| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹43.7 LAccepted-AOC 840 1B MADHUR VIHAR COLONY CIVIL LINES JHANSI UP 284 001 | JHANSI | JHANSI | UTTAR PRADESH | 284001 | L1 | Accepted-AOC Contract was awarded to lowest bidder | |
| 2 | L2₹46.9 L+₹2.4 L (5.47%)Rejected-Finance | L2 | Rejected-Finance Not become lowest bidder | |
| 3 | L3₹47.1 L+₹2.6 L (5.89%)Rejected-Finance | L3 | Rejected-Finance Not become lowest bidder | |
| 4 | L4₹47.9 L+₹3.4 L (7.73%)Rejected-Finance A 63 ELDECO COUNTY PHASE II RAJGARH JHANSI U P 284135 | JHANSI | JHANSI | UTTAR PRADESH | 284135 | L4 | Rejected-Finance Not become lowest bidder | |
| 5 | L5₹48.5 L+₹4.0 L (8.97%)Rejected-Finance NEAR PUMP HOUSE ROAD NEAR RED ROSE SCHOOL BABINA CANTT JHANSI DISTT UP 284401 | JHANSI | UTTAR PRADESH | 284001 | L5 | Rejected-Finance Not become lowest bidder |
| Sl No | Description | Qty | Unit | M/s Sohanil Construction L2 | ROHIT ENTERPRISES L4 | M/S Kumar Contractors L1 | M/s Ravi Traders L6 | M/S Ritu Tandon L5 | M/s Raghav Traders L9 | ADARSH ENTERPRISES L8 | FTH TRADERS L7 | M/S S K AGARWAL L3 | DURGAI ELECTRICALS L10 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 1.00 | Design, supplying,installing,testing and commissioning of 150 KVAR Automatic power factor corrector (APFC) suitable size factory made, cubical compartmentalized for each stage , outdoor type,IP 54 degree protection,dust, vermin and wheather proof,made out of CRCA MS sheet of 3.15mm thickness, front openable with locking arrengment,fixed on 50x50x6mm angle iron 4 leg frame structure having 40 cm ground clearance,duly grouted in PCC (1:2:4) complete panel powder coated with seven tank prosses from in side and out side, duly prewired with suitable size FRLS PVC insuleted copper conductor wire for capacitor stages,metering & controll accessories,earthing straps for connecting earth strips, cable entry from bottom and comprising the following :-
(a) Bas Bar system- aluminium busbars of size 40x10mm for phases and 40mmx05mm for neutral duly provided with colour coded heat shrinkable PVC sleeves. (b) Incommer:- MCCB 200 Amp,4 pole,10 KA, ICS=100% ICU, with adjustable thermal magnetic setting alongwith spreader terminals and rotary handle-01 No
(c) MCB, TP 63Amp, D series, 415 volts- 01 No
(d) MCB, TP 40Amp, D series, 415 volts- 03 Nos
(e) MCB, TP 25Amp, D series, 415 volts- 02 No
(f) MPP-H Capacitor, resin filled, heavy duty type for 3 phase 440 volts & 50 Hz system of 50 KVAR capacity- 01 No
(g) MPP-H Capacitor, resin filled, heavy duty type for 3 phase 440 volts & 50 Hz system of 25 KVAR capacity- 03 No
(h) MPP -H Capacitor, resin filled, heavy duty type for 3 phase 440 volts & 50 Hz system of 12.5 KVAR capacity- 02 No
(k) Capacitive duty contactor suitable for 50 KVAR Heavy duty capacitor - 01 No
(l) Capacitive duty contactor suitable for 25 KVAR Heavy duty capacitor - 03 No
(m) Capacitive duty contactor suitable for 12.5 KVAR Heavy duty capacitor - 02 No
(o) 06-stage Automatic power factor correction relay - 01 No
(p) Digital volt meter 0 to 500 volt of size 96mmx96mm with inbuilt selector switch duly.
(q) Digital Amp meter 0 to 200 Amp of size 96mmx96mm with inbuilt selector switch and CTR duly prewired with suitable size copper wire- 01 No
(r) Indicator lamp indicating cycle on with Amber sheds LED type- 03 Nos
(s) Space Heater, 60 watt, 230 volt AC alongwith toggle switch-01 Set
(t) Ventilating fans of 6" sweep size alongwith filter & Thermostat switch, to dissipate the heat liberated by capacitor units complete with automatic switching ON and OFF of fan depending upon the temperature of the panel, suitable for 230 volt, 50 Hz AC - 01 No
Note: 1. The drawing for APFC Panel shall be approved by GE before placement of order.
2. Any kind of brick work, PCC, Plastering etc as required during execution of work, is included in quoted rate and no extra cost will be paid in this effect. | 1 | Each | 3,50,000 ₹3,50,000 | 3,23,500 ₹3,23,500 | 2,70,000 ₹2,70,000 Lowest | 4,50,000 ₹4,50,000 | 5,05,000 ₹5,05,000 | 3,87,700 ₹3,87,700 | 3,40,000 ₹3,40,000 | 3,70,000 ₹3,70,000 | 3,50,000 ₹3,50,000 | 3,50,000 ₹3,50,000 |
| 2.00 | Design, supplying,installing,testing and commissioning of 200 KVAR Automatic power factor corrector (APFC) suitable size factory made, cubical compartmentalized for each stage , outdoor type,IP 54 degree protection,dust, vermin and wheather proof,made out of CRCA MS sheet of 3.15mm thickness, front openable with locking arrengment,fixed on 50x50x6mm angle iron 4 leg frame structure having 40 cm ground clearance,duly grouted in PCC (1:2:4) complete panel powder coated with seven tank prosses from in side and out side, duly prewired with suitable size FRLS PVC insuleted copper conductor wire for capacitor stages,metering & controll accessories,earthing straps for connecting earth strips, cable entry from bottom and comprising the following :-
(a) Bas Bar system- aluminium busbars of size 60x10mm for phases and 30mmx10mm for neutral duly provided with colour coded heat shrinkable PVC sleeves. (b) Incommer:- MCCB 250 Amp,4 pole,10 KA, ICS=100% ICU, with adjustable thermal magnetic setting alongwith spreader terminals and rotary handle-01 No
(c) MCB, TP 63Amp, D series, 415 volts- 03 No
(d) MCB, TP 40Amp, D series, 415 volts- 01 Nos
(e) MCB, TP 25Amp, D series, 415 volts- 02 No
(f) MPP-H Capacitor, resin filled, heavy duty type for 3 phase 440 volts & 50 Hz system of 50 KVAR capacity- 03 No
(g) MPP-H Capacitor, resin filled, heavy duty type for 3 phase 440 volts & 50 Hz system of 25 KVAR capacity- 01 No
(h) MPP -H Capacitor, resin filled, heavy duty type for 3 phase 440 volts & 50 Hz system of 12.5 KVAR capacity- 02 No
(k) Capacitive duty contactor suitable for 50 KVAR Heavy duty capacitor - 03 No
(l) Capacitive duty contactor suitable for 25 KVAR Heavy duty capacitor - 01 No
(m) Capacitive duty contactor suitable for 12.5 KVAR Heavy duty capacitor - 02 No
(o) 06-stage Automatic power factor correction relay - 01 No
(p) Digital volt meter 0 to 500 volt of size 96mmx96mm with inbuilt selector switch duly.
(q) Digital Amp meter 0 to 200 Amp of size 96mmx96mm with inbuilt selector switch and CTR duly prewired with suitable size copper wire- 01 No
(r) Indicator lamp indicating cycle on with Amber sheds LED type- 03 Nos
(s) Space Heater, 60 watt, 230 volt AC alongwith toggle switch-01 Set
(t) Ventilating fans of 6" sweep size alongwith filter & Thermostat switch, to dissipate the heat liberated by capacitor units complete with automatic switching ON and OFF of fan depending upon the temperature of the panel, suitable for 230 volt, 50 Hz AC - 01 No
Note: 1. The drawing for APFC Panel shall be approved by GE before placement of order.
2. Any kind of brick work, PCC, Plastering etc as required during execution of work, is included in quoted rate and no extra cost will be paid in this effect. | 1 | Each | 4,50,000 ₹4,50,000 | 3,88,500 ₹3,88,500 | 3,70,000 ₹3,70,000 Lowest | 4,80,000 ₹4,80,000 | 5,50,000 ₹5,50,000 | 4,37,700 ₹4,37,700 | 5,25,000 ₹5,25,000 | 4,50,000 ₹4,50,000 | 4,60,000 ₹4,60,000 | 4,00,000 ₹4,00,000 |
| 3.00 | Design, Fabricate, Supply, Installation, Testing & Commissioning in replacement of outdoor type dust proof & vermin proof cubical panel board compartmentalized with separate bus bar and cable alley chambers suitable for 3 phase, 4 wire, 415 volts, 50 Hz, Ac supply system as per latest IS/IEC standards & regulations, factory fabricated in an approved factory (manufacturer possessing CPRI test report for equivalent ratings) having modern fabrication facilities, made out of CRCA sheet steel of 3.15mm thick for outer shell and 2mm thick for inner shell with front and rear openable double leaf doors with two point locking arrangement i.e. locking system with handle up & down arrangement & pad locking facility. Complete panel board shall be applied with powder coat painting of approved shade duly pretreated with seven tank process and suitable packing material for IP-54 degree of protection and including provision of 50mm x 50mm x 6mm angle iron base frame of suitable size for mounting the panel board with a minimum ground clearance of 450mm above GL to the bottom of panel including PCC foundation with PCC 1:3:6, type C2 using 40mm graded stone aggregate. Detachable gland plates including double compression stainless steel cable glands of suitable size shall be provided for all incoming and outgoing cables. Steel plate Danger Notice Boards (02Nos) LT 415/440 Volts, and manufacturer's name plate shall be riveted on external doors of feeder pillar box. The size of panel board shall not be less than 1800mm x 1500mm x 450mm (outer dimensions) for accommodating and including provision of following switchgear, control gear and accessories including internal wiring using copper flexibles and lugs of suitable grade/capacity including taking down old unserviceable Feeder Pillar Box of any description complete all as specified and directed
Note : (i) Factory made name plates with feeder names/ Bldg Nos shall be fixed on relevant incomer/outgoing MCCB doors.
(ii) The contractor shall submit set of all drawings of the LT Pillar Boxes and its components in duplicate and get the same approved from GE before commencement of production. The contractor shall furnish all details and clarifications required if any for scrutiny and evaluation. Manufacture of material to be supplied shall be done strictly as per approved drawing.However, approval of drawing shall not absolve the contractor/supplier of his liability for ensuring correctness according to applicable standards & regulations.
Bus bar : TPN Aluminium bus bar of suitable rating provided with heat shrinkable coloured PVC sleeves insulation mounted on insulators for main bus bar and from main bus bar to outgoing MCCB's and outgoing MCCB's up to cable termination etc complete. (The rating of main bus bar shall be 1.5 times of ampere rating of incomer and outgoing bus bar rating shall be 1.5 times of ampere rating of each outgoing MCCB.) and continuous earth bus with GI strip of suitable size capable for carrying full short circuit current for 1 sec shall be provided at bottom of the panel.
(ii) Incomer :
(a) MCCB 500 Amps, 4 Pole, 50 KA (Ics=100%Icu), 415 Volts, 50 Hz, with adjustable thermal and fixed magnetic release - 01 No
(b) Digital Voltmeter with selector switch - 01 Set
(c) Digital Ammeter with selector switch & suitable ratio of CT's - 01 Set of 3
(d) LED Pilot light indication lamps R,Y,B phases - 01 Set of 3
(iii) Outgoing :-
(a) MCCB 400 Amps, 3 Pole, 36 KA (Ics=100%Icu), 415 Volts, 50 Hz, with adjustable thermal and fixed magnetic release - 01 Nos
(b) MCCB 250 Amps, 3 Pole, 36 KA (Ics=100%Icu), 415 Volts, 50 Hz, with adjustable thermal and fixed magnetic release - 02 Nos
(c) MCCB 100 Amps, 3 Pole, 25 KA (Ics=100%Icu), 415 Volts, 50 Hz, with adjustable thermal and fixed magnetic release - 03 Nos | 2 | Each Job | 2,25,000 ₹4,50,000 | 3,17,800 ₹6,35,600 | 2,80,000 ₹5,60,000 | 3,00,000 ₹6,00,000 | 2,65,000 ₹5,30,000 | 3,77,700 ₹7,55,400 | 3,00,000 ₹6,00,000 | 2,70,000 ₹5,40,000 | 2,00,000 ₹4,00,000 Lowest | 3,50,000 ₹7,00,000 |
| 4.00 | Design, Fabricate, Supply, Installation, Testing & Commissioning in replacement of outdoor type dust proof & vermin proof cubical panel board compartmentalized with separate bus bar and cable alley chambers suitable for 3 phase, 4 wire, 415 volts, 50 Hz, Ac supply system as per latest IS/IEC standards & regulations, factory fabricated in an approved factory (manufacturer possessing CPRI test report for equivalent ratings) having modern fabrication facilities, made out of CRCA sheet steel of 3.15mm thick for outer shell and 2mm thick for inner shell with front and rear openable double leaf doors with two point locking arrangement i.e. locking system with handle up & down arrangement & pad locking facility. Complete panel board shall be applied with powder coat painting of approved shade duly pretreated with seven tank process and suitable packing material for IP-54 degree of protection and including provision of 50mm x 50mm x 6mm angle iron base frame of suitable size for mounting the panel board with a minimum ground clearance of 450mm above GL to the bottom of panel including PCC foundation with PCC 1:3:6, type C2 using 40mm graded stone aggregate. Detachable gland plates including double compression stainless steel cable glands of suitable size shall be provided for all incoming and outgoing cables. Steel plate Danger Notice Boards (02Nos) LT 415/440 Volts, and manufacturer's name plate shall be riveted on external doors of feeder pillar box. The size of panel board shall not be less than 1800mm x 1500mm x 450mm (outer dimensions) for accommodating and including provision of following switchgear, control gear and accessories including internal wiring using copper flexibles and lugs of suitable grade/capacity including taking down old unserviceable Feeder Pillar Box of any description complete all as specified and directed
Note : (i) Factory made name plates with feeder names/ Bldg Nos shall be fixed on relevant incomer/outgoing MCCB doors.
(ii) The contractor shall submit set of all drawings of the LT Pillar Boxes and its components in duplicate and get the same approved from GE before commencement of production. The contractor shall furnish all details and clarifications required if any for scrutiny and evaluation. Manufacture of material to be supplied shall be done strictly as per approved drawing.However, approval of drawing shall not absolve the contractor/supplier of his liability for ensuring correctness according to applicable standards & regulations.
Bus bar : TPN Aluminium bus bar of suitable rating provided with heat shrinkable coloured PVC sleeves insulation mounted on insulators for main bus bar and from main bus bar to outgoing MCCB's and outgoing MCCB's up to cable termination etc complete. (The rating of main bus bar shall be 1.5 times of ampere rating of incomer and outgoing bus bar rating shall be 1.5 times of ampere rating of each outgoing MCCB.) and continuous earth bus with GI strip of suitable size capable for carrying full short circuit current for 1 sec shall be provided at bottom of the panel.
(ii) Incomer :
(a) Air Circuit Breaker (ACB), 630 Amps, 4 Pole, 50 KA (Ics = Icu = Icw for 1 Sec), 415 Volts, 50 Hz, Manual Draw Out (MDO) type with microprocessor based release - 01 No
(b) Digital Voltmeter with selector switch - 01 Set
(c) Digital Ammeter with selector switch & suitable ratio of CT's - 01 Set of 3
(d) LED Pilot light indication lamps R,Y,B phases - 01 Set of 3
(iii) Outgoing :-
(a) MCCB 350 Amps, 3 Pole, 36 KA (Ics=100%Icu), 415 Volts, 50 Hz, with adjustable thermal and fixed magnetic release - 01 Nos
(b) MCCB 250 Amps, 3 Pole, 36 KA (Ics=100%Icu), 415 Volts, 50 Hz, with adjustable thermal and fixed magnetic release - 02Nos
(c) MCCB 160 Amps, 3 Pole, 25 KA (Ics=100%Icu), 415 Volts, 50 Hz, with adjustable thermal and fixed magnetic release - 02 Nos
(d) MCCB 160 Amps, 3 Pole, 25 KA (Ics=100%Icu), 415 Volts, 50 Hz, with adjustable thermal and fixed magnetic release - 01 Nos | 2 | Each Job | 6,75,000 ₹13,50,000 | 6,47,500 ₹12,95,000 | 4,90,000 ₹9,80,000 Lowest | 6,44,000 ₹12,88,000 | 5,40,000 ₹10,80,000 | 6,27,700 ₹12,55,400 | 5,40,000 ₹10,80,000 | 7,10,000 ₹14,20,000 | 7,00,000 ₹14,00,000 | 7,00,000 ₹14,00,000 |
| 5.00 | Design, Fabricate, Supply, Installation, Testing & Commissioning in replacement of outdoor type dust proof & vermin proof cubical panel board compartmentalized with separate bus bar and cable alley chambers suitable for 3 phase, 4 wire, 415 volts, 50 Hz, Ac supply system as per latest IS/IEC standards & regulations, factory fabricated in an approved factory (manufacturer possessing CPRI test report for equivalent ratings) having modern fabrication facilities, made out of CRCA sheet steel of 3.15mm thick for outer shell and 2mm thick for inner shell with front and rear openable double leaf doors with two point locking arrangement i.e. locking system with handle up & down arrangement & pad locking facility. Complete panel board shall be applied with powder coat painting of approved shade duly pretreated with seven tank process and suitable packing material for IP-54 degree of protection and including provision of 50mm x 50mm x 6mm angle iron base frame of suitable size for mounting the panel board with a minimum ground clearance of 450mm above GL to the bottom of panel including PCC foundation with PCC 1:3:6, type C2 using 40mm graded stone aggregate. Detachable gland plates including double compression stainless steel cable glands of suitable size shall be provided for all incoming and outgoing cables. Steel plate Danger Notice Boards (02Nos) LT 415/440 Volts, and manufacturer's name plate shall be riveted on external doors of feeder pillar box. The size of panel board shall not be less than 1800mm x 1500mm x 800mm (outer dimensions) for accommodating and including provision of following switchgear, control gear and accessories including internal wiring using copper flexibles and lugs of suitable grade/capacity including taking down old unserviceable Feeder Pillar Box of any description complete all as specified and directed :- (Gun House MAP Qtrs)
Note : (i) Factory made name plates with feeder names/ Bldg Nos shall be fixed on relevant incomer/outgoing MCCB doors.
(ii) The contractor shall submit set of all drawings of the LT Pillar Boxes and its components in duplicate and get the same approved from GE before commencement of production. The contractor shall furnish all details and clarifications required if any for scrutiny and evaluation. Manufacture of material to be supplied shall be done strictly as per approved drawing.However, approval of drawing shall not absolve the contractor/supplier of his liability for ensuring correctness according to applicable standards & regulations.
Bus bar : TPN Aluminium bus bar of suitable rating provided with heat shrinkable coloured PVC sleeves insulation mounted on insulators for main bus bar and from main bus bar to outgoing MCCB's and outgoing MCCB's up to cable termination etc complete. (The rating of main bus bar shall be 1.5 times of ampere rating of incomer and outgoing bus bar rating shall be 1.5 times of ampere rating of each outgoing MCCB.) and continuous earth bus with GI strip of suitable size capable for carrying full short circuit current for 1 sec shall be provided at bottom of the panel.
(ii) Incomer :
(a) MCCB, 400 Amps, 4 Pole, 36 KA (Ics = Icu = Icw for 1 Sec), 415 Volts, 50 Hz, Manual Draw Out (MDO) type with microprocessor based release - 01 No
(b) Digital Voltmeter with selector switch - 01 Set
(c) Digital Ammeter with selector switch & suitable ratio of CT's - 01 Set of 3
(d) LED Pilot light indication lamps R,Y,B phases - 01 Set of 3
(iii) Outgoing :-
(a) MCCB 200 Amps, 3 Pole, 25 KA (Ics=100%Icu), 415 Volts, 50 Hz, with adjustable thermal and fixed magnetic release - 03 Nos
(b) MCCB 250 Amps, 3 Pole, 36 KA (Ics=100%Icu), 415 Volts, 50 Hz, with adjustable thermal and fixed magnetic release - 01 Nos | 2 | Each Job | 2,75,000 ₹5,50,000 Lowest | 3,42,500 ₹6,85,000 | 2,75,000 ₹5,50,000 Lowest | 3,54,000 ₹7,08,000 | 3,62,000 ₹7,24,000 | 3,27,700 ₹6,55,400 | 2,80,000 ₹5,60,000 | 3,00,000 ₹6,00,000 | 2,80,000 ₹5,60,000 | 3,25,000 ₹6,50,000 |
| 6.00 | M&L in replacement of Power Cables, Aluminum Stranded Conductor 630 sqmm, 3.5 core, XLPE Insulated, Cores laid up, PVC Inner sheathed, Armoured with galvanized wire or galvanized steel strip, overall PVC Sheathed, 1100V Grade as per IS 7098(Part 1) 1988 complete laid in trenches / floors / fixed to poles / walls / drawn through pipes etc including provn of lugs, glands, nuts, bolts & washers etc for connecting in LT feeder pillar box / transformer bushings/LT OH Line and testing on completion all as specified and directed by Engineer-in-Charge.
Note: Excavation, earth work and provn of cable covers / protection pipe etc shall be measured and paid separately under relevant items of BOQ. | 50 | RM | 3,400 ₹1,70,000 | 3,060 ₹1,53,000 | 3,200 ₹1,60,000 | 2,410 ₹1,20,500 Lowest | 3,100 ₹1,55,000 | 3,170 ₹1,58,500 | 3,050 ₹1,52,500 | 3,100 ₹1,55,000 | 3,000 ₹1,50,000 | 4,000 ₹2,00,000 |
| 7.00 | All as per item No. 6.00 here-in-before but of size 500 sqmm, 3.5 core. | 60 | RM | 3,050 ₹1,83,000 | 2,580 ₹1,54,800 | 2,500 ₹1,50,000 | 2,200 ₹1,32,000 Lowest | 2,655 ₹1,59,300 | 3,170 ₹1,90,200 | 2,750 ₹1,65,000 | 2,600 ₹1,56,000 | 2,500 ₹1,50,000 | 3,000 ₹1,80,000 |
| 8.00 | All as per item No. 6.00 here-in-before but of size 400 sqmm, 3.5 core. | 300 | RM | 2,050 ₹6,15,000 | 1,820 ₹5,46,000 | 2,400 ₹7,20,000 | 1,740 ₹5,22,000 Lowest | 1,845 ₹5,53,500 | 1,770 ₹5,31,000 | 2,600 ₹7,80,000 | 2,100 ₹6,30,000 | 2,000 ₹6,00,000 | 2,000 ₹6,00,000 |
| 9.00 | Excavation in trenches not exceeding 1.5m wide and not exceeding 1.5m depth and getting out in soft/loose soil for laying of cables complete all as specified and directed by Engineer-in-Charge. | 92 | CuM | 150 ₹13,800 | 108 ₹9,936 | 180 ₹16,560 | 100 ₹9,200 | 135 ₹12,420 | 77 ₹7,084 Lowest | 200 ₹18,400 | 160 ₹14,720 | 100 ₹9,200 | 200 ₹18,400 |
| 10.00 | Supply and spread M-sand in trenches for cushioning of cable complete all as specified and directed by Engineer-in-Charge. (Note: Punned down thickness only shall be measured for the purpose of payment) | 31 | CuM | 600 ₹18,600 | 55 ₹1,705 | 700 ₹21,700 | 80 ₹2,480 | 10 ₹310 Lowest | 27 ₹837 | 800 ₹24,800 | 700 ₹21,700 | 1,000 ₹31,000 | 700 ₹21,700 |
Tender Value
₹43.7 L
EMD Value
₹87,320
Closing Date
26 Mar 2026, 6:00 pmClosed
Maj Rajesh Rathore
Garrison Engineer Jhansi
SPL REPAIR MAINTENANCE OF APFC PANELS AND LT PANELS OF VARIOUS CAPACITY ALONGWITH CONNECTED WORKS AT JHANSI CANTT
2026_MES_753465_2
GE/JHA/TOK/86 OF 2025-26
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
GE Jhansi
AS per NIT and Tender Documents
9 documents required · 9 mandatory
₹500
GE Jhansi
₹87,320
Yes
13 May 2026
11 Mar 2026
28 Mar 2026
11 Mar 2026
26 Mar 2026
19 Mar 2026
M&L in replacement of Power Cables, Aluminum Stranded Conductor 630 sqmm, 3.5 core, XLPE Insulated, Cores laid up, PVC Inner sheathed, Armoured with galvanized wire or galvanized steel strip, overall PVC Sheathed, 1100V Grade as per IS 7098(Part 1) 1988 complete laid in trenches / floors / fixed to poles / walls / drawn through pipes etc including provn of lugs, glands, nuts, bolts & washers etc for connecting in LT feeder pillar box / transformer bushings/LT OH Line and testing on completion all as specified and directed by Engineer-in-Charge. Note: Excavation, earth work and provn of cable covers / protection pipe etc shall be measured and paid separately under relevant items of BOQ.
All as per item No. 6.00 here-in-before but of size 500 sqmm, 3.5 core.
All as per item No. 6.00 here-in-before but of size 400 sqmm, 3.5 core.
Excavation in trenches not exceeding 1.5m wide and not exceeding 1.5m depth and getting out in soft/loose soil for laying of cables complete all as specified and directed by Engineer-in-Charge.
Supply and spread M-sand in trenches for cushioning of cable complete all as specified and directed by Engineer-in-Charge. (Note: Punned down thickness only shall be measured for the purpose of payment)
Returning, filling in trenches including spreading, leveling, watering and well ramming in layers not exceeding 25cm complete all as specified and directed by Engineer-in-Charge.
Removing surplus excavated material to a distance not exc 50m and depositing where directed at a level not exceeding 1.5m above the starting point complete all as specified and directed by Engineer-in-Charge.
Supply and lay in trenches, un-reinforced precast concrete cable cover, Class LV, Type I, flat, size 250 mm x 150mm x 40mm for cable protection in trenches complete all as specified and directed by Engineer-in-Charge.
M&L for RCC route marker of size 1200mm x 300mm x 75mm of high compresive strength,durable for outer use for identifying cable route accurately using M-20 aggregate both side yellow painted and written as 11 KV HTUG CABLE by black paint complete as specified and directed by Engr-in-Charge.
Excavation in post holes (or similar holes) each not exc 0.5 Cum, getting out, returning filling in and ramming earth or broken rubble mixed with earth around, in layers not exc 25cm, watering, and removing surplus soil to a distance not exc 50m and making good surface complete in any type of soil.
M&L for PCC 1:3:6 type C2 using 40mm graded stone aggregate as in foundations complete all as specified and directed by Engineer-in-Charge.
stage.html
html • 0.07 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 1.16 MB
BOQ_846719.xls
BOQ • 0.55 MB
TenderDocuments2ndcalltok86.pdf
Tender Documents • 1.30 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .