Superintending Engineer
S.E., EUDC- offfice
Replacement of LT HT Line
2023_PVVNL_842835_1
Systems Strengthening Works
Open Tender
Electrical Works
Item Rate
90 days
S.E., EUDC- offfice
Attached in DOC
2 documents required · 2 mandatory
₹3,540
S.E., EUDC
₹95,000
16 Oct 2023
23 Sept 2023
12 Oct 2023
23 Sept 2023
12 Oct 2023
23 Sept 2023
Amount
Replacement/addition of Poles in HT Line at Different Locations under SDO - 5, Noida (100 No. STP )
Safe carriage of following stock material, from any of the Store Center of PVVNL to work site including Loading from Store and safe unloading at site for Item No. 3 to 4
11 Mtr. Long ST Pole
11KV PIN INSULATOR WITH PIN
SUPPLY OF FOLLOWING MATERIAL BY THE CONTRACTOR FROM THE PVVNL APPROVED VENDORS AS PER GTP APPROVED.
Stay set complete (G.I.Stay rod 16x1800mm, Stay wire 5Kg, Guy insulator, G.I.Stay clamp, bolt, nut & wasther with concrete grouting) for 11KV line as per specification
11KV V-type Cross Arm
Supply and Errection of the Following material for completing the work as per RESPO.
Providing and Fixing of Clamp suitable for 11 Mtr. Long ST Pole with Nut, Bolt and Washers as per site requirement.
The excavation of foundation pit in mix soil/normal soil/soft soil & hard rock as per site condition and its back filling and leveling etc. The size of the pit will be (750x450)mm and having depth of 1/6th of the full length of the support. Erection of support, complete with providing & fixing of all G.I.Clamps size of 75x10mm, 'F' bracket 75x10mm, G.I.Nut bolt & washer, Stone Pad Al. Binding wire and other accessories as per drawing. The work includes carriage and handling of supports from sectional store to pit site as well as an fabrication work if required. Single Pole (a) ST Pole 11 MtR Long
Grouting of supports in CC 1:3:6 (Cement, sand & 20mm stone grift). Grouting will be done in the block of size (450x450)mm x1/6th of full length of the support, upto ground level, 300mm plinth above the ground level with C.C. 1:3:6 (Cement, Course sand and Stone grift) with muffing as per RESPO. Work includes back filling and proper ramming. Single Pole and Double Pole (a) ST Pole 11 MtR Long
Fixing, tightening & nozzling of stay wire with stay rod with the poles of required tension as per drawing, including providing & fixing of Stay Insulators of 11KV and Stay Clamps.
Grouting of stay rods (20x1800)mm including all work of excavation, cement concrete in size (0.60x0.60x0.30)m in ratio 1:3:6 cement, sand, 20mm Stone grift) as per drg. Including back filling of soil and proper ramming etc.
Dismentaling of Old and Damaged ST Poles 11 Mtr Long and 8.5Mtr PCC Poles after safe removal of accessoriess and safe carraige of its from site to any PVVNL Store including loading and uNloading both ends.
Providing and Driving of MS earth rod of size 20x2500 mm in earth and jointing through G.I. wire of 6 SWG between support and earth electrode by providing proper size of bolts and nuts for pole earthing. Supply Erection, fixing, grouting of stay rod in cement, sand and brick ballast in ration 1:4:8 in Block 600*600*300 mm with binding & nuzzling including providing & fixing of stay insulator complete in all respect with grouting. (All Work and Material in the scope of Contractor) (28 Nos. at Jewar and 32 Nos. EDD- Greater Noida)
FIXING OF PIN INSULATOR with pin
PROVIDING OF FIXING OF F-CLAMP WITH CLAMP AND NUT BOLTS AS PER SITE REQUIREMENT.
Replacement/addition of Poles in HT Line at Different Locations under SDO - 6, Noida (350 No. STP)
Safe carriage of following stock material, from any of the Store Center of PVVNL to work site including Loading from Store and safe unloading at site for Item No. 20 to 22
11 Mtr. Long ST Pole
13 Mtr. Long ST Pole
11KV PIN INSULATOR WITH PIN
SUPPLY OF FOLLOWING MATERIAL BY THE CONTRACTOR FROM THE PVVNL APPROVED VENDORS AS PER GTP APPROVED.
Stay set complete (G.I.Stay rod 16x1800mm, Stay wire 5Kg, Guy insulator, G.I.Stay clamp, bolt, nut & wasther with concrete grouting) for 11KV line as per specification
MS Channel 100x50mm for STP Pole.
Supply and Errection of the Following material for completing the work as per RESPO.
Providing and Fixing of Clamp suitable for 11 Mtr. Long ST Pole, 13Mtr ST Pole and 8.5Mtr PCC Pole with Nut, Bolt and Washers as per site requirement.
FIXING OF PIN INSULATOR with pin
The excavation of foundation pit in mix soil/normal soil/soft soil & hard rock as per site condition and its back filling and leveling etc. The size of the pit will be (750x450)mm and having depth of 1/6th of the full length of the support. Erection of support, complete with providing & fixing of all G.I.Clamps size of 75x10mm, 'F' bracket 75x10mm, G.I.Nut bolt & washer, Stone Pad Al. Binding wire and other accessories as per drawing. The work includes carriage and handling of supports from sectional store to pit site as well as an fabrication work if required. Single Pole (a) ST Pole 11 & 13 MtR Long and 8.5MTR. PCC POLE
Grouting of supports in CC 1:3:6 (Cement, sand & 20mm stone grift). Grouting will be done in the block of size (450x450)mm x1/6th of full length of the support, upto ground level, 300mm plinth above the ground level with C.C. 1:3:6 (Cement, Course sand and Stone grift) with muffing as per RESPO. Work includes back filling and proper ramming. Single Pole and Double Pole (a) ST Pole 11 & 13 MtR Long and 8.5MTR. PCC POLE
Fixing, tightening & nozzling of stay wire with stay rod with the poles of required tension as per drawing, including providing & fixing of Stay Insulators of 11KV and Stay Clamps.
Grouting of stay rods (20x1800)mm including all work of excavation, cement concrete in size (0.60x0.60x0.30)m in ratio 1:3:6 cement, sand, 20mm Stone grift) as per drg. Including back filling of soil and proper ramming etc.
Dismentaling of Old and Damaged ST Poles 11 & 13Mtr Long and 8.5Mtr PCC Poles after safe removal of accessoriess and safe carraige of its from site to any PVVNL Store including loading and uloading both ends.
Providing and Driving of MS earth rod of size 20x2500 mm in earth and jointing through G.I. wire of 6 SWG between support and earth electrode by providing proper size of bolts and nuts for pole earthing. Supply Erection, fixing, grouting of stay rod in cement, sand and brick ballast in ration 1:4:8 in Block 600*600*300 mm with binding & nuzzling including providing & fixing of stay insulator complete in all respect with grouting. (All Work and Material in the scope of Contractor) (28 Nos. at Jewar and 32 Nos. EDD- Greater Noida)
Fixing of MS Channel as per site requirement.
Providing and Fixing of F Brackets for Pin Insulator.
Providing and Fixing of Holding Clamps with Nut, Bolts and Washer as per site requirement.
Replacement/addition of Poles in HT Line at Different Locations under SDO - 7, Noida (353 No. STP)
Safe carriage of following stock material, from any of the Store Center of PVVNL to work site including Loading from Store and safe unloading at site for Item No. 40 to 43
11 Mtr. Long ST Pole
13 Mtr. Long ST Pole
11KV PIN INSULATOR WITH PIN
11KV Disc Insulator with Fitting
SUPPLY OF FOLLOWING MATERIAL BY THE CONTRACTOR FROM THE PVVNL APPROVED VENDORS AS PER GTP APPROVED.
Stay set complete (G.I.Stay rod 16x1800mm, Stay wire 5Kg, Guy insulator, G.I.Stay clamp, bolt, nut & wasther with concrete grouting) for 11KV line as per specification
MS Channel for Cross Arm as per site requirement.
Supply and Errection of the Following material for completing the work as per RESPO.
Providing and Fixing of Clamp suitable for 11 Mtr. Long ST Pole, 13Mtr ST Pole and 8.5Mtr PCC Pole with Nut, Bolt and Washers as per site requirement.
FIXING OF PIN INSULATOR with pin AS PER SITE REQUIREMENT.
FIXING OF Disc Insulator with Fitting AS PER SITE REQUIREMENT.
The excavation of foundation pit in mix soil/normal soil/soft soil & hard rock as per site condition and its back filling and leveling etc. The size of the pit will be (750x450)mm and having depth of 1/6th of the full length of the support. Erection of support, complete with providing & fixing of all G.I.Clamps size of 75x10mm, 'F' bracket 75x10mm, G.I.Nut bolt & washer, Stone Pad Al. Binding wire and other accessories as per drawing. The work includes carriage and handling of supports from sectional store to pit site as well as an fabrication work if required. Single Pole (a) ST Pole 11 & 13 MtR Long and 8.5MTR. PCC POLE
Grouting of supports in CC 1:3:6 (Cement, sand & 20mm stone grift). Grouting will be done in the block of size (450x450)mm x1/6th of full length of the support, upto ground level, 300mm plinth above the ground level with C.C. 1:3:6 (Cement, Course sand and Stone grift) with muffing as per RESPO. Work includes back filling and proper ramming. Single Pole and Double Pole (a) ST Pole 11 & 13 MtR Long and 8.5MTR. PCC POLE
Fixing, tightening & nozzling of stay wire with stay rod with the poles of required tension as per drawing, including providing & fixing of Stay Insulators of 11KV and Stay Clamps.
Grouting of stay rods (20x1800)mm including all work of excavation, cement concrete in size (0.60x0.60x0.30)m in ratio 1:3:6 cement, sand, 20mm Stone grift) as per drg. Including back filling of soil and proper ramming etc.
Dismentaling of Old and Damaged ST Poles 11 & 13Mtr Long and 8.5Mtr PCC Poles after safe removal of accessoriess and safe carraige of its from site to any PVVNL Store including loading and uloading both ends.
Providing and Driving of MS earth rod of size 20x2500 mm in earth and jointing through G.I. wire of 6 SWG between support and earth electrode by providing proper size of bolts and nuts for pole earthing. Supply Erection, fixing, grouting of stay rod in cement, sand and brick ballast in ration 1:4:8 in Block 600*600*300 mm with binding & nuzzling including providing & fixing of stay insulator complete in all respect with grouting. (All Work and Material in the scope of Contractor) (28 Nos. at Jewar and 32 Nos. EDD- Greater Noida)
Fixing of MS Channel as per site requirement.
ANJNI TRANSFORMER AND SWITCH GEARS
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .