Tender Value
₹10.2 Cr
EMD Value
₹8.3 L
Closing Date
24 Nov 2020, 6:00 pmClosed
CE AF BANGALORE
Chief Engineer AF Bangalore No. 2 DC Area MES Road Yeshwantpur Post Bangalore 560022
WORK SERVICES FOR PROVISION OF PERMANENT INFRASTRUCTURE AT AF STATION JALAHALLI AUDITORIUM BUILDING AND COVERED SPACE
2020_MES_360820_1
801403/E8
Open Tender
Civil Works
456 days
GE (I) (P) (AF) JALAHALLI
As per NIT
8 documents required · 8 mandatory
₹3,000
Yes
GE (I) (P) (AF) BANGALORE
₹8.3 L
Yes
24 Dec 2020
14 Jul 2020
25 Nov 2020
14 Jul 2020
24 Nov 2020
10 Nov 2020
14 Jul 2020 - 21 Jul 2020
Amount
Revised BOQ dated 17 Oct 2020
GENERAL SUMMARY NOTE: Schedule ‘A’ Part I to XII are prepriced by MES under Ser No. 2.00 to 13.0. Bidders shall insert their lumpsum amount in the Green coloured field under Col-6 only.
Lumpsum price worked out by the contractor for “Building or works” as listed in Schedule ‘A’ Part–I
Lumpsum price worked out by the contractor for “Site Clearance & Area Development/Retaining wall” as listed in Schedule ‘A’ Part–II
Lumpsum price worked out by the contractor for “Internal Water Supply” as listed in Schedule ‘A’ Part–III
Lumpsum price worked out by the contractor for “Internal Electrification” as listed in Schedule ‘A’ Part–IV
Lumpsum price worked out by the contractor for “Road/Culvert” as listed in Schedule ‘A’ Part–V
Lumpsum price worked out by the contractor for “Area Drainage” as listed in Schedule ‘A’ Part–VI
Lumpsum price worked out by the contractor for “Sewage Disposal as listed in Schedule ‘A’ Part–VII
Lumpsum price worked out by the contractor for “Fencing/Compound wall” as listed in Schedule ‘A’ Part–VIII
Lumpsum price worked out by the contractor for “External Water Supply” as listed in Schedule ‘A’ Part–IX
Lumpsum price worked out by the contractor for “External Electric Supply” as listed in Schedule ‘A’ Part–X
Lumpsum price worked out by the contractor for “Lightning Protection” as listed in Schedule ‘A’ Part–XI
Lumpsum price worked out by the contractor for “Fire Fighting ” as listed in Schedule ‘A’ Part–XII
Sch 'A' Part - XIII: AIR Conditioning Design,supply, installation, testing and commissioning of high efficiency central Chilled water type air conditioning plant of water cooled chiller package type with minimum capacity of 150 TR and 75TR standby (3 units of multi scroll compressor 75 TR each . 2 Units running at a time and one as standby ) comprising of water cooled chillers with scroll compressor working on R-134A / R-410A / R- 407C refrigerant (Green gas), chiller, condenser,chilled water circulation system,condenser water circulation system, refrigerent piping, control valves, cooling tower, air handling units,supply and return air duct, electrical controls& protective systems,winter heating, dust control, humidity control equipments to operate wth 415V, 50Hz, 3phase AC supply. complete for new Auditorium building at AFTC Bangalore for maintaining inside condition air temperature 22 +/- 3 degree centigrade and RH 55 +/- 5 % dust control 10 Micron all as specified and as directed.
Make:- Blue Star/Carrier/York/Trane/Kirloskar
Design conditions required as per User Data sheet: Equipment load : 10.0 KW. Ocupancy :- 620 Persons., No. of air changes: Two per hour, Production of gas : Nil. Acceptance of noise level : Normal. Working hours of equipmet: 24 Hrs
(a). SPECIFICATIONS FOR SCROLL CHILLER PACKAGE UNITS:-
Each chiller package shall be factory built and tested, It shall consists of scroll compressors – motor units of total 75 TR capacity capable of controlling capacity from 25 % to 100%. Water cooled condenser MS shell and copper tube type with openable end plates, Safety Relief valve & Purge Valve etc. chiller with MS shell removable end plates, chiller shall be insulated with 19mm nitrile rubber insulation, segmental baffles and copper tubes , expansion valves as per compressor capacity, copper refrigerant piping and fittings, refrigerant feeding devices, valves, strainer, liquid moisture indicator,integral oil seperator, suction line insulation , first charge of oil and gas, starter panel etc. all the components shall be mounted on a rigid welded steel base frame shall be protected with primary coating.
The base frame shall incorporate suitable provisions for the rigging and handling of the machine during erection. Chillers shall be suitable for indoor installation. The panel shall contain motor starter and shall be suitable for single source power supply. It shall incorporate main disconnect MCCBs/MCBs for individual motors, contactors, over load relays, single phase preventers, under /over voltage trip, on / off push buttons, auxiliary contactors, temperature and current sensors in each phase to protect motor, control cabling from panel to compressors, pumps,CT,AHU, etc. . The control panel shall incorporate an easy-to-use operator interface panel and Shall display all operating and safety codes.
(b). SPECIFICATION FOR CHILLED AND CONDENSER WATER CIRCULATION SYSTEM:-
(i). Chilled water pump 3 Nos (2W+1 S/B) of Energy efficient centrifugal back pullout electric driven pump sets of suitable capacity heavy duty high efficiency complete with bronze impeller antivibration arrangements gland drain connections with base frame complete with all accessories as per OEM for recirculation of chilled water 3 Phase, 415V,50 Hz AC supply as specified.
(ii). Condenser water pump 3 Nos (2W+1 S/B) of Energy efficient centrifugal back pullout electric driven pump sets of suitable capacity heavy duty high efficiency complete with bronze impeller antivibration arrangements gland drain connections complete with all accessories as per OEM for recirculation of cooling water 3 Phase, 415V,50 Hz AC supply as specified.
(iii). Heavy duty butter fly valves( flanged type) , non return valve, y stainer ,Balancing valves,Rubber expansion joints,Flow switch, pressure gauges, temperature gauges at both suction and discharge points for each pump including rubber vibration isolation pads mounted on ISMC frame as per the manufacturer on PCC foundation including all connections all as specified.
(iv). Condenser water piping of MS Class 'B', pipe, welding and fitting of suitable size as per recommendation of manufacturer with non chemical type online water scale preventor of suitable size for interconnecting the cooling tower with condensers and pump complete with all necessary fittings.
(v). Chilled water piping with MS "C"class ERW pipe of suitable diameter including all weldable fittings, butterfly valve, NRV for interconnection between water chiller, chilled water pumps with AHUs, distilled water for chiller line system to prevent scale forming in chiller line, make up chilled water tank of suitable capacity duly insulated, Chilled water piping shall be insulated 50mm thickness and density not less trhan 20 kg/cum th layer of 120 gm/sqm polythene sheet (as vapour barrier) duly reinforced with 26 gauge chicken wire mesh with buffing of all joints and tied down with GI lacing wire and finally finished rigid with 26 guage aluminium foil cladding if laid inside the building, and with cement mortar of 1:3 of 12mm thick if laid in ground or air outside the building complete.
(vi). FRP induced draft counter flow cooling tower circular type suitable for not less than 180TR capacity .Structure should be honey comb (PVC) fill. Fan - Axial flow direct driven fan,Non corrosive. Motor -TEFC,IP-55 suitable for 3P / 50Hz / 415V (Technical Specifications as per the manufacturer) including necessary PCC foundation along with mechanical structure for the base of cooling tower, with suitable PCC/Brick staging water connection to the tank and from tank to cooling tower, electric connection from panel to cooling tower, etc . Minimum two meter all around area of cooling tower and makeup water tank will be provided with PCC with drain arrangement.
( c) . SPECIFICATION FOR AIR HANDLING UNIT AND AIR DUCTS
(i) Two Nos Double skinned construction Air Handling Units (AHU) suitable for chilled water system of minimum capacity 30000 CFM made out of GI sheets, frame vibration pads,chilled water in lets/out lets connctions, controls, horizontal axil flow blowers, chiled water cooling coil with associated controls, filter section with 10 micron HDPE woven meshfilter in aluminium frames etc all as per the site rquirement and all as per the design parameters and as specified, volume control damper, Energy Efficient TEFC Motor (IE2 Series) (IP-55) with class F insulation of suitable capacity and specified makes,The fan section should be mounted on anti vibration pads and free from main structure.
(ii). GI Ducting with necessary insulation non-combustible material with collers, brackets, MS supports,for supply/ return air ducts fixd as per design for Auditorium from AHU with necessary jet type(eye ball type) adjustable diffusers, return air grills, fresh air grills,dampers, plinum etc as per the design. All duct work shall be independently supported from building construction.All supply and return air ducts at AHU room shall be provided with approved make motorised fire dampers of at least 2.0 hour fire rating. The complete supply and return air duct to be insulated.
(iii) External thermal insulation on supply/return air ducts laid outside the conditioned room with aluminium foil faced Nitrile rubber of fire retardant class 'O' type 12mm thick for supply ducts and 9mm thick for return ducts.
(iv) Acoustic lining to the main supply air duct from AHU up to a minimum length of 6 mtrs with 25mm thick of Resin bonded glass wool of density 32 K/cum overlapped with RO tissue, sealing all joints and finally covered with 0.5mm perforated aluminium sheet.
(v) External thermal insulation to supply and retrun air duct laid outside the conditioned space/ room with 50mm thick expanded polystyrene slab (TF quality) of 24 Kg/cum density pasted with hot bitumen after one coat of black paint over duct surface, vapour barrier of 120 gm/sqm polystyrene sheet and finally finished with 26 guage aluminium tape complete to make it weather it weather proof all as specified in particular specification.( The supply air and return air ducts are to be provided externally outside the building).
(vi) One No electronic digital temperature and RH display board fixed in AC Plant room and sensors installed inside the auditorium hall to measure air temperature and RH with necessary switching arrangement.
( d) . SPECIFICATION FOR MAIN CONTROL LT PANEL
Floor type Cubical type IP-54 factory made by manufacturers having type test report of CPRI with suitable aluminium bus bar of adequate capacity for 3 phase, 415 volt, 50 Hz fabricated from 2mm thick CRCA sheet powder coated duly inter connected with all allied accessories as requried complete.
Necessary electric control wiring for running the plant including inter connection and inter locking wiring as per specification by PVC multi core 1.5 sq. mm stranded copper control cable.Status indication (ON/OFF) of each compressors, pumps, AHU, cooling tower, motor and other essential electrical components.
Main incoming MCCB of 400 amps, 4 pole of 50 KA with electronic release. All outgoing MCCBs for Chillers, Pumps, AHUs, cooling tower etc shall be 3 pole thermal magnetic release of suitable capacity.
Fully automatic star delta starters for motor of capacity above 5 HP and DOL starters for motors of capacity 5 HP and below for condenser pumps, chiller pumps, AHU blower motor, and cooling tower fan with necessary interlocking for safe operation of AC plant.
Power cabling of adequate size, rating and sufficient core from LT panel board to electric motors and other electrical equipment such as chiller units, pumps,AHUs. cooling tower with multistranded copper conductor armoured cable laid neatly and in straight line in trenches/wall/ cable trays with necessary saddles and clamps including copper lugs of suitable size and cable glands etc all as specified and as per IE rules and electrical codes.
(e) . SPECIFICATION FOR PAINTING
MS water pipe lines, suction and discharge refrigerant pipe line etc shall be painted as per standard colour code and showing arrow/indicator for flow of water /refrigerant/chilled water. Angle frame works, cooling tower, AHUs etc also shall be painted with two coat of synhetic enamel paint over a coat of red oxide primer as per standard colour code.
(f) DESIGN, EXECUTION AND TESTING
(i). The building drawings will be uploaded along with tender documents.
(iii) The capacity of the plant shall be not less than 150 TR with 75TR stand by, the heat load calculations, design of equipment, AHU DUCTs,Cooiing tower, pump sets, etc to be submitted duly scrutinized by IIT/NIT/IISC within one month after acceptance/before starting of work.
(iv) Manufacturers shall submit Computer generated rating chart for 100%, 75%, 50%, 25% load performance for Specified parameters & also for AHRI condition.
(v) Efficiency of scroll type chiller package shall comply with ECBC norms with power consumption less than 1.00 KW/TR on full or part load.
(vi) The contractor shall submit catalogue indicating model No of unit offered and test certificate indicating power consumption up to 25% of minimum load and 25%, 50%, 75% and 100% load for approval of GE before placing the final order.
(vii) RCC foundation as per manufacturers standards shall be deemed to be included in the rate quoted.
(viii) Contractor shall also submit the following :
(a) Sling pschychometer - 03 Nos, (b) Electronic wall hanging thermameter with RH meter - 03 Nos , (c) Louden meter- 01 No,(d) Anemo meter- 01 No,
(ix) Supply and fix one display board of schematic diagram/ layout of the AC plant drawn on Acrylic white sheet with coloured paints duly marking the details duly fabricated with suitable aluminium frame of not less than 1x1 mtr.
(x) Supply and fixing glow sign board of Central AC plant of size 3000x800x150mm, weather proof made of MS angle 50x50x6mm with white acrylic sheet 2mm thick and writing "Central AC Plant Auditorium ,AFTC" with arial black font with suitable size not exceeding 150mm and mininum size 100mm and provision of 04 Nos of LED tube light 1x20 watt and other accessories and grouting on floor/roof with suitable primary and secondary supports.
(xi) Supply and fix fire point comprising of water (Stored pressure) fire extinguisher (IS : 6234) 9 Ltrs capacity -02 Nos, dry chemmical powder (ABC) extingusiher (IS:2171) 5 kg capacity-02 Nos, light weight squeeze grip type CO2 extinguisher (IS : 2878) 3 Kg capacity- 02 Nos
(x) COP for the chiller package unit shall be above 4.70.
(xi) The contractor should get the plant installed and executed only by any one of the original equipment manufacturers viz Blue Star/Carrier/Voltas with reommended makes of complete components/items. Provision of combination of various items of different manufacturer of above or their recommended makesshall be with prior approvalof GE. The contractor shall intimate the name of OEM namely Voltas/Blue Star/Carrier and submit a certificate from the OEM confirming that the entire AC plant work shall be got executed with their recommended make through them / their accredited agencies, within one month of placement of work order on the contractor.
(xiv) Phase I test shall be 24 hours continuous running test to be carried out by the contractor in presence of the GE / Engineer-in-charge. Phase II Tests shall be 72 hours continuous running tests and shall be carried out when the extreme summer and monsoon conditions in presence of the GE and Officer detailed by the Accepting Officer, within the 12 months period following phase-I test. The artificial load for phase I and phase II shall be provided by the contractor without any extra cost to the department and necessary electric supply will be provided free of cost by department for testing the AC Plant.
(xv) All consumable items including refrigerant, compressor oil, lubricant , etc and other items required such as log sheets, stationery etc shall be provided by the contractor during the mainitenance period.
(xvi) Design and execution of Air Conditioning system shall be carried out as per the following Indian/International codes : (1) ASHRAE (2) ASME (3) ARI (4) AMCA (5) UL181- Factory made Air duct and connectors,(6) UL-555- Fire dampers (7) NFPA 90A- Installation of Air conditioning and ventilation system (8) IS 3615- Glossary of terms used in refrigeration and air conditioning (9) IS325- Three Phase Induction motor (10) IS-1239- Mild steel tubes,tubular and other wrought steel fittings,(11) IS277- Galvanised sheet steel (12) IS655- Metal Air ducts (13) IS3588 - Axial flow fans electric,(14) IS 4894 Centrifugal fan (15) IS659 - Air conditioning safety codes (16) 616- Mechanical refrigeration sefety code (17) NBC- National building code (18) IS 3043 - Code of parctice for earthing (19) ECBC 2007/2009 (20) And any other relevant codes related to Air conditioning.
Sch 'A' Part - XIV: Summer Appliances: Supply , installation and commissioning of water cooler with stainless steel body, electric driven single phase having approx storage capacity of 80 ltrs and nominal cooling capacity of 40 ltr/hr all as directed. Make: As per Annexure.
Supply and fix voltage stablizer for automatic operation/single phase AC supply 230V 50 Hz naturally air cooled indoor type designed for input variation between 170V to 250V with output voltage stablizer at 230V with accuracy of (+) or (-) 2.5% and capacity 1 KVA. Make: V Guard or its equivalent make as per Annexure.
Sch "A" Part - XV : DG Set : Supplying installing testing and commissioning diesel engine driven generating set 415 V, 3 phase, 4 wire as per BS 5514/IS-10002 complete including automatic on main failure (AMF) panel complete with relay for automatic operation on failure, of capacity 400 KVA (Standby duty) at NTP conditions with acoustic enclosure as per latest CPCB emission norms and including PCC foundation of required size ( The drawing & specification for foundation will be submitted by contractor) as recommended by the manufacturer and comprising of the following :-
DIESEL ENGINE :- Multi cylinder, 4 stroke compression ignition, heavy duty, turbocharged and after cooled diesel engine, water cooled with standard integral set mounted radiator system suitable for operation at 50 degree Celsius ambient temperature, A1 class Electronic governing mechanism, all as per BS-5514/IS-3046,1500 RPM, complete with all safety accessories and suitable for generating set application and capable to produce an output of 400 KVA/320 KW from a coupled alternator under NTP conditions, complete with following :-(i) Starting System:- 24 Volts DC electric starter with required batteries and charging alternator, engine wiring harness and sensors as required.
(ii) Fuel System:- Combined unit Injectors, electronic governor & Fuel Actuators with governing capability as per ISO 3046 Class A1 along with sychronous capability, replaceable fuel filter elements with primary filter and water separator, fuel piping complete with integral fuel tank of minimun capacity suitable for 8 hrs running of DG set at full load, provided with drain plug, air vent, inlet & outlet connection, level indicator and provn for cleaning.(iii) Lube Oil System:- Lube oil circulation pump with safety valve, Lub oil filter, Lub oil cooler, Oil filler neck and oil dipstick for measurement, Open crankcase venting system etc.
(iv) Combustion Air System:- Exhaust turbocharger, Charge Air Cooler mounted on engine, exhaust flexible bellows, residential type exhaust silencers and extended silencer pipe of same size up to 3.0 Mtr duly insulated and aluminium cladded as directed.(v) Cooling System:- Gear driven coolant pump required for both Jacket and intercooler along with necessary pipings on the engine. Water Pump should have suitable capacity to circulate cooling water to radiator mounted on the DG Acoustic Enclosure. (vi) Engine Mounting:- Engine mounting bracket with AVM pads mounted below base frame housing engine and alternator.
[b] ALTERNATOR: Self regulated self exited brushless alternator, 415 V, 3 phase, 4 wire, 50 HZ, S1 Duty, 400 KVA/320 KW at 0.8 P.F.,1500 RPM, with voltage variation plus or minus 10% of rated voltage from no-load to full-load, foot mounted, screen protected drip proof type with class 'H' insulation with temperature rise limited to Class 'F', with IP-23 ingress protection, ball/roller bearings at both ends of the alternator shaft, with necessary controls as recommended by the manufacturers, conforming to BS-5000/IS-4772/ IS/IEC 60034-1, capable of supplying unbalanced load with Inbuilt RTD & BTD all as specified.
(i) Engine Control Panel:- Electronic controller for indicating Engine parameters, emergency stop push button, genset monitoring and display of engine-alternator operating parameters and alarms, genset protection against critical operating parameters, automatic start sequence control, acquisition and display of plant-related measuring data, suiatble for communication with an external system with Modbus interface (RS 485 RTU) compatible for SCADA with synchronisation facility to be used in future. Features: Auto and mannual Start/Stop, Easy accessible,Display: Engine Parameters. - RPM, Oil Pressure, Coolant Temperature, Hour Meter, Battery Volts, Battery Charging Voltage, Running Status, Event Recording, Fault Code display.Electrical Parameters: Voltage, Current, Hz, KW, KVA, Pf, kWh and KVAr, Breaker Status. Engine Protection: High / low coolent Temperature, Low Lube oil Pressure, Engine over speed shutdown . Electrical Protection: Overcurrent, short circuit, under/over frequency, under/over voltage.
[c] AMF Panel :- Floor mounted, vertical, totally enclosed cubical with canopy, out door type dust and vermin proof, standard industrial pattern, factory fabricated out of 3.15 mm thick CRCA steel sheet painted with one coat of red oxide primer and two coats of powder coating of approved colour, complete with all mounting structures, insulators, bolts, nuts, washers etc, with necessary control wiring/internal connections with proper size of copper conductor cables / strips, suitable for 3 phase, 4 wire, 50Hz, 415 volts AC system, comprising of microprocessor based AMF relay unit with sensing on mains and DG with necessary protection,
(iii) Acoustic Enclosure:- The engine and alternator will be coupled,aligned and mounted on a specially designed common base frame fabricated from M.S. sheets/channels of suitable cross sectional area and length with bottom drilled holes suitable for and including supplying and fixing anti vibration pads. Outdoor Acoustic enclosure to be provided as per CPCB norms. Acoustic base frame shall be Fabricated using sheet / ISMC Channels with adequate stiffeners for strength. Should be Fabricated with Specially Formed CRCA Sheet metal of 2 mm thick shells with adequate stiffeners for strength. Roof panels designed with slopes to prevent rainwater stagnations and providing Silicon Sealants protects roof joints. Insulation Material should be: Rockwool of 64 KG/M3 density packed in minimum 100 mm thick or more layer panels to achieve suitable noise attenuation. Door Construction should be prefabricated CRCA sheet with double stepped formation.
Doors to be fixed to mainframe by hinges. Suitable sealing given at all the panel joints to avoid the sound & water leakage. the Acoustic Enclosure panels shall be powder coated using minimum of 11 tank process which should include intermediate rinsing modes between each step. (iv) First fill of Pre mix Corrosion inhibitor coolant.(v) First fill of lube oil should be supplied along with DG set.(vi) First set of fuel filter,airfilter,lube oil filters etc. consumables should be part of DG set supply.(vii) Any other devices/accessories required as per latest engineering practices as recommended/supplied by the manufacturers as standard eqpt. (viii) Documents : Two sets of following documents :- Maintenance and operation manuals for engine and alternator, spare parts catalogue, warranty/test certificates, wiring /schematic diagrams of control panels.
Sch 'A' Part - XVI : Fittings, fixtures & Misc. items INTERNALWATER SUPPLY. Supply and fix angle cock cast copper alloy fancy type, chromium plated screwed both ends for GI pipes or for unions and fixed suitable for 15mm dia complete all as specified and as directed. Make; As per Annexure
Supply and fix Health faucet brass chromium plated including 1 M long flexible pipe with flushing nozzle and trigger at one end and brass CP union other end fixed to GI pipe and fixed suitable for 15mm dia complete all as directed. Make; As per Annexure
Supply and fix15mm bore Stop valve, cast copper alloy, chromium plated, fancy type, screwed down high pressure with crutch or butterfly handle (concealed type) screwed both ends for iron pipe all as directed. Make; As per Annexure
Supply and fix 15mm bore two way Bib tap, cast copper alloy, chromium plated with crutch or butterfly handle, screwed down, screwed for iron pipe all as directed. Make; As per Annexure
Road/culvert: Applying evenly using pressure sprayer a priming coat with slow setting bitumen cationic emulsion (SS-1) conforming to IS - 8887/ IS - 217/ASTM D 2397 at 8.5 Kg / 10 Sq m over water bound macadam surfaces all as specified.
Sewage Disposal : Material and Labour for SFRC heavy duty cover of dia 450mm with frame for manhole complete with specifcation as per IS 12592 (2002) comprising high tech concrete, FI 90x 1.35mm thick outer cover, 4mm TMT wire mesh (core wire) with hook 4mm, 10mm TMT bar @ 100mm C/C both ways,16mm TMT bar for flushed handles, RCC M-35 (Design Mix) concrete, outer cover/collar of metal set in CM 1:4 and thickness 90mm all as specified and as directed.
Material and Labour for SFRC heavy duty cover of dia 600mm with frame for manhole complete with specifcation as per IS 12592 (2002) comprising high tech concrete, FI 90x 1.35mm thick outer cover, 4mm TMT wire mesh (core wire) with hook 4mm, 10mm TMT bar @ 100mm C/C both ways,16mm TMT bar for flushed handles, RCC M-35 (Design Mix) concrete, outer cover/collar of metal set in CM 1:4 and thickness 90mm all as specified and as directed.
Supply and fix Rungs made out of MS rod 16mm dia for steps encapsulated with PVC of size 180x270mm . (130mm concealed with concrete and 140mm projected) complete all as shown on drawing and as directed.
Internal Electrification: Sub main wiring complete with four runs of 10 sqmm single core PVC insulated FRLS cable 1100 volts grade, multistranded copper conductor cable with one run of 10 sqmm single core PVC insulated FRLS cable 1100 volts grade, multistranded copper conductor cable as earth continuity conductor, drawn through and including 32 mm dia stove enamelled metal conduit and conduit accessories concealed/ roof/wall all as specified and as directed.
Sub main wiring complete with 2 x 6.0 sqmm single core PVC insulated FRLS cable 1100 volts grade, multistranded copper conductor cable with one run of 6.0 sqmm single core PVC insulated FRLS cable 1100 volts grade, multistranded copper conductor cable as earth continuity conductor, drawn through and 25mm dia of stove enamelled metal conduit and conduit accessories concealed/ roof/wall all as specified and as directed.
Sub main wiring complete with two runs of 4.0 sqmm single core PVC insulated FRLS cable 1100 volts grade, multistranded copper conductor cable with one run of 4 sqmm single core PVC insulated FRLS cable 1100 volts grade, multistranded copper conductor cable as earth continuity conductor, drawn through and including 25mm dia stove enamelled metal conduit and conduit accessories concealed/ roof/wall all as specified and as directed. Notes for items 26 to 28 : 4/2 runs of FRLS cable , two/one run of earth continuity conductor and one run of stove enamelled metal conduit shall be measured as one length.
Supply and fixing blank off modular cover 1 module size complete all as directed.
Supply and fix ceiling surface mounted 2 feet x 2 feet LED down light fitting 36/40 watts with CRCA powder coated housing with high transitivity non yellowing virgin PMMA diffuser, system efficacy at luminary level is ≥ 80 Lumens/watt with a life time of 50000 burning hours as per L70 criteria,total lumens 3200, 6500 color temperature, CRI >80, Power Factor > 0.90, Driver should meet IEC compliant for safety with multi stage high Isolate CC-CV operated driver with voltage variation range - 150 to 270 Volts AC, surge protection of 3 KV, and including connecting up with PVC sheathed 3 core 1.5Sqmm copper conductor flexible wire fixed complete all as directed. Make:- Philips Catalogue No. SM365C LED32-6500 PSU OD WH or Wipro Cat No. CRCO10SO38HP57GLI or Crompton Cat No. LCTLSN-36CDL or its equivalent make as per Annexure.
Supply and fix ceiling recess mounted 2 feet x 2 feet LED down light fitting 36 watts with CRCA powder coated housing , system efficacy at luminary level is ≥ 100 Lumens/watt with a life time of 50000 burning hours as per L70 criteria, 6500K color temperature, total Lumens output 3600, CRI >80, Power Factor > 0.90, Driver should meet IEC compliant for safety with multi stage high Isolate CC-CV operated driver with voltage variation range - 150 to 270 Volts AC, surge protection of 3 KV, and including connecting up with PVC sheathed 3 core 1.5Sqmm copper conductor flexible wire fixed including necessary fixing arrangement from truss complete all as directed. Make: Philips Catalogue No. RC420B LED 35S/86S PSU W60 L60 GM or Wipro Cat No. CRCO10RO38HP57GLI or Crompton Cat No. LCTLRN-30-FO-CDL or its equivalent make as per Annexure.
S & F Step light suitable for auditorium/theatre in indoor application with low glare light LED 2.7 watt,IP67 Protection, system efficacy at luminary level is ≥ 20 Lumens/watt, 3000K color temperature, total Lumens output 55, CRI >80, Power Factor > 0.90, Driver should meet IEC compliant for safety with multi stage high Isolate CC-CV operated driver with voltage variation range - 150 to 270 Volts AC, Surge protection of 3 KV, and including connecting up with PVC sheathed 3 core 1.5Sqmm copper conductor flexible wire fixed complete all as directed. Make:- Wipro Cat No. LT50-050-XXX-30-XX or Phillips Cat part No BWG150 LED 50/WW PSU 220-240VI or its equivalent make as per Annexure.
S & F LED Signage light fittings (EXIT) single sided for auditorium/theatre in indoor application ,2 hrs Battery Backup all as directed . Make:- Bajaj cat no BESL 03LED SSD WBB Red of Bajaj or its equivalent make as per Annexure.
Supply and fix high efficient Recessed mounted round LED downlighter 10/11 Watt, with housing made up of pressure diecast aluminium, Luminaire lumen Output- 1200 lm, CRI>80, color temperature-6500K, IP20, system efficacy at luminarie level ≥ 110 Lumens/watt , 50000 burning hours as per L70 criteria, Driver efficiency>80%, THD<10%, Powerfactor>0.95, Surge protection in CM-2.5 KV, Multistage Isolate CC-CV Operated driver with range 150-270V AC, Safety Extra Low Voltage Safe level<60V DC as per IEC standard including necessary fixing arrangement from truss complete all as directed. Make : Philips Cat No DN296B LED 12S-6500 PSU WH or Havells Cat No. ENDURA NE ODLR 10W LED 857S or Wipro Cat No. LD71-III-SMS65-XX or its equivalent make as per Annexure.
Supply and fixing mirror light of LED Aluminium extruded batten luminaire surface mounted, 2 feet system wattage of 10 Watts with lifetime of 50000 burning hours with 70% of its initial lumen maintained. CRI>80, Power Factor > 0.95, THD< 10%, colour temperature - 6500K,Minimum lumens output 1000, surge protection 3KV in CM, IP-20 protected, meets LED IS specifications, Class - 1, Short circuit and over circuit protection, voltage range - 150 to 270 Volts AC, temperature range 0 to 50 DegreeC, system efficacy at luminarie level ≥ 100 Lumens/watt and including connecting up with PVC sheathed 1.5 sqmm 3 core copper conductor flexible wire from ceiling rose to fitting fixed complete all as directed. Make:- Philips Cat No BN021 LED10S-6500 PSU- GRS1 or Crompto Cat No. LCTL-9-CDL or Havells Cat No. LUMLINEBS9WLED-8655PCWH or its equivalent make as per Annexure.
Supply and fixing of LED batten luminaire surface mounted, aluminium extruded body,4 feet system wattage of 20 Watts with lifetime of 50000 burning hours with L70 criteria,Minimum lumens output 2400 , CRI>80, Power Factor > 0.95, THD< 10%, Minimum colour temperature - 5700K, surge protection 3KV in CM, IP-20 protected, meets LED IS specifications, Class - 1, SDCM<5, Short circuit and over circuit protection, voltage range - 140 to 270 Volts AC, temperature range 0 to 50 Degree C, system efficacy at luminarie level ≥ 120 Lumens/watt and including connecting up with PVC sheathed 1.5 sqmm 3 core copper conductor flexible wire from ceiling rose to fitting fixed complete all as directed. Make :- Bajaj Cat Part No.BLTRU nxt SP 24L WH PC or Wipro Cat No. LM34-251 XXX 57DDGI or Philips Cat No. BN150WLED2056500PSCDDGR or Havells Cat No. ENDURALINEOBS20WLED830SPCWH or its equivalent make as per Annexure.
Supply and Fixing 20W High efficient LED Building Security light fitting around the building, Aluminium pressure Die cast housing with pure polyester powder coated for long life, High purity lenses for superior performance, IP66 protection, Suitable for external pipe dia Up to 40 mm, with Luminiare efficacy >95 lm/W, driver Voltage range 150-270V AC, temperature range- 0 to 50DegC, Driver efficiency > 85%, Power factor > 0.95, THD<10%, CRI >70, Colour Temperature- 5700K, ,Surge protection from overvoltage- 3.5KV in CM, Safety Extra Low Voltage Safe level<60V DC as per IEC standard, 50000 burning hours as per L70 Criteria, including provision of 40mm dia GI light grade pipe1.2 mtr length bend to shape and necessary clamps etc for fixing the light fittings on wall fixed complete all as directed. Make: Philips of Catalogue No. BRP022 LED 20 CW MR S1 PSU or Crompton Cat No. LST20CDL or Havells Cat No. ENDURAPEARLSL20WLED757SASYTDPC or its equivalent make as per Annexure.
Supply and fix Extruded aluminium LED batten suitable for indoor application 18-20 watt , 4 feet complete including fixing arrangement to fix on steel truss all as directed . Make : Philips cat No. BN021C LED 20S PSU CW GR S2 HSN code 9405 or Havells cat Enduralinea NE0BS20W LED 8655POLOH or Wipro cat No. LM 34-501-xxx2765 or its equivalent make as per Annexure.
Note for items 30 to 38 : (i) Refer Annexure 'V' for the instructions to be followed for LED fittings. (ii) The contractor shall submit warranty certificate from manufacturer for both light and driver.
Supply , hanging and connecting up energy efficient, five star rated as per latest BEE norms, ceiling fan of size 1200mm sweep complete with down rod including provision of flexible copper cable 3 core of size 0.5 sqmm, including writing MES No 2cm height with synthetic enamel black paint complete all as directed . Make: As per Annexure. Note- The contractor shall submit warranty certificate from manufacturer for ceiling fan .
Supply and fix and connecting up Heavy duty Exhaust fan of size 300mm sweep, Minimum air delivery 1275 CMH, max power consumption 55W including louvers complete,with cable 3 core of size 0.5 sqmm from ceiling rose to fan, including writing MES No 2cm height with synthetic enamel black paint all as directed . Make: As per Annexure. Note- The contractor shall submit warranty certificate from manufacturer for Exhaust fan .
Supply and fix and connecting up Wall mounted Air Circulator of size 450 mm sweep ,Minimum air delivery 125CMM, Max power consumption 100 W, metal blades with pull cord mechanism for speed control complete with necessary fixing arrangement on acoustic panelled wall with suitable nut, bolts etc including writing MES No 2 cm height with synthetic enamel black paint complete all as directed. Make:As per Annexure. Note- The contractor shall submit warranty certificate from manufacturer for Wall mounting fan .
Supply and fix MCCB DB VTPN 4 way double door 415 V AC 50Hz with for MCCB FP as incomer and TP,SP MCBs as out going with integrated door earhting system, tinned copper bus bar ,neutral link, earth link complete all as directed. Make:- Legrand, Cat No - 507745 or its equivalent make as per Annexure.
Supply and fix MCB DB VTPN 4 way double door,IP43, 415 V AC 50Hz with for MCB FP as incomer and SP MCBs as out going with integrated door earhting system, tinned copper bus bar ,neutral link, earth link complete all as direcxted. Make:- Legrand, Cat No - 507725 or its equivalent make as per Annexure.
Supply and fix MCB DB SPN 4 way Horizontal, IP - 43 Protection double door 240 V AC 50Hz with for MCB DP as incomer and DP/SP MCBs as out going with integrated door earhting system,with tinned copper bus bar ,neutral link earth link complete all as directed.. Make- Legrand cat No 507610 or its equivalent make as per Annexure.
Supply and fix MCB DB SPN 8 way Horizontal, IP - 43 Protection double door 240 V AC 50Hz with for MCB DP as incomer and DP/SP MCBs as out going with integrated door earhting system, with tinned copper bus bar ,neutral link earth link complete all as directed. Make: Legrand cat No 507611 or its equivalent make as per Annexure.
Supply and fix MCB DB SPN 12 way Horizontal, IP - 43 Protection double door 240 V AC 50Hz with for MCB SPN as incomer and DP/SP MCBs as out going, with integrated door earhting system ,with tinned copper bus bar ,neutral link earth link complete all as directed. Make- Legrand cat No 507612 or its equivalent make as per Annexure.
Supply and fix MCB SP 6 to 32 Amps 240 volts 10 KA 50 HZ, C curve,Integrated level holder,colour coded on/off indication complete all as directed. Make- Legrand cat No 408587 to 408595 or its equivalent make as per Annexure.
Supply and fix MCB SPN 6 to 32 Amps 240 volts 10 KA 50 HZ, C curve,Integrated level holder,colour coded on/off indication complete all as directed. Make- Legrand cat No 408617 or its equivalent make as per Annexure.
Supply and fix MCB DP 6 to 32 Amps 240 volts 10 KA 50 HZ, C curve ,Integrated level holder,colour coded on/off indication complete all as directed. Make- Legrand cat No 408628 to 408636 or its equivalent make as per Annexure.
Supply and fix RCBO two pole, 2 module, 300mA, 40 amps 240 volts 10 KA 50 HZ, C curve ,Integrated level holder,colour coded on/off indication complete all as directed. Make- Schneider Cat No. A9N1962 or its equivalent make as per Annexure.
Supply and fix MCB FP 40 to 63 Amps 240 volts 10 KA 50 HZ, C curve ,Integrated level holder,colour coded on/off indication complete all as directed. Make- Legrand cat No 408700 to 408702 or its equivalent make as per Annexure.
Supply and fix MCB DP 40 to 63 Amps including MCB DB SPN 4 Way,double door,IP 43 protected suitable for flush mounting controlling step light, stage light and exit light complete all as directed. Make: As per annexure .
Supply and fix MCCB FP 125 Amps, 415 volts, 25 KA 50 HZ with adjustable thermal and magnetic setting complete all as directed . Make-Legrand Cat No 420056 or its equivalent make as per Annexure.
Wiring with 1.5 sqmm single core PVC insulated FRLScable 1100 volts grade with copper conductor drawn in and including stove enamelled conduit and all conduit accessories ( concealed) and including provision of 1.5 sqmm PVC insulated copper cable FRLS as earth continuity conductor fabricated branded Modular metal flush box 1.2mm thick concealed in walls with Modular inner metallic frame with outer cover for exit lights of seven numbers including one 15amps switches all as directed.
Wiring with 1.5 sqmm single core PVC insulated FRLS cable 1100 volts grade with copper conductor drawn in and including stove enamelled conduit and all conduit accessories ( concealed) and including provision of 1.5 sqmm PVC insulated copper cable FRLS as earth continuity conductor fabricated branded Modular metal flush box 1.2mm thick concealed in walls with Modular inner metallic frame with outer cover for step lights 64 numbers including one 15amps switch controlled for 8 number step light each all as directed.
Earthing complete with galvanised steel earth plate electrode 600 x 600 x 6mm thick buried in ground vertically to a depth not less than 2.25m below ground level with top edge of the earth plate not less than 1.5m below normal ground level, connected to galvanised earth lead wire 4.00mm GI earth continuity conductor including 15 mm bore pipe Light grade for protection of lead by means of bolts, nuts, check nuts and washers made out of galvanised iron or steel connected to maint switch control board upto 7.5 mt away from earth electrode all as shown as per plate No 03 of SSR part - I including necessary earth work, PCC 1:3:6 type C1 chamber, RCC cover slab of 50 mm thick 1:2:4 with 8 mm CTD 140 mm C/C with suitable handle, name plate, watering pipe 20 mm dia medium grade pipe with funnel, charcoal, salt and testing on completion and including taking out old unserviceable earthing with connected items all as directed. (int. electric supply - 3, Ext. electric supply - )
External Water Supply: Supply and lay in trench DI pipe ISI marked, spigot socketed including ISI marked tyton joints of suitable specials, class K-9 complete of 100mm dia all as directed. Note: Earth work excavation ,RF& R and removal shall be measured and paid seperately vide relevant items of Sch 'A' Part-IX.
DI pipe fittings complete like Tee, bend, tapper reducer tail piece, connection piece etc suitable for flanged / socket and spigot ended pipe of size upto 150 mm bore all as directed
Cutting road / foot path in a depth not more than 0.60 Mtr and a width not less than 0.40 Mtr for laying pipe line and getting out and returning filling, well ramming in layers and making good and matching with the exiisting surfaces after laying of pipe all as directed.
External Electric Supply: Returning and filling of trenches in two parts (i) using riddled soil obtain from excavated soil upto depth of 30cm (8cm below cable and remaining above cable) for cushioning of cable and (ii) refilling the trench of remaining depth with normal excavated soil all as specified and directed. Note: - Excavated soil shall be riddled by using sieve to separate composite particles etc as per IS 1255-1983 and refilling in trenches as in cable cushioning.
Supply and fix FRP cable looping boxes with PVC sheet finish inside including MCB SP 6 amps-1 No, heavy duty PVC connector 4 way terminal strip 1 No and fixed to pole with suitable size clamp with nuts, bolts complete all as directed.
Supply and fix LED street light fitting 45W, edge LED pressure die-cast housing, toughened glass with secondary optics and IP 66 protection with complete fixing arrangement all as directed. Make: Bajaj code No. 169931 luminaire type BRTFG 45W LED or Crompton Cat No. LSTP-45-CDL or its equivalent make as per Annexure.
Supply and fix LED Post top lantern 45 watts made in die-cast aluminium with innovative glare free indirect lighting distribution and IP 65 protection with complete fixing arrangement all as directed. Make: Bajaj code No. 111713 luminaire type BRIL 45W LED NW or its equivalent make as per Annexure.
Supply and fix bracket made out of GI tubing medium grade 40mm bore, 90cm long including MS clamps made out of 25x6mm, nuts, bolts,washers etc and including fixed to the tubular post , applying two coats of aluminium paint over a coat of primer complete all as directed.
Supply and fix of 2 runs of PVC insulated 2.5sqmm single core multistranded copper conductor cable and one run of 2.5sqmm copper wire as earth continuity conductor drawn through poles and connecting up all as directed. Note: Two runs of cable and one run of earth wire shall be measured as one length.
M & L earthing complete with galvanised steel earth plate electode 600 x 600 x 6 mm thick burried directly in ground earth pit not less than 2.25 mtr deep below ground level connected to & including galvanised iron strip 32 x 6 mm as earthing lead by means of nuts, bolts, check nuts and washers of galvanised iron, passing throgh protection pipe of 40 mm dia light grade GI pipe all as shown in electrical plate Nos 3 of SSR Part - I and connected to machinery/equipment complete including testing filling of adquate quantity of charcoal dust and common salt including excavation and refilling earth and removal of surplus soil upto 50 mtrs and PCC 1:3:6 type CI chamber, precast RCC cover 50 mm thick reinforced with 8 mm dia MS bar 3 Nos both way with handle made out of MS rod 12 mm dia and watering pipe 20 mm dia light grade with funnel, wire mesh etc and connecting and testing complete all as specified and directed.
Supply, install, testing & commissioning of ring main unit (RMU ) 11 KV 630 A 21 KA for 3 seconds, 3 phase 50 Hz outdoor type with canopy, extendable type free standing single break with HRC fuse, trip mechanism & earth switches consisting of 2 Nos load break switch of cap 630 Amps,12 KV with mech. interlock including Short Circuit and Earth Fault Indicator type EKL-8000 Capacitive voltage indication fixed type VPIS 9-15 kV as INCOMMER and 4 Nos fixed type (non draw out type) 630 Amps, 20 KA VCB as OUTGOING consisting of three position isolator/earthing switch, busbars, interlocking, earthbar and stored spring energy mechanism (EL2--mech.).with Microprocessor base Numerical type self powered relays with O/C and E/F protection .
Supply, install, testing and commissioning of out door type, step down transformer of 11 KV /433 V volts (at no load) AC 3 phase, 50 Hz, 400 KVA capacity, copper wound, oil immersed, naturally air cooled, oil natural - air natural (ON-AN) with external cooling tubes, delta connected on primary side (HV) and star connected on secondary (LV) side in accordance with vector group. (DYN) with neutral brought on secondary (LV) side and having +5 to -10% on HV side to be changed by means of hand operated OFF load tap changer gear. The maximum temperature rise should not exceed 45 degree celcious in oil and 55 degree celcious in HV/LV winding when measured by resistance method after continuous full load run on and ambient temperature of 40 degree celcious. The Transformer shall be as per IS - 1180 Part I - 2014 with Energy Efficiency Level-2 and comprising the following:-
(a) HT side consisting of three Nos porcelain bushing with copper rods, complete with nuts and washers, with cable box suitable for reception/taking out of 03 core HT 11000 volts grade PVC / XLPE insulated sheathed heavy duty, armoured cables all as specified. (b) LT side (secondary side) consisting of four Nos porcelain bushing with copper rods, complete with nuts and washers, with cable glands suitable for reception/taking out of 04 Nos single / 3.5 core of LT 1100 volts grade PVC / XLPE insulated sheathed heavy duty, armoured cables of suitable size all as specified. (c ) Oil conservator with filler cap and oil level guage. (d) De- hydrating breather with first fill dehydrating agent (Silca gel)
(e) Expolsive vent, Thermometer socket on tank cover, oil drain valve, lifting lugs and four plain solid cast steel detachable rollers.(f) One No 100 mm dia, dial type thermometer vapour pressure type, having range 0 - 120 degree celsius. (g) Two earthing terminal on tank cover to facilitate fixing of 32 x 6 mm galvanised iron earth strip for earthing of body. (h) Rating data and terminal marking plate.(j) Extra bushing for neutral, in the LT cable box providing independent earthing for neutral. (k) First filling or new and unused transformer oil, IS - 335/93 (Fourt revision marked (Make Savita / power Link) filtered and tested upto 60 KV dielectric strength at 2.5 mm air gap between testing electrodes.Note: (i) Construction of platform for transformer of size 1.80 x 1.80 x 1.50 Mtr as directed is deemed fit in above rate (ii) Certification of dielectric strength shall be submitted by the contractor after filling the oil.
M&L for expulsion fuse unit single pole with fuse barrel suitable for HT 11 KV out door installation mounted on steel frame, with rating upto 100 Amps all as directed .
Supply and fix wiring with three core 1.5 Sqmm PVC insulated FRLS cable with multistranded copper conductor, 1100 volts grade drawn though street light pole from loop in loop out box to street light fittings all as directed.
Supply and fix Loop-in Loop-out weather proof junction box of external size 230x170x105 mm made out of hot press moulded SMC with hinged door duly fitted with 1 No MCB SP 6 Amps, 1 No 4 pole connector 63 Amps with suitable gland and MS/Aluminium fixing clamps of 25x3mm size with nuts bolts & washers complete all as specified and as directed. Make: Sintex Model No. GSJB-2014 or equivalent in Hansu/Hensel
Supply and fixing 16 metre galvanized high mast suitable for 6 Nos lantern symmetrically fitted and having three point suspension system with stainless steel wire rope of grade 316/304 of 7/19 (6/19 WSC) construction and double drum winch and head mast fitted with luminaire mounting arms and carriage fabricated from ERW pipe for fixing 06 Nos integral type LED flood light fittings, pully assembly, single LED aviation obstruction light, lightining arrester spike, multi core flexible power cables for power supply to lantern carriage with suitable electrical control panel having elcetronic time switch with all accessories and 2 Nos pipe earthing for high mast/panel, including RCC foundation as per manufacturer's specification with foundation bolt set comprises anchor plate with high tensile studs complete all as specified and directed by Engr-in-Charge. [Note: LED flood light fittings shall be measured and paid seperately under relevant item here in after. Make: As per Annexure.
Supply and fix LED flood light fitting 150W with IP 66 protection for high mast including electric connection from terminal box to light fitting with suitable size 3 core PVC insulated copper wire complete all as directed. Make - As per Annexure.
Supply & fixing LED street light fitting with pressure die cast aluminium housing and has lenses specially designed for street lighting with a system wattage of 45 W, with a system level efficiency of greater than 100 Lum/W and a minimum lumen output of 4500 lumens with a corelated color temprature of around 5700K with IP 66 protection. It has an electronic driver complaint to IEC safety standards with a voltage variation range of 120-270V and power factor <0.90, high and low protection along with surge protection of minimum 5 KV including 40 mm bore light grade GI pipe bracket 1.20 Mtr long bent to shape with 2 Nos MS flat iron clamps of 40 x 6 mm size with nuts and bolts etc duly painted complete all as directed. Make - Wipro Cat No. LR02-501-XXX-57-XX or Crompton Greaves Cat No. LSTP-45-CDL or its equivqlent make as per Annexure. Note for items 73 to 75: Refer Annexure 'V' for the instructions to be followed for LED fittings.
Supply ,install,test and commissioning of HT load break switch out door type dust and vermin proof CPRI type tested HT 11 KV triple pole load break switch 630A, 21KA for 3 seconds, spring assited handle operated with quick break contacts with earth switch and interlock, as per IS- 9920, IFC 265. having HRC fuse of suitable rating which having access to the HT fuse chamber possible only after surtching OFF (BS) confirm to IP 55 as per IEC 60947 -1- 2004 all as directed . Make; As per Annexure
Supply install test and commissioning of contactor switched APFC panel 3 phase 50 HZ AC supply to achieve unit PF micro processed based relays with metering panel compartmentalized outdoor type fabricated from 3.15 mm thick CRCA sheet with canopy duly powder coated with APFC relay and heavy duty resin filled capacitor, metalized poly prosylene type-S (MPP-S) for 3 phase 440V & 50Hz system for permissible non-linear load 10% of capacity with suitable MCCB 4 pole as incommer for 60 KVAR capacity with capacitor bank of 2x20 KVAR + 1x10 KVAR + 2x5 KVAR complete all prewired including necessary load sencing CT and control wiring all as directed. Make : As per Annexure
Disconnecting and taking down carefully underground cable 11 KV of size upto 185 Sqmm 3 core from trench/loop and relaying and making necessary connection to RMU including necessary excavation and earth work all as directed.
FIRE FIGHTING: Supplying, installing, testing and commissioning of electric driven centrifugal pump set (Terrace pump) TEFC type having discharge of 900 LPM (As per NVC Cat D2 Bldg) (Ltrs per min) at 40m head, 2900 RPM with bronze impeller, driven by induction motor AC, 3 Phase 400/440 Volts 50 Hz, suitable for automatic operation on pressure drop principle complete including necessary foundation for the pump set connecting to suction and delivery pipes etc complete with the following accessories :-
(a) Motor control panel consisting of MCCB 4 pole 63Amps as incomer and star delta starter of suitable capacity for the motor including arrangement for automatic operation of the pump set on pressure drop and stopping the pump by push button at panel board located in ground floor and connecting up the motor with suitable size PVC sheathed copper conductor cable drawn through suitable size PVC conduit all prewired and as directed - 01 Set
(b) Common base plate for electric motor and Pump – 01 No.(c) Gun metal check valve of suitable size for delivery side - 01 No. (d) Earth connection to the pump set with earthing lead of 8 SWG GI conductor two runs from pump set to panel board and connecting to earth dolly. (e) Pump manifold consisting of suitable universal type pressure switch- 1 No, Pressure gauge 0-140 PSI - 1 No, Gate/globe valve - 1No, Needle valve - 1 No and 25 mm piping as required.
M & L for painting with anticorrosive bituminous paint and wraping with pipe kote material 2.0 mm thickness on burried portion of the under ground yard piping of 100 mm bore all as directed.
Supply install testing and commissioning of analogue addresable type control relay module for AHU with UL based integration all as directed. Make : Honeywell/System sensor/Spencers
Supply and laying 2 Core 1.5 Sqmm copper cable shield sheathed twisted pair FRLS, HFC wires each core insulated with FRLS sheathed complete through and including stove enamelled metal conduit 20mm dia fixed/concealed in walls, ceilings etc all as directed.
Supply install testing and commissioning of sprinkler annunciation control panel with audio visual indications, relay logic type complete with water release module and Auto / Manual release mode, auto with built in timer (settable) & emergency manual over ride switch Make : Honeywell/System sensor/Spencers.
Supply and laying 2 Core 1.5 Sqmm copper FRLS cable armoured complete fixed in walls, ceilings etc all as directed.
Supply and fixing in position the following type of sign boards made out of 3.00 mm thick "Opaque" PVC foam board with computer cut, PVC non reflective self adhesive vinyl painted foam board complete with mirror fasteners all as directed. [a] Floor identification signage of size 15 CM x 60 CM (GROUND FLOOR… etc) at each stair case enclosure on every floor, indicating the floor number in words, with lettering size 7.5 CM with contrasting colour from back ground.
Supply and fixing in position the signages "FIRE ORDER" boards 3' x 4' size made out of 3.00 mm thick "Opaque" PVC foam board with computer cut, PVC non reflective self adhesive vinyl painted foam board complete with the following text all as directed. [A] ALERT THE SECURITY AT SECURITY ROOM BY ACTUATING MANUAL CALL POINT LOCATED AT STRATEGIC LOCATIONS.[B] EVACUATE THE OCCUPANTS BY USING FIRE EXITS AND EMERGENCY EXITS ONLY AND ASSEMBLE AT VARIOUS ASSEMBLY POINTS.
[C] IF POSSIBLE TRY TO EXTINGUISH THE FIRE BY USING NEAREST / SUITABLE PORTBLE EXTINGUISHER OR WATER FROM NEAREST WET RISER.[D] BE CALM AND DO NOT GIVE ANY ROOM FOR PANIC, WALK, DO NOT RUN.[E] IF YOU ENCOUNTER SERIOUS DIFFICULTY IN EVACUATION, LIE DOWN FLAT AND TRY TO ATTRACT ATTENTION OF RESCUE TEAM.
Supply and fixing in position the signages "FIRE ORDER" boards 3' x 4' size made out of 3.00 mm thick "Opaque" PVC foam board with computer cut, PVC non reflective self adhesive vinyl painted foam board complete with the following text all as directed. ACTION BY SECURITY / RECEPTION UPON RECEIPT OF INFORMATION THROUGH FIRE ALARM OR FIRE DETECTORS OR BY USING PUBLIC ADDRESS SYSTEM. [A] ALERT THE OCCUPANTS BY USING PUBLIC ADDRESS SYSTEM
[B] INFORM FIRE CONTROL THROUGH ANY ONE OF THE FOLLOWING PHONE NUMBERS:---------------- (Current phone numbers to be provided in this location by the contractor). [C] REFER EVACUATION PLAN FROM EVACUATING STANDARD PEOPLE. [D] GUIDE THE FIRE FORCE, ON THEIR ARRIVAL TO THE SEAT OF FIRE. [E] IN CASE OF THE CASUALTIES, CALL AMBULANCE BY DIALLING NUMBER ------------------ (Current phone numbers to be provided in this location by the contractor)
[F] FIRE FIGHTING AGENCY: PHONE : -------------------- (Current phone numbers to be provided in this location by the contractor). FAX : --------------------- (Current Fax numbers to be provided in this location by the contractor)
Supply and fixing in position assemblypoint signage of size 600 x 400 mm made out of 3.00 mm thick "Opaque" PVC foam board with computer cut, PVC non reflective self adhesive vinyl painted foam board complete with mirror fasteners all as directed
Schedule ‘A’ Part – XVII : CHAIR AUDITORIUM : Supply and fixing Auditorium chair with cup holders (GLAMOUR), Model 2751, size 64cm (54.60 c/c)(L)x67.50cm (D)x107cm(H) LN code 56112101SD00231, HSN code: 94017100 of make Godrej all as specified as under and as directed: SEAT REST ASSEMBLY: The seat rest assembly should be 1.2±0.1 cm thk. flat plywood in-situ moulded with polyurethane foam & upholstered with 3 layered foam laminated fabric and injection moulded cover. The seat should be auto tip-up type and folds when not in use.The Seat profile should be developed to help the users to get necessary comfort in popliteal region. SEAT SIZE: 45.0 cm. (W) x 48.5 cm (D) x 14. 5 cm (T) approximately.
BACKREST ASSEMBLY: The backrest assembly should be made up of 1. 2±0 .1cm thick flat plywood upholstered with 3 layered foam laminated fabric and injection moulded back cover The back foam should be designed with contoured lumbar support for extra comfort. BACK SIZE: 47.50 cm (W) x 80.0 cm (H) x 12. 5 cm (T) approximately. POLYURETHANE FOAM: The polyurethane foam for Seat and Back should be moulded with Density = 48 +1- 2kgs/m3. LEG FRAME ASSEMBLY: The leg frame assembly should be fabricated from M S. tube 6.0±0.03cm x 4. 0±0. 03cm x 0.2±0.016cm thick welded with grouting member. It should be black powder coated ( DFT 40-60 microns ) & grouted to the floor using anchors. ARMREST ASSEMBLY: The Arm rest should be of the following:
(a) P.U. ARMREST: The armrest should be made up of black integral skin Polyurethane with 65+/-10 Shore'A’ hardness and reinforced with M.S. insert fixed with leg frame The armrests should be scratch and weather resistant tant. The arm rest shoud be with and with cup holder. Arm rest shall be offered as common/individual armrest beween chairs as required.(b) ARMREST CLADDING:The armrest claoding shouid be made up of 0.9±0.05cm thick particle board & upholstered with fabric. POWDER COATING: All steel components should be Epoxy Polyester Powder Coated ( DFT 40-60 microns ).
UPHOLSTERY FABRIC: The 3 layered foam laminated fabric should be Ruby Red and Azure Blue shades as approved by GE so as to create desired patterns in the layout. Understructure fixed to ground by anchors with washer and nut. The auditorium chair is designed to get mounted/grouted on floors with flooring specification as mentioned in Godrej doc-no: STG 129368 .
Phoenix Infra
Gnani Builders
C R R CONSTRUCTIONS
M/S Janak Raj Gumber
RNR CONSTRUCTIONS
Baka Construction