Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹2.4 LAccepted-AOC A 111 JHILMIL COLONY EAST DELHI 110095 | SHAHDARA | DELHI | 110095 | L1 | Accepted-AOC work order has been awarded |
Tender Value
₹2.1 L
EMD Value
₹4,150
Closing Date
1 Jun 2023, 1:00 pmClosed
EEE-I/SSZ
Room No.5 First Floor Vishwakarma Nagar Near Hanuman Mandir Jhilmil Colony Delhi-110095
Renovation/Rewiring along with installation of 2 Nos. A.C. at administrative block of Slaughter House in ward no. 05E under Shahdara South Zone.
2023_MCD_155204_1
EE (Elect)-I/2023-24/3.1
Open Tender
Electrical Works
Item Rate
60 days
work
Please refer to tender documents
4 documents required · 4 mandatory
₹500
₹4,150
28 Jan 2025
25 May 2023
2 Jun 2023
25 May 2023
1 Jun 2023
25 May 2023
Amount
Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. (Single Pole)
Supplying and fixing following rating, double pole, 240 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required. a. 63Amp.
SITC of 60 Watt LED Flood light luminiare fitted with lens made of pressure die cast aluminium housing & toughened glass cover complete with following specification as reqd. (a) Total System wattage =60 watt ± 5% (b) Luminaire Efficacy ˃= 100 Lm/w (c) Power Factor˃ = 0.95 (d) Protection Class- IP-66
S/I/T/C of LED Tube type luminaire 20 watt rating box type complete with Extruded Aluminium Batten prewired with hgh efficient LEDswith the following: (A) Total system wattage 20 watt+/- 5% (B) Luminous efficacy lumens/watt >=95 (C) Power Factor >=0.95
supply of XLPE Insulated PVC Sheathed Al. Conductor Armoured Cable for working voltage upto 1.1kV confirming to IS-7098(Part-I) of following sizes: a. 2x10 sq. mm
S/I/T/C of 10'(250 mm) sweep Fresh Air fan complete with shutters, blades etc as reqd.
Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on wall surface as required. Up to 35 sq mm (clamped with 1 mm thick saddle)
SITC of 1200 mm sweep BEE 5 star rated AC ceilling with brussless direct current motor, class of insulation:B, 3 nos. blade,30cm down road 2 nos. canopies shackle kit safety ropr,copper winding, power factor not less than .9,service value minimum 6.85,air delivery minimum 215 cmm,350 rpm,THD less than 10%,remote or electrnoic regulator unit for speed control and all remaining accessories including safety pin nuts,bolts,washertemperature rise=75 degree,insulation resistance more than 2 megha ohm,suitable for 230 v,50 hz,single phase ac supply, earthing etc complete as required fan for suitable for 230 V, 50 Hz AC supply.
Wiring for light/ power plug with 2x4 sq.mm FRLS PVC insulated copper conductor single core cable in surface/ recessed steel conduit alongwith 1 No 4 sq.mm FRLS PVC insulated copper conductor single core cable for loop earthing as required.
Wiring for circuit / submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed steel conduit as required. (a) 2x2.5 sq.mm + 1x2.5 sq.mm earth wire
(b) 2x6 sq.mm + 1x6 sq.mm earth wire
Supply of 2.0 Ton Window Air Conditioner (5 Star Rating) along with Copper condensor coil and remote suitable for 230 V electric supply as reqd.
P&F of 4.0 KVA Voltage Stabilizer with TDR and Triple step, High & Low voltage Cutt off device complete as reqd.
Standard Installation charges for Window AC including labour and petty items reqd. for the installation of the same as complete as reqd.
stage.html
html • 0.04 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .