Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L-1₹35.5 LAccepted-AOC SHOP NO 10 BMC SHOPPING CENTRE MITHA NAGAR GOREGAON WEST MUMBAI 400 104 | MUMBAI | MUMBAI SUBURBAN | MAHARASHTRA | 400104 | L-1 | Accepted-AOC Being L-1 | |
| 2 | L-2₹42.3 L+₹5.4 L (14.6%)Rejected-Finance | L-2 | Rejected-Finance Being L-2 | |
| 3 | L-3₹50.4 L+₹13.6 L (36.8%)Rejected-Finance | L-3 | Rejected-Finance Being L-3 | |
| 4 | L-4₹51.2 L+₹14.3 L (38.8%)Rejected-Finance PI NO 13 S NO 81 82 BEHIND 132 33 KVA MSEB SUBSTATION MIDC AREA AMBAD NASHIK 422 010 | NASHIK | NASHIK | MAHARASHTRA | 422010 | L-4 | Rejected-Finance Being L-4 |
Tender Value
₹60 L
EMD Value
₹1.1 L
Closing Date
24 Apr 2023, 6:00 pmClosed
CWE (SUBS) MUMBAI
Commander Works Engineer Subs NCHC Powai Bhandup Post Office Mumbai 400 078
REPAIR AND MAINT OF HT VCB, ISOLATOR, RELAYS, TRANSFORMERS, APFC PANELS AND HT CABLES AT MO (MB) GHATKOPAR, NAE SANTACRUZ AND INS HAMLA AND REPAIRS TO HT INSTALLATIONS INCL HT DISTR NETWORK AT NCHC POWAI UNDER GE (NW) BHANDUP
2023_MES_583740_1
8444/E8
Open Tender
Electrical and Maintenance Works
Item Rate
300 days
BHANDUP
Please refer Tender documents.
8 documents required · 8 mandatory
₹1,000
GE (NW) BHANDUP
₹1.1 L
Yes
20 May 2023
4 Mar 2023
26 Apr 2023
4 Mar 2023
24 Apr 2023
10 Apr 2023
Amount
Overhauling and servicing through agency authorised by OEM of HT VCB, 11 KV, 400/630/800 Amps of make Megawin / AREVA / CG/Schneider/ Seimens installed at various lacations including cleaning of all VCB contacts with CT's and replacement of minor parts such as Gaskets, washers, panel heater, indicator bulbs and carry out any other repairs required at site to make the VCB fully functional, complete all as specified and directed (i) Checking of Draw out mechanism/arrangement of VCB (ii)Inspection of isolating Contacts, and decarburizing the male /female contacts, jaws complete and replacement of worn out contacts if any. (iii) Checking of alignment with spout and setting of contact gaps. (iv) Replacement of worn out/defective minor spares parts, lubrication of moving parts of the truck by moly grease. (v) Checking/setting of master control relay, earth fault realy and overload realy. (vi) Also checking ON/OFF/TRIP indication and make it serviceable by necessary checking/repair/replacement of control wiring. Replacement of Push button for open and Close, micro switches, indication lamps. (vii) Decarburizing and reinsulation of complete busbar track system complete in all respect. (viii) Misc works deemed essential to make VCB in perfectly working order complete all as directed. Note : Major spare parts are to be paid separately as supplied only under respective items here in after, however cost of minor spares shall be deemed to be included in the rate quoted in the items. Cost of labour deemed to be included with rate quoted in this items
Overhauling and servicing through agency authorised by OEM of HT RMU 11 KV, 400/800 Amps of make Schneider / ABB installed at NCHC Powai including cleaning of all RMU contacts with CT's and replacement of minor parts such as Gasket, washers, panel heater and indicator bulbs and any other repair required at site to make the RMU fully functional, complete all as specified and directed,
Filtration & Dehydration of transformer oil (at different locations) using ON-LINE filtration plant to achieve dielectric strength minimum 50 KV/ 4mm including testing of oil before and after dehydration, complete all as specified and directed.. Note: Oil sample are to be collected from top and bottom of oil tank and test results to be recorded for each sample before and after filteration.
M&L for top up to transformer oil conforming to IS 395-1983 (Make : 'Savita', 'Power Oil', APAR) having die electric strength minimum 50 KV at 4mm gap complete all as specified and directed. Notes : (a) New Transformer oil will be filled in the transformer only after filteration and dehydration of existing transformer oil of the transformer. (b) Transformer oil shall be supplied in sealed barrel with test result and test certificate.
M&L for calibration of relays of HT VCB by secondary and primary injection, replacement of defective operating handles, checking of under voltage, over current relays and replacement of UNSV parts of master relays complete all as specified and directed.
Overhauling /servicing through agent authorised by OEM of step down outdoor/indoor transformer (Make:- WESTERN / INDIAN Transformer Ltd / Voltamp) 11/0.433 KV by disconnecting HT/LT terminals, decanning transformer oil, removing sludge, cleaning of HT /LT bushings to remove dust particles /dirt etc, cleaning the core and winding with compressed air including replacement of copper washers, rubber bushes of HT/LT bushings, replacement of cork sheet of 6 mm thick suitable for transformer top cover, terminal boxes, reassembling refilling the transformer oil after filteration and dehydration and toping up with new transformer oil, painting with two coats of synthetic enamel paint after preparation of painted surfaces of transformer and testing and recommissioning on load etc, complete all as directed for the transformers of following rating (Filteration and dehydration of transformer oil, supply only transformer oil for topping up, supply only of HT & LT bushings shall be measured and paid separately under respective items)
Transformer 750 KVA
Transformer 500 KVA
Transformer 250 KVA
Overhauling/Servicing through agent authorised by OEM of step down indoor/outdoor transformer (Makes Western/Indian/ABB/Voltamp) 11/0.433 KV Dry type by disconnecting HT/LT terminals, cleaning of HT/LT bushings to remove dust particles/dirt etc, cleaning the core and winding with compressed air and reassembling complete including replacement of copper washers, rubber bushes of HT/LT bushings, replacement of core sheet suitable for transformer topcover, terminal boxes, painting with two coats of synthetic enemal paint and testing and recomissioning on load etc, complete all as directed for the transformers of following rating:- supply only of HT & LT bushings shall measured and paid separately under respective items
Transformer 750 KVA
Transformer 500 KVA
Transformer 250 KVA
Supply only HT bushing suitable for the following capacity transformer of make Western/Indian transformer Ltd/Voltas etc. complete all as specified and directed :-
Transformer 750 KVA
Transformer 500 KVA
Transformer 250 KVA
Supply only LT bushing suitable for the following capacity transformer of make Western/Indian transformer Ltd/Voltas etc. complete all as specified and directed :-
Transformer 750 KVA
Transformer 500 KVA
Transformer 250 KVA
Supply and fix silica gel breather for 11/0.433 KV transformer upto 750 KVA capacity with silica jel etc. complete all as specified and directed.
Repairs and overhauling of Air Circuit Breaker (ACB) 3/4 pole, 415 Volt, upto 800/1200 Amp with thermal magnetic release by replacement of worn out parts and cleaning the complete ACB and testing the same after repair for smooth functioning etc complete all as specified and directed.
S&F Power factor improvement capacitor ultra heavy duty APP (5 to 25 kVAr bank ) for 3 phase 440V 50 Hz system suitable to existing load of make:- Havells/Asian/EPCOS/L&T/C&S/HPL
Supply and fix cable jointing kit for 11 KV (earthed) grade cable for indoor termination heat shrinkable type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium cable of size 50 Sqmm to 95 Sqmm with connecting single thimbles etc complete all as specified and directed
Supply and fix cable jointing kit for 11 KV (earthed) grade cable for indoor termination heat shrinkable type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium cable of size 120 Sqmm to 185 Sqmm with connecting single thimbles etc complete all as specified and directed.
Supply and fix cable jointing kit for 11 KV (earthed) grade cable for outdoor straight through heat shrink type joint complete with jointing material and accessories suitable for 3 Core XLPE armoured aluminium cable of size 50 Sqmm to 95 sqmm including connecting single thimbles etc complete all as specified and directed.
Supply and fix cable jointing kit for 11 KV (earthed) grade cable for outdoor straight through heat shrink type joint complete with jointing material and accessories suitable for 3 Core XLPE armoured aluminium cable of size 120 Sqmm to 185 sqmm including connecting single thimbles etc complete all as specified and directed.
Taking out existing unserviceable HT XLPE cable of size 3 core x 120 Sqmm (including joints where exists) and in lieu supply, laying in trenches/along wall/ pole/ in pipe etc, connecting and testing new HT under ground cable of size 3 Core 120 Sqmm, XLPE insulated, screened, eartherd, PVC sheathed, galvanised steel strip armoured (heavy duty), 11000 Volts grade with stranded aluminium conductor etc complete all as specified and directed. (Note: Excavation & earthwork, cable covers, protection pipes and sand cushioning shall be measured and paid seperately).
Taking out existing unserviceable HT XLPE cable of size 3 core x 185 Sqmm (including joints where exists) and in lieu supply, laying in trenches/along wall/ pole/ in pipe etc, connecting and testing new HT under ground cable of size 3 Core 185 Sqmm, XLPE insulated, screened, eartherd, PVC sheathed, galvanised steel strip armoured (heavy duty), 11000 Volts grade with stranded aluminium conductor etc complete all as specified and directed. (Note: Excavation & earthwork, cable covers, protection pipes and sand cushioning shall be measured and paid seperately).
Material and labour for filling fine, river sand for sand cushioning in trenches for cable protection all as specified and directed. (Note : Punned thickness will be measured and paid).
Material and labour for unreinforced pre-cast concrete cable cover class HV type-1, flat of size 300mm x 180mm x 40mm etc complete all as specified and directed
Material and labour for in replcement of Danger notice plate of 1.6mm thick mild steel sheet, vitreous enamelled white, with letters, figures and conventional skull and bones in signal red colour and fixed with M.S. clamps, bolts and nuts of approved size, for HT, 25x20cm size complete all as spcified and directed.
Excavation in trenches not exc 1.5m wide and not exc 1.5m depth in soft/loose soil for foundation or for laying of cable and getting out etc complete all as specified and directed.
Returning filling, including spreading levelling, watering and well ramming in layers not exc 25cm thick etc complete all as specified and directed
Removal of excavated material (soil) n. exc 50 mtr and depositing where directed etc complete all as specified and directed.
Supply & fix cylindrical type PT fuse, 2A/3Amps, complete all as specified and directed, Make:- Bussmann/MEI/Eswari.
Supply and fix PT 11KV/110V AC, 50 Hz epoxy resin casting type with 2A/3A PT fuses barrel type 3 Nos fixed indoor type etc complete all as specified and directed.
Supplying and laying synthetic Rubber insulated mats 25 mm thick for voltage upto 11 kv for electrical purpose as per IS 15652-2006, (superseding IS 5424) suitable for electrical shock safety of sizes 2m x 1m complete all as specified and directed.
M & L for servicing of battery bank of relay panel complete opening, cleaning and checking all circuits for its serviceablity and replacing consumable spares, complete all as specified and directed.
Supply and fix Power Pack Equipment suitable for working on 230V and with output voltage of 110V and having 300 VA capacity, complete all as specified and directed. Make:- Gogate Electro System (N) Pvt Ltd or equivalent as approved by GE.
Material and labour for preparation of existing painted steel surface of HT/LT panel by scraping and cleaning the surface and apply two coats of synthetic enamel paint by spray painting to achieve glossy finish in approved colour/shades including writing number and location of feeders with black paint etc complete all as specified and directed.
M & L in repair Earthing with galvanised steel earth plate electrode 600 x 600 x 6mm thick buried directly in ground (earth pit not less than 2.25 m deep below ground level) with top edge of the plate not less than 1.5 m below normal ground level, connected to galvanised earth lead strip of size 25 x 4 mm by mean of bolts, nuts, check nuts and washers of galvanised iron steel including necessary excavation, earth work, earth pit of PCC 1:2:4 type B-1 (using 20mm graded stone aggregate) with RCC 1:2:4, 50mm thick cover reinfoced with XPM etc all as shown in electrical plate No. 5 of SSR 2009 Part I and connected to earthing test point all as specified including, funnel with GI watering pipe of 20mm bore medium grade & GI protection pipe 40mm bore light grade including testing etc complete all as specified and directed.
Supply and fixing of fire Extinguisher Co2 type 2 kg capacity to fixed on wall including fixing bracket complete all as specified and directed.
Supply and fixing in replace of fire extinguisher Co2 type 4.5/5 kg capacity to fixed on wall including fixing bracket complete all as specified and directed.
S&F fire in replace ball extinguisher ABC dry powder type, 1.3 kg for electrical installation complete all as specified and directed.
Supply and fix heating strip and supply and install fin strip terminals parallel, 400 watt 8" long mounted on insulators suitable for 11 KV HT panel for de-humudifying moisture with proper connection from separate source to existing panel and testing complete all as specified and directed.
Supply and fix LED type RYB indicator set complete all as specified and directed
M& L for pressure test suitable for 11 KV HT panel, VCBs, CT/PT bus bar complete and appling two coats of insulation spray complete and submit report in writing all as specified and directed
Supply and fixing complete vacuum interupter bottle (VG-2)-03 Nos suitable for HT 11 KV existing VCB , 800 Amp trolly mounted. The vacuum bottles should be capable of withstanding minimum 100 full short circuit operations as per test duty 1 to 5 of IEC-56. The vacuum bottles manufacture’s test reports / literature for vacuum bottles, supplied in duplicate complete all as specified of existing type - HVX-X, make: Schneider
Supply and fixing insulating enclosure triple pole-01 no suitable for HT 11 KV existing VCB , 800 Amp complete all as specified of existing type - HVX-X, make: Schneider
Supply and fix of 11KV three phase CT cast resin made indoor type for metering and protection purpose of CT having rated current ratio 100/65/5 for dual configure purpose with 15 VA secondary burden rating etc and confirming to IS-2705 with accuracy class 0.5 complete all as specified and directed.
M&L for finding faults of HT UG cable XLPE, 11KV of any size and any length upto 240 Sqmm by using computerised / primary current injection method / any other method as directed by the GE and locating fault, cutting and removing the faulty portion of the cable and jointing with suitable cable joint and testing after jointing all as required and directed. Note: Excavation deemed to be included in above rates. Cable joint shall be measured and paid separately.
Supply and fix battery charger 40 volt DC/25 Amp suitable for working on 230V and with output voltage of 40V DC and having 25 A capacity, 50 Hz single phase working on air natural cooling complete all as specified and directed. Make:- Power Guard Systems or equivalent as approved by GE.
Supply and Fixing 3 Phase Shunt recator of 5 KVAR with exisiting shunt capacitors of APFC Panel for PF improvement & reduce harmonic distortion complete all as specified and directed.
M&L for Plates chequered of Fe 410 W Gde E-250 quality A channels, square cut or notched (ordinary and counter sunk) forming holes, without any attachment complete all as specified and directed
Supply & replace existing out dated First Aid kit complete all as specified and directed
Material and labour for fixing standard shock treatment chart in English & Hindi duly framed and covered with glass complete all as specified and as directed by Engr-In-Charge.
Supply and fix 6.6-11 KV single phase current transformer (CT's) conforming to IS-2075, VA burden - 1VA, class of accuracy - 0.5/5P-10 / PS, Type of CT as per existing with CTR 40-20/5A/5A/100-50/5A/5A complete all as specified and as directed by Engr-In-Charge.
Taking out defective HT winding and M& L for rewinding of HT coil with super enameled best quality copper wire of existing gauge with superior quality insulation material for transformer of capacity 250 to 500 KVA complete all as specified and directed by Engr in Charge.
M& L for rewinding of LT coil with super enameled best quality copper wire of existing gauge with superior quality insulation material for transformer of capacity 200 to 500 KVA complete all as specified and directed by Engr in Charge.
Material and labour for (i) Disconnecting the HT/LT side and earthing connections of the transformer, (ii) Lifting transformer with the help of crane, loading on suitable vehicle to transport it to the workshop at and Unloading at workshop for servicing (iii) Dismantling of HV/LV bushing, opening of top cover, disconnecting of connections of tap changer of transformer (iv) Draining out the complete transformer oil (vi) Heating and winding of core and winding assembly complete in vacum chamber (vii) Taking down by complete core & winding assembly & fixing tap changer after servicing and testing, (viii) Provide New HV/LV bushing and making all internal connections, (ix)Providing new gasket packing minimum 12mm thick, including nut bolt washer complete, (x) Transporting transformer back to the site , Lifting it down with the help of crane and reconnecting the HT/LT cable and earthing connections complete all as directed for transformer of up to 500 kva capacities Note-: (1)It is mandetary to attend and rectified all HT break down immediately after received complaint or telephonic call. (2) 50 % penality will be raise if break down will not attended within 12 Hours of particular items.
Overhauling of step down outdoor/indoor transformer (Make:- WESTERN / INDIAN Transformer Ltd / Volts) 11/0.433 KV by disconnecting HT/LT terminals, decantation transformer oil, removing sludge, cleaning of HT /LT bushings to remove dust particles /dirt etc, cleaning the core and winding with compressed air including replacement of copper washers, rubber bushes of HT/LT bushings, replacement of cork sheet of 6 mm thick suitable for transformer top cover, terminal boxes, reassembling refilling the transformer oil after filteration and dehydration and toping up with new transformer oil, painting with two coats of synthetic enamel paint after preparation of painted surfaces of transformer and testing and recommissioning on load etc, complete for the transformers of following rating. Note: Oil for transformer dehydration & filteration top up purpose shall be supplied respectively, cost of labour deemed to be included in the quoted rate of this item.
(a) Transformer 400KVA
(b) Transformer 315 KVA
Supply only HT bushing suitable for the following capacity transformer of make Western/Indian transformer Ltd/Voltas etc. complete all as specified and directed :-
(a) Transformer 400KVA
(b) Transformer 315 KVA
Supply only LT bushing suitable for the following capacity transformer of make Western/Indian transformer Ltd/Voltas etc. complete all as specified and directed :-
(a) Transformer 400KVA
(b) Transformer 315 KVA
S&F panel mounted digital type, PF meter, flush mounted, single phase, class 0.01 accuracy, 96mm x 96mm, including modiication of panel for fixing of PF meter, complete all as specified and directed.
Taking out existing unserviceable HT XLPE cable of size 3 core x 95 Sqmm (including joints where exists) and in lieu supply, laying in trenches/along wall/ pole/ in pipe etc, connecting and testing new HT under ground cable of size 3 Core 95 Sqmm, XLPE insulated, screened, eartherd, PVC sheathed, galvanised steel strip armoured (heavy duty), 11000 Volts grade with stranded aluminium conductor etc complete all as specified and directed. (Note: Excavation & earthwork, cable covers, protection pipes and sand cushioning shall be measured and paid seperately).
Supply and fix MCCB 4 pole, 415 Volt adjustable type with breaking capacity 36 KA from panel boards etc complete all as specified and directed of following rating:-
(ii) 250 Amp
S&F Microprocessor controlled numeric relay, three phase overcurrent and earth fault auxiliary voltage of 18-52 V DC, current setting from 0.1 to 25 IN with LED display for trip, alarm warning & auxillary output and back lit, LCD display of parameter with programmable key board settings type CGI14N/C of make : Crompton Greaves or equivalent all as specified and directed.
M&L for 500 watt incandescent lamp with ceramic holder for absorbing the moisture from outside all as required and directed.
Supply installation, testing and commissioning of FAST ELECTRODE maintenance free Chemical Earthing of Dual Pipe Technology, each of 3 Meter long with Outer Pipe Diameter of 88mm (galvanised for 80-120 micron and wall thickness 1.80mm) and Inner Pipe diameter 48mm (galvanised for 80-120 micron and wall thickness 2.60mm). There shall be terminal of size 75 x 5.20mm for connection with two holes of 14mm diameter. FAST ELECTRODE shall be duly filled with the highly conductive, Non Magnetic, Non Corrosive material and duly sealed at both ends with lead terminal of 75x5.2mm at top. The ELECTRODE shall be of 'make' having approval of CPRI (Central Power Research Institute), Govt of India for a minimum short circuit current of 42 KArms for 1 Second with initial pick of 88.2 KA. The FAST ELECTRODE Earth Enhancing Compound (minimum 25Kg) shall be pored on alround the electrode. The chemical compound to be used shall be as per the manufacturer's instructions of 'Electrode' and as also certified by any BIB (Bureau of Indian Standards) accredited laboratory. Make : Fast Electrode or equivalent as approved by the GE. Notes:- (i) The contractor shall procure the above materials either directly from the manufacturer(s) or their authorised dealers only and shall produce the original purchase vouchers alongwith original manufacturer's test certificates and other authenticated documents in compliance of the provisions as mentioned in the above item. Also all the requisite testing as specified above, in relevant IS and as directed by the GE shall be got done by the contractor. Cost of all the above elements shall be deemed to be included in the contractor's quoted rates. (ii) Any additional quantity of Earth Enhancing Compound in case required to obtain the desired results, the same also be provided by the contractor without any additional cost to the Govt. and quoted rates of above item shall be deemed to include the above element also. (iii) Copper strip upto 7.5 meters included above quoted rates.
Servicing of APFC Panel cubical, floor moulded, indoor type Panel, 440 Volts AC 50Hz 3 phase made out of CRCA sheet of thickness 2.0 mm and 1.6mm for partition IP-42 protection with aluminium bus bars of cross section 40 x 10 mm, MPP-H capacitor including MCCB 400 A, 35 KA (incoming), HRC fuses, Tyrister switches,microprocessor based APFC relay, Volt meter, Ammeter, CTs, phase indicating lamps and powder coated seimens grey painting etc complete. Make:- L&T or make as approved by GE.
Supply and fix in repairs Power Capacitors of Rating 25 KVAR 415 Volt Naturally air cooled Double dielectric heavy duty, MPP type 440 Volt 50 HZ Watt Less Power Capacitors wattage not more than 0.5 Watt per KVAR with meter system conforming to IS 13340 and 13341 ISI Marked complete all as specified and directed.
All as per item No 63.00 above but Power Capacitors of Rating 10 KVAR 415 Volt complete all as specified and directed.
All as per item No 63.00 above but Power Capacitors of Rating 5 KVAR 415 Volt complete all as specified and directed.
All as per item No 63.00 above but Power Capacitors of Rating 2 KVAR 415 Volt complete all as specified and directed.
Supply only Aluminum lugs for cable 120 to 300 sqmm, 3.5 core complete all as specified and directed.
Spply only Aluminum lugs for cable 25 to 95 sqmm, 3.5 core complete all as specified and directed.
Spply only Copper lugs for cable 16 to 95 sqmm, 3.5 core complete all as specified and directed.
Spply only Aluminum glands for cable 120 to 300 sqmm, 3.5 core complete all as specified and directed.
Spply only Aluminum glands for cable 16 to 95 sqmm, 3.5 core complete all as specified and directed.
Supply and fix flexible copper cable size of 16 sqmm single core for connection MCCB to busbar complete all as specified and directed.
Supply and fix flexible copper cable size of 25 sqmm single core for connection MCCB to busbar complete all as specified and directed.
Material and Labour For Connecting HT 3 Phase,11KV,630Amps rated Adaptor panel( located at 'B' Zone Power House) By direct Bus Coupling with Existing Incomer ICOG VCB 11KV panel of Schnider make and Comissioning including necessary modifications such as Fixing of Copper Bus Bar 630A rated of size Approx 50x10 mm for all three phases R,Y,B. along with HT colour coded sleeve insulation to bus bars, necessary GI Bolts and washers Panel cutting and welding etc.Complete all as specified and directed by the Engr-in-Charge. Note : The rate quoted by the contractor shall also be including Extra Copper Bus bars of same size required to Bus coupling of Adaptor panel, with ICOG VCB Panel,also Shifting of Existing ICOG Panel from MRS S/S To B zone power house and Connection and Commissioning After modification of Adaptor panel .
Supply only following spare parts suitable for 30 VDC/ 110VAC to be incorporated under item No 02 above : (a) Replacement of spring charge motor single phase 110/220 volts
S & F in repairs Closing Coil Or Tripping Coil 30V DC For VCB Item No 2.00
Supply Install Testing and Commissioning of Digital Microprocessor Based Numerical Self Powered Over current+ Earth fault relay of Make : Ashida Model ADR 141S or equivalent, including necessary Control wiring Connections and Setting of relay parameters complete all as specified and Directed.
Overhauling of step down indoor transformer (Make:- WESTERN / INDIAN Transformer Ltd / Volts/Silverline) 11/0.433 KV by disconnecting HT/LT terminals, decanning transformer oil, removing sludge, cleaning of HT /LT bushings to remove dust particles /dirt etc, cleaning the core and winding with compressed air including replacement of copper washers, rubber bushes of HT/LT bushings, replacement of cork sheet of 6 mm thick suitable for transformer top cover, terminal boxes, reassembling refilling the transformer oil after filteration and dehydration and toping up with new transformer oil, painting with two coats of synthetic enamel paint after preparation of painted surfaces of transformer and testing and recommissioning on load etc, complete for the transformers of following rating (Filteration and dehydration of transformer oil, supply only transformer oil for topping up, supply only of HT & LT bushings shall be measured and paid separately under respective items)
(a) Transformer 160 KVA
Overhauling of step down indoor transformer 11/0.433 KV Dry Type by disconnecting HT/LT terminals, decanning transformer oil, removing sludge, cleaning of HT /LT bushings to remove dust particles /dirt etc, cleaning the core and winding with compressed air including replacement of copper washers, rubber bushes of HT/LT bushings, replacement of cork sheet of 6 mm thick suitable for transformer top cover, terminal boxes, reassembling,painting with two coats of synthetic enamel paint after preparation of painted surfaces of transformer and testing and recommissioning on load etc, complete for the transformers of following rating (Filteration and dehydration of transformer oil, supply only transformer oil for topping up, supply only of HT & LT bushings shall be measured and paid separately under respective items)
(a) Transformer 150 KVA
Supply and fix in repairs HT bushing suitable for the following capacity transformer of make Western/Indian transformer Ltd/Voltas/Silverline etc. complete all as specified and directed :-
(a) Transformer 160KVA
Supply and fix in repair for eplacement of LT bushings of RYBN suitable for the following capacity transformer of make Western/Indian transformer Ltd/Voltas/Silverline etc. complete all as specified and directed :-
(a) Transformer 160KVA
Supply & Fixed in repair of breather assembly transparent plastic body with top and bottom portion pressed with metallic cover, filled with silica gel blue in colour and suitable for fixing on existing pipe of size 15/20/25 mm dia with suitable reducers/connectors etc as per site requirement /capacity of transformer. Note : Rate quoted shall be deemed to include the cost of modification if any required to fix on existing MS Pipe.
Supply and fix in replacement of 11 KV, 3 phase CT(Current Transformer set of 3 Single phase) cast resin made indoor type for metering and protection purpose of CT having rated current ratio 100/65/5 A for dual configure purpose with 15 VA secondary burden rating etc and conforming to IS - 2705 with accuracy class 0.5 complete all as specified and directed.
Supply and fix in replacement of 11 KV, 3 phase PT(Potential Transformer) RYB(Set of 3 Single phase) cast resin made indoor type for metering and protection purpose of PT having rated Voltage ratio 11kv/110v with 2A/3A PT Fuses for dual configure purpose with 50 VA secondary burden rating etc and conforming to IS - 3156 with accuracy class 0.5 complete all as specified and directed.
Supply, laying, in trenches connecting and testing in replacement of unserviceable or additional HT under ground cable of size 3 Core 150 Sqmm XLPE insulated, screened, eartherd, PVC sheathed, galvanised steel strip armoured (heavy duty) 11000 Volts grade with stranded aluminium conductor etc complete all as specified and directed. (Note: Excavation & earthwork, PCC cable cover and sand cushioning shall be measured and paid seperately).
Material and labour for earthing complete with Copper earth plate electrode 600x600x3.15 mm thick burried directly in ground (earth pit not less than 2.25 mtr deep below ground lavel) with top edge of the plate not less than 1.5mtr below normal ground lavel connected to Copper Earth strip 20x3 mm by mean of bolts, nuts, check nuts and washer of brash all as shown in electrical plate No 5 connected to earthing test point all as specified or indicated including PCC pit and CI cover fullel with watering pipe, wire mess and copper lugs etc GI protection pipe 40 mm dia medium grade including testing on completion all as specified and directed.
Supply and fixing in repair Heating strip suitable for 11 KV HT Panel for de-humidifying moisture with proper connection from separate source to existing panel and testing complete all as specified and directed.
Supply and Fixing complete HT Layout of INS Hamla and NSD Ghatkopar area including all substations with HT Cable,Transformer,VCBS and Other items over the Sun board Standard size Approx 4ft x 3ft with Computerized Printing given by Engr-in-Charge in proper laminated sheet Complete all as specified and directed.
NOEL ENGINEERS
Radha Engineering Services
NARMARAJ ELECTRICALS
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .