GE AF JAMMU
GE AF JAMMU
REPAIR MAINTENANCE OF APFC PANEL, LT PANEL AND ALLIED WORKS AT AF STN JAMMU UNDER GE (AF) JAMMU
2026_MES_790562_1
CA NO GE/AFJ-63/2026-27
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
JAMMU
Please refer Tender documents.
8 documents required · 8 mandatory
₹500
GE AF JAMMU
₹40,000
Yes
22 Sept 2026
22 Sept 2026
21 Oct 2026
22 Sept 2026
13 Oct 2026
6 Oct 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | Disconnecting / taking down carefully existing unserviceable LT Panel Board any type and capacity including all control switches, fittings and fixtures from different location complete all as specified and as directed by Engineer-in-Charge. | 5 | Each | - | - |
| 2 | Supplying, Installing, Testing and Commissioning Outdoor type Cubical Panel Board outer shell made out of 3.15 mm thick MS sheet including door and inner shell made out of 2.0 mm thick MS sheet and MS angle section 50 x 50 x 6mm mounted on platform of PCC 1:2:4 type B-1, 60 cm above and 45 cm below the ground level, Frame Factory fabricated with front and back openable, double door system and cable alley (Each door hinged with body at three places through weldeding) Lockable / Openable by Keys having chromium plated 19 mm dia fancy lock, “U” type gasket shall be used to make the outer shell completely vermin proof suitable for Three Phase Four Wire 415 Volts, 50 Hz, tested at factory approved from CPRI factory fabricated having modern fabrication and testing process followed by powder coat painting having thickness not less than 100 microns provided with suitable gasket to make it Dust / Vermin Proof and general construction confirming to IS:8623/93 comprising of the following :
(a) Busbar rating 800 Amps Capacity 4 wires fixed on insulator not less than 1.0 mtr long bus bar - 01 Set
(b) Incoming MCCB 630 Amps FP 415 Volts AC with adjustable thermal magnetic trip release 50 KA, Ics=100%, Icu class-2 front face isolation with positive break indication with double break contacts with spreader and phase barrier - 01 Nos.
(c) Outgoing MCCB 250 Amps FP 415 Volts AC with adjustable thermal magnetic trip release 36 KA, Ics=100%, Icu class-2 front face isolation with positive break indication with double break contacts with spreader and phase barrier - 01 Nos.
(d)Outgoing MCCB 200Amps F 415 Volts AC with adjustable thermal magnetic trip release 36 KA,Ics=100%, Icu class-2 front face isolation with (+) break indication with double break contacts with spreader and phase barrier 1 Nos. | 1 | Each | - | - |
| 2.01 | (c) Outgoing MCCB 160 Amps FP 415 Volts AC breaking capacity 25 KA, - 04 Nos
(f) Outgoing MCB FP 100 Amps 'C' curve type with rupturing capacity 16 KA - 02 Nos
(g) Digital Ammeter 0-800 A with Selector Switch - 01 Nos.
(h) Digital Volt meter 0-500 V with Selector Switch - 01 Nos
(j) Indicator Lamp RYB 22.5mm dia LED type 240 Volts AC with holder- 01 Set of Three
(k) CT Coils of suitable ratio - 01 Set
Note:-
The quoted rate shall includes minor items such as lugs, nuts & bolts, washers, top insulators, sleeves, provision of extra holes in bus bar etc.
All internal wiring shall be done with suitable size of PVC insulated solid copper conductor FRLS cable conforming to IS-694.
The bus connection for cable from main bus bar to outgoing MCCB will be connected through suitable rating bus bar strip type duly insulated. | - | - | - | - |
| 3 | Supplying, Installing, Testing and Commissioning Outdoor type Cubical Panel Board outer shell made out of 3.15 mm thick MS sheet including door and inner shell made out of 2.0 mm thick MS sheet and MS angle section 50 x 50 x 6mm mounted on platform of PCC 1:2:4 type B-1, 60 cm above and 45 cm below the ground level, Frame Factory fabricated with front and back openable, double door system and cable alley (Each door hinged with body at three places through weldeding) Lockable / Openable by Keys having chromium plated 19 mm dia fancy lock, “U” type gasket shall be used to make the outer shell completely vermin proof suitable for Three Phase Four Wire 415 Volts, 50 Hz, tested at factory approved from CPRI factory fabricated having modern fabrication and testing process followed by powder coat painting having thickness not less than 100 microns provided with suitable gasket to make it Dust / Vermin Proof and general construction confirming to IS:8623/93 comprising of the following : | 1 | Each | - | - |
| 3.01 | (a) Busbar rating 1200 Amps Capacity 4 wires fixed on insulator not less than 1.0 mtr long bus bar - 01 Set
(b) Incoming ACB 800 Amps FP 415 Volts AC with adjustable thermal magnetic trip release 50 KA, adjustable type front face isolation with positive break indication with ON/OFF/Trip indication with switch along with operating rod complete all acesssories - 01 Nos.
(c) Outgoing MCCB 630 Amps FP 415 Volts AC breaking capacity 50 KA, adjustable type - 01 Nos
(d) Outgoing MCCB 100 Amps FP 415 Volts AC with adjustable thermal magnetic trip release 25 KA - 02 Nos
(e) Outgoing MCB 32 Amps DP 230 Volts AC 10 KA, with -02 Nos
(f) Digital Ammeter 0-1000 A with Selector Switch -01 Nos.
(g) Digital Volt meter 0-500 V with Selector Switch -01 Nos
(h) Indicator Lamp RYB 22.5mm dia LED type 240 Volts AC - 01 Set of Three
(j) CT Coils of suitable ratio - 01 Set
Note:-
The quoted rate shall includes minor items such as lugs, nuts & bolts, washers, top insulators, sleeves, provision of extra holes in bus bar etc.
All internal wiring shall be done with suitable size of PVC insulated solid copper conductor FRLS cable conforming to IS-694.
The bus connection for cable from main bus bar to outgoing MCCB will be connected through suitable rating bus bar strip type duly insulated. | - | - | - | - |
| 4 | Supplying, Installing, Testing and Commissioning Outdoor type Cubical Panel Board outer shell made out of 3.15 mm thick MS sheet including door and inner shell made out of 2.0 mm thick MS sheet and MS angle section 50 x 50 x 6mm mounted on platform of PCC 1:2:4 type B-1, 60 cm above and 45 cm below the ground level, Frame Factory fabricated with front and back openable, double door system and cable alley (Each door hinged with body at three places through weldeding) Lockable / Openable by Keys having chromium plated 19 mm dia fancy lock, “U” type gasket shall be used to make the outer shell completely vermin proof suitable for Three Phase Four Wire 415 Volts, 50 Hz, tested at factory approved from CPRI factory fabricated having modern fabrication and testing process followed by powder coat painting having thickness not less than 100 microns provided with suitable gasket to make it Dust / Vermin Proof and general construction confirming to IS:8623/93 comprising of the following :
(a) Busbar rating 600 Amps Capacity 4 wires fixed on insulator not less than 1.0 mtr long bus bar - 01 Set
(b) Incoming MCCB 400 Amps FP 415 Volts AC breaking capacity 36 KA-1 Nos.
(c) Outgoing MCCB 160 Amps FP 415 Volts AC breaking capacity 36 KA-01 Nos
(d) Outgoing MCCB 125 Amps FP 415 Volts AC breaking capacity 25 KA-03 Nos
Note:-
The quoted rate shall includes minor items such as lugs, nuts & bolts, washers, top insulators, sleeves, provision of extra holes in bus bar etc.
All internal wiring shall be done with suitable size of PVC insulated solid copper conductor FRLS cable conforming to IS-694.
The bus connection for cable from main bus bar to outgoing MCCB will be connected through suitable rating bus bar strip type duly insulated. | 1 | Each | - | - |
| 5 | Supplying, Installing, Testing and Commissioning Outdoor type Cubical Panel Board outer shell made out of 3.15 mm thick MS sheet including door and inner shell made out of 2.0 mm thick MS sheet and MS angle section 50 x 50 x 6mm mounted on platform of PCC 1:2:4 type B-1, 60 cm above and 45 cm below the ground level, Frame Factory fabricated with front and back openable, double door system and cable alley (Each door hinged with body at three places through weldeding) Lockable / Openable by Keys having chromium plated 19 mm dia fancy lock, “U” type gasket shall be used to make the outer shell completely vermin proof suitable for Three Phase Four Wire 415 Volts, 50 Hz, tested at factory approved from CPRI factory fabricated having modern fabrication and testing process followed by powder coat painting having thickness not less than 100 microns provided with suitable gasket to make it Dust / Vermin Proof and general construction confirming to IS:8623/93 comprising of the following :
(a) Busbar rating 600 Amps Capacity 4 wires fixed on insulator not less than 1.0 mtr long bus bar - 01 Set
(b) Incoming MCCB 400 Amps FP 415 Volts AC with adjustable thermal magnetic trip release 50 KA, Ics=100%, Icu class-2 front face isolation with positive break indication with double break contacts with spreader and phase barrier - 01 Nos.
(c) Outgoing MCCB 250 Amps FP 415 Volts AC with adjustable thermal magnetic trip release 36 KA, Ics=100%, Icu class-2 front face isolation with positive break indication with double break contacts with spreader and phase barrier - 01 Nos.
(d) Outgoing MCCB 200 Amps FP 415 Volts AC with adjustable thermal magnetic trip release 36 KA, Ics=100%, Icu class-2 front face isolation with positive break indication with double break contacts with spreader and phase barrier - 01 Nos. | 1 | Each | - | - |
| 5.01 | (e) Outgoing MCCB 160 Amps FP 415 Volts AC breaking capacity 25 KA-01 Nos
(f) Outgoing MCB FP 100 Amps'C' curve type with rupturing capacity 16 KA-1Nos
(g) Digital Ammeter 0-600 A with Selector Switch - 01 Nos.
(h) Digital Volt meter 0-500 V with Selector Switch - 01 Nos
(j) Indicator Lamp RYB 22.5mm dia LED type 240 Volts AC with holder- 01 Set of Three
(k) CT Coils of suitable ratio - 01 Set
Note:-
The quoted rate shall includes minor items such as lugs, nuts & bolts, washers, top insulators, sleeves, provision of extra holes in bus bar etc.
All internal wiring shall be done with suitable size of PVC insulated solid copper conductor FRLS cable conforming to IS-694.
The bus connection for cable from main bus bar to outgoing MCCB will be connected through suitable rating bus bar strip type duly insulated. | - | - | - | - |
| 6 | Supplying, Installing, Testing and Commissioning Outdoor type Cubical Panel Board outer shell made out of 3.15 mm thick MS sheet including door and inner shell made out of 2.0 mm thick MS sheet and MS angle section 50 x 50 x 6mm mounted on platform of PCC 1:2:4 type B-1, 60 cm above and 45 cm below the ground level, Frame Factory fabricated with front and back openable, double door system and cable alley (Each door hinged with body at three places through weldeding) Lockable / Openable by Keys having chromium plated 19 mm dia fancy lock, “U” type gasket shall be used to make the outer shell completely vermin proof suitable for Three Phase Four Wire 415 Volts, 50 Hz, tested at factory approved from CPRI factory fabricated having modern fabrication and testing process followed by powder coat painting having thickness not less than 100 microns provided with suitable gasket to make it Dust / Vermin Proof and general construction confirming to IS:8623/93 comprising of the following :
(a) Busbar rating 200 Amps Capacity 4 wires fixed on insulator not less than 1.0 mtr long bus bar - 01 Set
(b) Incoming MCCB 100 Amps 4 pole 415 Volts AC with thermal magnetic 36 KA, Ics=100%, Icu class-2 front face isolation with positive break indication with double break contacts with spreader and phase barrier all as directed :-1 Nos.
(c) Outgoing MCCB 63 Amps 4 pole 415 Volts AC with thermal magnetic 25 KA, with double break contacts with spreader and phase barrier complete all as directed. -3 Nos
(d) Outgoing MCB 32 Amps 4 pole 415 Volts AC with thermal complete all as directed. -2 Nos
e) Single dial time switch, 65A TP contactor for the automatic switching of luminaries, power tool control with 2 No. 65A contactors and raise lower push button, Incoming 35 sq. mm and out going 25 sq. mm 4 core terminals. - 02 Sets | 1 | Each | - | - |
| 6.01 | (g) Digital Ammeter 0-200 A with Selector Switch - 01 Nos.
(h) Digital Volt meter 0-500 V with Selector Switch - 01 Nos
(j) Indicator Lamp RYB 22.5mm dia LED type 240 Volts AC with holder- 01 Set of Three
(k) CT Coils of suitable ratio - 01 Set
Note:-
The quoted rate shall includes minor items such as lugs, nuts & bolts, washers, top insulators, sleeves, provision of extra holes in bus bar etc.
All internal wiring shall be done with suitable size of PVC insulated solid copper conductor FRLS cable conforming to IS-694.
The bus connection for cable from main bus bar to outgoing MCCB will be connected through suitable rating bus bar strip type duly insulated. | - | - | - | - |
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.54 MB
BOQ_886251.xls
BOQ • 1.16 MB
TendeR63.pdf
Tender Documents • 1.61 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .