140 MGD WTP SONIA VIHAR MAIN WAZIRABAD ROAD
Installation, Testing and Commissioning of Compact Substation and APFC panel at P-3, and V-14 Ranney wells.
2025_DJB_271067_1
PRESS NIT No.01(2025-26) / EE(EandM)TYR-SV
Open Tender
Miscellaneous Works
Works
75 days
140 MGD WTP SONIA VIHAR MAIN WAZIRABAD ROAD
Please refer Tender documents.
3 documents required · 3 mandatory
₹1,000
DJBEMD A/c No-50448339804 THROUGH SUBPAISA GATEWAY
₹1.4 L
10 May 2025
21 Apr 2025
1 May 2025
21 Apr 2025
1 May 2025
21 Apr 2025
21 Apr 2025 - 1 May 2025
11kV Compact Substation (CSS) shall be a type-tested, metal-enclosed prefabricated substation suitable for outdoor installation. It shall house an 11kV Ring Main Unit (RMU), distribution transformer, and Low Voltage (LV) switchboard in a compact, weatherproof, tamper-proof enclosure comply with standard or relevant IS of components ,Parameter Specification:-System Voltage (HV) 11kV, 3-Phase, 50Hz,Transformer Rating [Specify: 500 kVA],HV Switchgear SF6 or Vacuum insulated RMU,LV Voltage Output 433 V, 3-Phase, 4-wire Cooling Type ONAN (Oil Natural Air Natural)Degree of Protection IP54 for enclosure,Installation Location Outdoor (Pad-mounted / Plinth-mounted),Ambient Temp Range -5°C to +50°C 1. Major Components-1.1 High Voltage Compartment (RMU):Type-tested RMU, SF6 or vacuum insulated, Rated Voltage: 12kV,Rated Current: 630A,Short-time withstand: 20kA for 3 sec,Protection: Feeder protection relay with metering,Manual or motorized operation 1.2 Transformer Compartment:Type: Hermetically sealed or conservator-type, Core type: CRGO / Amorphous (as specified), Insulating Medium: Mineral Oil / FR3 / Synthetic Ester (as specified) • Temp Rise: 50°C for Oil, 55°C for Winding, HV & LV bushings: Cable box or plug-in type 1.3 Low Voltage Compartment • Outgoing feeders: MCCBs/MCBs as specified, Incomer: ACB MDO 800Amp. TP with metering,Metering: Digital multi-function meter, Cable entry: Bottom / Top (as specified),Busbar: Rated for transformer capacity, 50kA for 1 sec 2. Enclosure • Material: Galvanized Steel Sheet (minimum 2 mm thick),Finish: Powder-coated with anti-corrosive treatment, Roof: Sloped with rainwater drainage, Doors: Lockable with anti-vandal features,Lighting and ventilation: Internal light and louvers/fans 3. Protection and Safety • Overcurrent and earth fault protection for HV and LV sides, Surge arresters on HV side,Neutral grounding on transformer LV side (solid/through resistor), Earthing terminals for all compartments, Danger signage and mimic diagram 4. Accessories • Cable glands and lugs, Lifting hooks and skid base, Fire extinguisher bracket, Earthing rods and cables (as per BOQ) Make: L&T/ABB/Siemens/CG/DJB Approved
S/O XLPE insulated 11KV 185 sq mm 3 core cable Make: Gloster/Havells/Polycab/ Grandlay/DJB APPROVED MAKE
P/F of sencing current Transformer with control wire for current sencing for APFC panels
S/O PVC insulated 240sq mm 3.5 core aluminum armored Make: Gloster/Havells/Polycab/Grandlay/DJB APPROVED MAKE
Installation of CSS unit ,making foundation/base frame as per relevant IS for fixing the CSS unit
Installation of APFC panels ,making foundation/base frame as per relevant IS for fixing the APFC panel
Laying of HT cable & making connection as per site requirement & making connection of termination kit
Laying of LT cable & making connection as per site requirement in CSS unit 2Nos. & APFC panels 2Nos.
Testing & commissioning of CSS unit as per required parameters with relevant IS. testing of the System prior to switching on as Continuity and earth testing, Meggaring of all equipment’s for phase to phase, neutral to body, neutral to earth and phase to earth.
Testing & commissioning of APFC panels as per required parameters with relevant IS. testing of the System prior to switching on as Continuity and earth testing, Meggaring of all equipment’s for phase to phase, neutral to body, neutral to earth and phase to earth.
Gupta Brothers (BID ID -1578643)
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .