| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹1.8 LAccepted-AOC 344 1 SB GORAI ROAD HILL VIEW PARK NORTH ASANSOL | ASANSOL | WEST BENGAL | L1 | Accepted-AOC Accepted | |
| 2 | L2₹1.8 L+₹2,503.18 (1.42%)Rejected-Finance 19 A NIRUPAMA DEVI ROAD LANE 1 BERHAMPORE MURSHIDABAD | BERHAMPORE | MURSHIDABAD | L2 | Rejected-Finance Rejected | |
| 3 | L3₹1.8 L+₹2,950.11 (1.67%)Rejected-Finance 6 KRIPANATH DUTTA ROAD KOLKATA 700 002 | KOLKATA | KOLKATA | WEST BENGAL | 700002 | L3 | Rejected-Finance Rejected | |
| 4 | L4₹1.8 L+₹3,206.34 (1.82%)Rejected-Finance 138 CANNING STREET GROUND FLOOR KOLKATA | KOLKATA | WEST BENGAL | L4 | Rejected-Finance Rejected |
Tender Value
Refer Docs
EMD Value
₹3,800
Closing Date
3 Jan 2025, 6:00 pmClosed
ASSISTANT ENGINEER
O/O ASSISTANT ENGINEER,BMSD,PHE DTE,BANKURA-722102
Restoration of 11KV 3 panel VCB at CWPH of Puncha water supply scheme under Bankura Mechanical Division,P.H.E. Dte.
2024_PHED_786998_13
WBPHED/AE/BMSD/NIeT- 8 OF 2024-2025
Open Tender
Electrical Work/ Equipment
Item Rate
10 days
Bankura
Please refer Tender documents.
5 documents required · 5 mandatory
₹3,800
Yes
19 Feb 2025
20 Dec 2024
6 Jan 2025
20 Dec 2024
3 Jan 2025
20 Dec 2024
Amount
Hiring charges of 5KV DG set for back up power during testing period including carriage & storage and supply of fuel.( 6 hrs ,@ 1550.00=9300 )
3 panel VCB: Disconnection of 11 KV HT cables, through cleaning & servicing of entire panel by carbon cleaner to remove all carbon particles, insulation resistance value checking in ON & OFF condition, closing and tripping time checking along with servicing of electrical and mechanical ON-OFF mechanism, Rack-in Rack-out mechanism, spring changing mechanism . C.T: Dismantling the 6 nos CT's from circuit, cleaning & rubbing properly, then heat treatment done and also barnishing for insulation resistance value improvement, re-connecting the CT's in circuit, then conduct testing. P.T: Dismantling the PT from circuit, cleaning & rubbing properly, heat treatment and varnishing for IR valve improvement and then re-connecting the PT's in circuit then conduct testing. Relays: Dust cleaning, O/C & E/F relays testing by secondary current injection, functional checking of aux. relays, trip circuit supervision relays & master trip relays.(For 3 nos Panel) Bus Bar: Charges for outgoing VCB (4 panel VCB) Bus-Bar Spouts Dismantling, Rubbing, Cleaning, Heating, varnishing by applying CRC, WD-40, Red Insulation Varnish for IR Improvement and finally Re-fitting. Cable and terminal : Cleaning by carbon cleaner , testing all the HT cables (11 KV) reconnected for sucessfully charging of 11 KV supply and put on load condition.
AVR : Charges for AVR thoroughly checking, IR Improvement by cleaning of HT bushings and various HT supporting related material.
Add: 18% GST
Add: 1% Cess
M/S. Sajahan Chowdhury (BID ID -5928794)
B T PROJECTS PRIVATE LIMITED (BID ID -5928493)
WEST BENGAL ENGINEERING CO. (BID ID -5928930)
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .