Tender Value
₹40.2 L
EMD Value
₹80,400
Closing Date
9 Mar 2026, 2:00 pmClosed
"Electrical General work in connection with - LLH- Extension, Modification and Renovation of Cell Section for POH of LHB and EMU/MEMU coaches and Vande Bharat Trainset at C & W Workshop, Eastern Railway Liluah."
W_LLH_31_2025-26
W_LLH_31_2025-26
Open
12 Months
Howrah, West Bengal
₹0
₹80,400
12 Feb 2026
12 Feb 2026
A-Electrical General work in connection with - LLH- Extension,
Supply of ISI marked Cross Linked Polyethelene ( Metre XLPE ) insulated, PVC outer sheathed, non- magnetic galvanized steel strip armoured, stranded compact circular Aluminium conductor Cable of size 4 core x 35 sq.mm, nominal system Voltage 1100V grade and highest system voltage 1210V conforming to IS 7098 (Part I - 1988 ) with amendment number 1and 2 and 3 Re-affirmed 2005 or with latest amendment. ( Make Of LT Cables: Havells, Polycab, Gloster, KEI Cables, RR kabel). (S= 357.97, L= 0.00) CW-SHOP-LLH-MECHANICAL/EASTERN RLY
Supply of ISI marSupply of ISI marked Cross Metre Linked Polyethelene ( XLPE ) insulated, PVC outer sheathed, non-magnetic galvanized steel strip armoured, stranded compact circular Aluminium conductor Cable of size 4 core x 50 sq.mm, nominal system Voltage 1100V grade and highest system voltage 1210V conforming to IS 7098 (Part I - 1988 ) with amendment number 1and 2 and 3 Re-affirmed 2005 or with latest amendment. ( Make of LT Cables: Havells, Polycab, Gloster, KEI Cables, RR kabel). (S= 369.35, L= 0.00)
Supply of ISI marked Cross Linked Polyethelene ( Metre XLPE ) insulated, PVC outer sheathed, non- magnetic galvanized steel strip armoured, stranded compact circular Aluminium conductor Cable of size 4 core x 185 sq.mm, nominal system Voltage 1100V grade and highest system voltage 1210V conforming to IS 7098 (Part I - 1988 ) with amendment number 1and 2 and 3 Re-affirmed 2005 or with latest amendment. ( Make of LT Cables: Havells, Polycab, Gloster, KEI Cables, RR kabel). (S= 1068.93, L= 0.00)
Laying, commissioning of LT cable 1100V grade of small size (Upto 95 sq mm ) along the wall by necessary clamping arrangement or concealed including making good of wall including socketing and termination with epoxy end jointing where necessary (clamps should be made of 50mmx 6mm MS flat). (S= 69.47, L= 0.00)
Laying, commissioning of LT cable 1100V grade of small size (Above 95 sq mm ) along the wall by necessary clamping arrangement or concealed including making good of wall including socketing and termination with epoxy end jointibg where necessary (clamps should be made of 50mmx 6mm MS flat). (S= 137.32, L= 0.00)
Cutting of concrete and trenching drawing laying Metre and jointing of the 1100V grade cable through underground as per CEE's drawing no.E4/GPST/033/87 and refilling the trench after laying the cable including making good the damages and then smooth flooring and re- concreting (18" wide xmin 3' deep) with cement, sand,& stone chips inratio 1:2:4 and connection with switcher gear along with supply of suitable size gland, socket etc. as required. (S= 471. 60, L= 0.00)
Supply of Straight Through jointing kits (Heat Numbers shrinkable ) suitable for XLPE / PVC insulated stranded Aluminium conductor cable of size 4 / 3.5 x 225-400 sq.mm., 1100V grade complete with all accessories 'including jointing, testing and commissioning. ( Make - 3M,Dension,Raychem). (S= 2909.90, L= 0.00)
Releasing of old, unused LT cables of various Metre s i z e s and electrical fittings or accessories ( C o m p l e t e dis-mentalling of old defective cable/overhead bunch cable from shed/structure/pole/wall along ground/surface/overhead with supportive structure, cutting it into pieces , bunched it , tranportation from site & deposite it to SSE/PH/STORE). (Details as per explanatory notes) (S= 45.68, L= 0.00) Total 738530.60 Item- 2 General Electrical Works CW-SHOP-LLH-MECHANICAL/EASTERN RLY S No. Item Description of Item Unit Qty Rate Amount No
Supply of Dust and vermin proof metal Busbar Numbers Chamber fabricated using sheet steel (CRCA) of 16 SWG ( 1.6mm ) thickness and epoxy powder coated consisting of 4 nos. tinned copper busbar of each bar of capacity 400 Amp, 4/6/8 way, suitable for 415V,50Hz , 35KA Short Circuit withstand Capacity(1Sec.,KA) supply system including all accessories along with fixing,connection, testing and commissioning of incoming and outgoing cables glanding, cable socketing and connection with all suitable a r r a n g e m e n t . (similar to Havells cat, No.:IHBC040006. /IHBC020008) (Conforming to EC-60439/IS-8623 & IEC-60529/IS-2147 (now superseded by IS 13947)) ( Make -Havells /Indo- Asian/ Standard / HPL/ C&S / LK (L&T)). (S= 23417.41, L= 0.00)
Supply of Dust and vermin proof metal Busbar Numbers Chamber fabricated using sheet steel (CRCA) of 16 SWG ( 1.6mm ) thickness and epoxy powder coated consisting of 4nos. tinned copper busbar of each bar of capacity 200 Amp, 4/6/8 way, suitable for 415V,50Hz , 25KA Short Circuit withstand Capacity(1Sec.,KA) supply system including all accessories along with fixing,connection, testing and commissioning of incoming and outgoing cables glanding, cable socketing and connection with all suitable arrangement. (similar to Havells cat, No.: IHBC020006 /IHBC020008) (Conforming to EC- 60439/IS-8623 & IEC-60529/IS-2147 (now superseded by IS 13947)) ( Make -Havells /Indo- Asian/ Standard / HPL/ C&S / LK (L&T) (S= 10704. 62, L= 0.00)
Supply of SPN DB ( Metal Enclosure with Metal Numbers Door ), 10 way, 1Ph,240V, 50Hz, complete with 6 nos. SP MCB of current rating from 6A to32A, 10kA, 240V, 50Hz as per requirement of load and 1 no. DP RCBO of current rating 40A,300mA, 10kA, 230V,50Hz ( Make of MCB, RCBO and Metal Distribution Board - L & T Switchgear (Lauritz Knudsen) / Siemens/ ABB / Legrand / Schneider/ C&S) (MCBs should confirm to IS/IEC 60898-1 or latest & 60947-2 or latest )(RCBO should confirm to IS 12640-2 /IEC 61009-1 or latest) (SPN DB should confirm to IEC 61439-1&3 & IS 8623 -1&3 or latest with CRCE sheet steel,RAL9003,powder coated) (S= 8083.81, L= 0.00)
Fixing , installation ,testing and commissioning of Numbers above SPN MCB DB with suitable arrangement. (S= 0.00, L= 132.98) CW-SHOP-LLH-MECHANICAL/EASTERN RLY
Supply of TPN MCB DB (Heavy duty, Outdoor Numbers type, UV ray protected,self fire-extinguishing and resistant to abnormal heat and fire up to 650 degree C GWT,shock resistance IK10 (20 Joules ) and IP65 degree of protection grade transparent DB box, similar to ABB Mistral65 - 20 Modules or equivalent ), 3Ph, 50Hz,415V, 4 way per phase,415V, 50Hz, complete with total 12 nos. SPMCB of current rating from 6A to 32A, 10 kA,240 Volt, 50Hz per phase as per requirement of load and one no. FP RCBO 63A, 300mA, 10kA, 415V, 50Hz, Suitable for AC + Pulsating DC(Type A) + Harmonics Make of MCB and Metal Distribution Board - L & T Switchgear (Lauritz Knudsen) / Siemens / ABB / Legrand / Schneider / C&S). (RCBO should confirm to IS 12640-2 /IEC 61009-1 or latest) (MCBs should confirm to IS/IEC 60898-1 or latest & 60947-2 or latest ) (TPN DB should confirm to IEC 61439-1&3 & IS 8623 -1&3 or latest with CRCE sheet steel,RAL9003,powder coated). (S= 19377.06, L= 0.00)
Fixing, connection, testing and commissioning of Numbers above panel including all incoming and outgoing cables glanding, cable and connection and construction of concrete foundation or suitable wall hanging arrangement as per site condition with all associated accessories. (S= 0.00, L= 167.48)
Supply commissioning o f 32A, 3-pin, 3 module, 230V, 50Hz and earth metal plug socket in SPN enclosure with SPN MCB (6-32Amp) (accessories a s required at per instalation site condition ) (Metal Plug & Socket should confirm to IS 8623-1 & 3, IEC 61439-1 & 3 latest year) with CRCA sheet steel, RAL9003, powder coated ( Make of Metal Plug & Socket - L & T Switchgear (Lauritz Knudsen) / Siemens/ ABB / Legrand / Schneider/ C&S) (S= 4776.78, L= 0.00)
Supply commissioning of 30/32Amp, 3 Ph, 5 pin , 4 module and earth metal plug socket in TPN enclosure with TP MCB (6-32Amp) (accessories as required at per instalation site condition ) (Metal Plug & Socket should confirm to IS 8623-1 & 3, IEC 61439-1 & 3 latest year) with CRCA sheet steel, RAL9003, powder coated ( Make of Metal Plug & Socket - L & T Switchgear (Lauritz Knudsen) / Siemens/ ABB / Legrand / Schneider/ C&S). (S= 4542.40, L= 0.00)
Supply commissioning of 63 Amp 415v,50Hz, 3 Ph ,5 pin , 4 module and earth metal plug socket in TPN enclosure with TPN MCB (40-63 Amp) (accessories as required at per instalation site condition ) (Metal Plug & Socket should confirm to IS 8623-1 & 3, IEC 61439-1 & 3 latest year) with CRCA sheet steel, RAL9003, powder coated ( Make of Metal Plug & Socket - L & T Switchgear (Lauritz Knudsen) / Siemens/ ABB / Legrand / Schneider/ C&S) (S= 12937.92, L= 0.00) CW-SHOP-LLH-MECHANICAL/EASTERN RLY
Supply commissioning of (200-250 Amp) 415 Volt, 50 Hz,minimum 50KA, 4 pole microprocessor control LT MCCB with inbuilt overload, short circuit and ground fault protection(Ics=Icu=100%),under voltage release with all accessories including Digital type multifunction meter and panel LED indicator light and cable entry box with gland and thimble for connection of cables with SS enclosure and proper fixing arrangement with clamp,(MCCBs should confirm to IEC:60947- 2/IS:13947-2 latest year) ( Make of MCCB- L & T Switchgear (Lauritz Knudsen) / Siemens/ ABB / Legrand / Schneider/ C&S) , (Multi-function Meters make- ABB, Fluke, HTC, Kaycee, L & T Switchgear (Lauritz Knudsen), Motwane, Siemens, Schneider/ C&S), ( CT make L & T Switchgear (Lauritz Knudsen), kappa, SG,AE) Qty=03 nos for each meter. (S= 53011.37, L= 0.00)
Supply commissioning of 415V, 4Pole, 63 Amp Switch disconnector fuse unit conforming to IS/IEC:60947- Part 1 &3 with SS enclosure with Door interlock withTerminal Shrouds on both sides and Phase Barriers included (FN- TPN S-D-F in SS Enclosure : similar to Lauritz Knudsen: Type - FN 63 TPN / FP CE* & Cat. No. - SK90484* ) & proper fixing arrangement on the wall with MS clamps with cable entry box with gland and thimble as necessary for connection of cables with 63 Amp HRC fuse - 04 Nos. (Switchgear Make: Siemens/ ABB/ Schneider/Lauritz Knudsen/ C&S/ Havells/ Legrand)" (S= 4532. 39, L= 0.00)
Supply and installation of GI flat of 50 mm x 6 Kg mm or GI Wire (4 SWG) for earthing arrangement of transformer, HT & LT panel and connection with earth pipe (GI Flat/ Wire to be decided by the EIC) from wall by Gl nut-bolts and washer with support. (S= 97.87, L= 0.00)
Supply of BLDC Wall Mount Air Circulator Fan size Numbers - 30 inch/750 mm sweep, 220-230 Volt AC , 50 H Z (Make- Airzon/Atomberg/Greenberg) (S= 13727. 34, L= 0.00)
Installation, commissioning of single phase 750 mm sweep, 230 Volt AC ,50 HZ BLDC Wall Mount Air Circulator Fan including all accessories and proper fixing arrangements. (S= 1077.31, L= 0.00) CW-SHOP-LLH-MECHANICAL/EASTERN RLY
Wiring of air circulator fan point with 2 nos. PVC Numbers multi strand single core HRFR/FRLSH copper wire 2.5 sq. mm 1100V grade confirming to IS 694/2010 or latest along with earth connection continuity with 1 no. PVC multi starnd single core HRFR/FRLSH copper wire 1.0 sq,mm 1100V grade confirming to IS 694/2010 or latest through GI conduit with GI clarnp/GI nut bolts including all other accessories (The point wiring will be made using modular switchesor MCBrating 6-32 Amp. ( rating as per site requirement) and GI boards ) (Nos. of air circulator fan in each row/ bay should be additionally controlled by 01 no. of SPNDB of suitable rating & techinical sepicification ) (Make of Air circulators: Bajaj, Cromption, EPC, Orient) (Make of Copper conductor wire -Anchor / Havells /Finolex / Gloster / KEI /Polycab / RR Kabel ) (Make of Modular switch,socket, box, cover plate etc. - ABB / Anchor (Panasonic ) / Havells (Crabtree ) / Legrand / LK(L&T) , North West , Schneider , C&S )(GI conduit make- Jindal / TATA / Zenith / Surya Prakash / Lotus / Swastik / Hindustan / Lloyds/ MCC/ AKG / BCC) (S= 650.13, L= 0.00)
Supply of basic material to construct unit Numbers maintenance free earth as per RDSO specs NO.RDSO/SPN/197 Ver. 1.0 or latest and conforming to RDSO Drg No. SDP/RDSO/E&B/001 or latest. Necessary testing Certificate of UL,IEC to be produced. [Numbers = Lot] (S= 15760.07, L= 0.00)
Installation of unit maintenance free earth as Numbers supplied in above item. The installation of this item shall be carried out by the contractor as per RDSO Specs. No. RDSO/SPN/197 Ver. 1.0 or latest and conforming to RDSO Drg No. SDO/RDSO/E&B/001or latest. (S= 5287.77, L= 0.00) CW-SHOP-LLH-MECHANICAL/EASTERN RLY
Supply, commissioning of out door type 70-72 Watt LED street light luminaries with BIS certified driver and luminare, operating voltage of 140-270 Volt having industrial grade constant current driver (minimum driver efficiency of 85%), (LED make - Nichia,Osram, Seoul, Lumileds, Avago, Cree ) complete with all accessories,ingress protection of IP66 (or better), impact protection of IKO7 (or better), minimum system lumen efficacy of 120 Lm/W (or higher), LED life of 50000 burning hours (or greater), pressure die cast aluminium housing, color temperature of 5700K, CRI>=70, THD<=20%, PF> 0.95, SPD>=10KV with Life span of LED chip - Greater than 50000 burnings hours with 60 months warranty including fixing,connection and commissioning of Street Light luminaire with suitable dia heavy gauge GI bend pipe with GI clamps made of GI flat of size 40mm x 6mm and GI nut-bolts on Structure/ Wall/ Pole. DRIVER SAFETY REQUIREMENT STANDARDS :IS 15885-2-13, TEST REPORT TO BE SUBMITTED; DRIVER PERFORMANCE REQUIREMENTS: IS 16104, TEST REPORT TO BE SUBMITTED; PHOTO BIOLOGICAL SAFETY NORMS: IS 16108, TEST CERTIFICATE TO BE SUBMITTED; CERTIFICATION: LM 79 FOR LUMINAIRE SHALL BE PROVIDED FROM MANUFACTURES OWN NABL LAB , LM 80 FOR LED SOURCE i.e; NICHIA/OSRAM/LUMILED/SEOUL/BRIDGELUX 5 YEARS WARRANTY,T21 PROJECTION REPORT,LUMINAIRE & LED DRIVER TYPE TEST CERTIFICATES. ( Make: Philips (Signify) / Havells / Crompton / Bajaj/ Panasonic / Orient) (S= 5083.65, L= 0.00) CW-SHOP-LLH-MECHANICAL/EASTERN RLY
Supply, commissioning of out door type 50W LED Flood light having High-efficiency IP66 LED floodlight with pressure die-cast aluminium housing in rectangle shape and toughened glass in the front. (similar to Orient -SIGMA ULTRA- LFSMU-050-C- V 1 ) with BIS certified driver and luminare, operating voltage of 140-270 Volt having industrial grade constant current driver (minimum driver efficiency of 85%), (LED make - Nichia,Osram, Seoul, Lumileds, Avago, Cree ) complete with all accessories,ingress protection of IP66 (or better), impact protection of IKO7 (or better), minimum system lumen efficacy of 120 Lm/W (or higher), LED life of 50000 burning hours (or greater), pressure die cast aluminium housing, color temperature of 5700K, CRI>=70, THD<=20%, PF> 0.95, SPD>=10KV with Life span of LED chip - Greater than 50000 burnings hours with 60 months warranty including fixing,connection and commissioning of with all other accessories at per site requriment for fixing of light fitting DRIVER SAFETY REQUIREMENT STANDARDS :IS 15885-2-13, TEST REPORT TO BE SUBMITTED; DRIVER PERFORMANCE REQUIREMENTS: IS 16104, TEST REPORT TO BE SUBMITTED; PHOTO BIOLOGICAL SAFETY NORMS: IS 16108, TEST CERTIFICATE TO BE SUBMITTED; CERTIFICATION: LM 79 FOR LUMINAIRE SHALL BE PROVIDED FROM MANUFACTURES OWN NABL LAB , LM 80 FOR LED SOURCE i.e; NICHIA/OSRAM/LUMILED/SEOUL/BRIDGELUX 5 YEARS WARRANTY,T21 PROJECTION REPORT,LUMINAIRE & LED DRIVER TYPE TEST CERTIFICATES. ( Make: Philips (Signify) / Havells / Crompton / Bajaj/ Panasonic / Orient) (S= 3900.00, L= 0.00)
Supply,fixing, commissioning of outdoor type 150 Watt LED Highbay luminaries (lower wattage luminaries can be accepted if total system lumen is >= 22500) with BIS certified driver and luminare,operating voltage of 150-270 Volt having industrial grade constant current potted driver(minimum driver efficiency of 85%), ingress protection of IP65 (or better), impact protection of IK07 (or better),minimum system lumen efficacy of 150Lm/W (or higher), LED life of 50000 burning hours (or greater),pressure die cast aluminium housing, color temperature of 5700K-6500K, CRI>=70,THD<=10%, PF>=0.95,Inbuild Surge Protection 4kv Internal & 10 kv external with all accessories for erection of the same. DRIVER SAFETY REQUIREMENT STANDARDS :IS 15885-2-13, TEST REPORT TO BE SUBMITTED; DRIVER PERFORMANCE REQUIREMENTS: IS 16104, TEST REPORT TO BE SUBMITTED; PHOTO BIOLOGICAL SAFETY NORMS: IS 16108/ IEC 62471, TEST CERTIFICATE TO BE SUBMITTED; CERTIFICATION: LM 79 FOR LUMINAIRE SHALL BE PROVIDED FROM MANUFACTURES OWN NABL LAB , LM 80 FOR LED SOURCE i.e; NICHIA/OSRAM/LUMILED/SEOUL/BRIDGELUX 5 YEARS WARRANTY,T21 PROJECTION REPORT,LUMINAIRE & LED DRIVER TYPE TEST CERTIFICATES. ( Make: Philips (Signify) / Havells / Crompton / Bajaj/ Panasonic / Orient) (S= 7869.20, L= 0.00) CW-SHOP-LLH-MECHANICAL/EASTERN RLY
Wiring of light/fan point with 2 nos. PVC multi Numbers strand single core HRFR/FRLSH copper wire 2.5 sq. mm 1100V grade confirming to IS 694/2010 or latest along with earth connection continuity with 1 no. PVC multi starnd single core HRFR/FRLSH copper wire 1.0 sq,mm 1100V grade confirming to IS 694/2010 or latest through GI conduit with GI clamp/GI nut bolts including all other accessories (The point wiring will be made using modular switches or MCB rating 6-32 Amp. ( rating as per site requirement) and GI boards ) (Nos. of light/ fan in each row/ bay should be additionally controlled by 01 no. of SPNDB of suitable rating & techinical sepicification ) (Make of Copper conductor wire -Anchor / Havells /Finolex / Gloster / KEI /Polycab / RR Kabel ) (Make of Modular switch,socket, box, cover plate etc. - ABB / Anchor (Panasonic ) / Havells (Crabtree ) / Legrand / LK(L&T) , North West , Schneider , C&S ) (GI conduit make- Jindal / TATA / Zenith / Surya Prakash / Lotus / Swastik / Hindustan / Lloyds/ MCC/ AKG / BCC). (S= 1006.23, L= 0.00)
Concealed through PVC conduit / casing with PVC clamp/GI nut bolts of suitable diameter for Submain by two nos. single core HRFR / FRLSH grade, PVC insulated, copper conductor cable of size 6.0 sq.mm., 1100V grade for phase and neutral along with one no. single core HRFR / FRLSH grade,PVC insulated, copper conductor cable of size 2.5 sq.mm., 1100V grade for Earth Continuity conductor including supply of cable, GI box with modular cover plate, PVC conduit with PVC clamp/GI nut bolts including all other accessories and all other associated work along with make good of surface as its original condition. (Make of Copper conductor wire -Anchor / Havells /Finolex / Gloster / KEI /Polycab / RR Kabel ) (Make of Modular switch,socket, box, cover plate etc. - ABB / Anchor (Panasonic ) / Havells (Crabtree ) / Legrand / LK(L&T) , North West , Schneider , C&S ) (GI conduit make- Jindal / TATA / Zenith / Surya Prakash / Lotus / Swastik / Hindustan / Lloyds/ MCC/ AKG / BCC). (S= 227.86, L= 0.00)
Conceal wiring onwall/ceiling/floor through PVC Numbers 175.00 pipe of suitable diameter for Light point /Fan point / Call Bell point/ Indication point / Glow Sign point by two nos.single core, HRFR / FRLSH grade, PVC insulated,copper conductor cable of size 1.5 sq.mm,1100V grade for phase and neutral along with one no. single core,HRFR / FRLSH grade, PVC insulated, copper conductor cable of size1.5 sq.mm., 1100V grade for Earth Continuity Conductor ( ECC ) including supply of cable,GI concealed box with modular cover plate, PVC pipe, junction / circular box, modular switch,ceiling rose and all other associated work along with make good of wall surface as its original condition. (Make of Copper conductor wire -Anchor / Havells /Finolex / Gloster / KEI /Polycab / RR Kabel ) (Make of Modular switch,socket, box, cover plate etc. - ABB / Anchor (Panasonic ) / Havells (Crabtree ) / Legrand / LK(L&T) , North West , Schneider , C&S) (S= 368.05, L= 0.00) CW-SHOP-LLH-MECHANICAL/EASTERN RLY
Conceal wiring onwall/ceiling/floor through PVC Numbers pipe of suitable diameter for 6A/5 pin plug point by two nos. single core, HRFR / FRLS grade, PVC insulated,copper conductor cable of size 1.5 sq.mm,1100V grade for phase and neutral along with one no. single core,HRFR / FRLS grade, PVC insulated, copper onductor cable of size1.5 sq.mm., 1100V grade for Earth Continuity Conductor ( ECC )including supply of cable,GI concealed box with modular cover plate, PVC pipe, junction / circular box, modular switch,modular plug socket and all other associated work along with make good of wall surface as its original condition. (Make of Copper conductor wire -Anchor / Havells /Finolex / Gloster / KEI /Polycab / RR Kabel ) (Make of Modular switch,socket, box, cover plate etc. - ABB / Anchor (Panasonic ) / Havells (Crabtree ) / Legrand / LK(L&T) , North West , Schneider , C&S) (S= 255.49, L= 0.00)
Conceal wiring on wall /ceiling / floor through PVC Numbers pipe of suitable diameter for 16A/6 pin plug point by two nos.single core, HRFR/FRLSH grade, PVC insulated,copper conductor cable of size 4.0 sq.mm.,1100V grade for phase and neutral along with one no. single core,HRFR / FRLS grade, PVC insulated, copper conductor cable of size1.5 sq.mm., 1100V grade for Earth Continuity Conductor ( ECC ) including supply of cable,GI concealed box with modular cover plate, PVC pipe, junction / circular box, modular switch,modular plug socket and all other associated work along with make good of wall surface as its original condition. (Make of Copper conductor wire -Anchor / Havells /Finolex / Gloster / KEI /Polycab / RR Kabel ) (Make of Modular switch,socket, box, cover plate etc. - ABB / Anchor (Panasonic ) / Havells (Crabtree ) / Legrand / LK(L&T) , North West , Schneider , C&S) (S= 467.02, L= 0.00)
Conceal Wiring on wall/ceiling/floor through PVC Numbers pipe of suitable diameter for modular type Computer board with modular type switches, sockets and boards consisting of the following: i) 03 nos. 6 Amp switch (ISI marked), ii) 03 nos.6 Amp shuttered plug socket (ISI marked), iii) 01 no. 16Amp switch (ISI marked), iv)01 no. 16 Amp shuttered plug socket (ISI marked), v) 01 no.16/20 Amp ,B/cap- 10kA ,MCB, vi) 01 no.Indicator.( Red ) by two nos. single core, HRFR / FRLSH grade,PVC insulated, copper conductor cable of size 4.0 sq.mm., 1100V grade for phase and neutral along with one no.single core, HRFR / FRLSH grade, PVC insulated,copper conductor cable of size 2.5 sq.mm.,1100V grade for Earth Conti- nuity Conductor (ECC ) including supply of cable, GI concealed box with modular cover plate,PVC pipe, 'junction /circular box, modular switch, modular plug socket and all other associated work along with make good of wall surface as its original condition. (Make of Copper conductor wire -Anchor / Havells /Finolex / Gloster / KEI /Polycab / RR Kabel ) (Make of Modular switch,socket, box, cover plate etc. - ABB / Anchor (Panasonic ) / Havells (Crabtree ) / Legrand / LK(L&T) , North West , Schneider , C&S) (S= 1373.00, L= 0.00) CW-SHOP-LLH-MECHANICAL/EASTERN RLY
Conceal wiring on wall/ceiling/floor through PVC Numbers pipe of suitable diameter for Window AC/Split AC/ Water Cooler by two nos. single core,HRFR / FRLSH grade, PVC insulated, copper conductor cable of size 4.0 sq.mm, 1100V grade for phase and neutral along with one no. single core, HRFR / FRLSH grade,PVC insulated, copper conductor cable of size 2.5 sq.mm., 1100V grade for Earth Continuity Conductor ( ECC )including supply of cable,GI concealed box with modular cover plate, PVC pipe, junction / circular box, modular switch,ceiling rose and all other associated work along with make good of wall surface as its original condition. (Make of Copper conductor wire -Anchor / Havells /Finolex / Gloster / KEI /Polycab / RR Kabel ) (Make of Modular switch,socket, box, cover plate etc. - ABB / Anchor (Panasonic ) / Havells (Crabtree ) / Legrand / LK(L&T) , North West , Schneider , C&S) (S= 1175.42, L= 0.00)
Supply commissioning of Recess Downlighter 15 Watt LED light fitting with Flicker controlledtechnology (Orient Electric Modelno.- LDRER-15-C-V2-FC or equlivant) (LED make - Nichia,Osram, Seoul, Lumileds, Avago, Cree ) DRIVER SAFETY REQUIREMENT STANDARDS :IS 15885-2-13, TEST REPORT TO BE SUBMITTED; DRIVER PERFORMANCE REQUIREMENTS: IS 16104, TEST REPORT TO BE SUBMITTED; PHOTO BIOLOGICAL SAFETY NORMS: IS 16108, TEST CERTIFICATE TO BE SUBMITTED; CERTIFICATION: LM 79 FOR LUMINAIRE SHALL BE PROVIDED FROM MANUFACTURES OWN NABL LAB , LM 80 FOR LED SOURCE,T21 PROJECTION REPORT,LUMINAIRE & LED DRIVER TYPE TEST CERTIFICATES. ( Make: Philips (Signify) / Havells / Crompton / Bajaj/ Panasonic / Orient) (S= 781.03, L= 0.00)
Supply ,Fixing ,connection , testing and Numbers commissioning of 2ft x 2ft Recess mounted 36 Watt LED light fitting with flicker controlled technology (Orient Electric Model no.- LTRAQ-36- C-FC or equlivant) (LED make - Nichia,Osram, Seoul, Lumileds, Avago, Cree ) DRIVER SAFETY REQUIREMENT STANDARDS :IS 15885-2-13, TEST REPORT TO BE SUBMITTED; DRIVER PERFORMANCE REQUIREMENTS: IS 16104, TEST REPORT TO BE SUBMITTED; PHOTO BIOLOGICAL SAFETY NORMS: IS 16108, TEST CERTIFICATE TO BE SUBMITTED; CERTIFICATION: LM 79 FOR LUMINAIRE SHALL BE PROVIDED FROM MANUFACTURES OWN NABL LAB , LM 80 FOR LED SOURCE,T21 PROJECTION REPORT,LUMINAIRE & LED DRIVER TYPE TEST CERTIFICATES. ( Make: Philips (Signify) / Havells / Crompton / Bajaj/ Panasonic / Orient) (S= 1729.49, L= 0.00)
Supply, o f 450 mm sweep Heavy Duty Single Numbers Phase IP 55 & ISI marked metal exhaust fan with necessary masonry work (Crompton make Cat no. EXHD450-4-1 (450mm 1400 rpm S.Ph.) or similar ) (Make - Havells/Usha/Anchor/Orient/Bajaj/Crompton/EPC) (S= 6799.20, L= 0.00)
Fixing & connection of 450 mm sweep Heavy Numbers Duty Single Phase IP 55 & ISI marked metal e x h a u s t fan with necessary masonry work (Crompton make Cat no. EXHD450-4-1 (450mm 1400 rpm S.Ph.) or similar ) (Make - Havells/Usha/Anchor/Orient/Bajaj/Crompton/EPC) (S= 305.47, L= 0.00) CW-SHOP-LLH-MECHANICAL/EASTERN RLY
Supply, fixing, connection and testing of A.C. Numbers Exhaust Fan, 300 mm sweep, 230V,50 Hz complete with louver and shutter and all a c c e s s o r i e s . (Make - Havells/Usha/Anchor/Orient/Bajaj/Crompton/EPC) (S= 1367.02, L= 0.00)
Supply of LT Wall Mounted/ Floor Mounted Double Numbers Door Cubical Outdoor type Distribution Panel Board made of 14 SWG ( 2mm ) MS sheet duly powdered comprising with the following items for 150 KVA to 180 KVA Load :- a) MCCB, 4 Pole,( 400 )Amp, 415V,50Hz, 50kA, ( Ics =100% Icu )Microprocessor based release similar to iTRP1 type of LK (L&T)-make or equivalent with following features as an incomer :- 1) Adjustable Over Load, 2) Adjustable Short Circuit, 3) Inbuilt Instantaneous protection, 4) Provision of Thermal Memory, 5) Microprocessor protection-based MCCB must have facility of individual 'LSIG' fault indication - 2 nos. b)MCCB, 4 Pole, ( 200 )Amp, 415V, 50Hz, 36kA,( Ics = 100% Icu ) Microprocessor based release similar to iTRP1 type of LK (L&T)-make or equivalent with above mentioned features - 2nos. c) MCCB, 4 Pole,(63- 100 Amp), 415V, 50Hz,36kA,( Ics = 100% Icu ) Microprocessor based release similar to iTRP1 type of LK (L&T)-make or equivalent with above mentioned features - 4nos. d) Tinned Copper Busbar (4 Bar) each of capacity 800 Amps., 415V, 50 Hz.- 1 set. (99.99% p u r i t y ) e) Static Multifunction panel mounting LED Energy Meter suitable for Interrupts, THD, Events (High-Low ), Neutral Current, K Factor - 8nos. CT of suitable ratio for MFM - 24 nos. g) LED indication lamp for 3-Phases for incoming feeders and "ON, OFF &TRIP" indication for all incoming and outgoing feeders - suitable nos. h) Petty Store for control cable, MCBs, gland, socket, fuse, push button, TNC switch, selector switch, rotary handle operating mechanism, spreader terminals, interlocking arrangement, auxiliary contacts, shunt release, terminal blocks & NO/NC relays etc. - 1 job. (S= 472565.18, L= 0.00) Total 3279824.63
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
HTML
nit.pdf
NIT
AnnexureV.pdf
BankGuaranteeBondAnnexure-VIA.pdf
VerificationofContractualStaff.pdf
RBA__48_09052018.pdf
RBA_10_21022018.pdf
Undertaking2022.pdf
TenderForm.pdf
GeneralCompliance2022.pdf
CommercialCompliance2022.pdf
GCCApril-2022.pdf
OnlinePoliceVerification.pdf
ExplanatoryNote1696.pdf
Download all tender documents and submit your bid