.)
in to be item was was
executed awarded awarded in
Tender at Risk & in original
Cost original tender
1 No. 63 Amp 4 pole MCCB '25ka' with ON/OFF indicating lamp
1 Set of three phase R,Y,B, ON indicating lamps, along with 2A SP MCB backup
Digital flush type class - 1.0 accuracy Amp. Cum Volt meter showing V, A with 3
Nos. current transformers of suitable ratio, 10 VA Class 1.0 metering.
100Amps including in different sections of the panel for connection to various
outgoing feeders as per drawing.
a) 63 Amp 4P MCB '10ka' - 3 Nos.
b) 32 Amp DP MCB '10ka' - 2 Nos.
Lift Panel as above Set 1.00 1.00 64250.76 64250.76
Supplying, Installation, Testing and Commissioning of dust, damp and vermin
proof free floor standing / wall mounted factory built sheet steel enclosed
modular construction extendable panel, suitable for operation on 415 + 10%
volts, 50 Hz AC 3 phase 4 wire system fabricated out of suitable sized square
tubular section and covered with 2.0mm thick CRCA sheet, hinged doors of
1.6mm thick CRCA sheet, duly painted complete with aluminium bus bars,
interconnection with solid copper conductor wires / aluminium strips, neutral
links, earth bus etc. necessary metering protections & indications and mounted
with the following as per drawing and technical specifications attached etc.
complete as required.
1 No. of 63 Amp 4P MCCB of 25 kA Breaking capacity with On Indicating Lamp
with 2A SP MCB back-up.
100 Amp. 4P Al. Bus Bar
63A 4P MCB of 10kA Breaking Capacity - 4 Nos.
40A DP MCB of 10kA Breaking Capacity - 7 Nos. (6 for DB + 1no. Spare) Set 1.00 1.00 44242.78 44242.78
Total 774109.04
SUB HEAD - II - UPS
3 NBCC (I) Ltd.
LECTURE COMPLEX-2- Electrical IIT, Bhubaneswar
S. DSR DESCRIPTION OF ITEM Total Balance DSR Rate MR RATE at DSR Amount MR Amount (Rs.)
NO. 2014 Quantity Quantity at which which item (Rs.)
in to be item was was
executed awarded awarded in
Tender at Risk & in original
Cost original tender
Supply, Installation, Testing and Commissioning of (3 phase IN & 3 phase OUT) tender
UPS system suitable for input and output parameters strictly as per
specifications. The system shall be provided in powder coated fan cooled
enclosure painted in colour as per specifications. The system shall be suitable for
1 MR normal, emergency, recharge, by-pass and maintenance mode. The system be
expandable in such a manner that addition of another module of similar capacity
can double the system output with common by-pass. inverter shall have own
batteries with 15 minute battery back-up. System shall have a voltage range of
1.1 10 KVA UPS described as above Each 2.00 2.00 439796.63 879593.26
Total 879593.26
SUB HEAD - III- LT CABLES, RACE WAYS, CABEL TRAYS & EARTHING
Supply, laying, testing and commissioning of 1.1 kv grade XLPE insulated PVC
sheathed steel armoured alluminium stranded conductor ISI marked LT Cables
in trenches/ ducts/ through RCC pipes under roads/ on cable trays of following
1 MR sizes, complete all as specified (as per CPWD specifications for External Electrical
works), i/c clamping, dressing, earth work digging, sand filling, bricks protection,
back filling etc. as required & approved by Engineer's Incharge. (Tagging to be
provided with aluminium strips on both the ends as approved).
Supplying and making end termination with double brass compression gland and
2 9.1 aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE
aluminium conductor cable of 1.1 kV grade as required.
4 NBCC (I) Ltd.
LECTURE COMPLEX-2- Electrical IIT, Bhubaneswar
S. DSR DESCRIPTION OF ITEM Total Balance DSR Rate MR RATE at DSR Amount MR Amount (Rs.)
NO. 2014 Quantity Quantity at which which item (Rs.)
in to be item was was
executed awarded awarded in
Tender at Risk & in original
Cost original tender
Supplying and installing following size of perforated pre-painted M.S. cable trays tender
with perforation not more than 17.5%, in convenient sections, joined with
3 4.1 connectors, suspended from the ceiling with M.S. suspenders including bolts &
suspenders etc as required..
3.1 4.1.6 450 mm width X 50 mm depth X 2.0 mm thickness Mtr 40.00 40.00 1173.79 46951.53
3.2 4.1.4 300 mm width X 50 mm depth X 1.6 mm thickness Mtr 80.00 80.00 829.11 66329.02
3.3 4.1.2 150 mm width X 50 mm depth X 1.6 mm thickness Mtr 150.00 150.00 546.44 81965.52
Supply, installation & testing of advance maintenance free Chemical Gel Earthing
of Dual Pipe Technology (GI) of 3mtr long 80mm dia of outer shell (MS) with the
50mm dia of inner shell (MS) of 80-100 microns galvanized earth electrode filled
with highly conducting metallic compounds with the permanent sealings at both
the ends with the lead terminal of 50 x 10mm size at the top along with 50 Kgs
4 MR of chemical mixture of Resistance Lowering Grounding Minerals. The loss on Set 2.00 2.00 20722.83 41445.66
ignition by mass of the chemical compound shall be less than 20%. The chemical
compound should be tested and certified by any International accredited and BIS
(Bureau of Indian Standards) accredited laboratory. The earth electrode shall be
duly tested & certified by CPRI (Central Power Research Institute), Govt of
India. The chemical earth electrode manufacturer shall be an ISO 9001: 2008 &
Supply, installation & testing of advance maintenance free Chemical Gel Earthing
of Dual Pipe Technology (GI) of 3mtr long 50mm dia of outer shell (MS) with the
25mm dia of inner shell (MS) of 80-100 microns galvanized earth electrode filled
with highly conducting metallic compounds with the permanent sealings at both
the ends with the lead terminal of 32x10mm size at the top along with 50 Kgs of
chemaical mixture of Resistance Lowering Grounding Minerals. The loss on
ignition by mass of the chemical compound shall be less than 20%. The
chemical compound should be tested and certified by any International
accredited and BIS (Bureau of Indian Standards) accredited laboratory. The
earth electrode shall be duly tested & certified by CPRI (Central Power Research
Institute), Govt of India for a minimum short circuit current of 30 KA rms. The
chemical earth electrode manufacturer shall be an ISO 9001:2008 & ISO
14001:2004 certified organization. The Earth pit should be covered with heavy
duty polyplastic weather proof chamber.
Providing and fixing 25 mm X 5 mm G.I. strip in 40 mm dia G.I. pipe from earth
6 5.11 electrode including connection with G.I. nut, bolt, spring, washer excavation and Mtr. 80.00 80.00 442.40 35392.29
re-filling etc. as required.
Providing and fixing 25 mm X 5 mm G.I. strip on surface or in recess for
connections etc. as required.
Providing and fixing 25 mm X 5 mm G.I. strip in 40 mm dia G.I. pipe from earth
8 5.10 electrode including connection with G.I. nut, bolt, spring, washer excavation and Mtr. 80.00 80.00 1137.01 90960.71
re-filling etc. as required.
5 NBCC (I) Ltd.
LECTURE COMPLEX-2- Electrical IIT, Bhubaneswar
S. DSR DESCRIPTION OF ITEM Total Balance DSR Rate MR RATE at DSR Amount MR Amount (Rs.)
NO. 2014 Quantity Quantity at which which item (Rs.)
in to be item was was
executed awarded awarded in
Tender at Risk & in original
Cost original tender
Providing and fixing 25 mm X 5 mm copper strip on surface or in recess for tender
connections etc. as required.
Providing and fixing 6 SWG dia G.I. wire on surface or in recess for loop earthing
along with existing surface/ recessed conduit/ submain wiring/ cable as required.
SUB HEAD - IV - Point Wiring
Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm
FRLS PVC insulated copper conductor single core cable in surface / recessed
1 1.10.3 medium class PVC conduit, with modular switch, modular plate, suitable GI box Point 1560.00 305.00 544.34 166022.21
and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor
single core cable etc. as required.
Wiring for light/ power plug with 2X4 sq. mm FRLS PVC insulated copper
conductor single core cable in surface/ recessed medium class PVC conduit
alongwith 1 No. 4 sq. mm FRLS PVC insulated copper conductor single core cable
for loop earthing as required.
Wiring for light/ power plug with 4X4 sq. mm FRLS PVC insulated copper
conductor single core cable in surface/ recessed medium class PVC conduit
alongwith 2 Nos. 4 sq. mm FRLS PVC insulated copper conductor single core
cable for loop earthing as required.
Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of
4 1.14 FRLS PVC insulated copper conductor, single core cable in surface/ recessed
medium class PVC conduit as required.
Supplying and fixing suitable size GI box with modular plate and cover in front
5 1.31 on surface or in recess, including providing and fixing 3 pin 5/6 A modular socket Each 85.00 85.00 318.40 27064.38
outlet and 5/6 A modular switch, connections etc. as required.
Supplying and fixing suitable size GI box with modular plate and cover in front
6 1.32 on surface or in recess, including providing and fixing 6 pin 5/6 A & 15/16 A Each 166.00 166.00 415.08 68903.58
modular socket outlet and 15/16 A modular switch, connections etc. as required.
6 NBCC (I) Ltd.
LECTURE COMPLEX-2- Electrical IIT, Bhubaneswar
S. DSR DESCRIPTION OF ITEM Total Balance DSR Rate MR RATE at DSR Amount MR Amount (Rs.)
NO. 2014 Quantity Quantity at which which item (Rs.)
in to be item was was
executed awarded awarded in
Tender at Risk & in original
Cost original tender
Supplying and fixing of following sizes of medium class PVC conduit along with
7 1.21 accessories in surface/recess including cutting the wall and making good the
same in case of recessed conduit as required.
Supplying and fixing modular blanking plate on the existing modular plate &
switch box excluding modular plate as required
TOTAL 721094.19
SUB HEAD - V -Distribution Board
Supplying and fixing of following ways surface/ recess mounting, vertical type,
415 V, TPN MCB distribution board of sheet steel, dust protected, duly powder
painted, inclusive of 200 A, tinned copper bus bar, common neutral link, earth
bar, din bar for mounting MCBs (but without MCBs and incomer) as required.
(Note : Vertical type MCB TPDB is normally used where 3 phase outlets are
Supplying and fixing following way, horizontal type three pole and neutral, sheet
steel, MCB distribution board, 415 V, on surface/ recess, complete with tinned
copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder
painted including earthing etc. as required. (But without MCB/RCCB/ Isolator)
Supplying and fixing following way, single pole and neutral, sheet steel, MCB
distribution board, 240 V, on surface/ recess, complete with tinned copper bus
bar, neutral bus bar, earth bar, din bar, interconnections, powder painted
including earthing etc. as required. (But without MCB/RCCB/Isolator)
Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, “C” curve, miniature
4 2.10 circuit breaker suitable for inductive load of following poles in the existing MCB
DB complete with connections, testing and commissioning etc. as required.
7 NBCC (I) Ltd.
LECTURE COMPLEX-2- Electrical IIT, Bhubaneswar
S. DSR DESCRIPTION OF ITEM Total Balance DSR Rate MR RATE at DSR Amount MR Amount (Rs.)
NO. 2014 Quantity Quantity at which which item (Rs.)
in to be item was was
executed awarded awarded in
Tender at Risk & in original
Cost original tender
Supplying and fixing following rating, four pole, 415 V, isolator in the existing
MCB DB complete with connections, testing and commissioning etc. as required.
Supplying and fixing following rating, double pole, (single phase and neutral),
240 volts, residual current circuit breaker (RCCB),having a sensitivity current
6 2.14 upto 300 milliamperes in the existing MCB DB complete with connections, testing
and commissioning
etc. as required
Supplying and fixing single pole blanking plate in the existing MCB DB complete
etc. as required.
TOTAL 257637.60
SUB HEAD -VI - Light Fitting and Fans
Supplying of the following light fixtures complete with housing, reflectors, all
1 accessories i.e. copper wound Electronic ballast, HPF condensers, starters,
holders, hanging/fixing arrangements etc. complete as required
900mm CEILING FAN (Make Havells XP-390 / XP-390 Plus or Anchor Pansonic
FLO GS HS or equivalent Crompton, Orient, Usha)
1200mm CEILING FAN (Make Havells ES-50 Premium 5 or Anchor Pansonic
STILER PLUS ISI & 5 STAR or equivalent Crompton, Orient, Usha)
300 mm SWEEP EXHAUST FAN (1400 RPM) (Make Havells Turbo Force SP or
equivalent Crompton, Orient, Usha)
SITC of LED DownLighter body made of Die cast aluminium with heat sink.
Fixture should have IP20-IP44 with IK07 rating. Fixture dia should not be more
than 250 mm., Color temp. should be 3000/4000k, LED wattage should be
maximum 25W, Luman output should be minimum 2000lm, CRI is 80, Efficacy
1.4 MR 100 lm/W. Fixture should be available with LM79 & LM80 reports.Fixture should Nos. 720.00 720.00 7646.34 5505366.73
have reputaed LED like lumiled, cree or Nichia. Country of origin would be
required at the time of supply.Complete with brackets for recessed. As per
apporoved make Disano- Fosnova make Comfort LEX/ Igguzini make Reflex/
Zumtobel make Panos
8 NBCC (I) Ltd.
LECTURE COMPLEX-2- Electrical IIT, Bhubaneswar
S. DSR DESCRIPTION OF ITEM Total Balance DSR Rate MR RATE at DSR Amount MR Amount (Rs.)
NO. 2014 Quantity Quantity at which which item (Rs.)
in to be item was was
executed awarded awarded in
Tender at Risk & in original
Cost original tender
SITC of LED DownLighter body made of Die cast aluminium with heat sink. tender
Fixture should have IP44/IK07 rating. Fixture dia should not be more than 135
mm., Color temp. should be 3000/4000k, LED wattage should be maximum
15W, Luman output should be minimum 900lm, CRI is 80, Efficacy 60 lm/W,
Satin aluminium high efficiency. Fixture should be available with LM79 & LM80
reports.Fixture should have LED of lumiled, cree or Nichia or any other
reputated LED manufacturer. Fixture should be made in Europe & country of
origin would be required at the time of supply.Complete with brackets for
recessed. As per apporoved make Disano- Fosnova make Micro LEX/ Igguzini
make Pixel Plus MM20/ Zumtobel DIAMO R68 LED1100-930 FL WH.
SITC of IP20/IK03 Wall Mounted Linear LED Light, Fixture should be in extruded
aluminium with ABS end caps. Diffuser should be in opal polycarbonate, fluted
inside, smooth on the outside, dust-proof, UV stabilized. Fixture should have
polyester powder coating, UV stabilized. Equipment should be supplied with
brackets for wall or ceiling mounting. Fixture should have maximum length of
500mm. Fixture should be compliant to EN60598-1 CEI 34-21, EN 60529, EC
1.6 MR 89/336/EEC, CE73/23/EEC, EN 62471 standards. CCT should be 4000K. CRI Nos. 40.00 40.00 10541.54 421661.74
should be equal or above 80. Fixture should have maximum LED wattage of 10W
with minimum LED lumen package of 1000lm/W. Minimum LED efficacy required
is 100lm/W. Fixture should have inbuilt driver provision. Driver current should
not be more than 120mA. LM79, LM80 reports along with country of origin
should be produced at the time of supply. Make: Disano make Rigo, Zumtobel
make Linaria/ Iguzzini Make Reglette
SITC of IP40/IK05 Recessed/ Pendent Mounted Rectangular LED Panel, Fixture
should housing be injection moulded in white polycarbonate, shatterproof and
self-extinguishing, diffuser should be extruded in opal engineering plastic with
high thermal transmittance. Fixture should have rapid wiring connection
provision with no need to open the fixture. Fixture should be ENEC approved and
flicker free. CCT should be 3000K/4000K as per architect approval. CRI should
be more than 90. Power factor should be equal or above 0.9. LED luminous flux
maintenance 40000hrs(L70B50). Maximum LED wattage should not be more
than 40W with minimum LED lumen package of 3000lm. Minimum LED efficacy
required should be 70lm/W. Fixture should be compliant to EN62471 standard.
Dimensions of the fixture should not be more than 600x600x15mm. Country of
origin should be produced before execution. Make: Disano- Fosnova make
Pannello LED panel, Zumtobel Lightfield Evolution 42181845, Igguzini make i
plan easy square P 180
9 NBCC (I) Ltd.
LECTURE COMPLEX-2- Electrical IIT, Bhubaneswar
S. DSR DESCRIPTION OF ITEM Total Balance DSR Rate MR RATE at DSR Amount MR Amount (Rs.)
NO. 2014 Quantity Quantity at which which item (Rs.)
in to be item was was
executed awarded awarded in
Tender at Risk & in original
Cost original tender
SITC of IP 65/IK08 LED LIGHT FIXTURE CONTINEOUS SURFACE MOUNTED. tender
Fixture’s Housing should be made up of injection moulded, in grey
polycarbonate, shatter-proof, UV-stabilized, highly resistant to mechanical
impacts thanks to the reinforced structure with internal ribbing. Diffuser should
1.8 MR be made up of injected moulded in polycarbonate with internal ribbing for
greater lighting control, in V2 self-extinguishing, UV-stabilized material; its
smooth outer finish makes cleaning easier and increases lighting efficiency.
Equipped with stainless steel screw clamping. Reflector: in galvanized steel,
previously stone-enamelled with UV-stabilized polyester resin.
Clamping device manufactured directly onto the housing. Standard supply should
be eco-friendly and anti-aging expanded polyurethane injected gasket. The
fixing brackets for ceiling and suspension mounting should be in stainless steel.
Socket-plug connector. The fixture should be secured to the fixing brackets
through quick connectors. Fixture should be Flicker-Free to produce uniform light
with no flicker for greater eye protection. Fixture should be SELF-
EXTINGUISHING and approved by UL94 standard and ENEC approved. Fixture
should be made of V2 self-extinguishing plastic material: burning should stop
within 25 seconds. Photo biological safety class: exempt.
GLOW WIRE TEST should be done at 850°C. Perfect alignment of the lighting
fittings should be achieved using moulded guiding notches. Surface finish of the
diffuser should allow light to escape, creating an “all light” effect. The fluted
diffuser should spread light evenly without leaving dark areas. Continuous line
alignment should be through-line wiring arrangement and socket/plug type
connectors from the first of the last lighting fitting should be required for this
type of installation. ENEC Approval, LM 79, LM 80 reports should be produced
before execution.
Fixture length’s should be 1150mm – 1280mm long, height and width of fixture
should not be more than 60mm & 135 mm respectively. Fixture should have
inbuilt LED chips mounted on PCB but not external LED tubes. LED: Power
factor: ≥• 0.95. Colour rendering index: ≥• 80. Luminous flux maintenance,
Fixture should confirm L70B20-50000 hrs. Ambient temperature: -30°C to + Nos. 64.00 64.00 10193.55 652387.03
40°C. Fixture wattage should have power consumption maximum 30W with
minimum LED Lumen package of 3600Lm, Minimum LED efficacy should be 120
Lm/w. As per approved make and model nos- Disano 961 Hydro, Zumtobel-
CHIARO-II- 42182985, Igguzini i sign 6787
SITC of IP65/ IK08 LED DownLighter body made of vandal resistane , self
extinguishing, UV estaliblised, Diffuser Vandal resistane, V2 self extinguidhing,
UV stablished clear poly carbonate, dust proof power factormore than .95 Fixture
dia should be in between 280mm- 320 mm., Color temp. should be 4000k, LED
1.9 wattage should be maximum 25W, LED Luman output should be minimum Nos. 6.00 6.00 7589.75 45538.53
1500lm, CRI is 80, LED Efficacy 60 lm/W. Fixture should be available with LM79
& LM80 reports.Fixture should have reputaed LED like lumiled, cree or Nichia.
LM79, LM80 reports along with country of origin should be produced at the time
of supply. Make: Disano make Globo, Zumtobel Helissa, Igguzini Ellipse.
10 NBCC (I) Ltd.
LECTURE COMPLEX-2- Electrical IIT, Bhubaneswar
S. DSR DESCRIPTION OF ITEM Total Balance DSR Rate MR RATE at DSR Amount MR Amount (Rs.)
NO. 2014 Quantity Quantity at which which item (Rs.)
in to be item was was
executed awarded awarded in
Tender at Risk & in original
Cost original tender
Installation, testing and commissioning of ceiling fan, including wiring the down tender
2 1.44 rods of standard length (upto 30 cm) with 1.5 sq. mm FRLS PVC insulated, Nos. 233.00 233.00 99.83 23260.34
copper conductor, single core cable etc. as required.
Installation of exhaust fan in the existing opening, including making good the
damage, connection, testing, commissioning etc. as required.
Installation, testing and commissioning of pre-wired, fluorescent fitting /
compact fluorescent fitting of all types, complete with all accessories and
4 1.41 tube/lamp etc. directly on ceiling/ wall, including connections with 1.5 sq. mm Nos. 1318.00 1318.00 95.63 126035.65
FRLS PVC insulated, copper conductor, single core cable and earthing etc. as
SUB HEAD -VII - Data and TV points
Supplying and drawing of UTP 4 pair CAT 6 LAN Cable in the existing surface/
recessed Steel/ PVC conduit as required.
Supplying and drawing following pair, 0.5 sq.mm FRLS PVC insulated copper
2 1.18 conductor, unarmoured telephone cable in the existing surface / recessed steel /
PVC conduit as required.
Supplying and drawing co-axial TV cable RG-6 grade, 0.7 mm solid copper
3 1.19 conductor PE insulated, shielded with fine tinned copper braid and protected with Metre 100.00 100.00 29.42 2942.35
PVC sheath in the existing surface / recessed steel / PVC conduit as required.
Supplying and drawing co-axial TV cable RG-11 grade, 0.7 mm solid copper
4 MR conductor PE insulated, shielded with fine tinned copper braid and protected with Metre 100.00 100.00 67.91 6790.53
PVC sheath in the existing surface / recessed steel / PVC conduit as required.
Supplying and fixing following modular switch / socket on the existing modular
5 1.24 plate & switch box including connections but excluding modular plate etc. as
5.1 1.24.7 TV antenna socket outlet Each 4.00 4.00 98.78 395.12
5.2 1.24.6 Telephone socket outlet Each 54.00 54.00 99.83 5390.81
5.3 MR Socket for RJ 45 Jack for Cat - 6 Cable Each 32.00 32.00 533.77 17080.77
Supplying and Fixing following sizes / modules , GI box along with modular base
& cover plate for modular switches in recess etc as required.
11 NBCC (I) Ltd.
LECTURE COMPLEX-2- Electrical IIT, Bhubaneswar
S. DSR DESCRIPTION OF ITEM Total Balance DSR Rate MR RATE at DSR Amount MR Amount (Rs.)
NO. 2014 Quantity Quantity at which which item (Rs.)
in to be item was was
executed awarded awarded in
Tender at Risk & in original
Cost original tender
Supply, erection, testing and commissioning of following tap off / splitter as per
specification in 1.6mm thick CRCA sheet steel enclosure for CATV system.
7.1 MR 4 way splitter box Each 1.00 1.00 249.91 249.91
Supplying and fixing of following sizes of steel conduit along with accessories in
8 1.20 surface / recess including painting in case of surface conduit, or cutting the wall
and making good the same in case of recessed conduit as required.
SUB HEAD - VIII - EXTERNAL LIGHTING
Supply, assembly, erection, connecting, testing & commissioning of LT weather
proof dust and vermin proof (IP-65), outdoor feeder pillar, fabricated out of
suitable sized angle iron and flats and covered with 3mm thick CRCA sheet steel
including canopy, duly stove enamel painted, both sides (front and rear)
openable with locking arrangement, rubber gasket cable glands, etc. Bakelite
1 phase separators and bus bar supports including RCC 1:2:4 (1 cement: 2 coarse
sand : 4 graded stone aggregate 20mm nominal size) foundation, 450 mm deep
and 150 mm above the ground. The feeder pillars shall be complete with 3 phase
and neutral bus bars of capacities as described below and moulded case circuit
breakers (MCCBs) with adjustable overload relay, copper FRLS control wiring
with 1.5sq.mm, complete in all respects as per specifications as required.
a) 63A 4P MCCB (25ka) with thermal magnetic release & rotary handle - 1no.
b) 3 Phase and neutral (100%N) aluminium bus bars of 150/ 100 amps. Capacity.
a) 70 AMP. TP CONTACTOR WITH NO/ NC CONTACTS -1 set.
b) 24 HOUR TIMER - 1 set.
c) 20A 4P MCB (10ka) - 5 nos.
d) 16A DP MCB (10ka) - 2 nos.
e) 63A 4P MCB (10ka) - 1 no.
16 AMP. SWITCH & SOCKET - 1 no. with in the feeder pillar.
M.R. External Lighting Feeder Pillar as above Set 1.00 1.00 80229.99 80229.99
12 NBCC (I) Ltd.
LECTURE COMPLEX-2- Electrical IIT, Bhubaneswar
S. DSR DESCRIPTION OF ITEM Total Balance DSR Rate MR RATE at DSR Amount MR Amount (Rs.)
NO. 2014 Quantity Quantity at which which item (Rs.)
in to be item was was
executed awarded awarded in
Tender at Risk & in original
Cost original tender
Supply of standard 6.0 metre high (above ground) hot dip galvanized (grading tender
of galvenisation average 70 micron or better as per IS2629 or equivalent)
octagonal pole, as per IS 875 Part-3, with stiffeners, chain, allen bolt, single
arm bracket one metre long, foundation bolt, anchor plate, template, nut and
washers galvanized, factory finish base plate of size 250 x 250 x 12 mm etc
2 MR complete as required. The pole shall be made of 3 mm thickness sheet with Nos 15.00 15.00 15677.45 235161.76
tolerance of +/- 5%. The column shall also be provided with flush door at the
bottom with proper strengthening to the cutout of the door opening, a junction/
looping box with Heavy duty 3 phase, 32 Amp connector with 16A DP MCB
including all accessories complete as required. (make & model will be selected
by the client).
Supply of solar power Street Lighting Fixture complete with 7.5 meter long
Octaganol GI poles as per approved makes and as per standard design. The
3 MR luminaire shall be of aluminium die cast construction with minimum IP65
protection with inter-connection copper cable from solar panel to battery, to
controller and to luminaire etc as required.
The storage capacity of the battery should be sufficient to run the full load for 18
hours on rainy/ heavy cloudy days.The unit should also have an additional AC
charging arrangement to charge the batteries in case of very long heavy cloudy
A junction chamber of size 300mm/ 100mm with cable termination arrangement
connector block and 1 No. 10 Amp SPMCB shall be provided. The street light
fixture shall be 1 x 70 watt capacity with LED bulbs of white colour of 1 watt
each. the fixture shall be complete with control gear for auto switching ON,
switching OFF supplementary power charging in case of non availability of solar
power on very long heavy cloudy days etc. as required. The solar panel shall be
of sufficient capacity to charge the sealed maintenance free battery of minimum
160 AH capacity. The RCC pedestral shall be made of 1:2:4 ratio as required.
The column shall be smooth surface finished degreased, derusted, primary
coated, cavity sealed and painted with PU based self curing polyurethane based Nos 2.00 2.00 129182.42 258364.84
automotive paint. Complete item will be finalised by the client/ consultant.
Receiving, Assembly, Erection, Testing & Commissioning of Street
Lighting Fixture complete with 6.0 meter long octagonal GI pole with excavation,
back filling,all material, steel reinforcement with cold twisted bar, PCC with
1:3:6 (1 Cement : 3 coarse sand : 6 graded stone aggregate 20 mm nominal
4 MR size) & main foundation 1:2:4 (1 cement : 2 coarse sand : 4 graded stone Nos 15.00 15.00 5186.84 77802.62
aggregate 20 mm nominal size), fixing of 'J' Bolts ('J' bolts provided by other
agency) including curing, back filling etc. as required, including suitable length of
32 mm GI pipe for cable entry size & design of foundation as per standard
design & approved by the consultant/ client etc. as required.
13 NBCC (I) Ltd.
LECTURE COMPLEX-2- Electrical IIT, Bhubaneswar
S. DSR DESCRIPTION OF ITEM Total Balance DSR Rate MR RATE at DSR Amount MR Amount (Rs.)
NO. 2014 Quantity Quantity at which which item (Rs.)
in to be item was was
executed awarded awarded in
Tender at Risk & in original
Cost original tender
Receiving, Assembly, Erection, Testing & Commissioning of Street tender
Lighting Fixture complete with 7.5 meter long octagonal GI pole with excavation,
back filling,all material, steel reinforcement with cold twisted bar, PCC with
1:3:6 (1 Cement : 3 coarse sand : 6 graded stone aggregate 20 mm nominal
5 MR size) & main foundation 1:2:4 (1 cement : 2 coarse sand : 4 graded stone Nos 2.00 2.00 5186.84 10373.68
aggregate 20 mm nominal size), fixing of 'J' Bolts ('J' bolts provided by other
agency) including curing, back filling etc. as required, including suitable length of
32 mm GI pipe for cable entry size & design of foundation as per standard
design & approved by the consultant/ client etc. as required.
Supply of following luminaries (IP-65) with housing made of single piece high
pressure die cast alluminium alloy/ as per standards, energy efficient copper
ballast, heat resistant toughened flat glass / cover glare free, pole mounting
mechanism etc. (make & model will be approved by the client).
post top fixture (Bajaj cat. LED POLE LIGHT - BAJAJ BRIL 45W LED WH or
6.1 MR Panasonic make APT010404 or equivalent from approved Philips, Panasonic, Nos 15.00 15.00 14097.83 211467.42
Wipro makes). pole light.
Supply, laying, testing and commissioning of 1.1 kv grade XLPE insulated PVC
sheathed steel armoured alluminium stranded conductor LT Cables including
both end termination with lugs & brass glands in trenches/ ducts/ through RCC
pipes under roads of following sizes, complete all as specified (as per CPWD
specifications for External Electrical works) including the cost of digging and back
filling the trenches, sand filling, brick covering for protection etc complete as
required & approved by Engineer's Incharge. (Tagging to be provided with
aluminium strips on both the ends as approved).
7.1 MR 4 core X 4 Sq.mm (For external Lights) Meter 300.00 300.00 118.83 35648.70
Providing and fixing 6 SWG dia G.I. wire on surface or in recess for loop earthing
Providing and fixing 25 mm X 5 mm G.I. strip on surface or in recess for
connections etc. as required.
SUB HEAD - IX - ADDRESSABLE FIRE ALARM SYSTEM
14 NBCC (I) Ltd.
LECTURE COMPLEX-2- Electrical IIT, Bhubaneswar
S. DSR DESCRIPTION OF ITEM Total Balance DSR Rate MR RATE at DSR Amount MR Amount (Rs.)
NO. 2014 Quantity Quantity at which which item (Rs.)
in to be item was was
executed awarded awarded in
Tender at Risk & in original
Cost original tender
Supply, Installation, Testing & Commissioning of Networkable Microprocessor tender
based analogue addressable type 10 Loop expandable Fire Alarm Control Panel
with 640 character LCD display,integrated QWERTY Keypad, 4000 History
logging event. The panel should be equipped with sufficient numbers of loops
with 20 % Spare capacity in each loop. The panel shall be capable of taking
atleast 300 analog addressable devices (150 Detectors & 150 Devices) in one
1. loop. he panel shall have Four access levels, capable of taking Flash Scan
devices, flash EPROM sufficient numbers of programmable relay controls for
controlling AHUs, pressurization fans, ventilation fans at fire pump room,
monitoring of fire sprinkler and fire hydrant pump, 240 volts AC power supply,
automatic battery charger, 24 volts sealed lead acid batteries sufficient for 24
hours normal working and then be capable of operating the system for 2 hours
during an emergency conditions as required. (UL 9th Edition Approved).
Supply, Installation, Testing & Commissioning of Power Supply Unit - 240VAC to
Supply, installation, testing and commissioning of Operator work station
3 complete with necessary compatible operating and fire alarm system control
software, complete as specified including following accessories.
Operator work station with PC having Intel i7, 2.4 GHz Duo Processor including
Serial ports (RS232) and USB ports and following accessories etc. complete with
software all as specified.
4 Gigabytes of RAM memory
540Gigabytes of hard disk space
21” TFT colour monitor
Mouse with Mouse Pad
Standard Key Board
Latest Windows Operating System
Compatible Fire Alarm System Control Software
Color Laser Printer A-4 size- 1 No Set 1.00 1.00 289872.52 289872.52
Supply, Installation, Testing & Commissioning Networkable Reapter Panel with
4 640 Character Backlit LCD Display and fixed function Keys and Soft Nos 1.00 1.00 201580.29 201580.29
Keys.Reapter Panel should be on true peer to peer network. (UL Listed )
15 NBCC (I) Ltd.
LECTURE COMPLEX-2- Electrical IIT, Bhubaneswar
S. DSR DESCRIPTION OF ITEM Total Balance DSR Rate MR RATE at DSR Amount MR Amount (Rs.)
NO. 2014 Quantity Quantity at which which item (Rs.)
in to be item was was
executed awarded awarded in
Tender at Risk & in original
Cost original tender
Supply, Installation , Testing & Commissioning of the GUI based main network tender
Fire Detection, Digital voice evacuation system and 2 way communication
common software must be capable of graphically representing each facility being
monitored with floor plans and icons depicting the actual locations of the various
systems; and / or sensors’ locations. The GUI software shall be located in control
room in one of the Floors and shall monitor all the Floor Fire Detection, Digital
5 voice evacuation system and 2 way communication panel connected with each 1.00 1.00 223506.47 223506.47
other through fibre optics. The software shall be capable of monitoring 100
Nodes with minimum 300Kbps baud Transmission rate on Network and 12 MB
baud Transmission on cable or more. The software shall provide the facility to
Monitor, Control all the Digital voice evacuation system as well as 2 way
communication from main control room using voice signals over Fire Network
along with the Fire detection signal. The software shall be capable of
Supply, installation, testing and commissioning of Automatic Analog addressable
Photoelectric smoke detector with mounting Base,alarm LED . The Detector shall
have automatic Electronic /dip switch addressing feature complete as
required.(UL Listed )
Analog addressable Rate of Rise Cum Fixed temperature detector with mounting
7 based LED, Address Switch from 01-159 , to programme the detectors complete Nos 16.00 16.00 3643.99 58303.80
as required.(UL Listed )
Supply, Installation, Testing and commissioning of Response Indicator for all
detectors located above false ceiling.(UL Listed)
Supply, installation, testing & commissioning of intelligent addressable Hooter
Cum Sounder Complete as required.(UL Listed )
Supply, installation, testing & commissioning of intelligent addressable manual
call station (Breakglass type), complete as required.(UL Listed)
Fault Isolator module complete as required for determining the short in a circuit
11 and separating the segment having the short capable of being addressed Nos 25.00 25.00 4324.88 108121.98
electronically, complete as required.(UL Listed)
Supply, installation, testing and commissioning of Automatic Addressable control
12 module for Hooters cum Sounder . The Module shall have automatic Electronic Nos 95.00 95.00 4873.74 463005.62
/dip switch addressing feature complete as required.(UL Listed )
Supply, installation, testing and commissioning of Monitor module complete as
13 required for monitoring flow switches / interface with any third party equipment Nos 8.00 8.00 4110.80 32886.42
suitable for being addressed electronically, complete as required.(UL Listed )
Supply, installation, testing and commissioning of Automatic Addressable Relay
14 module for NO/NC Contacts.The Module shall have automatic Electronic /dip Nos 8.00 8.00 4873.74 38989.95
switch addressing feature complete as required.(UL Listed )
16 NBCC (I) Ltd.
LECTURE COMPLEX-2- Electrical IIT, Bhubaneswar
S. DSR DESCRIPTION OF ITEM Total Balance DSR Rate MR RATE at DSR Amount MR Amount (Rs.)
NO. 2014 Quantity Quantity at which which item (Rs.)
in to be item was was
executed awarded awarded in
Tender at Risk & in original
Cost original tender
Supplying, laying, testing and commissioning of following sizes of Low Smoke tender
Zero Halogen Silicon Insulated Fire Survival Cable with Drain Wire Armouring,
solid copper conducter cable approved by LPCB as per BSEN 50200:2015 PH 120
(Fire, Mech Shock & Water 120 Minutes @ 830 deg Celcius, Fire & Mech Shock
every 5 Min for 2 Hours- Both test conducted on same sample) and BS-6387
CWZ The cable shall sustain 950 deg. C. For 3 hours approved along with
accessories/ termination glands and all necessary materials to complete. The
cable shall be approved for. The cable shall be BS EN 60332-1-2:2004 for
Bunched Flame Retardancy (installed as a single or bunched cable self
extinguishes leaving the upper cable sheath unaffected showing the cable does
not propagate fire). Cable shall be guaranteed for 10 years from the date of
manufacture marked on the cable.
SUB HEAD - X - CCTV SURVEILLANCE SYSTEM
Supply, installation, Testing & Commissioning of IR Dome camera having 1/2.8"
or better Progressive CMOS, Vari-focal Motorized remote lens of 3~10.5mm
Lens, 2048 X 1536 resolution at 30 fps, DC-Iris, WDR 75db or more, Day-Night
with senstivity of 0.03 lux color & 0 lux B/W with IR , Electronic Shutter Range:
1/5 ~ 1/25,000 sec , 64GB MicroSD/SDHC card Slot, 30fps, min. 2 simultaneous
1 streams, Camera should have dual channel audio by default adjustable
resolution & bit rate, H.264, MPEG-4, MJPEG, Time stamp & text caption overlay,
IPv4, IPv6, TCP/IP, HTTP, HTTPS, UPnP, RTSP/RTP/RTCP, IGMP, SMTP, FTP,NTP,
DNS,QoS, SNMP and 802.1X, Video motion detection, manual trigger, digital
input. Camera should have camera sabotage analytic so that a alarm is triggered
if the lens is obstructed or when the camera is repositionedcomplete as required.
The Camera should be ONVIF Profile S and Profile G compliant. The camera shall
have following certifications CE - EN 55022 (Class A), EN 50130-4, EN 60950-1,
FCC (Class A) - 47 CFR Part 15 , UL and cUL Listed - UL 60950-1, CAN/CSA-
C22.2 No. 60950-1-07 and ICES-003
Supply installation Testing and Commissioing of 40 Channel Network Video
recording servers to be considered. It shall have Intel® Xeon® E5-2620 v4 or
better with 16 GB DDR3 ECC RAM or better. It should run on Windows® 10 IoT
Enterprise 64-bit (LTSB) or latest.It should have SSD storage for operating
2 system.Shall support Dynamic Host Communication Protocol (DHCP) and Nos 2.00 2.00 1458490.50 2916981.00
Network Time Syncronisation Protocol (NTP) functionality. It shall have Mapping
function. It should have in built plugins to integrate third party systems. It shall
have 28TB HDD in each Box for recording at 1280 X 720 @ 15fps for 30
dayscomplete as required.
Supply, Installation, Testing & Commissioning of 42” LED Screen with wiring &
all accessories complete as required.
Supply, installation, testing and commissioning of Operator work station
4 complete with necessary compatible operating and CCTV system control
software, complete as specified including following accessories.
17 NBCC (I) Ltd.
LECTURE COMPLEX-2- Electrical IIT, Bhubaneswar
S. DSR DESCRIPTION OF ITEM Total Balance DSR Rate MR RATE at DSR Amount MR Amount (Rs.)
NO. 2014 Quantity Quantity at which which item (Rs.)
in to be item was was
executed awarded awarded in
Tender at Risk & in original
Cost original tender
Operator work station with PC having Intel i7, 2.4 GHz Duo Processor including tender
Serial ports (RS232) and USB ports and following accessories etc. complete with
software all as specified.
4 Gigabytes of RAM memory
540Gigabytes of hard disk space
21” LED colour monitor
Mouse with Mouse Pad
Standard Key Board
Latest Windows Operating System
Compatible Fire Alarm System Control Software
Color Laser Printer A-4 size- 1 No Set 1.00 1.00 289872.52 289872.52
Supply, Installation , Testing & Commissioning of 48 Port 10/100/1000 Mbps
5 POE+ RJ45 Ports Giga Switch 4 Combo SFP Ports, 2 dedicated stacking ports Nos 1.00 1.00 42731.99 42731.99
complete as per technical specifications complete as required.
Supply, Installation , Testing & Commissioning of 24 Port 10/100 / 1000 Mbps
6 RJ45 Ports Switch 4 Combo SFP Ports, 2 dedicated stacking ports as per Nos 3.00 3.00 16959.08 50877.23
technical specifications enclosed etc. complete as required.
Supply, Installation, Testing & Commissioning of 42 U Free standing cabinet
with front locable door, side panels ,2 set of castor wheel , 230 V AC 90 CFM fan
4, three Hardware packet 1 set (containing 20 Nos each of 3), AC power strip
combination of 5 A- 15 A 12 socket, heavy duty stationary shelf 600 W x 475 D,
2 cable channel 100 mm wide 42 U, one earthing Strip 150 mm H, 4 Cable
manager 1U height complete as required.
Supply, Installation, Testing & Commissioning of 9U Wall mounted Rack with fan
and power strip with spike arrestors complete as required.
Supply, Installation, Testing & Commissioning of rack mount patch panel, 1U,
9 24 port loaded with Adapter Plates SC Style complete as required. approved Nos 2.00 2.00 14165.72 28331.45
make (Schneider, Siemon, Systimax)
Supply, Installation , Testing & Commissioning of rack mount patch panel, 1U,
10 24 port loaded with Adapter Plates SC Style complete as required. approved Nos 2.00 2.00 14165.72 28331.45
make (Schneider, Siemon, Systimax)
Supply, installation, testing and commissioning of Power Backup & UPS 2 KVA for
supporting each NVR complete as required.
Supply, installation, testing and commissioning of Power Backup & UPS 1 KVA for
switches complete as required.
Supply, Installation, Testing & Commissioning of 1U Horizontal Cable Manager
(For Field Cables & Switches) complete as required.
Supply, Installation, Testing & Commissioning of 6 Socket Universal Power Strip
complete as required.
18 NBCC (I) Ltd.
LECTURE COMPLEX-2- Electrical IIT, Bhubaneswar
S. DSR DESCRIPTION OF ITEM Total Balance DSR Rate MR RATE at DSR Amount MR Amount (Rs.)
NO. 2014 Quantity Quantity at which which item (Rs.)
in to be item was was
executed awarded awarded in
Tender at Risk & in original
Cost original tender
Supply, Installation, Testing & Commissioning of Mounting Hardware Pkt of 10
complete as required.
Supply, Installation , Testing & Commissioning of Slime line RJ45 to RJ45 Cat6
UTP Patchcord with flexible transparent Boot, Blue = 1m complete as required.
Supply, Installation, Testing & Commissioning of Slime line RJ45 to RJ45 Cat6
UTP Patchcord with flexible transparent Boot, Blue = 2m complete as required.
Supply, Installation, Testing & Commissioning of 1 Port Iconable Faceplate with
18 RJ-45 I/O -White complete as required. approved make (Schneider, Siemon, Nos 44.00 44.00 619.60 27262.24
19 Supplying and fixing of CAT 6 Cable Roll of 305 meter complete as required. Roll 13.00 13.00 17019.43 221252.53
Supplying and fixing of following sizes of steel conduit along with accessories in
20 1.20 surface/recess including painting in case of surface conduit, or cutting the wall
and making good the same in case of recessed conduit as required.
Supply and fixing of 16 gauge MS conduits in following sizes including cost of
junction boxes, bends, elbows, sockets, tees and GI flexible conduit to connect
from ceiling to false ceiling etc. laying in slab, cutting chases and making good or
surface mounted Supplying and fixing of
SUB-HEAD - XII - LIGHTNING CONDUCTOR
Providing and fixing of lightning conductor finial, made of 25 mm dia 300 mm
1 6.2 long, G.I. tube, having single prong at top, with 85 mm dia 6 mm thick G.I. base Each 4.00 4.00 387.76 1551.04
plate including holes etc. complete as required.
Fixing of lightning conductor finial (single prong) with base plate including holes
etc. complete as required.
Jointing copper / G.I. tape (with another copper/ G I tape, base of the finial or
3 6.4 any other metallic object) by riveting / nut bolting/sweating and soldering etc as Each 4.00 4.00 75.66 302.64
Providing and fixing G.I. tape 20 mm X 3 mm thick on parapet or surface of wall
for lightning conductor complete as required. (For horizontal run)
Providing and fixing G.I. tape 20 mm X 3 mm thick on parapet or surface of wall
for lightning conductor complete as required. (For vertical run)
19 NBCC (I) Ltd.
LECTURE COMPLEX-2- Electrical IIT, Bhubaneswar
S. DSR DESCRIPTION OF ITEM Total Balance DSR Rate MR RATE at DSR Amount MR Amount (Rs.)
NO. 2014 Quantity Quantity at which which item (Rs.)
in to be item was was
executed awarded awarded in
Tender at Risk & in original
Cost original tender
Providing and fixing testing joint, made of 20 mm X 3 mm thick G.I. strip, 125 tender
6 6.12 mm long, with 4 nos. of G.I. bolts, nuts, chuck nuts and spring washers etc. Each 8.00 8.00 74.61 596.88
complete as required
TOTAL 29684.13
20 NBCC (I) Ltd.
LECTURE COMPLEX- FIRE - 2 IIT, Bhubaneswar
SUMMARY OF FIRE FIGHTING FOR LECTURE HALL - 2, IIT AT BHUBNESWAR
S. No. DESCRIPTION DSR Amount
1 SUB HEAD - I - (PUMPING EQUIPMENTS) 0 175907.35
2 SUB HEAD - II - (HYDRANTS SYSTEM) 0 218066.86
3 SUB HEAD - III - (PIPING, VALVES AND ACCESSORIES) 0 411576.27
4 SUB HEAD - IV - (FIRE EXTINGUISHERS) 0 144069.49
LECTURE COMPLEX-FIRE-2 IIT, Bhubaneswar
DETAILED ESTIMATE
NAME OF WORK : CONSTRUCTION OF LECTURE HALL - 2, IIT BHUBANESWER
Item DSR - Description Of Item Unit Total Balance MR RATE at MR Amount
No 2014 Quantity in Quantity to be which item was (Rs.)
Original executed at awarded in
Tender Risk & Cost original tender
SUB HEAD - I - (PUMPING EQUIPMENTS)
Supplying of Electric Driven Terrace Pump suitable for auto operation
and consisting of following: complete in all respect as required.
Horizontal type, multistage centrifugal end suction type split casing
pump of cast iron body & bronze impeller with stainless steel shaft,
mechanical seal and flow of 900 Ipm at 45 Mtr head confirming to
Suitable HP (Minimum 7.5 / 10.0 HP) squirrel cage induction motor
TEFC type suitable for operation on 415 volts, 3 phase 50 Hz. AC with IP
55 class of protection for enclosure, horizontal foot mounted type with
Class-'F' insulation, confirming to IS:325.
M.S. fabricated Common base frame, flexible coupling, coupling guard,
foundation bolts and pressure gauge with valve etc. Suitable cement
concrete foundation duly plastered with anti vibration pads. etc. 1 1.00 118128.80 118128.80
complete as per manufacturer's design & standards and as per detailed
specifications.
Fabricating, Supplying, Installation, Testing and Commissioning Air
Vessel of continuous welded construction with flanged discharge
header on the top of each riser fabricated out of 10 mm thick dished
ends and 8 mm thick MS sheet, Air Release Valve complete with suitable
drain arrangement with 25 mm dia gun metal wheel valve complete
with all accessories etc. as required of the following sizes:
2.1 1.2 Meter high and 250 mm dia. Each 4 4.00 12817.15 51268.59
1 NBCC (I) Ltd.
LECTURE COMPLEX-FIRE-2 IIT, Bhubaneswar
Item DSR - Description Of Item Unit Total Balance MR RATE at MR Amount
No 2014 Quantity in Quantity to be which item was (Rs.)
Original executed at awarded in
Tender Risk & Cost original tender
Supply, Installation, testing and commissioning of pressure switches for
Hydrant / Diesel Engine Driven Pump / Jockey Pumps, diaphragm
type, adjustable range from 0-9 bar and a regulation range of 0.1 1.5 bar
3 direct mounted SNAP acting type made from die cast aluminium with Each 1 1.00 6509.95 6509.95
epoxy powder coated finish and SS316 diaphragm and other wetted
parts, including necessary wiring upto control panel & other materials
as required as per specifications.
TOTAL 175907.35
SUB HEAD - II - (HYDRANTS SYSTEM)
Supplying and Fixing First Aid Hose Reel, wall mounting swinging
type complete with drum & bracket of MS construction, spray painted in
Post office Red, confirming to IS 884/1995 with upto date amendments,
complete with the following as required.
36 Meter long 20 mm dia water hose Thermoplastic (Textile reinforced)
Type - 2 as per IS : 12585
(b) 25 mm dia ball valve & nozzle.
(c) Drum and brackets for fixing the equipments on wall.
(d) Connection from riser with stop valve (gun metal) & M.S. Pipe Each 16 16.00 6678.76 106860.17
2 SITC weather proof M.S cabinet size 800 mm x 600 mm x 250 mm
Supplying, installation, testing and commissioning of weather proof
M.S cabinet size 800 mm x 600 mm x 250 mm deep fabricated from
1.6mm thick M.S. sheets and M.S angle 40mmx40mmx6mm complete
with glass, locking arrangements to accommodate the following: -
a) First Aid hose Reel - 1 No.
b) Fire Extinguisher - 2 Nos. Each 16 16.00 5644.22 90307.51
2 NBCC (I) Ltd.
LECTURE COMPLEX-FIRE-2 IIT, Bhubaneswar
Item DSR - Description Of Item Unit Total Balance MR RATE at MR Amount
No 2014 Quantity in Quantity to be which item was (Rs.)
Original executed at awarded in
Tender Risk & Cost original tender
Providing and fixing single gunmetal suction collecting head as per IS:
904-1983, hose coupling (draw out connection) with female outlet as per
903 complete with 150 mm dia. G.I. Suction pipe (with puddle flange)
with a foot valve with strainer complete as per drawings.
Supplying and fixing 4 way 63 mm instantaneous Fire Brigade Inlet
Connection (FBIC) comprising of gunmetal body and gunmetal
instantaneous male inlet coupling confirming to IS:904 with plug and
cap with chain as required with nuts & bolts and high pressure rubber
gasket, suitable for 150 mm dia MS pipe connection etc. complete as
TOTAL 218066.86
SUB HEAD - III - (PIPING, VALVES AND ACCESSORIES)
SLTC of M.S. pipe on surface
Supplying, laying, fixing, testing and commissioning of following sizes
(NB) of ISI marked heavy class M.S. pipes including cutting, threading,
welding etc. and providing all fittings e.g. elbows, reducers, clamps,
hangers, flanges, gaskets, nuts, bolts and washers etc. including painting
of pipes and fittings with red paint over a coat of ready mixed primer,
both of approved quality and shade including cutting holes and chases
in brick or RCC walls/ slabs and making good the same etc. complete in
all respect as required.
Note:-The Pipes of sizes 150 mm & below shall be M.S. ‘C’ class as per IS
: 1239 and pipes size above 150 mm shall be welded black steel pipe
heavy class as per IS: 3589, from minimum 6.35 mm thick M.S. Sheet for
pipes upto 350 mm dia. and from minimum 7mm thick MS sheet for
pipes of 400 mm dia and above.
3 NBCC (I) Ltd.
LECTURE COMPLEX-FIRE-2 IIT, Bhubaneswar
Item DSR - Description Of Item Unit Total Balance MR RATE at MR Amount
No 2014 Quantity in Quantity to be which item was (Rs.)
Original executed at awarded in
Tender Risk & Cost original tender
Supplying, Installation, Testing and Commissioning of Butterfly valves
of PN 1.6 rating of following sizes with nitrile Bronze / G.M. seat duly
2 ISI marked and stainless steel stem with lever/gear operation and cast
iron body in powder coated finish for fire fighting application complete
in all respects confirming to IS: 13095 as required.
Providing, Installation, Testing and Commissioning of double flanged
cast iron Non-Return Valve, PN 1.6 of following sizes confirming to IS :
5312 complete with rubber gasket, Gl bolts, nuts, washers etc. as
Supplying, Installation, Testing and Commissioning of CI body flanged
(both ends) type serviceable suction / Y strainer with (stainless steel /
4 brass mesh) conforming to relevant IS specifications amended upto date
complete including providing and fixing nuts, bolts, washers, gaskets
etc. complete as required.
TOTAL 411576.27
SUB HEAD - IV - (FIRE EXTINGUISHERS)
Supply & fixing of Water type (Stored Pressure) fire extinguisher,9 ltrs.
Capacity mfd to IS: 15683 with BIS mark, supplied with Brass forged
Squeeze leaver valve , discharge hose fitted with nozzle. Wall mounting
bracket with screw. FIRE RATING - 3A FIRE RATING - 3A
4 NBCC (I) Ltd.
LECTURE COMPLEX-FIRE-2 IIT, Bhubaneswar
Item DSR - Description Of Item Unit Total Balance MR RATE at MR Amount
No 2014 Quantity in Quantity to be which item was (Rs.)
Original executed at awarded in
Tender Risk & Cost original tender
Supply & fixing of Co2 type Fire Extinguisher 4.5kg capacity with Brass
forged Screw down / squeeze lever type valve, initial gas charged as per
2 IS 15222, rubber braided discharge hose & Horn, complete with
accessory as per IS:15683 with BIS mark, MTC & PESO (OLD CCOE)
certificate.Wll mounting bracket with screw. FIRE RATING - 34B
2.1 4.5kg capacity cylinder Each 16 16.00 5177.40 82838.47
Supply & fixing of ABC Dry Powder Fire Extinguisher 4 Kg apacity mfd
to IS: 15683 with BIS mark, Brass forged squeeze lever discharge valve,
fitted with pressure indicating guage with discharge hose & well design
3 ALUMINIUM discharge nozzle, duly charged with ISI Marked MONO Each 16 16.00 1721.09 27537.39
AMONIUM PHOSPHATE (MAP) SILICONISED powder and
pressurized with Nitrogen Gas. CE MARKED. Wall mounting bracket
with screw. FIRE RATING - 2A, 21B
TOTAL 144069.49
5 NBCC (I) Ltd.
LECTURE COMPLEX- 2- LIFT IIT, Bhubaneswar
NBCC (INDIA) LIMITED
(A Govt. of India Enterprise)
Name of work - Passenger Elevators for IIT BHUBANESWAR,ODISHA
Summary- Lift for Lecture Theatre Complex
Sno Item Description Unit DSR NON-DSR Amount
1 Estimate cost as per BOQ Passenger Elevators : Rs. 0 4,469,092.05
LECTURE COMPLEX-2-LIFT IIT Bhubaneswar
NATIONAL BUILDINGS CONSTRUCTION (I) LIMITED
A GOVERNMENT OF INDIA ENTERPRISE
Name of work - PASSENGER ELEVATORS FOR IIT BHUBANESWAR,ODISHA
LECTURE THEATRE BLOCK-2
Bill of Quantity
Supplying,Installation ,Testing & Commissioning of Passenger Elevators With AC ,VVVF drive,stainless steel door, and automatic power operated doors,ARD,with standard
controls and operating divices for G+2 Floors.
S. no. Fixtures Description Unit Total Balance MR RATE at MR Amount
Quantity in Quantity to be which item was (Rs.)
Original executed at awarded in
Tender Risk & Cost original tender
Passenger Lifts
Sno Items Description
1 Type of elevator Without Machine room
2 Capacity 884Kgs Approx /13 Passangers
3 Speed (Mtrs / sec ) 1.0
4 Travel distance / Stops (Mtrs) 14.85 Mtr Approx 3.0 stop /3.0 Opening
5 Drive V.V.V.F.(Variable Voltage Variable Frequency )
Microprocessor Based Simplex Selective collective Control
with/without Attendent.
7 Available Hoistway size 2400x2100 (D)
8 Car size (inside dimensions) 1100(W) x 2000(D) x 2200(H)
9 Typeor desigen of lift Stainless Steel Hairline Finish
10 Ceiling False ceiling with Stainless Steel finish
PVC 20- 25 mm Recess or any other flooring (supplied by client)
as approved by client
Automatic centre Opening Framed 60 minutes 6 mm fire
12 Car Entrance
resistant Glass door in Stainless Steel Hairline finish
Automatic centre Opening Framed 60 minutes 6 mm fire
13 Landing Entrance
resistant Glass door in Stainless Steel Hairline finish
14 landing Frame Stainless Steel Hairline finish Nos 2.0 2.0 2,234,546.02 4,469,092.05
Automatic Centre opening door with Stainless steel finish panels
15 Hoistway Entrance
(800 X 2000)mm Approx
16 Power supply AC 400/440 Volts , 3 phase, 50 Cycles
17 Operation Automatic with VVVF door operator & Electronic door operator
18 Fixtures Stainless Steel Face plates
19 Special features Automatic Rescue Device
20 Fireman switch at main lobby
21 Infra red door Screen -2d
22 Push Button -Orange LED Illumination
23 Overload warning indicators
25 SS Hand Rail
26 Battery Operated Emergency light & alarm Bell
27 Dot Matrix Led D & P Indicators in car & landing
28 Vandal Proof SS Button with SS cover
29 Lift License
30 AMC Free service for one year & Ex.for 5 year
LECTURE COMPLEX-HVAC-2 IIT, Bhubaneswar
NAME OF WORK : CONSTRUCTION OF LECTURE HALL 2, IIT BHUBANESWER
SUMMARY OF COST
DSR AMOUNT MR AMOUNT
S. No. DESCRIPTION
1 SUB-HEAD 'A' - MACHINERY - 9,467,398.97
2 SUB-HEAD 'B' WATER PIPING 430,322.13 2,850,805.84
3 SUBHEAD-'C' - DUCTING AND GRILLS 435,594.20 8,360,813.44
4 SUBHEAD-'D' INSULATION 241,262.36 -
5 SUBHEAD-'E' MECHANICAL VENTILATION SYSTEM - 3,665,784.81
6 SUBHEAD-'G' ELECTRICAL 158,126.20 4,170,998.06
TOTAL DSR+MR 29,781,106.00
LECTURE COMPLEX-HVAC-2 IIT, Bhubaneswar
DETAILED ESTIMATE
NAME OF WORK : CONSTRUCTION OF LECTURE HALL 2, IIT BHUBANESWER
ITEM DSR UNIT Total Balance DSR Rate at MR RATE at DSR AMOUNT MR AMOUNT
NO 2014 Quantity Quantity to which item which item (Rs.) (Rs.)
DESCRIPTION OF ITEM in Original be executed was awarded was awarded
Tender at Risk & Cost in original in original
tender tender (Rs.)
A SUB-HEAD 'A' - MACHINERY
Supply, installation, testing & commissioning of Aircooled Water Chilling M/C of
325 TR (Actual) capacity at operatiing conditions given below with multiple screw
compressors open / semi hermatic type and independent multiple refrigerant
circuits operating on refrigerant R-134a, driven by suitable KW motor complete
1 MR with aircooled condenser having copper tubes with aluminium fins and VFD on
condenser fans, insulated shell and tube flooded chiller, refrigerant piping,
refrigerant & oil (First Change), control panel, incoming switch gear mounted in
the starter panel and accessorites etc. all mounted on M.S. frame. The motors
shall be suitable for 415 volts+10% , 50Hz +5%, three phase AC supply.
Chiller shall be supplied with the machine flanges / Grooves & should have
adopter boxes with bus bar and connected with flexible copper cables . Isolator
box shall be supplied along with chiller.
Motor shall be suitable for 415 Volts ± 10%, 50Hz AC supply. Control wiring
between various components of chiller package and control panel board of the
chiller unit shall be provided. The machine should be complete with factory wired,
machines mounted microprocessor based control panel with necessary
interlocking & safeties as per specifications. Flow switch and interconnecting wire
between flow switch and chiller microprocessor shall be included
VFD shall be Free Standing / Unit Mounted. VFD shall be UL Listed & shall have
IP 54/ NEMA 13 enclosure. Incase of a free standing VFD, it will be ensured that
the same is sourced from the chiller manufacturer's works after pairing and
programming / testing the same. All the cost should be included in the chiller price
for wiring between chiller & VFD if free standing VFD.
Chiller shall have Modbus communication card to replicate all chiller parameter
over BMS terminal and touch screen for display of operating parameters.
Chiller (evaporator etc.) should be factory insulated. Cost on account of Including
Suitable vibration isolation pads shall be included
Flexible below , Flow switch and interconnecting wire between flow switch and
chiller microprocessor shall be included
Lot- Initial/ first charge of refrigerant gas & compressor oil.
Custom duty, port clearing, any other incidental charges, Loading, Local
transportation, insurance upto handing over and all other incidental charges upto
delivery at site included.
RCC/ cement concrete foundation for the chilling unit.
Chiller :- CHW in at 12.30C & CHW Out at 6.70C
Chiller Fouling Factor - 0.00025 (FPS UNIT)
Ambient Temperature = 40 degrees C (system should be capable of operating
upto the ambient temperature of 42 deg C)
IKW/TR on design conditions: 1.10 IKW/TR (including condenser fans)
NPLV on design conditions not o exceed 0.70
The chilling machine as described above shall be in line with specifications.
(2 working +1 stand by) set 3.00 9465145.98
1 NBCC (I) Ltd.1
LECTURE COMPLEX-HVAC-2 IIT, Bhubaneswar
DETAILED ESTIMATE
NAME OF WORK : CONSTRUCTION OF LECTURE HALL 2, IIT BHUBANESWER
ITEM DSR UNIT Total Balance DSR Rate at MR RATE at DSR AMOUNT MR AMOUNT
NO 2014 Quantity Quantity to which item which item (Rs.) (Rs.)
DESCRIPTION OF ITEM in Original be executed was awarded was awarded
Tender at Risk & Cost in original in original
tender tender (Rs.)
Supplying, erection, testing and commissioning of Centrifugal
Horizontal / Vertical type primary chilled water pump set capable of
2 MR delivering 780 GPM/ 2948.4LPM of water against a head 12 Mtr.
(2Working + 1 Standby). each pump shall comprise the following as
required as per specifications.
Horizontal/Vertical Split Casing type pump with bronze impeller, S.S
a. Shaft, C.I body and mechanical seal with integral reinforced flanged
rubber bellows at suction and discharge side.
Duly insulated with 80 kg/cum density resin bonded fiber glass duly
b. cladded with aluminium sheets of 0.5mm thickness and properly
clamped to pump in two semicircular sections as per specifications.
Suitable HP, TEFC squirrel cage induction motor,Eff-1 with class 'F'
c. insulation,IP -55 Protection, 1450 RPM , operating on 415 volts ±
10%, 3 phase, 50 Hz A.C. supply.
Pump set shall be complete with necessary vibration isolation
d. arrangement ,MS base plate, coupling guard, foundation bolts and all
other accessories.
RCC/ cement concrete foundation for the pumps.(2 working +1Stand
Supplying, erection, testing and commissioning of package type skid
3 MR mounted secondary chilled water pumping system with VFD (2
working + 1 Standby) and all pump system controller, comprising of:
Horizontal / Vertical type pump set with Cast Iron casing, Bronze
impellers with stainless steel shaft & with integral reinforced flanged
rubber bellows at suction and discharge side. Pump connected to
suitable capacity TEFC ventilated induction motor ,Eff-1 with class 'F'
insulation, 1450 RPM, suitable for 415 volts ± 10%, 3 phase, 50 Hz
Duly insulated with 80 kg/cum density resin bonded fiber glass duly
b. cladded with aluminium sheets of 0.5mm thickness and properly
clamped to pump in two semicircular sections as per specifications.
Electrical Control Panel capable of cyclic operation of pumps - Pump
working sequence should change after every operation. Control
panel with programmable logic controller (PLC) with inbuilt PID
controller, digital display with fluorescent screen with two lines of
c. min. 20 character each and equipped with function keys and service
keys. 3 ph, 415 volts ±10%, AC variable speed drive for each pump
of suitable capacity rating having standard function of BI loop, energy
saving catching a spinning load with speed search, etc. complete as
required as per specification
Microprocessor based control panel shall have suitable hardware &
d. software so that it can be integrated directly to BMS with standard
communication protocol using backnet / Modbus /any open Protocol
(All the Pump set will have their control panel with respect to the
motor rating & should be suitable for chilled water circulation).
All pumps to be provided with separate variable frequency drives.
Control panel with respect to motor rating and should also consist of
cooling fan,enclosoures etc as required.
2 NBCC (I) Ltd.2
LECTURE COMPLEX-HVAC-2 IIT, Bhubaneswar
DETAILED ESTIMATE
NAME OF WORK : CONSTRUCTION OF LECTURE HALL 2, IIT BHUBANESWER
ITEM DSR UNIT Total Balance DSR Rate at MR RATE at DSR AMOUNT MR AMOUNT
NO 2014 Quantity Quantity to which item which item (Rs.) (Rs.)
DESCRIPTION OF ITEM in Original be executed was awarded was awarded
Tender at Risk & Cost in original in original
tender tender (Rs.)
Mounting frame work with vibration isolation arrangement , coupling
guard, foundation bolts and all other accessories.
f. Electronic Differential Pressure Transmitters as required.
Integral reinforced flanged rubber bellows at suction and discharge
h. RCC/ cement concrete foundation for the pumps.
Complete system to be mounted on a common MS base frame
i. structure with base plate of pump and shall have following duty
and characteristic:
Secondary chilled water pump sets -
Flow Rate : 780 GPM/ 2948.4LPM
Head : 45 Metre WC
(2 Working + 1 Stand by) Complete Set 3.00 3.00 993026.57 2979079.70
Supply, Installation, Testing and commissioning of factory built Floor
mounted double skin type air handling units made of 43 mm thick
panels consisting of G.I. casing of thickness 0.8 mm outside layer and
0.8mm inside layer with polyurethene foam (PUF) insulation with
density of 40 kg/cum. factory injected between them by injection
moulding machine,complete with blower section with blower DIDW
forword curved centrifugal fan suitable for static pressure 45mm of
WG, 6 row deep cooling coil, with aluminium finned copper
4 tubes(tube thickness not less than 0.5mm), filter sections with 50
mm thick washable synthetic type air pre-filters having efficiency
90% down to 10 micron, belt drive package with TEFC drive motor
suitable for 415±10% volts, 50Hz, 3 Phase AC supply with IP-54
protection,F Class insulation, Eff-1 motor,mixing box, drain
connections with drain valve, stainless steel (18 G) drain pan, PUF
insulation, Thermometer, pressure Gage, necessary vibration
isolation arrangement including suitable rating TPN isolater with box
etc. complete as per specification and of following capacities
3 NBCC (I) Ltd.3
LECTURE COMPLEX-HVAC-2 IIT, Bhubaneswar
DETAILED ESTIMATE
NAME OF WORK : CONSTRUCTION OF LECTURE HALL 2, IIT BHUBANESWER
ITEM DSR UNIT Total Balance DSR Rate at MR RATE at DSR AMOUNT MR AMOUNT
NO 2014 Quantity Quantity to which item which item (Rs.) (Rs.)
DESCRIPTION OF ITEM in Original be executed was awarded was awarded
Tender at Risk & Cost in original in original
tender tender (Rs.)
Supply, Installation, Testing and commissioning of factory built Floor
Mounted double skin type with thermal break profile Treated fresh
air units made of 43 mm thick panels consisting of G.I. casing of
thickness 0.8 mm outside layer and 0.8mm inside layer with
polyurethene foam (PUF) insulation with density of 40 kg/cum.
factory injected between them by injection moulding machine,
complete with blower section with blower DIDW backward curved
centrifugal fan suitable for static pressure 65 mm WG, cooling coil
section with aluminium finned copper tubes(tube thickness not less
5 than 0.5mm), section for heat pipe with heat pipe (horse shoe type)
for pre-cooling and pre-heating , filter sections with 50 mm thick
washable synthetic type air pre-filters having efficiency 90% down to
10 micron, belt drive package with TEFC drive motor Eff-1 ,IP-55
protection, suitable for 415 ± 10% volts, 50 Hz, 3 phase, A.C. supply,
drain connections with drain valve, stainless steel (18 G) drain pan,
PUF insulation, Descaling valve, auto air purge valve, necessary
vibration isolation arrangement including suitable rating TPN isolater
with box etc., complete as per specifications and of followings
6 VARIABLE FREQUENCY DRIVES FOR FLOOR MOUNTED AHU
Supply,Installation,Testing and Commissioing of HVAC dedicated
VFDs with IP 54 enclosures with Mains disconnect, complying with the
tender specifications and having:
Built-in dual 5% impedance DC link reactor (harmonic filters) on the
positive and negative rails of the DC bus of the VFD.
Built-in EMC Filters (electromagnetic compatibility filters) for VFDs for
restriction of conducted emissions to comply with IEC61800: 3
(unrestricted distribution):2004
Two-feedback PID controller having capability to simultaneously
accept 2 feedback signals from temperature sensors or pressure
sensors for process optimization and accordingly regulate the speed
Additional 3 PID controllers to control external devices such as chilled
water modulating valve, fresh air damper, etc. for improving system
Automatic Energy Optimization / Load dependent flux optimization
functionality for maximum energy savings.
MODBUS RTU/Any open protocol as communication protocol
between BMS & VFDs.Compatible to protocol of BMS system.
4 NBCC (I) Ltd.4
LECTURE COMPLEX-HVAC-2 IIT, Bhubaneswar
DETAILED ESTIMATE
NAME OF WORK : CONSTRUCTION OF LECTURE HALL 2, IIT BHUBANESWER
ITEM DSR UNIT Total Balance DSR Rate at MR RATE at DSR AMOUNT MR AMOUNT
NO 2014 Quantity Quantity to which item which item (Rs.) (Rs.)
DESCRIPTION OF ITEM in Original be executed was awarded was awarded
Tender at Risk & Cost in original in original
tender tender (Rs.)
B SUB-HEAD 'B' WATER PIPING
1 INSULATED CHILLED WATER PIPING
Supplying, laying/ fixing, testing and commissioning of following
nominal sizes of chilled water piping inside the building (with
necessary clamps, vibration isolators and fittings but excluding
valves, strainers, gauges etc.) duly insulated with following closed
cell elastometric nitrile rubber of minimum 45 Kg / m3 density,
thermal conductivity 0.037 W/MK or better at 20 deg mean
temperature class ‘O’ insulation applied by suitable adhesive
complete including repairing of damage to building etc. as per
specifications and as required complete in all respect.
Note:-The Pipes of sizes 150 mm & below shall be M.S. ‘C’ class as
per IS : 1239 and pipes size above 150 mm shall be welded black
steel pipe heavy class as per IS: 3589, from minimum 6.35 mm thick
M.S. Sheet for pipes upto 350 mm dia. and from minimum 7mm thick
MS sheet for pipes of 400 mm dia and above.
1.1 MR 100mm dia. (32mm insulation) Meter 195.00 171.00 2182.25 373164.39
1.2 MR 80mm dia. (32mm insulation) Meter 120.00 120.00 1862.55 223506.10
1.3 MR 65mm dia. (32mm insulation) Meter 135.00 135.00 1558.88 210448.68
1.4 MR 50mm dia. (32mm insulation) Meter 40.00 40.00 1336.32 53452.87
1.5 MR 40mm dia. (32mm insulation) Meter 10.00 10.00 1058.11 10581.12
1.6 MR 32mm dia. (19mm insulation) Meter 80.00 80.00 900.62 72049.79
1.7 MR 25mm dia. (19mm insulation) Meter 10.00 10.00 799.72 7997.21
Supplying, fixing, testing and commissioning of following valves,
strainers, gauges in the chilled water plumbing duly insulated to the
same specifications as the connected piping and adequately
supported as per specifications.
BUTTERFLY VALVE (MANUAL) with C I body SS Disc, Nitrile Rubber
Seal & O- Ring PN 16 pressure rating for chilled water/ hot water
circulation as specified
5 NBCC (I) Ltd.5
LECTURE COMPLEX-HVAC-2 IIT, Bhubaneswar
DETAILED ESTIMATE
NAME OF WORK : CONSTRUCTION OF LECTURE HALL 2, IIT BHUBANESWER
ITEM DSR UNIT Total Balance DSR Rate at MR RATE at DSR AMOUNT MR AMOUNT
NO 2014 Quantity Quantity to which item which item (Rs.) (Rs.)
DESCRIPTION OF ITEM in Original be executed was awarded was awarded
Tender at Risk & Cost in original in original
tender tender (Rs.)
Supplying, fixing, testing and commissioning of following sizes
Motorized Butterfly Valve with CI Body, SS Disc, O - ring and
minimum PN-16 pressure rating, conforming to BS 5155, IS 13095,
with IP-55 actuator, capable of accepting upto 10V DC, and upto 20
mA electric signal and providing similar transduced feedback output
to control system as required.
BALANCING VALVE WITH BUILT IN MEASURING FACILITY with C I
body flanged construction with EPDM coated disc with long pitch with
protected out pipe insulation & PN 16 pressure rating for chilled / hot
water circulation as specified.
NON - RETURN VALVE with duel plate of C I body SS plates
5 16.7.3 vulcanized NBR seal flanged end & PN 16 pressure rating for chilled /
hot water circulation including insulation as specified.
Y - STRAINER of Ductile CI Body flanged ends with stainless steel
6 16.7.4 strainer for chilled / hot water circulation including insulation as
PRESSURE INDEPENDENT BALANCING CUM CONTROL VALVE WITH
Supplying, laying/ fixing, testing and commissioning of Pressure
Independent Balancing cum Control Valve (PIBCV) which shall be 2
way combined valve of PN 16 rating for flow limitation, controlling
flow & controlling Delta P. Valve body upto 32mm shall be brass
body ext. threaded type and 40mm dia to 50mm dia shall be cast
iron/ brass body ext. thredaed type and above 50mm shall be cast
iron .Valve should be equipped with electronic modulating actuator IP
54 for AHU which can accept either "4(0)-20 mA / 2(0)-10 V DC
signals. Operating voltage for actuator shall be 24 V AC. The actuator
should be connected to proportionate thermostat. Delta p controller
should ensure 100% control valve authority always at all load
conditions (part load and full load).Stepless balancing adjustments
shall be in valve and control adjustments in actuator. The differential
pressure function shall be a diaphragm and shall be out of the main
flow to avoid valve blockages and other services issue. Valve along
with actuator and cold/hot thermostat shall offer logarithmic control
characteristics complete as per specification. The flow rates of chilled
water are as below :
6 NBCC (I) Ltd.6
LECTURE COMPLEX-HVAC-2 IIT, Bhubaneswar
DETAILED ESTIMATE
NAME OF WORK : CONSTRUCTION OF LECTURE HALL 2, IIT BHUBANESWER
ITEM DSR UNIT Total Balance DSR Rate at MR RATE at DSR AMOUNT MR AMOUNT
NO 2014 Quantity Quantity to which item which item (Rs.) (Rs.)
DESCRIPTION OF ITEM in Original be executed was awarded was awarded
Tender at Risk & Cost in original in original
tender tender (Rs.)
Providing and fixing in position the industrial type pressure gauges
with gun metal / brass valves complete as required
9 16.9 Providing & fixing in position of Dial type glycerin fill thermometres. Nos. 24.00 24.00 722.98 17351.47
Supply, Installation, Testing, & Commissioning of 750 ltrs pressurized
6mm thick MS Expansion tank with centrifugal air separator and
pressurization unit with double pump, IP55 control panel and other
allied accessories etc as required. The hydronic pressurization system
10 should duly insulated complete with necessary safety valve, auto air
purging arrangement with drain valve, pressure gauge etc. with
necessary connections complete as required. The system efficiency
of 96-98% with safe working pressure of 3.5 bar & following
10.1 MR Line Size: 250mm diameter; Set 1.00 1.00 768888.25 768888.25
11 Drain Piping
Providing & fixing of PVC Pipe complete with fittings, supports as per
specifications and duly insulated with 6/9 mm thickness of closed cell
nitrile rubber as per direction of Engineer-in-charge & specifications
enclosed as reqd.
11.1 MR 50 mm dia with 9 mm thick insulation Meter 10.00 10.00 518.68 5186.84
11.2 MR 40 mm dia with 9 mm thick insulation Meter 10.00 10.00 461.16 4611.61
11.3 MR 32 mm dia with 6 mm thick insulation Meter 10.00 10.00 403.63 4036.28
11.4 MR 25 mm dia with 6 mm thick insulation Meter 20.00 20.00 288.58 5771.63
C SUBHEAD-'C' - DUCTING AND GRILLS
Supply, installation, balancing and commissioning of factory
fabricated GSS sheet metal rectangular/round ducting complete with
1 16.12.1 neoprene rubber gaskets, elbows, splitter dampers, vanes, hangers,
supports etc. as per approved drawings and specifications of following
sheet thickness complete as required.
Supply, installation, balancing and commissioning of fabricated at site
GSS sheet metal rectangular/round ducting complete with neoprene
2 16.12.2 rubber gaskets, elbows, splitter dampers, vanes, hangers, supports
etc. as per approved drawings and specifications of following sheet
thickness complete as required.
7 NBCC (I) Ltd.7
LECTURE COMPLEX-HVAC-2 IIT, Bhubaneswar
DETAILED ESTIMATE
NAME OF WORK : CONSTRUCTION OF LECTURE HALL 2, IIT BHUBANESWER
ITEM DSR UNIT Total Balance DSR Rate at MR RATE at DSR AMOUNT MR AMOUNT
NO 2014 Quantity Quantity to which item which item (Rs.) (Rs.)
DESCRIPTION OF ITEM in Original be executed was awarded was awarded
Tender at Risk & Cost in original in original
tender tender (Rs.)
Preinsulated Fibreglass wool Duct
Supply, fabrication, installation, balancing and commissioning Pre-
Insulated Fiberglass wool Duct having 25mm thickness with both
side factory laminated aluminum foil. Density of pre insulated glass
wool duct board shall be 75-80Kg/m3 and at the edge of panels shall
have density of 150Kg/m3. size of panels for duct construction.The
fire and smoke classification shall comply to Class "O" of BS 476 part
6 &7. All accessories, adhesive, sealent and tape used in duct
fabrication shoud be same as panel manufacturer.
Outer facing Reinforced aluminum. Kraft and glass veil and inner
facing foil - Aluminum, Kraft and glass veil.
Outer facing Reinforced aluminum. Kraft and glass veil and inner
facing foil - Black glass textile.
Supply, installation, testing and commissioning of GI volume control
4 16.13 duct damper complete with neoprene rubber gaskets, nuts, bolts, SQM. 8.00 8.00 5688.20 45505.58
screws linkages, flanges etc, as per specifications.
Supply, installation, testing of extruded aluminium powder coated
linear grill without volume control damper as per drawings.
Supply, Installation and Testing of collar damper of galvanised steel
sheet, provided with suitable links, levers and quadrants for manual
control of volume of air flow and for proper balancing of air
distribution as per approved shop floor drawings and specifications.
Supplying & fixing of powder coated extruded aluminium Supply Air
Grills with aluminium volume control dampers as per specifications.
Supplying & fixing of powder coated extruded aluminium Return
8 16.16 Air/Exhaust Air Grills with louvers but without volume control SQM. 30.00 30.00 4245.39 127361.81
dampers complete as required.
Supplying, fixing testing commissioning of supply air diffusers of
9 16.17 powder coated aluminium with aluminium volume control dampers SQM. 1.00 1.00 9101.33 9101.33
with anti smudge ring & removable core.
Supplying, fixing testing commissioning of Return air diffusers of
10 16.18 powder coated aluminium without volume control dampers with anti SQM. 1.00 1.00 5878.40 5878.40
smudge ring & removable core.
8 NBCC (I) Ltd.8
LECTURE COMPLEX-HVAC-2 IIT, Bhubaneswar
DETAILED ESTIMATE
NAME OF WORK : CONSTRUCTION OF LECTURE HALL 2, IIT BHUBANESWER
ITEM DSR UNIT Total Balance DSR Rate at MR RATE at DSR AMOUNT MR AMOUNT
NO 2014 Quantity Quantity to which item which item (Rs.) (Rs.)
DESCRIPTION OF ITEM in Original be executed was awarded was awarded
Tender at Risk & Cost in original in original
tender tender (Rs.)
Supply, fixing and commissioning of Fresh/ exhaust air louvers with
11 MR section comprising of powder coated Aluminium louvers & bird screen SQM. 12.00 12.00 7137.08 85645.02
Supply, fixing and commissioning of powder coated 2/3/4 slot Linear
12 MR slot diffuser complete with nuts, bolts, SS screws etc. complete as SQM. 5.80 5.80 10381.22 60211.06
Supply, fixing and commissioning of powder coated extruded
13 MR aluminium Door Transfer Grill complete with nuts, bolts, SS screws SQM. 1.00 1.00 10381.22 10381.22
etc. complete as required.
Supply, installation, testing and commissioning of duct mounted air
purification system/ cell based on advanced oxidation technology with
broad spectrum UV lamp (100-380 NM) enhanced on the quad
metallic compound target/ hydrated catalytic matrix cell with the
capability to produce friendly oxidizers like Ionized Hydro Peroxides,
Super Oxide Ions, Hydroxides Ions and duly enclosed by a poly casing
tube that should prevent glass or mercury leakage into the
conditioned/ served space. The units should be designed after
14 undertaking a load factor calculation for each specific area where the
equipment is to be installed. The load shall clearly state the number
of units required vis-à-vis the wattage of the units. The system shall
be capable of reducing microbial bacteria, virus and spores and VoC’
and odors. The UV lamp must be enclosed in a poly casing to prevent
mercury at all cost.The equipment shall conform to UL 1598, CAN/
CSA 222, EN 60335-1, EN 60335-2-65, TUV, CSA, EU standards,
certifications shall be submitted along with the technical submital.
Refer technical specififcations for more details and compliance.
D SUBHEAD-'D' INSULATION
Supplying and fixing of following thickness duly laminated aluminum
foil of mat finish closed cell Nitrile rubber (Class “O”) insulation on
1 16.23 duct after applying suitable adhesive for Nitrile rubber. The joints
shall be sealed with 50 mm wide and 3 mm thick self adhesive nitrile
rubber tape insulation complete as per specifications and as required.
9 NBCC (I) Ltd.9
LECTURE COMPLEX-HVAC-2 IIT, Bhubaneswar
DETAILED ESTIMATE
NAME OF WORK : CONSTRUCTION OF LECTURE HALL 2, IIT BHUBANESWER
ITEM DSR UNIT Total Balance DSR Rate at MR RATE at DSR AMOUNT MR AMOUNT
NO 2014 Quantity Quantity to which item which item (Rs.) (Rs.)
DESCRIPTION OF ITEM in Original be executed was awarded was awarded
Tender at Risk & Cost in original in original
tender tender (Rs.)
Supply and fixing of acoustic lining of supply air duct and plenum with
25 mm thick resin bonded glass wool having density of 32 kg/m³,
with 25 mm X 25 mm GI section of 1.25 mm thick, at 600 mm centre
2 16.21 to centre covered with Reinforced Plastic tissue paper and 0.5 mm SQM. 10.00 10.00 570.61 5706.06
thick perforated aluminum sheet fixed to inside surface of ducts with
cadmium plated nuts, bolts, stick pins, CPRX compound etc. complete
as required and as per specifications.
Supplying, fixing acoustic lining on wall and ceiling of AHU rooms with
50mm thick, density 32 kg/cu.m resin bonded glass fiber insulation
friction fixed in 610mm x 610 mm frame work made of 25 X 50 X50 X
3 16.22 50 X 25 mm made out of 0.6mm thick GI sheet U shaped channel SQM. 250.00 250.00 907.93 226981.44
and covered with reinforced fiber glass tissue and finished with 0.80
mm perforated aluminium sheet etc. complete as required and as per
specifications.
TOTAL 241262.36
E SUBHEAD-'E' MECHANICAL VENTILATION SYSTEM
1 Axial Flow Fan unit
Supplying, installation, testing and commissioning of Axial flow
(Exhaust Air)fan of following capacity with powder coated M.S. casing
and aluminium alloy impellers with high efficiency aero-foil sections,
blades, the impeller directly driven by TEFC induction motor (motor
should be of high efficiency (Eff 1) suitable for 3 Phase 50 Hz 415 V ±
10 %,1400 RPM of class 'H' insulation etc. complete as required and
as per specifications (For Exhaust) . Suitable TP isolator within MS
enclosure should be Provided.
1.1 MR 3000 CFM (20 mm Static Pressure WC) Nos. 27.00 27.00 35312.93 953449.16
1.2 MR 5800 CFM (20 mm Static Pressure WC) Nos. 12.00 12.00 46121.36 553456.29
1.3 MR 14000 CFM (20 mm Static Pressure WC)Pressurization Nos. 5.00 5.00 71858.45 359292.23
Supplying, installation, testing and commissioning of Axial flow
fan(Fresh Air) of following capacity with powder coated M.S. casing
and aluminium alloy impellers with high efficiency aero-foil sections,
blades, the impeller directly driven by TEFC induction motor (motor
should be of high efficiency (Eff 1) suitable for 3 Phase 50 Hz 415 V ±
10 %,1400 RPM of class 'F' insulation etc. complete as required and
as per specifications (For Supply). Suitable TP isolator within MS
enclosure should be Provided.
2.1 MR 3000 CFM (20 mm Static Pressure WC) Nos. 27.00 27.00 31802.85 858677.03
2.2 MR 5800 CFM (20 mm Static Pressure WC) Nos. 12.00 12.00 41573.91 498886.92
2.3 MR 14000 CFM (20 mm Static Pressure WC) Nos. 5.00 5.00 67902.30 339511.48
10 NBCC (I) Ltd.10
aoc.pdf
Download all tender documents and submit your bid