Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹10.4 CrAccepted-AOC 9 A PONGALIVALASU KODUMUDI POST ERODE 638 151 | KARUR | TAMIL NADU | 638151 | ₹10.4 Cr Quoted ₹11.1 Cr | L1 | Accepted-AOC Accepted |
| 2 | L2₹11.3 CrRejected-AOC NO 801 1 M VELAMPALAYAM MODAKURICHI ERODE DISTRICT 638 104 | ERODE | TAMIL NADU | 638104 | ₹11.3 Cr | L2 | Rejected-AOC Rejected |
| 3 | Rejected-Technical | - | - | Rejected-Technical not uploaded prescribed document |
Tender Value
₹10.1 Cr
EMD Value
₹5.2 L
Closing Date
11 Mar 2024, 3:00 pmClosed
Chief Engineer
Office of Chief Engineer, Sardar Patel Road, Dote Campus, Chennai 25
Providing Additional facilities such as Approach road, fire fighting arrangements, sump, Overhead tank and plinth protection to the five Special Institutions and strenghtening the HT power supply to the entire CIT campus, Tharamani, Chennai 113
2024_HE_424317_1
CPT_Tharamani_2023
Open Tender
Civil Works - Buildings
270 days
Tharamani
Please refer Tender documents.
9 documents required · 9 mandatory
₹0
₹5.2 L
Yes
3 Oct 2024
13 Feb 2024
12 Mar 2024
13 Feb 2024
11 Mar 2024
13 Feb 2024
Amount
Earthwork Open excavation in all soils and sub soils to full depth as may be directed except in hard rock requiring blasting inclusive of shoring shuttering, baling out water wherever necessary refilling the foundation with excavated earth other than sandy soil in layers of not more than 15 cm thick layers well rammed and depositing the surplus earth within compound in places shown by the departmental officers with an initial lead of 10 metre and initial lift of 2 metre and clearing and leveling the site etc., complete complying with standard specification and as directed by the departmental officers.
Earthwork excavation for foundation in all soils and sub soils to full depth as may be directed except in hard rock requiring blasting inclusive of shoring shuttering, baling out water wherever necessary, refilling the foundation with excavated earth and depositing the surplus earth within compound in places shown by the departmental officers with an initial lead of 10 metre and initial lift of 2 metre and clearing and leveling the site etc., complete complying with standard specification and as directed by the departmental officers.
Earth work open well excavation complying with relevant clauses of T.N.D.S.S. Well sinking and with lead upto 10 metre in Hard stiff clay, stiff black coton soil, hard red earth, shales, murram, gravel, stoney earth and earth mixed with small size boulders and hard gravely soil - First depth of 2 metre etc., complete complying with standard specification and as directed by the departmental officers.
Earth work open well excavation complying with relevant clauses of T.N.D.S.S. Well sinking and with lead upto 10 metre in soft disintegrated rock, laterite, soft rock or kankar not requiring blasting etc., complete complying with standard specification and as directed by the departmental officers.
2.00 to 4.00 m depth
Open well excavation complying with relevant clauses of T.N.D.S.S. Well sinking and with lead upto 10 metre in Medium rock and dense medium rock not requring blasting etc., complete complying with standard specification and as directed by the departmental officers.
4.00 to 6.00 m depth
6.00 to 8.00 m depth
8.00 to 10.00 m depth
Supply and filling basement with excavated earth other than sand with an initial head lead of 100 mts. and depositing the earth as shown by the departmental officers in layers of not more than 15cm thick well rammed, watered and consolidated etc. complete complying with standard specification.
Supplying and Filling in foundation and basement with filling M sand in layers of not more than 15cm thick well rammed watered and consolidated etc., complete complying with standard specification and as directed by the departmental officers.
Cement concrete 1:5:10 (one cement, five M sand and ten aggregate) using 40mm gauge hard broken blue granite stone jelly for foundation and basement including dewatering if found necessary and laid in layers of not more than 15cm thick and compacted etc., complete complying with standard specification and as directed by the departmental officers.
Providing and laying in position, Standardised Concrete Mix M-20 Grade in accordance using with IS:456-2000, 20mm and down graded hard broken granite stone jelly for all RCC items of works with minimum cement content of 325 kg/m3 and maximum water cement ratio of 0.55, including admixture (plasticiser / super plasticiser) in recommended proportions as per IS:9103 to accelerate, retard setting of concrete, improve workability without impairing strength and durability with about (5cu.m.) 7730 kg. of 20mm machine crushed stone jelly and with about (3.3 cu.m.) 5156 kg. of 10-12mm machine crushed stone jelly and with about (4.79 cu.m.) 7670 kg. of m sand, but excluding cost of reinforcement grill and fabricating charges, centering and shuttering and also including laying, vibrating with mechanical vibrators, finishing, curing, etc. and providing fixtures like fan clamps in the RCC floor/ roof slabs wherever necessary without claiming extra, etc., complete complying with standard specification and as directed by the departmental officers. The coarse and fine aggregates to be used should comply with the requirements of IS standards. (No separate payment will be made by the Department for the excess usage of materials).
For foundation and basement
Supplying and Fixing RCC precast slab of 50mm thickness in reinforced cement concerete 1:2:4 (One of cement, two of M sand and four of aggregate) using 20mm hard broken stone jelly and M sand, excluding the cost of reinforcement grills and including fabrication charges, moulding, curing, finishing charges and fixing in position neatly etc., complete complying with standard specification and as directed by the departmental officers.
Supplying and erecting steel centering including necessary supports for plane surfaces for Reinforced Cement Concrete works such as column footings, column pedestals, plinth beams, grade beams, staircase steps, etc. which require only nominal strutting using mild steel sheets of size 90cm x 60cm and 10 BG stiffened with welded mild steel angles of size 25mm x 25mm x 3 mm for boarding, laid over silver oak joists of size 10cm x 6.5cm spaced at about 75cm centre to centre or at suitable intervals etc. complete in all floors complying with standard specifcation. (Payment for centering shall be given after the concrete is laid).
Supplying and erecting steel centering including necessary supports for plain surfaces, for all RCC works including strutting upto 3.29m in all floors using mild steel shutters of size 90cmx60cm of BG 10 stiffened with mild steel angles of size 25mmx 25mmx3mm laid over silver oak (Country wood) Joists of size 10cmx6.5cm spaced at about 90cm c/c and supported by casurina props of 10cm to 13cm dia. (spaced at 75cm c/c) etc., complete complying with standard specification and as directed by the departmental officers. (The centering will be removed after specified period of concrete without damaging the concrete)
For plane surface such as RCC floor slab, roof slab, beam litels bed blocks, landing slab, waist slabs and beams, etc.,
For plane surfaces such as RCC square or rectangular column, top and bottom slab of sunshade, boxing sill etc. complete as directed
For plane surface such as Vertical surfaces such as sunshade, boxing vertical drops, facia for sunshade and other vertical walls etc.,
For Curved surfaces such as vertical slab, side slabs of boxing, vertical drops, facia, vertical wall etc
Providing and laying in position, Standardised Concrete Mix M-30 Grade in accardance with IS 456-2000 using 20mm and down graded Hard broken Granite stone jelly for all RCC items of works with minimum Sulphate resistant cement content of 400 Kg/m3 and maximum water cement ratio of 0.45, including admixture ( plastciser/ super plasticiser ) in recommanded proportions as per IS 9103 to accelerate, retard setting of concrete, improve workability withiut impairing strength and durability with about ( 5.0 cu.m ) 7730 Kg. of 20mm machine crushed stone jelly and with about ( 3.30 cu.m) 5156 Kg. of 10-12mm machine crushed stone jelly with about ( 4.79 cu. m) 7670 Kg. of M sand, but excluding cost of reinforcement grill and fabricating charges, centering and shuttering and also including laying, vibrating with machanical vibrators, finishing,curing etc; and providing fixures like fan clamps in RCC floor/roof slab wher ever necessary without claiming extra, etc., complete complying with standard specifications and as directed by the Departmental officers. The coarse and fine aggregates to be used should comply with the requirements of IS standards. ( No separate payment will be made by the Department for the excess usage of materials)
upto 1.50 m - Below ground level upto 1.50 m
From 1.50m to 4.50 m Below ground level
Above 4.50m - Below ground level
Providing and laying in position, Standardised Concrete Mix M-30 Grade in accardance with IS 456-2000 using 20mm and down graded Hard broken Granite stone jelly for all RCC items of works with minimum cement content of 400 Kg/m3 and maximum water cement ratio of 0.45, including admixture ( plastciser/ super plasticiser ) in recommanded proportions as per IS 9103 to accelerate, retard setting of concrete, improve workability withiut impairing strength and durability with about ( 5.0 cu.m ) 7730 Kg. of 20mm machine crushed stone jelly and with about ( 3.30 cu.m) 5156 Kg. of 10-12mm machine crushed stone jelly with about ( 4.79 cu. m) 7670 Kg. of M sand, but cxcluding cost of reinforcement grill and fabricating charges, centering and shuttering and also including laying, vibrating with machanical vibrators, finishing,curing etc; and providing fixures like fan clamps in RCC floor/roof slab wher ever necessary without claiming extra, etc., complete complying with standard specifications and as directed by the Departmental officers. The coarse and fine aggregates to be used should comply with the requirements of IS standards. ( No separate payment will be made by the Department for the excess usage of materials)
For Foundation and basement - upto 1.50m
From 1.50 m to 4.50 m Below ground level
From 4.50 m to 9.00 m Below ground level
For Ground floor
For Second floor
For Third floor
Providing and Laying Granular Sub- Base Grade - III consisting of well graded material, mixing in a mechanical mix plant at OMC, carriage of mixed material to work site, spreading in uniform layers with motor grader on prepared surface and compacting with vibratory roller to achieve the desired density as per MORTH No. 111, 112, 401,900 etc., Complete complying with standard specification and as directed by the departmental officers.
Providing and Laying Wet Mix Macadam consisting of clean crushed aggregates, including premixing the material with water at OMC in mechanical mix plant carriage of mixed material by tipper to site, laying in uniform layers with paver on well prepared surface and compacting with vibrator roller to achieve the desired density as per MORTH No. 111, 112, 401, 900 etc., Complete complying with standard specification and as directed by the departmental officers.
Providing and applying Prime Coat over granular Base with bitumen emulsion (SS-I type) on prepared surface including preparing the road surface and spraying the primer at the rate of 0.70 kg/sqm using bitumen sprayer over WMM as per MORTH No. 111, 112, 502, 900etc., Complete complying with standard specification and as directed by the departmental officers.
Providing and applying Tack Coat over granular surface treated with primer using Bitumen Emulsion (RS-I type) with mechanical sprayer at the rate of 0.25 kg per sqm as per MORTH No.111,112,503,900 etc., Complete complying with standard specification and as directed by the departmental officers.
Providing and laying Dense Bituminous Macadam which work shall consist of construction, using crushed aggregates, premixed with VG 30 Grade Bitumen at the rate of 3.40% by weight of the total mix confirming to the aggregates and binder in the Hot mix plant, transporting the mix to the worksite, laying with paver finisher and compaction with smooth wheeled and vibratory roller in accordance with the requirements of the specification and in conformity with the drawing DBM (Grade-II) as per MORTH No. 111, 112, 505, 900 etc., etc., Complete complying with standard specification and as directed by the departmental officers.
Providing and laying Bituminous Concrete which work shall consist of construction using coarse aggregates premixed with VG 30 Grade Bitumen confirming to the aggregates and binder as per the job mix formula in the Hot mix plant, transporting the mix to the worksite, laying with paver finisher and compaction with smooth wheeled and vibratory roller in accordance with the requirements of the specification and in conformity with the drawing (Grade-II) as per MORTH No. 111, 112, 507,900 etc., Complete complying with standard specification and as directed by the departmental officers.
Supplying, fabricating and placing inposition of steel reinforcement using MS/Ribbed tor steel rods for all RCC works as per the design given including cost of steel and G.I binding wire also in all floors etc., complete complying with standard specification and as directed by the departmental officers.
Brick work in cement mortar 1:5 (one cement and five M sand) using Fly Ash bricks of size 230×110×70mm including curing etc., complete complying with standard specification and as directed by the department officers. (Masonry projections wherever necessary for obtaining required elevation shall be done without extra cost).
For foundation and basement
From 1.50 m to 4.50 m Below ground level
From 4.50 m to 9.00 m Below ground level
For superstructure in Second floor
For superstructure in Third floor
Brick work in cement mortar 1:6 (one cement and six M sand) using Fly Ash bricks of size 230×110×70mm including curing etc., complete complying with standard specification and as directed by the department officers. (Masonry projections wherever necessary for obtaining required elevation shall be done without extra cost).
For Ground floor
Brick partiton wall 11.10cm thick in cement mortar 1:3 (one cement and three M sand) using Fly Ash bricks of size 230×110×70mm including fixing hoop iron reinforcement if found necessary, laying, finishing and curing etc., complete complying with standard specification and as directed by the departmental officers.
For superstructure in Ground floor
For superstructure in Second floor
For superstructure in Third floor
Special ceiling plastering in all floors and finishing the exposed surface of RCC items of work such as slab, beam, sunshade, facia, canopy slab, staircase waist slab, landing slab etc., with cement mortar 1:3 (One cement and three P-sand) 10mm thick mixed with Bonding agent Cebex112, Zydex- Zycrete 2X or other Equalent compound conforming to BIS at 200 ml of one cement bag (50kg) for increased workablity and air entrainment including hacking the surfaces and providing cement mortar nosing, beading for sunshade, staircase, step, landing slab etc., including neat finishing and curing etc., complete complying with standard specification and as directed by the departmental officers.
Plastering with cement mortar 1:5 (one cement and five p-sand) 12mm thick mixed with Bonding agent Cebex112, Zydex- Zycrete 2X or other Equalent compound conforming to BIS at 200 ml of one cement bag (50kg) for increased workablity and air entrainment used finishing in all floors using fine P sand including neat finishing, curing, etc., complete complying with standard specification and as directed by the department officers.
Plastering with cement mortar 1:3 (one cement and three p sand) 20 mm thick with WPC 2% by weight of cement and mixed with Bonding agent Cebex112, Zydex- Zycrete 2X or other Equalent compound conforming to BIS at 200 ml of one cement bag (50kg) for increased workablity and air entrainment used in all floors using fine P sand including neat finishing, curing, etc., complete complying with standard specification and as directed by the department officers.
Providing mixing laying polymer based water proofing treatment for the sunkan toilet by applying cement based fiexable WPC conforming to IS 2645 to a thickness of 1mm of the prepared surface of the roof slab / floor slab as per specification mendioned above providing cm 1:3 water proofing cover plaster to a thickness 12mm. The malaime coating with admixture of approved make rate quoted is inclusive of preparation of surface which including cleaning of surface polymer morter, curing, labour, tools equipments etc., rate inclusive of cement and sand required for the treatment the coat and labour charges for fixing 25mm dia pressure pipe 15 kg / m2 to length of 45 cm for drip pipe etc., complete complying with standard specification and as directed by the departmental officers.
White washing two coats with freshly burnt white shell lime in all floors including cost of lime, blue powder fevicol type gum, brushes, scaffolding charges, etc., complete complying with standard specification and as directed.
Painting two coats of newly plastered wall surface with ready mixed plastic emulsion paint of first quality and of approved colour over a priming coat including preparing the surface, clean removal of dirt and including necessary plaster of paris putty wherever required etc., complete complying with standard specification.
Weathering course using best quality of broken brick jelly of 20mm gauge in pure slacked lime (no sand to be added) the proportion of brick jelly to lime being 32:12.5 Cft. by volume and laid over the RCC roof slab in a single layer and consolidated to the required design and finished thickness and slope by beating the concrete with wooden beater of approved pattern and keeping the surface constantly wet by sprinkling lime jaggery water etc., complete complying with standard specification and as directed by the departmental officers.
Finishing the top of roof with one course of Machine pressed tiles of size 23×23×2cm of approved quality laid in cement mortar 1:3 (One cement and three M-sand) 12mm thick mixed with water proofing compound (confirming to Indian standard specification) 2% by weight of cement used and pointed with the same mortar including mixing of red oxide and water proofing compound etc., complete complying with standard specification and as directed by the departmental officers.
Finishing the top of flooring with granolithic floor finish of 40mm thickness with plain cement concrete of mix 1:2:4 (One cement, two M sand and four aggregate) using 20mm / 10 to 12mm ISS gauge hard broken granite stone including finishing the top smooth and forming thread lining and curing etc., complete complying with standard specification and as directed by the Departmental officers.
Paving the floor with Stain free nano polished vitrified tiles (like Marbonite or equivalent) of approved quality and colour of size 600 x 600x 8 mm thickness in all floors over a base layer of cement mortar 1:3 (one cement and three M sand) 20mm thick and pointing with white cement using 0.30kg/m2 including adding suitable colour pigments to suit the colour of tiles finishing perfectly and curing etc., including cost of tiles, all materials and incidential charges, transportation charges and labour charges for laying tiles etc., complete complying with standard specification and as directed by the Departmental officers. (The tiles should be got approved by the Departmental officers before use on works).
Paving the floor with colour design ceramic tiles of approved quality and colour of size 305 x 305 x 6mm in all floors over a base layer of cement mortar 1:3 (one cement and three m sand) 20mm thick and pointing with white cement using 0.30kg/m2 including adding suitable colour pigments to suit the colour of tiles finishing perfectly and curing etc., including cost of tiles, all materials and incidential charges, transportation charges and labour charges for laying tiles etc., complete complying with standard specification and as directed by the departmental officers . (The tiles should be got approved by the departmental officers before use on works).
Dadooing the walls with colour design glazed tiles of size 300mmx 450mmx 8mm of approved quality in all floors set in cement mortar 1:2 mix (one cement & two M-sand) 10mm thick and pointing with white cement using 0.4 kg/m2 including adding suitablee colour pigments to suit the colour of tiles including finishing the joints neatly and curing etc.,complete complying with standard specifications. (The tiles should be got approved by departmental officers before use on the work).
Supplying and fixing of PVC corner beeding of best approved quality and colour standard size and thickness of required height of walls using cement mortar 1:2 (One cement and two sand) and finishing the surface smooth with ceramic tiles etc., complete complying with standard specification and as directed by the departmetal officers.
Fabricating supplying and fixing in position CRCA pressed steel box section 18 gauge or 1.25mm thick for door frames of section size 105mmx60mmx1.25mm thick with necessary rebate of size 35x15mm for housing door shutters conforming to IS specification. Frames shall be fabricated to the specified door size with joints properly welded and grinded. Stiffeners with 25x3mm MS flat shall be provided around the frame at 60cm intervals. The cost shall also include for providing 3 Nos. of MS clamps with 25x3 flats each on either sides of door frame, providing bottom tie, with 10mm dia MS rod, providing necessary holes for receiving tower bolts 2 Nos. with stiffeners on inner side, providing the required number of I.O hinges of size 125x30mm for shutters properly welded to the frames, finishing the door with one coat of good quality red oxide primer with cement concrete 1:2:4 (One cement, two sand and four aggregate) using 20mm gauge hard broken granite stone jelly packed inside to the frame including cost of all materials, fabrication and conveyance to the site and fixing in position with necessary scaffolding etc., complete complying with standard specification and as directed by the departmental officer.
Supplying and fixing in postion of 35mm thick solid core flush door shutters with following specification. with Commercial ply on both sides and with TW lipping of size 35x12mm on all edges with necessary adhesives and C.P. Screws Alu. Butt Hinges (6 nos. 250 x 16 mm Size) Alu. Aldrop1 No. 250 x 16 mm Size, Alu. Tower Bolt 2 No. 250 x12 mm size, alu. Tower Bolt 2 No. 200 x 12 mm size, D type alu. Handle 200mm length 2 No., alu. door stopper with rubber bush 2 No. shall be provided, complete complying with standard specification and as directed by the departmental officers.
Single leaf
Double leaf
Supplying and fixing 30mm thick solid core PVC door shutter with PVC frame of size 50x45mm with suitable rebate for housing the shutter consisting of frame made out of MS tubes 19 gauge thickness and size of 19x19mm for styles and 15x15mm for top and bottom rails, MS frame shall be covered ith 5mm thick heat moulded PVC 'C' channel of size 30x50mm forming styles and 75x50mm for top rai8l, lock rail and bottom rail on either side and 10mm thick 20mm wide cross PVC sheet as gap insert for tap rail, botytom rail, panelling of 5mm thick PVC sheet bearing on either side and join together other side etc. An additional 5mm thick PVC strip of 20mm width is to be stack and the interior side of the 'C' channel using PVC sealant adhesiv e including cost of all furniture fittings, such as aluminium aldrop of size 250x16mm -1 No. aluminium tower bolt 250x12mm-1 No. aluminium D type handled 200mm etc. complete complying with standard specification and as directed by the departmental officers.
Supplying and fixing UPVC (Un-Plasticized Polyvinyl Chloride) Windows of casement type (open) from the profile the size of outer frame 60mm x 58mm and shutter profile are reinforcement with GI/1mm 125GSM and 100% corrosion free, the profiles are multi chambered sections with wall thick of 2mm. The EPDM rubber (black colour) covered with over all the edges of frame and shutter the shutter will be provided with Espag multi power point locks and also it operates as handle. The corners and joints should be welded and cleaned. Radiations free pin headed plain or brown colour glass 4mm thick should be provided to the shutter and it should not allow leakage of water even at most ranging storms and should have key lockable action, security protective hinges, strong locking systems and as per size for arresting noise and energy loss. The connecting mechanism between sash and outer frame that enables opening of the window. The window should be fixed to the wall with 100% packing with screws and silicon packing all round the frames. The window should be got approved from the Executive Engineer before use on work.
Supplying and fixing UPVC (Un-Plasticized Polyvinyl Chloride) Louvered Ventilators of from the profile the size of outer frame 60mm x 58mm and shutter profile size of 60 x 78mm both profiles are reinforced with GI/1mm 125GSM and 100% corrosion free, the profile are multi chambered sections with wall thick of 2mm. The EPDM rubber (black colour) covered with all over the edges of frame and shutter. The corners and joints should be welded and cleaned. Radiations pin headed glass 4mm thick should be provided in the louvers. The window should be fixed to the wall with 100% packing with screws and silicon packing all round the frames. The ventilator should be got approved from the Executive Engineer before use on work
Supply and Fixing of M.S. steel doors with Single Leaf following specification. MS angles of size 40x40x 6mm at 3.5 kg/m used for the outer frame and MS angles of size 35x35x5mm at 2.60 kg/m for the shutter frames. Stiffners with 32x6mm at 1.50 Kg/m. MS flat is provided as the lock rail of the door and welded infact of both ends to the shutter frame, 18 gauge CR sheets of best quality is laid as panel in the shutter frames. 18x5mm at 0.70 kg/m MS flat is welded over the 32x6mm at 1.50 Kg / RM and MS flat on the rear side of the door sandwitching the CR sheet for rigidity with locking rail and bottom tie arrangements. Additional stiffners with 18x5 mm at 0.7 kg/m MS flats are provided horizontally diagonally on the rear side of the shutter. 2Nos of hinges in case of single leaf and 4Nos of hinges in case double leaf shutter is provided 6 Nos of hold fasts 200 length 40x40x6mm M.S. angle spliced at the ends are welded to the outer frame of the door. Tower bolt 2 Nos. one at top and the other at bottom are provided. One aldrop is provided incase of double leaves door at lock rail section in the door. For single leaf doors, one more aldrop is provided in the inner side at the lock rail section of the door.
One rotating locking arrangements at the inner side of the door and additional provision for locking arrangements for lock is provided with 32x6mm MS flat on the rear side of the door at an appropriate place incase of a double leaves door MS flat 32x6mm at 1.50 kg/m is provided on the edge of one shutter to conceal the gap between the shutters. A tie bar is provided at the bottom of the outer frame to prevent twisting of frame during transportation of fixing. All members are given a shop coat of red oxide primer as directed by the departmental officers. The rate includes cost of all materials labour charges transportation taxes and all other incidental charges etc., complete complying with standard specification and as directed by the departmental officers .
Supplying and fixing in position Glazed steel louvered ventilator with Side/Central hung shutters( Two Leaves) frames and made shutter frame made out of steel section conforming to IS 7452 /1990.The outer frame made out of z section (F7D) of size 33 x22 x3 mm conforming to IS 7452/1990.The mullions are made out of (F4B) section of size 46x25x3 mm and conforming to IS7452/1990. The shutter section one regidly fixed with outer frame section with fixing brackets of sufficient length are provided for each shutter 4 nos of 40 x 40 x 3 mm angle hold fast 230mm length are welded with the frame at appropriate point M.S Square bars of 12 mm dia is welded to the inner face of the ventilator at equal intervals not exceeding 10 cm spacing 3mm pin headed glass is used for Glazing with good quality anf fixed with 15 x 12 mm teak wood beadings with screws for fixing including one coat of red oxide primer for steel section etc., complete complying with standard specification. The ventilator should be got approved by the Executive Engineer before use on work.
Supplying and fixing of rolling shutters shall be pull and push type made of 18G/3" lathe sections which consist of five main parts such as curtain, lock plate, guide channels rollers and hood cover. These five main parts are made out of special components detailed below: curtain shall be of 18G/3" lath sections cut to required size and filled with heavy cast iron / MS clips. For 8'0"(2.45m) high rolling shutter lath sections provided shall be not less than 37 numbers. Lock plate shall be 10GMS sheet and attached to the side brackets with 20mm square bar.Side brackets shall be of 10G MS plate and cast iron "U" clamps shall be rivetted to the side brackets. Roller shall be of heavy cast iron pullies fitted with heavy duty "C" class 40mm steel pipe and high tensile high carbon coil springs. 2 springs shall be supplied. Side brackets shall be of 10G MS plate and cast iron "U" clamps shall be rivetted to the side brackets. Roller shall be of heavy cast iron pullies fitted with heavy duty "C" class 40mm steel pipe and high tensile high arbon coil springs - 2 springs shall be supplied. Hood cover shall be of 0.8mm CRCA sheet reinforced with 25mmx25mmx3mm MS angle or gate channel. The rolling shutter in addition to the above should have pulling hook and shall be coated on exposed area with heavy coat of red oxide primer etc., complete.(Manualty operated)
Supplying and fixing of rolling shutters shall be pull and push type made of 18G/3" lathe sections which consist of five main parts such as curtain, lock plate, guide channels rollers and hood cover. These five main parts are made out of special components detailed below: curtain shall be of 18G/3" lath sections cut to required size and filled with heavy cast iron / MS clips. For 8'0"(2.45m) high rolling shutter lath sections provided shall be not less than 37 numbers. Lock plate shall be 10GMS sheet and attached to the side brackets with 20mm square bar.Side brackets shall be of 10G MS plate and cast iron "U" clamps shall be rivetted to the side brackets. Roller shall be of heavy cast iron pullies fitted with heavy duty "C" class 40mm steel pipe and high tensile high carbon coil springs. 2 springs shall be supplied. Side brackets shall be of 10G MS plate and cast iron "U" clamps shall be rivetted to the side brackets. Roller shall be of heavy cast iron pullies fitted with heavy duty "C" class 40mm steel pipe and high tensile high arbon coil springs - 2 springs shall be supplied. Hood cover shall be of 0.8mm CRCA sheet reinforced with 25mmx25mmx3mm MS angle or gate channel. The rolling shutter in addition to the above should have pulling hook and shall be coated on exposed area with heavy coat of red oxide primer etc., complete.(Gear operated type)
Supplying and fixing MS grills to doors, windows and ventilators etc. using necessary MS flats (or) square rods for inner members and outer members which should be fixed to window frames as directed and design given by the departmental officers inclusive of cost of providing one coat of best quality red oxide primer etc., complete complying with standard specification and as directed by the departmental officers .
Painting the new iron work with two coats of best approved first quality and colour of synthetic enamel paint over the existing red oxide priming coat in all floors excluding cost of priming coat and including cost of painting materials, brushes, putty, preparation of surfaces and scaffolding charges etc., complete complying with standard specification and as directed by the departmental officer. (The quality and colour of paint should be got approved by the departmental officer before use on work).
Painting the new wood work two coats with best approved first quality and colour of synthetic enamel paint over a priming coat of approved quality in all floors including cost of paint, labour and other materials like brushes, putty and scaffolding charges etc., complete complying with standard specification and as directed by the departmental officers. (The make quality and colour of paint should be got approved by the departmental officer before use on work).
Paving the floor with best approved quality fine polished Granite Stone Slabs of size 1200 x 600 of 18 / 20mm thick of Synthetic Grey / Paradise and similar varieties with machine cut edges laid over a cement mortar bed of 20mm thick using cement mortar 1:3 (One cement and three sand) fixing the slabs with required cement slurry and laid in true right angles with minimum possible width of joints and pointing the joints with white cement mixed with mathcing colouring pigments etc., The granite stone slabs and other materials to be used shall be got approved by the Executive Engineer concerned before use on work, etc., complete as per standard speicification.
Paving the floor with best approved quality fine polished Granite Stone Slabs of size 1200 x 600 of 18 / 20mm thick of Flamed ruby red granite slab and similar varieties with machine cut edges laid over a cement mortar bed of 20mm thick using cement mortar 1:3 (One cement and three sand) fixing the slabs with required cement slurry and laid in true right angles with minimum possible width of joints and pointing the joints with white cement mixed with mathcing colouring pigments etc., The granite stone slabs and other materials to be used shall be got approved by the Executive Engineer concerned before use on work, etc., complete as per standard speicification.
Supplying and Fixing of Cuddappah slab fine polished of approved quality of 38 / 40mm thick including cost of cuddappah slab for cupboards, transportation to work site, labour charge for forming grooves in masonry if necessary and laying the slab in position with cement mortar 1:3 (One cement and three m-sand) etc., complete complying with standard specification and as directed by the departmental officers.
Supply and fixing of PVC Cupboard Shutter (PolyVinyl Chloride) multi chambe red "Texture / Scratch Proof grade profile for Cupboard outer covering. & Modular Kitchen Cabinet. Shelf (Rack) single panel made of 20 mm thick profile with wall thickness of 0.9MM (+ or - 0.2MM). The shutter will have SS coated piano butt hinges and SS Handle & Locking system all use in SS screws. The Panels being fixed with proper reinforcement of Silver Wood for the screw holding capacity and it will be inserted into C - Section etc., Complete complying as directed by departmental officers.
Providing cupboard shutter using termite/ water proof plywood of 19mm thick over which laminated sheet of 0.8mm thick fixed inside the shutter and 1mm thick fixed in the outside of the shutter using fevicol along with necessary furniture fittings, such as, hydralic hinges, tower bolt, handles, multi purpose locks etc. as directed by the departmental officers. The design pattern, water proof plywood, laminate sheet and other materials should be got approved from the Executive Engineer before use on work.
Supplying and Fixing of white Porcelin sink of size 600mm x 450 mm x 200 mm including cost of 32mm dia 'B' class GI waste water pipe with rubber, plug and chain and 32mm dia CP waste coupling, 15mm dia brass nipple including fixing the sink in position and testing for leakage etc., complete complying with standard specification and as directed by the departmental officers. (The sink and specials should be got approved by the Executive Engineer before use on works). (For fixing the sink on masonry support walls to be measured and paid in main item.)
Supplying and fixing in position 150x100mm square mouth 'P' or 'S' stoneware gully Trap 'A' grade with cast iron gratings of size 150x150mm with CI air tight cover with frames of size 300x300mm at bottom and top respectively with necessary earth work excavtion and laid over a bed of brick jelly concrete 1:3:6, 150mm thick using 40mm sixe brick jelly including necessary brick work and plastering, dismantling masonry wherever necessary and redoing the damaged portion to the original condition.Fixing the gully trap and giving connection to the sewer lines etc,. complete complying with standard specification and as directed by the departmental officers. (The Stone ware gully trap with grating should be got approved by the Executive Engineer before use on works).
Supplying and fixing in position best approved of ISI quality PVC rain water down fall pipes of 160 mm dia having a working pressure of 4 kg / sq.cm including cost of necessary PVC shoe, PVC bend, C.I. gratings of required dia. and special clamps, brass screws, nails etc., and fixing of cast iron gratings at juction of parapet and the RCC roof slab including finishing neatly etc., complete. The rate shall be inclusive of cost of removable iron grating. The PVC pipe shall be fixed on wall with special type of clamps. Special type "U" clamp at the centre of the pipe line shall be fixed in addition to those for more than 3.0M pipe length complying with standard specification.
Supplying, laying and jointing UPVC pipes (having working pressure 10 kg. / sq.cm) of approved quality and best variety conforming to BIS of the following dia including cutting, threading and fixing UPVC specials using UPVC adhesives (but excluding cost of such specials) and fixing into wall with teak wood plugs, UPVC clamps and screws making holes on the wall (or) drilling holes in the roof and making good the dismantled portion to original condition with necessary brick work / cement concrete and plastering neatly wherever necessary with necessary scaffolding charges upto 4 metre height above ground level, etc., complete complying with standard specifications. The UPVC pipes shall be got approved by Executive Engineer before use on works. For Internal Water supply arrangements. (Above Ground Level)
25 mm dia UPVC pipe
20 mm dia PVC pipe
Supplying, laying and jointing UPVC pipes (having working pressure 10 kg. / sq.cm) of approved quality and best variety conforming to BIS of the following dia including cutting, threading and fixing UPVC specials using UPVC adhesives (but excluding cost of such specials) and fixing into wall with teak wood plugs,UPVC clamps and screws making holes on the wall (or) drilling holes in the roof and making good the dismantled portion to original condition with necessary brick work / cement concrete and plastering neatly wherever necessary with necessary scaffolding charges upto 4 metre height above ground level, etc., complete complying with standard specifications. The UPVC pipes shall be got approved by Executive Engineer before use on works. For External Water supply arrangements. (Above Ground Level)
32 mm dia UPVC pipe
40 mm dia UPVC pipe
50 mm dia UPVC pipe
Supplying and fixing in position of the following UPVC specials best approved quality conforming to ISS and providing leak proof joints with UPVC adhesive etc., including fixing to walls with necessary teak wood plugs screws etc., and giving connections to the UPVC pipe dismantling the brick masonry RCC floor or roof slab and redoing the disturbed portion to original conditions etc., complete complying with standard specifications. (The UPVC specials should be got approved from the Executive Engineer before use on works ).
20mm dia UPVC Union
25mm dia UPVC Union
32mm dia UPVC Union
40mm dia UPVC Union
50mm dia UPVC Union
20mm dia UPVC Elbow
25mm dia UPVC Elbow
32mm dia UPVC Elbow
40mm dia UPVC Elbow
50mm dia UPVC Elbow
20mm dia UPVC Tee
25mm dia UPVC Tee
32mm dia UPVC Tee
32 x 25mm dia UPVC Reducer Tee
25 x 20mm dia UPVC Reducer Tee
20 x 15mm dia UPVC Reducer
Supplying, laying and jointing PVC soil / waste pipes of approved and best variety conforming to IS. Specification with ISI. mark of the following sizes including, cutting and threading of PVC Pipes, fixing specials but excluding cost of such specials but including fixing to wall with necessary teak wood plugs, PVC clamps and screws making holes on the wall (or) drilling holes in roof and making good the dismantled portion to original condition with necessary brick work and plastering wherever necessary with necessary scaffolding charges. The PVC Pipes should be got approved by the Departmental Officers before use on work.
75mm dia PVC soil pipe
110mm dia PVC soil pipe
160mm dia PVC soil pipe
Supplying and fixing in position PVC specials of the following dia and types of approved quality confirming to BIS and providing leak proof joints including fixing to the walls and giving connection to the PVC soil stacks, dismantling the masonry or RCC works and re-doing the dismantled portion to original condition etc., complete complying with standard specifications. (The PVC specials should be got approved by the Executive Engineer before use on works).
75mm dia PVC Tee with Single Door
75mm dia PVC bend
110mm dia PVC bend
110mm dia PVC Tee
75mm dia PVC Cowl
110mm dia PVC Cowl
160mm dia PVC Elbow
Supply, laying and testing of DWC Structured Wall Polyethylene Piping Systems (Pipe with online/offline coupler and elastomeric sealing ring) with required specials non-smooth external annular corrugated and smooth internal surface (Double wall) (SN 8 Class) for non-pressure underground sewerage, drainage application generally as per IS16098 (Part-2) type B. Including pipe joint, etc., complete complying with standard specification and as directed by the departmental officers .
Supplying and fixing in position 15mm dia Chromium Plated brass screw down tap (heavy type) of approved make conforming to ISS.and including cost of shellac, thread complete complying with standard specification and including cutting and threading wherever necessary.(Taps should be got approved by the Departmental Officers before use on the work)
Supplying and fixing in position Indian make bevelled edge mirror of approved quality and brand of size 600x450mm x5.5mm thick with necessary plastic back, PVC frame with bottom stand of approved colour with brass screws, rawal plugs etc. complete complying with standard specification and as directed by the departmental officers. (The materials should be got approved by the departmental officers before use on works)
Supplying and fixing in position Indian water closet oriya type of size 580x440mm white glazed earthernware of approved quality with 'P" trap or 'S' trap conforming to IS 2556-Part XII with sand cushion and forming flooring alround the closet using 40mm broken brick jelly in lime concrete 1:2:5 (One part of lime, two parts of sand and five parts of brick jelly) 100mm thick and finishing the top to required slope and including giving necessary connection to PVC. pipes by dismantling brick masonry, reinforced cement concrete roof/floor slab and making good the disturbed portion to original condition without leakage etc., complete complying with standard specification and as directed by the departmental officers.(The Oriya type Water Closet and all accessories should be got approved by the departmental officers before use on work)
Supplying and fixing in position White Glazed European water closet of best quality and approved make with 100mm P or S trap with double flapped rigid PVC.seat cover with chromium plate brass hinges, including supplying and fixing PVC. Low level flushing tank 10 litre capacity of approved quality on wall with teak wood plugs, brass screws and 2 numbers 15mm dia gun metal wheel valve, 15mm dia nylon connection and giving necessary water supply connection as directed by the departmental officers. The rate includes cost of 100mm dia PVC.Pipe 60cm long including cost of 3 Kg.of white cement 6Kg.of cement, spunyarn, shellac, thread ball, teak wood plugs, brass screws 75mmx10mm etc., complete complying with standard specification and as directed by the departmental officers. (The European Water Closet and flushing tank should be got approved by the Departmental Officers before use on work.)
Supplying and fixing in position of Indian make white glazed earthen ware lipped mouth flat back Urinal of best approved quality with 32mm dia bell mouthed PVC connection,15mm dia G.M wheel valve,fixing the Urinal to the wall in position with necessary T.W. plugs,clamps,screws shellac etc.,including dismantling masonry if necessary and redoing the same to original condition,fixing the 15mm GI pipe connection and wheel valve, painting the pipe with two coats and checked without any leakage etc., complete complying with standard specification and as directed by the departmental officers.(The urinal should be got approved by the departmental officers before use on work)
Supplying and fixing in position best quality of approved make white glazed earthernware wash hand basin (without pedestal) of size 550x400mm with a pair of cast iron brackets , including cost of 15mm diametre brass chromium plated pillar tap, 32mm diametre C.P.waste, 32mm diametre PVC waste pipe with rubber plug and chain, 15mm diametre gun metal wheel valve, 15mm dia brass nipple, 15mm dia nylon connection etc. including fixing the wash hand basin in the wall in position with pair of C.I.brackets with teak wood plugs and screws and giving necessary water supply connection and painting the brackets with two coats of paint over a priming coat of anti-corrosive paint including testing for leakage etc., complete complying with standard specification and as directed by the departmental officers.(The wash hand basin and specials should be got approved by the departmental officers before use on work)
Supplying and fixing Stainless steel health faucet of best quality with control valve etc., complete complying with standard specification and as directed by the departmental officers (The materials should be got approved by the Executive Engineer before use on works).
Supplying and fixing in position PVC Nahini trap of size 110x75mm with best pvc gratings of approved brand and quality with fixed over a bed of brick jelly lime concrete 1:2:5(one part of lime,two parts of sand and five parts of 40mm size brick jelly)and finished with cement Mortar 1:3(one cement and three sand)including dismantling masonry works wherever found necessary and making good the damaged portions to the original condition giving connections to the pipe etc., complete complying with standard specification and as directed by the departmental officers. (The PVC Nahini trap with grating should be got approved by the departmental officer before use on works).
Supplying and Fixing of PVC ready made water tank of approved quality capacity with standard specification and best brand including testing for leakages after making installations and connections. The cost inclusive of lid and lock with bolt and nuts for PVC tank, transportation, loading, unloading, lifting, installation and necessary connections etc., complete complying with standard specifications and as directed by the departmental officers.(The PVC Water Tank should be got approved by the Executive Engineer before use on works).
Supplying and laying of 63 mm thick high strength type of interlocking rubber moulded hydraulic pressed paver block of approved colour made up of designed concrete mix 1:1:2 using 10 to 12mm size HBG stone jelly in required shapes and sizes having minimum compressive strength of 40 N/mm2 to be laid in flurrying bone pattern with approved non sticking surface at top. The rate is inclusive of levelling the site, compacting with power compactor and sweeping the sand grouting and also inclusive of transportation charges, loading, unloading and labour charges for laying the paver block, etc. complete complying with standard specification and as directed by the departmental officers.
Supply and fixing in position of English Stainless steel letter of size 25 cm approved quality including cost of material, labour, dismantling masonry wherever necessary and redoing the damaged portion to the original condition etc., Complete complying with standard specification and as directed by the departmental officers.
Supply and fixing in position of Tamil Stainless steel letter of size 25cm approved quality including cost of material, labour, dismantling masonry wherever necessary and redoing the damaged portion to the original condition etc., Complete complying with standard specification and as directed by the departmental officers.
Supply and fixing of PVC mould CI steps for sump of approved quality including cost of material, labour, dismantling masonry wherever necessary and redoing the damaged portion to the original condition etc,complete as directed by the Departmental Officers.
Supplying, erection, testing and commissioning of Diesel Engine Pump Main Control Panel & Jockey Pump including necessary auto cut-in, cut-off and manual operations, battery charger switch arrangements, voltmeter, ammeter and running indication siren provision, wall mounting type, etc., as per the standard method and as directed by the Departmental Officers.
Supplying and erecting 3 phase multi stage 5.00 H.P Monoblock Pumpset with ISI IS 8034 with 3 phase Panel Board - Star Delta with two level guard and Auto start including of approved make conforming to ISI.including cost of all accessories, transportation charges, labourcharges for erecting and fixing the motor in position testing as directed by the Departmental Officers complete complying with standard specification. The quality and standard of product should be got approved by the Departmental Officers before erecting. Necessary warranty card should be produced before erection of Motor.
Supplying and erecting 3 phase multi stage 5.00 H.P Submersible Pumpset suitable for 150mm dia Borewell with ISI IS 8034 with 3 phase Panel Board - Star Delta with two level guard and Auto start including of approved make conforming to ISI.including cost of all accessories, transportation charges, labourcharges for erecting and fixing the motor in position testing as directed by the Departmental Officers complete complying with standard specification. The quality and standard of product should be got approved by the Departmental Officers before erecting. Necessary warranty card should be produced before erection of Motor.
Supply, erection, testing and commissioning of fire fighting application monoblock motor pumpset of 900 LPM at 40 metres head to develop 3.5 kg/sq.cm at the heightest and farthest hydrant point to make 30 m water jet at the time of fire fighting emergency cicumstances, coupled with 11 KW / 15 HP rated three phase 414 volts, 50 Hz, 2880 rpm electrical motor the pump with cast ron body, bronze impeller, rope gland packaging, suction size of 80 mm dia. delivery size of 65 mm dia., including the cost of foundaton concrete anti vibration mounting, rain safety hood and etc. complete as directed by the Departmental Officers (Kirloskar make KDS 1555+ or Equivalent)
Supply and laying of 4 core 10 sq.mm. armoured copper cable for power wiring to the Terrace Pump Motor with runs of 14 SWG TC wire for earthing, providing in wall with suitable size GI clamps, screws, wooden plug, end termination by using suitable size cable glands, copper sockets and etc., as directed by the Departmental Officers.
Supply and laying of 2 core 1.5 sq.mm. armoured copper cable for control wiring to the Terrace Pump Motor with runs of 14 SWG TC wire for earthing, providing in wall with suitable size GI clamps, screws, wooden plug, end termination by using suitable size cable glands, copper sockets and etc., as directed by the Departmental Officers.
Supplying and laying of 8 gauge bare copper wires for panel earthing, pump earths and other equipment body earthing as required etc., as directed by departmental officers.
Supply, erection, testing and commissioning of suitable Pressure Switch of reputed make line Indfoss or Donfoss including necessary valves, couplings, etc., connected with electrical main control panel and setup at proper differential so as to auto start and auto stop the electrical motor, jockey motor including conveyance, all incidental charges, neccessary scaffolding and re-doing the dismantled portions to its original condition wherever found neccessary, etc., completed as per standard specification and as directed by the Departmental Officers. Make: DONFOSS / INDFOSS / ISI MAKE / EQUIVALENT.
Supply, erection, testing and commissioning of Pressure Gauge with 0 to 14 kg. range of reputed make with necessary valve, milling thread MS coupling fixed at delivery pipe line in pump house to read the developing pressure including conveyance, all incidental charges,neccessary scaffolding and re-doing the dismantled portions to its original condition wherever found neccessary, etc., complete as per standard specification and as directed by the Departmental Officers. Make: HGURU / ISI MAKE / EQUIVALENT.
Supply, erection, testing and commissioning of Air Release Valve of 20mm dia, so as to release airlock in 100mm dia MS pipe at top most wet riser, including conveyance, all incidental charges, neccessary scaffolding and re-doing the dismantled portions to its original condition wherever found neccessary, etc., complete as per standard specification and as directed by the Departmental Officers. Make: KARTAR / EQUIVALENT.
Supply, erection, testing and commissioning of following MS ‘C’ Class Heavy Duty Pipe as per IS 1239 to withstand a developing pressure of 10 kg. / sq.cm including necessary fittings like MS flange of table ‘E’, elbows, reducers, gaskets, bolt, nuts with washers & joints as per standard method of arc welding, including one coat metal primer and two coat Post Office Red painting including conveyance, all incidental charges, neccessary scaffolding and re-doing the dismantled portions to its original condition wherever found neccessary, etc., complete as per standard specification and as directed by the Departmental Officers. Make: JINDAL / EQUIVALENT.
150mm dia
80mm dia
25mm dia
Supply, erection, testing and commissioning of cast iron body and bronze internal non-rising spindle sluice valve of sizes at required places to control the flow of water including necessary MS flange of table ‘E’, gaskets, bolts & nuts including conveyance, all incidental charges, neccessary scaffolding and re-doing the dismantled portions to its original condition wherever found neccessary, etc., complete as per standard specification and as directed by the Departmental
150mm dia
Supply, erection, testing and commissioning of Cast iron body and Gun metal or stainless steel internal Non-return valve of following sizes to control one way flow of water to be installed pump room at delivery line and near overhead tank at terrace level near to jockey pump and motor including necessary MS flange of table ‘E’, gaskets, bolts & nuts, etc. as per IS 5312 including conveyance, all incidental charges, neccessary scaffolding and re-doing the dismantled portions to its original condition wherever found neccessary, etc., complete as per standard specification and as directed by the Departmental Officers.
150mm dia
Supplying and installation of 150 mm dia C.I Body Y stainer with necessary flanges, nuts, bolts & washers painting etc., complete complying as directed by departmental officers.
Supplying and installation of 25mm Gate valves with fittings of screwed end type with necessary accessories etc., complete complying as directed by departmental officers.
Supply and fixing of Fire fighting application oblique type stainless steel Hydrant Valve of size 63mm dia with oblique type instantaneous coupling with rotating wheel to open and close the valve including MS flange of table “E”, bolts & nuts with washer as per IS 5290 at ring main around the building and wet riser inside the building including conveyance, all incidental charges, neccessary scaffolding and re-doing the dismantled portions to its original condition wherever found neccessary etc complete as per standard specification and as directed by the Departmental Officers. Make: OMEX / KARTAR / LIFE GUARD / SAFE GUARD / EQUIVALENT.
Supply, and fixing in position of Fire Fighting Application Hose of 63mm dia of 15 metres length binded by copper wire with 63mm dia stainless steel male and female instantaneous fire fighting special coupling as per IS 901 as directed by the Departmental Officers. Near every hydrant points including conveyance, all incidental charges, neccessary scaffolding and re-doing the dismantled portions to its original condition wherever found neccessary etc complete as per standard specification and as directed by the Departmental Officers. Make: OMEX / KARTAR/ LIFE GUARD / SAFE GUARD / EQUIVALENT.
Supply, installation of Fire Fighting Application 180 degree swinging type, hose reel drum with 20mm dia braided thermoplastic hose of 30 metres long, so as to extend to necessary distance by self rolling spindle wheel including necessary 20mm dia ball valve and open and close spray nozzle, warm clip, etc., as per the standard pattern of any reputed make at every floor nearer to hydrant valve, including conveyance, all incidental charges, neccessary scaffolding and re-doing the dismantled portions to its original condition wherever found neccessary., etc., complete as per standard specification and as directed by the Departmental Officers. Make: OMEX / KARTAR / LIFE GUARD / SAFE GUARD / EQUIVALENT.
Supply, and fixing in position of Fire Fighting Application 63mm dia stainless steel short length Branch Pipe with hexagonal type spray nozzle of 15mm (or) 20mm jet bore. Near every hydrant points including conveyance, all incidental charges, neccessary scaffolding and re-doing the dismantled portions to its original condition wherever found neccessary, etc., complete as per standard specification and as directed by the Departmental Officers. Make: OMEX / KARTAR / LIFE GUARD / SAFE GUARD / EQUIVALENT.
Supply of Fire Fighting Application MS Hose Box to keep two number of hoses and 1 No. of branch pipe with nozzle having proper glass window type double door with universe open key, painted inside white and outside Post Office Red. Near every hydrant point including conveyance, all incidental charges, neccessary scaffolding and re-doing the dismantled portions to its original condition wherever found neccessary, etc., complete as per standard specification and as directed by the Departmental Officers. Make: OMEX / KARTAR
Supply, erection, testing and commissioning of Fire Fighting 2 Way Fire Brigade Inlet with necessary gun metal 63mm dia non-return spring shutter arrangements so that to control one way flow at the time of emergency water supply by fire and rescue service fire engine entry including conveyance, all incidental charges, neccessary scaffolding and re-doing the dismantled portions to its original condition wherever found neccessary., etc., complete as per standard specification and as directed by the Departmental Officers. (Make: KIARTAR / OMEX / EQUIVALENT)
Supply and fixing of MS Structural supports for pipes in on walls/ columns with 1 coat of red oxide primer and two coat of black paint etc., complete as per standard specification and as directed by the Departmental Officers.
Supply and fixing of stored pressure ABC (Mono Ammonium Phospate) Powder Type Fire Extinguisher of 6 kg. capacity as per IS:15683 with pressure gauge, discharge hose & control nozzle, wall mounting bracket, safety clip etc., including conveyance, all incidental charges, neccessary scaffolding and re-doing the dismantled portions to its original condition wherever found neccessary etc, complete as per standard specification and as directed by the Departmental Officers. Make: EXCELLENT / SAFETY FIRST / EQUIVALENT
Providing and fixing 4.5 kg. capacity Co2 type Fire Extinguisher confirming to ISI:15683 with required accessories including labour cost etc., Complete complying with standard specification and as directed by the departmental officers.
Supply and kept in position of 9 litres capacity Fire Buckets of 4 Nos. with Bucket Stand painted white inside & red out side and letter "FIRE" in black out side etc., Complete complying with standard specification and as directed by the departmental officers.
Supply, installation, testing and commissioning of Manual Call Point (MCP) providing on wall using fixing accessories like screws, plug, clamps and etc., as per standard methods etc., Complete complying with standard specification and as directed by the departmental officers. (Make: Ravel / Equivalent)
Supply, installation, testing and commissioning of Electronic Hooter / Sounder providing on wall using fixing accessories like screws, plug, clamps and etc., as per standard methods etc., Complete complying with standard specification and as directed by the departmental officers. (Make: Ravel / Equivalent)
Supply, installation, testing and commissioning of Micro Processor based conventional 8 Zone Fire Alarm Control Panel having the rating of 24 volt DC power supply, consisting 230 / 24 volt SMPS unit, 2 Nos. of 12 volt 7 AH standby batteries, suitably mounted on wall using fixing accessories like screws, plug, clamps and etc., as per standard methods and as directed by the Departmental Officers.
Supply and laying of FRLS PVC insulated 2 core 1.5 sq.mm. Armoured Copper Cable on ceiling / wall using fixing accessories like screws, plug, clamps, etc., as per standard methods and as directed by the Departmental Officers.
Supply, Installation, Testing and Commissioning of 25 mm PVC Conduits pipe on wall/ ceiling/ floor etc., complete with accessories like junction boxes, collars, bends etc., as directed by the Departmental Officers.
Providing and fixing in position the signage of " Fire Extinguisher " to be pasted immediately above the every extinguisher of Size 6" x 8" etc., complete complying as directed by departmental officers.
Providing and fixing in position the signage of " Fire Hydrant & Hose Reel " to be pasted on door of the every fire shaft at all floors. Size 6" x 8" etc., complete complying as directed by departmental officers.
Providing and fixing in position the sign board of " ASSEMBLY POINT " complete with 1 mm thick rigid plastic board size of 400 mm x 300 mm to be fixed on ground by using a steel rod / pipe at designated places etc. complete complying as directed by departmental officers.
Providing and fixing in position the sign boad of " EXIT " with arrow to be placed at walking pathways by hanging on ceiling to direct occupants to outside the building in an emergency. The exit sign board will be auto glow photoluminiscent type which will glow at dark etc. complete complying as directed by departmental officers.
Providing and Fixing A3 Size Fire Evacuation Map with required acrylic sheet and Studs etc. complete complying as directed by departmental officers.
HT Equipments (HT Substation) : Supply, Erection, Testing and Commissioning of 500KVA 11KV/433V off load tap changing copper wound Outdoor type distribution transformer confirming to relevant IS 1180-level-2 mounted on suitable RCC plinth of height 5 ft and rcc foundation to a depth of 2 ft with reinforcement capable of bearing the load of the transformer and fitted with the following. 1.Conservator with shutoff valves 2.Conservator drain plug 3.Silicagel dehydrating breather 4.Bottom channel, 5. Thermometer pocket 6.Oil drain valve at bottom 7.Oil level gauge-plain 8.Air release plug 9. Detachable Radiators with shut-off valves 10. Marshalling box for both OTI with capillary. 11.Lifting lugs-4Nos 12.Earthing Terminal-2Nos 13.Rating and terminal marking diagram plate 14.Rollers plain/flanged/unit /bidirectional4Nos 15.Explosion vent with diaphragm 16.Top filter valve
17.Off circuit tap switch with locking deviceSpecial accessories 1.Oil Temperature indicator:-Vapors pressure type-Rigid stems type or with capillary tubing/MRP/RSD A/Contacts 2. winding Temperature indicator:- Dial Type Thermometer with MRP/RSD A/T contacts 3.Neutral CT 18. Bucholz relay with shutoff valve The transformer should be supplied with first filling of oil. Terminal arrangement:- HV-and LV-Cable box. (Energy Efficient Transformer as per IS 1180 Level 2 Star Rating . All the removable cover shall be provided with hot oil resistant gasket - Make: Kirloskar / Rowsons/ Voltech/ Equivalent etc. complete complying as directed by departmental officers.
Supply, erection, testing and commissioning of 11KV, 25KA, 630A 3 panel HT INDOOR RING MAIN GEAR switch board suitable for indoor installation comprising Two incomer panels with Air Break/ Load Breaks switches and one outgoing panel with Vacuum Circuit Breaker complete as per specification. 1) Supply and Erection of Draw out type 11KV,25KA, 630A, Horizontal Draw out/ Horizontal Isolation Vaccum Circuit Breaker fitted with Motor (230V AC) operated Spring charging mechanism, with ON & OFF Mechanical indicator Anti Pumping Device, 110V DC, shunt Trip and closing Coils (DC source of supply to be derived from a Power Pack suitable for 3 Tripping and Two closing operations incorporated on incoming panel only) Mechanical operation counter,4 NO + 4NC spare Aux. contact with contact multiplication contactor for customer use, Automatic safety shutter,Mechanical Close / Trip knob,Mechanical ON/OFF indication, Operating Handle, 230V AC to 110V DC Power Pack operating handles etc -1 No. 2.Supply and Erection of 11KV 630Amps 25kA HT Air Break/Load Break Switch with mechanically interlocked Earth switch, Front operated spring assisted manual closing mechanisam, 2NO + 2NC Aux. contact operating handle etc- 2nos. 3) 11KV /Root 3/110V/Root 3 - Three Phase,3 Limb 50V A Class 0.5 Resin Cast Draw Out type Potential transformer complete with HTand LT HRC fuses with sealing arrangement - 3nos 4) Current Transformers of suitable ratio 5.5A Dual Core (Core 1 - 5 VA class 0.2 for metering and core 2 - 15 P 20 for Protection-3 nos) with surge diverters
6. Breaker ON/OFF/Auto Trip/Healthy/Spring Charged Indication Lamp LED Type 7. Phase Indication Lamps R,Y,B(Incomings 3Nos) 8. Control Wiring 9. 800Amps Copper Bus bar PVC Sleeved and required panel copper earthing. 10. Contro l s w it c h T N C ( I n c o m i n g - 1 N o , O u t g o i n g - 2 N o ) 11.Trip Circuit healthy PushButton(Incoming-1No, Outgoing -1No) 12. Common for Switch gear, MCB's for AC DC Control, Heater ON/OFF Switch with space Heater and thermostat Single phase switch socket, cubicle illumination lamp, Disconnecting type terminal Block.etc., 13. MS Sheet enclosure for Indoor Installations Powder coated with Paint shade siemens Grey, paint finish Provision through Bottom entry to receive Incoming and Outgoing cable excluding cable glands and cable termination etc.,(Make:- Megawin / Systemcontrol / ABB/or Equivalent) etc. complete complying as directed by departmental officers.
Supply, Erection, Testing and commissioning of 400A capacity Dust and Vermin Proof Cubical Panel Board made up of 16 SWG CRCA sheet steel with supply and fixing of the following interior mounting fuse switches with HRC fuses arranged in two Horizontal or vertical rows with one switch over the other with a central bus bar chamber and two nos of Horizontal or vertical cable chambers at the two ends one on each side next to the fuse switch chamber and confirming to IE rules. 1. 400A FP SDF unit interior only with HRC fuses Double break Switch - = 2 nos 2. 200A TPN SDF unit interior only with HRC fuses Double break Switch = 4 nos 3. 125A TPN SDF unit interior only with HRC fuses Double break Switch - = 2 nos 4. 63A TPN SDF unit interior only with HRC fuses Double break Switch - = 3 nos (All the TPN switches should be Siemens/L&T / eqt with front handle make only) The incoming switches are interlocked with Two lock one key system.
The bus bar chamber will consist of suitable size of copper flat (not below 50x6mm) for phase and neutral buses on epoxy moulded bus insulators at proper and sufficient spacing between the buses as per IE rules. This bus bar chamber should be segregated from the adjacent chambers by providing hylem sheet of suitable thickness as partitions suitable size of copper flats should be provided all round the panel for earth bus. The fuse switches should be connected with the phase and neutral buses with suitable size of rigid copper rod or flat and each switch should be connected with 2 nos. 25x3 mm earth bus with 2 runs of No:8 SWG rigid copper rod with suitable lugs. Phase and neutral copper buses should be tinned properly. The panel should have a separate metering chamber at the top side consisting of Digital Multifunction meter Model LT MFM 4405 LED meter Cl 0.5/ like and CT arrangements LED indicator lamps should be provided with control switches and fuse units. The panel should be painted with one coat of Red oxide as primer coat and two coats of enamel paint of approved colour, Approved by the site engineer and also the danger board. The capacity of fuse switches, size of the incoming and outgoing cables, the place to which the supply is fed shall be marked on switch chamber. The panel board should be mounted on suitable MS channel provided all round at bottom of the panel. The whole arrangement should be erected on a masonry pedestal to be constructed with suitable foundation bolts and nuts such that the lowest switch handle is at the height of 0.75m from the ground level etc., complete complying as directed by departmental officers.
Design, Supply, erection, testing and commissioning of 1000A draw out type floor mounted MV cubical bus bar chamber dust and vermin proof and accommodating the following SDF’s and 2 Nos. ACB as Incomer units with the following items of work complete to satisfy the latest IE rules and CEIG guidelines. Supply and fixing of suitable bus bar chamber made up of 16SWG CRCA sheet steel with 4 Nos. of suitable tinned copper bus bar not below 75 x 9mm for 3 phases and neutral and 2Nos. of earthing bus of size 1” X 1/8" tinned copper bus on suitable bus bar insulator(SMC insulator) with maximum creepage distance and supported on MS Base channel frame work of size 4”X 2”X ¼”–1Set Incoming 1)Supply and fixing of 2 Nos. 800A basic rating 4 pole 433V LT ACB confirming to IS 13947–2 IEC 60947–2 with breaking capacity of 50 KA at 690V AC with all accessories for standard horizontal EDO type ACB equipped with auxiliary contacts and all accessories for closing and opening operation with Micro processor SR 18 G relay, over current trip device adjustable to LTD, STD and release for over current protection UV release with time delay, EF release short circuit protection, Mains CTs for 3 phases lockout, features,separate mould base for each pole for easy maintenance all relevant protection safety accessories as per CEIG, IE rules inforce with inter connection and terminations as required in specification. BUS COUPLER:- Supply and fixing of 1 No 800A basic rating 4 pole 433 V LT ACB to IS-13947-21EC60947-2 600VAC with all accessories for standard horizontal type (draw out type) ACB equipped with Microprocessor based SR18G. Outgoing
1)Supply and fixing of 400A TPN SDF unit interior only with HRC fuses Double break Switch = 4 nos 2)Supply and fixing of 250A TPN SDF unit interior only with HRC fuses Double break Switch = 3 nos 3)Supply and fixing of 125A TPN SDF unit interior only with HRC fuses Double break Switch = 3 nos Inter connecting the all LT ACB’s and Switches to bus bar with suitable insulated tinned copper flats and painting/PVC sleeve colour coding of phases and neutral indication. Interlocking of all LT ACB's shall be provided with 3lock and 2key arrangement. Double Earth connection of the SDF’s and ACB’s to earth bus using suitable tinned copper flats by 2 runs of 1” X 1/8” Supply and fixing of LED lamp arrangements with toggle switches to the control to each phases and with rigid connection in suitable separate compartments with in the cubicle by CEIG rules with , 2 sets of supply and fixing Digital multifuntion meter with necessary CT coil arrangements. Supply and fixing of danger board with siemens grey powder coating with super scribing the names of places to which supply is fed feeder sizes of cables direction of cables etc. Erection of panel board complete with suitable foundation bolts and nuts including suitable M.S Channel, concreting, testing and commissioning. (L&T,C&S,SIEMENS,ABB /eqt) etc., complete complying as directed by departmental officers.
Supply, Erection, Testing and commissioning of 250A capacity Dust and Vermin Proof Cubical Panel Board made up of 16 SWG CRCA sheet steel with supply and fixing of the following interior mounting fuse switches with HRC fuses arranged in two Horizontal or vertical rows with one switch over the other with a central bus bar chamber and two nos of Horizontal or vertical cable chambers at the two ends one on each side next to the fuse switch chamber and confirming to IE rules. 1. 250A FP SDF unit interior only with HRC fuses Double break Switch = 1 nos 2. 200A TPN SDF unit interior only with HRC fuses Double break Switch = 1 nos 3. 125A TPN SDF unit interior only with HRC fuses Double break Switch = 3 nos 4. 100A TPN SDF unit interior only with HRC fuses Double break Switch = 3 nos (All the TPN switches should be Siemens/L&T/eqt with front handle make only) The bus bar chamber will consist of suitable size of copper flat (not below 25x6mm) for phase and neutral buses on epoxy moulded bus insulators at proper and sufficient spacing between the buses as per IE rules. This bus bar chamber should be segregated from the adjacent chambers by providing hylem sheet of suitable thickness as partitions suitable size of copper flats should be provided all round the panel for earth bus.
The fuse switches should be connected with the phase and neutral buses with suitable size of rigid copper rod or flat and each switch should be connected with 2 nos. 25x3 mm earth bus with 2 runs of No:8 SWG rigid copper rod with suitable lugs. Phase and neutral copper buses should be tinned properly. The panel should have a separate metering chamber at the top side consisting of Digital Multifunction meter Model LT MFM 4405 LED meter Cl 0.5/ like and CT arrangements LED indicator lamps should be provided with control switches and fuse units. The panel should be painted with one coat of Red oxide as primer coat and two coats of enamel paint of approved colour, Approved by the site engineer and also the danger board. The capacity of fuse switches, size of the incoming and outgoing cables, the place to which the supply is fed shall be marked on switch chamber. The panel board should be mounted on suitable MS channel provided all round at bottom of the panel. The whole arrangement should be erected on a masonry pedestal to be constructed with suitable foundation bolts and nuts such that the lowest switch handle is at the height of 0.75m from the ground level etc., complete complying as directed by departmental officers.
Design, supply, erection of 100 KVAR, 8 stage switching, sequence automatic power factor correction floor mounting stand vermin proof cubical panel board made of 16 SWG CRCA sheet steel with supply and fixing of the following interior mounting capacitor chamber relay with metering chamber and compartmentalised out going feeders with suitable capacity MCCB with panel board with provision for louvers and cooling fan for proper ventilation to manage heat load incoming - DPX 250A FP MCCB with rotary handle. Outgoing : 8 stage capacitor bank Contactors : Bharatia Cuttler Hammer/L&T Heavy Duty contactors. Relays : World class solid state relays with TM2 technology as an option. Heavy Duty Cylindrical Capacitor MPP capacitor 8 stage from 1 KVAR to 50 KVAR 1. stage -1 KVAR 2. stage -4 KVAR 3. stage -10 KVAR 4. stage -10 KVAR 5. stage -10 KVAR 6. stage -15KVAR 7. stage -25 KVAR 8. stage -25 KVAR Bus bar: 2 run of 25mm x 3mm tinned copper Metering : 1-250A Ammeter with CT coil 2) 0-500V voltmeter 3) Advance micro controller based intelegent power factor controller with self dianostic sensing and digital net work analyser with software for mentioning and saving para meter of a suitable multi function meter. Indication: R,Y,B The panel should be coated with Epoxy based painting and the whole assembly fixed in suitable cubical panel grouted in floor with connection etc., complete complying as directed by departmental officers.
Design, supply, erection of 50 KVAR, 6 stage switching, sequence automatic power factor correction floor mounting stand vermin proof cubical panel board made of 16 SWG CRCA sheet steel with supply and fixing of the following interior mounting capacitor chamber relay with metering chamber and compartmentalised out going feeders with suitable capacity MCCB with panel board with provision for louvers and cooling fan for proper ventilation to manage heat load incoming - DPX 125A FP MCCB with rotary handle. Outgoing : 6 stage capacitor bank Contactors : Bharatia Cuttler Hammer/L&T Heavy Duty contactors. Relays : World class solid state relays with TM2 technology as an option. Heavy Duty Cylindrical Capacitor MPP capacitor 8 stage from 1 KVAR to 50 KVAR 1. stage -2 KVAR 2. stage -3 KVAR 3. stage -5 KVAR 4. stage -10 KVAR 5. stage -15 KVAR 6. stage -15KVAR Earth Bus bar: 2 run of 25mm x 3mm tinned copper Metering : 1-150A Ammeter with CT coil 2) 0-500V voltmeter 3) Advance micro controller based intelegent power factor controller with self dianostic sensing and digital net work analyser with software for mentioning and saving para meter of a suitable multi function meter. Indication: R,Y,B The panel should be coated with Epoxy based painting and the whole assembly fixed in suitable cubical panel grouted in floor with connection complete etc., complete complying as directed by departmental officers.
Supply and laying of HT 11KV 3 Core 185 Sqmm. XLPE UG cable in a trench to be excavated at a depth of 1.0 mtr. Putting 0.15 mtr. Layers of sand and HTUG cable in HDPE pipe and refilling the earth to make good etc., complete complying as directed by departmental officers.
Supply and clamping at 11 KV 3 core 185 sq.mm XLPE HTUG cable in existing trench / pipe laid in ground etc., complete complying as directed by departmental officers.
Supply and providing cable end termination suitable for 11KV 3 core 185 sq.mm XLPE HTUG cable with necessary indoor type heat /cold shinkable joint kit and accessories (Make:RayChem/M.Seal.) etc., complete complying as directed by departmental officers.
Supply and laying of 3 Runs 3 ½ x400 sq.mm PVC armoured LTUG armoured cable in a trench to be excavated at a depth of 0.75 meter and covering the cable completely with HDPE Pipe 120mm / 103.50mm and refilling the earth to make good etc., complete complying as directed by departmental officers.
Supply and clamping of 3 Runs 3 ½ x400 sq.mm PVC LTUG cable on wall with M.S. special clamps etc., complete complying as directed by departmental officers.
Supply and fixing of brass cable gland for 3½ x 400 Sq.mm PVC armoured LTUG armoured cable with earth connection etc., complete complying as directed by departmental officers.
Supply and providing cable end termination of 3½ x 400 Sq.mm PVC LTUG aluminium armoured cable with necessary aluminium cable socket by crimping etc., with electrical connection complete etc., complete complying as directed by departmental officers.
Supply and laying of 2 Runs 3 ½ x 185 sq.mm PVC armoured LTUG armoured cable in a trench to be excavated at a depth of 0.75 meter and covering the cable completely with HDPE Pipe 120mm / 103.50 and refilling the earth to make good etc., complete complying as directed by departmental officers.
Supply and clamping of 2 Runs 3 ½ x 185 sq.mm PVC LTUG armoured cable on wall with M.S. special clamps etc., complete complying as directed by departmental officers.
Supply and Laying of 3 1/2 x 185 sq.mm. PVC armoured LTUG cable in suitable size HDPE pipe in a trench to be excavated at a depth of 0.75 metre and refilling the earth to make good etc., complete complying as directed by departmental officers.
Supply and clamping of 3 ½ x 185 sq.mm PVC LTUG armoured cable on wall with M.S. special clamps etc., complete complying as directed by departmental officers.
Supply and fixing of brass cable gland for 3½ x 185 Sq.mm PVC armoured LTUG armoured cable with earth connection etc., complete complying as directed by departmental officers.
Supply and providing cable end termination of 3½ x 185 Sq.mm PVC LTUG aluminium armoured cable with necessary aluminium cable socket by crimping etc., with electrical connection complete etc., complete complying as directed by departmental officers.
Supply and Laying of 3 1/2 x 120 sq.mm. PVC armoured LTUG cable in suitable size HDPE pipe in a trench to be excavated at a depth of 0.75 metre and refilling the earth to make good etc., complete complying as directed by departmental officers.
Supply and clamping of 3 ½ x 120 sq.mm PVC LTUG armoured cable on wall with M.S. special clamps etc., complete complying as directed by departmental officers.
Supply and fixing of brass cable gland for 3½ x 120 sq.mm PVC armoured LTUG armoured cable with earth connection etc., complete complying as directed by departmental officers.
Supply and providing cable end termination of 3½ x 120 sq.mm PVC LTUG aluminium armoured cable with necessary aluminium cable socket by crimping etc., with electrical connection complete etc., complete complying as directed by departmental officers.
Supply and clamping of 2 x 2.5 sq.mm copper PVC LTUG armoured cable on wall with M.S.clamps etc., complete complying as directed by departmental officers.
Supply and fixing of brass cable gland for 2 x 2.5 sq.mm copper PVC armoured LTUG armoured cable with earth connection etc., complete complying as directed by departmental officers.
Supply and clamping of 10 x 2.5 sq.mm copper PVC LTUG armoured cable on wall with M.S.clamps etc., complete complying as directed by departmental officers.
Supply and fixing of brass cable gland for 10 x 2.5 sq.mm copper PVC armoured LTUG armoured cable with earth connection etc., complete complying as directed by departmental officers.
Supply, and fixing GI Hot Dip/Powder coated 16SWG Cable Tray with 300mm width and 50mm Height on suitable angle iron frame on wall or ceiling etc., complete complying as directed by departmental officers.
Preparation of Electrical schematic diagram, site plans, physical layout 10 copies for all buildings in the campus and payment of CEIG documentation charges submission of completion report, rectification report, obtaining drawing approval, safety certification etc., complete including lamination copy fixed at HT substation. (Alteration/ Addition in HT substation, ILT, ITT, ICT and IPT, SICE buildings) etc., complete complying as directed by departmental officers etc., complete complying as directed by departmental officers.
Towards safety accessories and tools. First Aid Box-1set 4 Nos. Fire Buckets with stand- 1 set Rubber Mat 20mm X 1m X 2m (5Nos) – 1 Set. Fire Extinguisher-CO2- 5 Kgs – 4 Nos. 11 KV Hand Gloves-2 pair shock treatment chart fixed in glass frame- 1 set Earth Discharge Rod -3 No. Danger Board (11 KV) - 6 Nos.
Supply and fixing of 65 mm dia (2 - 1/2") GI pipe (class B) of 6 metre length with 300mm x 300mm x 6mm MS base plate duly welded at the bottom with concreting with construction of masonary pedestal with suitable SMC box with door arrangement to house 6A SP MCB swithc, 2/4 way connector on suitable hylem sheet and supply and fixing of 48W LED Street light fitting with LED (Higher end) with 1 metre 32mm dia GI pipe (class B) complete with suitable MS clamps for LED street light fitting and SMC box with PVC unsheathed copper leads from SMC box to fitting and with painting of suitable colour etc., complete complying as directed by departmental officers.
Supply and Laying of 4 x 16 sq.mm. PVC armoured LTUG cable in suitable size HDPE pipe in a trench to be excavated at a depth of 0.75 metre and refilling the earth to make good etc., complete complying as directed by departmental officers.
Supply and clamping of 4 x 16 sq.mm PVC LTUG armoured LTUG cable on post or on wall with MS Clamps etc., complete complying as directed by departmental officers.
Supply and fixing of brass cable gland for 4 x 16 sq.mm PVC armoured LTUG cable with earth connection etc., complete complying as directed by departmental officers.
Rising main (Power): Design, Supply, Installation, Testing and Commissioning of 400A, 3L+N+PE / 3L+PE, Sandwich type Copper, Straight feeder (Rising Main), insulation Class F (155°C), IP 55 Dust and Vermin proof made up of 1.6mm CRCA sheet powder coating, Copper earthing plug in points at every floor necessary angle iron supporting of Rising Mains as per CEIG rules & regulations. (Like Legrand/ Equivalent) etc., complete complying as directed by departmental officers.
Supply and fixing End Feed Unit and 4P 400A MCCB and flange End unit as per CEIG rules and regulations. (Like Legrand/ Equivalent) (power) etc., complete complying as directed by departmental officers.
Supply and fixing of End Cover for Rising Main as per CEIG rules & regulations. (Like Legrand/ Equivalent) etc., complete complying as directed by departmental officers.
Supply and fixing of 250A, 4P MCCB Tap off Box with necessary connection. (Like Legrand/ Equivalent) (floor power panel) etc., complete complying as directed by departmental officers.
Supply and fixing of 200A, 4P MCCB Tap off Box with necessary connection. (Like Legrand/ Equivalent) (floor power panel) etc., complete complying as directed by departmental officers.
Supply and fixing of 125A, 4P MCCB Tap off Box with necessary connection. (Like Legrand/ Equivalent) etc., complete complying as directed by departmental officers.
Supply and fixing of Spring Hanger, Edge wise hanger for 400A Rising main as per CEIG rules and regulations.(Like Legrand/ Equivalent) a) vertical bracket b)spring support c) Rigid support etc., complete complying as directed by departmental officers.
Supply and fixing of 32A FP MCB 10 KA in suitable sheet steel enclosure in flush with wall with earth connection. (Legrand/Hager/ Equiv) etc., complete complying as directed by departmental officers.
Supply and fixing of 63A FP MCB 10 KA in suitable sheet steel enclosure in flush with wall with earth connection. (Legrand/Hager/ Equiv) (DATA U) etc., complete complying as directed by departmental officers.
Supply and fixing of 4 way Vertical Triple pole and neutral MCB sheet steel enclosure distribution board with double door (metal) with 1 no. 63A 4P MCB switch as incoming and 12 nos. 6A to 32A SP MCB as outgoing on wall with earth connection only. Higher End (HTSS) etc., complete complying as directed by departmental officers.
Supply and fixing of 8 way Vertical Triple pole and neutral MCB sheet steel enclosure distribution board with double door (metal) with 1 no. 100 A 4P MCB Isolator as incoming and 3 nos. 32A 3P MCB , 15 nos. 6A to 32A SP MCB as outgoing on wall with earth connection only. Higher End etc., complete complying as directed by departmental officers.
Supply and Laying of 3 1/2 x 70 sq.mm. PVC armoured LTUG cable in suitable size HDPE pipe in a trench to be excavated at a depth of 0.75 metre and refilling the earth to make good etc., complete complying as directed by departmental officers.
Supply and clamping of 3 ½ x 70 sq.mm PVC LTUG armoured cable on wall with M.S.clamps etc., complete complying as directed by departmental officers.
Supply and fixing of brass cable gland for 31/2 x 70 sq.mm PVC armoured LTUG armoured cable with earth connection etc., complete complying as directed by departmental officers.
Supply and providing cable end termination of 3 1/2 x 70 sq.mm PVC LTUG Aluminum armoured cable with necessary aluminium cable sockets by crimping etc. with electrical connection complete etc., complete complying as directed by departmental officers.
Supply and Laying of 3 1/2 x 25 sq.mm. PVC armoured LTUG cable in suitable size HDPE pipe in a trench to be excavated at a depth of 0.75 metre and refilling the earth to make good etc., complete complying as directed by departmental officers.
Supply and clamping of 3 ½ x 25 sq.mm PVC LTUG armoured cable on wall with M.S.clamps etc., complete complying as directed by departmental officers.
Supply and fixing of brass cable gland for 31/2 x 25 sq.mm PVC armoured LTUG armoured cable with earth connection etc., complete complying as directed by departmental officers.
Supply and providing cable end termination of 3 1/2 x 25 sq.mm PVC LTUG Aluminum armoured cable with necessary aluminium cable sockets by crimping etc. with electrical connection complete etc., complete complying as directed by departmental officers.
Supply and fixing of Single phase 3 KVA Online UPS system (with Two hour back up ) with rack arrangement and following specifications and protection against reverse circuit polarity, 440V main input protection, Dynamic short protection with fold back current limiting, low overload, short circuit and pure sine wave output resulting in silent operation of motors and fans. Input voltage : 170V -27V AC Frequency : 50 Hz Input battery voltage : 144 V DC (Make Exide/Numeric/Kirloskar/Numeric/Equivalent) Charger : constant current SMPS charger with full charge cutoff Charging current : Settable upto 8 Amps Inverter: MOSFET Based Full Bridge inverter Output: 230V +/- 3% 50 Hz Output Apparent power: 3000VA Control: Microprocessor based Display : LED display with mains ON, Charger ON, Inverter ON, Battery LOW, Overload Trip
Wiring with 2 x1.5 sq.mm. (22/0.3) PVC insulated single core unsheathed copper conductor of 1100 V grade in suitable PVC rigid pipe on wall and ceiling with PVC accessories with Module GI switch box on wall with 6A one way module switch with module front plate with continuous earth wire connection of 14 SWG TC wire withpainting of Suitable colour for Open PVC Light point / fan point (for electronic regulator) ( 5points / Coil) Higher End etc., complete complying as directed by departmental officers.
Wiring with 2 x1.5 sq.mm. (22/0.3) PVC insulated single core unsheathed copper conductor of 1100 V grade in suitable PVC rigid pipe on wall and ceiling with PVC accessories with Module GI switch box in flush wall with 6A one way module switch with module front plate with continuous earth wire connection of 14 SWG TC wire with painting of Suitable colour for Open PVC Light point / fan point (for electronic regulator) ( 6 points / Coil) Higher End etc., complete complying as directed by departmental officers.
Supply and fixing of 4'20 W LED Single box type fitting complete with TW round blocks on wall with PVC unsheathed Copper leads from the terminals to the fittings with 20 W LED tubes with inbuilt electronic driver complete. (Philips/Havells/Equivalent) etc., complete complying as directed by departmental officers.
Supply and fixing of WT bulk head fitting with guard suitable for 15W LED bulb with 15W LED bulb etc., complete complying as directed by departmental officers.
Supply and fixing of 1200 mm (48") AC ceiling fan complete with 300W stepped electronic regulator with 500 mm down rod on the existing clamp.(Crompton / Havells / Usha/ Equiv) etc., complete complying as directed by departmental officers.
Supply and fixing of 5A / 15A 3 pin combined flush type wall socket with 15A flush type switch concealed in suitable MS box in flush with wall and covered with 3mm thick hylem sheet etc., complete complying as directed by departmental officers.
Supply and fixing of 12 way single pole and neutral MCB sheet steel enclosure Distribution board with IP 42 protection metal door type with 1No 16 Amps DP MCB & 1No 63A 4P MCB as incoming and 2 Nos 6A to 32A SP MCB outgoing in flush with wall and making good of the concealed portion with earth connection only. The MCB DB and MCB's should be with ISI mark (Like Legrand / Hager/ Equiv make) etc., complete complying as directed by departmental officers.
Supply and Run of 2 of 2.5 sq.mm. (36/0.3) PVC insulated SC unsheathed copper conductor of 1100 V grade in suitable PVC rigid pipe on wall and ceiling with continuous earth wire connection by 2.5 sq.mm. PVC insulated SC unsheathed copper wire with painting of suitable colour etc., complete complying as directed by departmental officers.
Supply and Run of 4 of 10 sq.mm. (140/0.3) PVC insulated SC unsheathed copper conductor of 1100 V grade in suitable gauge MS conduit pipe on wall and ceiling with continuous earth wire connection of 14 SWG TC wire with painting of suitable colour etc., complete complying as directed by departmental officers.
Supply, Erection, Testing, Commissioning and Handing over of 1No 15 Persons capacity (Disability person) Lift (SS304 grade) without machine room as per the following technical specifications. Technical Specifications: 1) Locations:- G+3 building 2) No. of Lift: One No. 3) Type of Lift : Disability person Lift 4) Capacity of lift: 15 persons 5) Speed : 1.0 mtr/sec 6) Type of Drive: Microprocessor V3F. 7) No. of floor Ground + 3 floor 8) Total Travel: 12 mtrs (approx) 9) Leveling Accuracy: High level accuracy with smooth & jerk free stopping 10) Construction of car: Stainless steel hairline finish with direct lighting with new beautiful single tube false ceiling with tubular handrail on three sides, 300mm sweep fan 11) Position of Machine :Directly above the Lift level 12) No. of Landing Entrance – One in front 4 Nos 13) No of Car Entrance: One in front only. 14) Car Entrance Door:- Stainless steel centre opening auto door. 15) Landing Entrance Door:- V3F Drive side opening sliding 18SWG stainless steel (Hairline finish) door with provision for emergency key opening at all landing. 16)Carsize : 1550 x 1550 mm 17)Car Clear Opening: 900mmx2100mm 18)Lift Well size : 2200mm wide x 2100 deep (existing)
19) Lift pit depth:-1600mm (existing) 20) Power supply: 400/440 V Three phase 50Cy/Sec A.C.supply and 230V 50 Hz single phase AC supply for light. 21)Control: Micro processor based Duplex full collective control with/without attendant. 22)Car fittings: Compact fluorescent lighting with 2Nos 300mm sweep fans. 23) Lift Well: RCC Construction with brick masonry. 25) Indication: Up/ Down Digital direction and position indicator for all landing and in car. 26)Emergency alarm bell:-Battery operated alarm bell to be provided with automatic charging device. 27)Emergency light : Battery operated light to be provided with automatic charging device. 28)Fire man’s switch ;To be provided at Ground Floor 29)Minor builders work: To be provided by Lift Contractor. 30)Scaffolding : To be provide by lift contractor 31) Stainless steel sill angles and facia plates. 32) Steel for lift Machinery :To be provided by lift contractor 33)Servicing and Maintenance: Free comprehensive servicing and maintenance should be provided by lift contractor during the guarantee period of one year and extended warranty period for further period of 2 years beyond free warranty period of one year from the date of commissioning of lift. 34)Automatic Rescue Device: To facilitate the landing of the lift to the nearest floor at the time of power failure. 35)Provision of Intercom with Phone: To be provided by lift contractor. 36)Lift license : Preparation of drawing payment of charges to CEIG and Insurance policies and obtaining CEIG safety certificate as per lift act should be done by lift contractor 37)Floor annunciator with music
38) Special Features. (a). Infra red door sensor with full height screen. (b). Full width half height rear panel Mirror. (c). Tubular stainless steel handrail on three sides in car. (d). Voltage stabilizer for circuit control. (e). Stainless steel signal fixtures. (f). Vandal proof S.S button with S.S Cover. Lift buttons with Braille codes and handicap sign. (g) Stainless steel door frames for landing doors (h) VF door operator. (i) Call register Signal (j) Stainless steel fascia plate for car operating panel and landing fixtures. (k) ON-OFF switch for fan & light (l). Over load warning indicator. (m) Pit Ladder 39) Over speed governor, phase failure and phase reversal relay, alarm bell, T guide brackets for car and counter weight. Rubber padding under winding unit. Motor of adequate capacity, electromagnetic brake with compression springs, car safety gears, buffers, electro mechanical door locks. Emergency key. Side supporting angles motor over load protection devices, final limit switch main suspensions ropes, counter weights, lifting joint joist mounting the machineries. 40) Guarantee: Guarantee for the materials and workman ship of equipments complete should be offered by the Lift firm for a period of not less than one year.
41)Site testing in accordance with IS 14665 should be carried out at the time of handing over. 42) Providing Architraves by supply and fixing for all landing door entrances. Rate of one lift as per above specifications like (Make:Johnson /Kone /equivalent)
Supply, Erection, Testing, Commissioning and Handing over of 1No 15 Persons capacity (Disability person) Lift (SS304 grade) without machine room as per the following technical specifications. Technical Specifications: 1) Locations:- G+5 building 2) No. of Lift: One No. 3) Type of Lift : Disability person Lift 4) Capacity of lift: 15 persons 5) Speed : 1.0 mtr/sec 6) Type of Drive: Microprocessor V3F. 7) No. of floor Ground + 5 floor 8) Total Travel: 20 mtrs (approx) 9) Leveling Accuracy: High level accuracy with smooth & jerk free stopping 10) Construction of car: Stainless steel hairline finish with direct lighting with new beautiful single tube false ceiling with tubular handrail on three sides, 300mm sweep fan 11) Position of Machine :Directly above the Lift level 12) No. of Landing Entrance – One in front 6 Nos 13) No of Car Entrance: One in front only. 14) Car Entrance Door:- Stainless steel centre opening auto door. 15) Landing Entrance Door:- V3F Drive side opening sliding 18SWG stainless steel (Hairline finish) door with provision for emergency key opening at all landing. 16)Carsize : 1550 x 1550 mm 17)Car Clear Opening: 900mmx2100mm 18)Lift Well size : 2200mm wide x 2100 deep (existing) 19) Lift pit depth:-1600mm (existing) 20) Power supply: 400/440 V Three phase 50Cy/Sec A.C.supply and 230V 50 Hz single phase AC supply for light.
21)Control: Micro processor based Duplex full collective control with/without attendant. 22)Car fittings: Compact fluorescent lighting with 2Nos 300mm sweep fans. 23) Lift Well: RCC Construction with brick masonry. 25) Indication: Up/ Down Digital direction and position indicator for all landing and in car. 26)Emergency alarm bell:-Battery operated alarm bell to be provided with automatic charging device. 27)Emergency light : Battery operated light to be provided with automatic charging device. 28)Fire man’s switch ;To be provided at Ground Floor 29)Minor builders work: To be provided by Lift Contractor. 30)Scaffolding : To be provided by lift contractor 31) Stainless steel sill angles and facia plates. 32) Steel for lift Machinery :To be provided by lift contractor 33)Servicing and Maintenance: Free comprehensive servicing and maintenance should be provided by lift contractor during the guarantee period of one year and extended warranty period for further period of 2 years beyond free warranty period of one year from the date of commissioning of lift. 34)Automatic Rescue Device: To facilitate the landing of the lift to the nearest floor at the time of power failure. 35)Provision of Intercom with Phone: To be provided by lift contractor. 36)Lift license : Preparation of drawing payment of charges to CEIG and Insurance policies and obtaining CEIG safety certificate as per lift act should be done by lift contractor 37)Floor annunciator with music 38) Special Features. (a). Infra red door sensor with full height screen. (b). Full width half height rear panel Mirror.
(c). Tubular stainless steel handrail on three sides in car. (d). Voltage stabilizer for circuit control. (e). Stainless steel signal fixtures. (f). Vandal proof S.S button with S.S Cover. Lift buttons with Braille codes and handicap sign. (g) Stainless steel door frames for landing doors (h) VF door operator. (i) Call register Signal (j) Stainless steel fascia plate for car operating panel and landing fixtures. (k) ON-OFF switch for fan & light (l). Over load warning indicator. (m) Pit Ladder 39) Over speed governor, phase failure and phase reversal relay, alarm bell, T guide brackets for car and counter weight. Rubber padding under winding unit. Motor of adequate capacity, electromagnetic brake with compression springs, car safety gears, buffers, electro mechanical door locks. Emergency key. Side supporting angles motor over load protection devices, final limit switch main suspensions ropes, counter weights, lifting joint joist mounting the machineries. 40) Guarantee: Guarantee for the materials and workman ship of equipments complete should be offered by the Lift firm for a period of not less than one year. 41)Site testing in accordance with IS 14665 should be carried out at the time of handing over. 42) Providing Architraves by supply and fixing for all landing door entrances. Rate of one lift as per above specifications like (Make:Johnson /Kone /equivalent)
Earthing as per the ISI specification with an earth electrode of 2.1mt class 'B' GI pipe of dia not less than 40mm, with copper earth plate of size 125mm x 50mm x 6mm, with necessary funneling arrangements with necessary masonry work and with 38mm RCC cover slab for the brick masonry etc., complete complying as directed by departmental officers.
Supply and run of 25mm x 6mm tinned copper flat with necessary clamps / supports on wall / floor / ground for earth connection etc., complete complying as directed by departmental officers.
Supply and run of 25mm x 3mm tinned copper flat with necessary clamps / supports on wall / floor / ground for earth connection etc., complete complying as directed by departmental officers.
Supply and run of 1 of NO: 8 SWG cu wire for earth connection etc., complete complying as directed by departmental officers.
Sub Total
SRI BHANNARI AMMAN BUILDERS
stage.html
html • 0.04 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid