Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹32.7 LAccepted-AOC 1442 1 NANADANPURA BABINA CANTT TEHSIL DISTT JHANSI UP | BABINA | JHANSI | UP | ₹32.7 L Quoted ₹34.8 L | L1 | Accepted-AOC Lowest BIdder |
| 2 | L2₹36.6 L+₹1.8 L (5.06%)Rejected-Finance 37 222 BUNDU KATRA AGRA UP | AGRA | UP | ₹36.6 L+₹1.8 L (5.06%) | L2 | Rejected-Finance Other than Lowest |
| 3 | L3₹38.0 L+₹3.2 L (9.17%)Rejected-Finance | ₹38.0 L+₹3.2 L (9.17%) | L3 | Rejected-Finance Other than Lowest |
| 4 | L4₹38.4 L+₹3.6 L (10.2%)Rejected-Finance | ₹38.4 L+₹3.6 L (10.2%) | L4 | Rejected-Finance Other than Lowest |
| 5 | L5₹39.0 L+₹4.2 L (11.9%)Rejected-Finance | ₹39.0 L+₹4.2 L (11.9%) | L5 | Rejected-Finance Other than Lowest |
Tender Value
₹41 L
EMD Value
₹82,000
Closing Date
1 Jul 2023, 6:00 pmClosed
GE NASIRABAD
GE NASIRABAD 305601 (RAJ)
REPAIR/MAINT OF PERIMETER SECURITYLIGHT, STREET LIGHTS, HIGH MAST LIGHTS, STREET LIGHT TIMER, PANEL, POLE BOXES, POST TOP LIGHT, SOLAR LIGHT AND EARTHING OF POWER HOUSE, PUMP HOUSE, AC PLANTS, DG SETS
2023_MES_602209_1
8342/E8
Open Tender
Electrical and Maintenance Works
Item Rate
335 days
NASIRABAD
AS PER NIT
6 documents required · 6 mandatory
₹500
GE NASIRABAD
₹82,000
Yes
14 Sept 2023
9 Jun 2023
3 Jul 2023
9 Jun 2023
1 Jul 2023
23 Jun 2023
9 Jun 2023 - 17 Jun 2023
Amount
Dismantling/Taking out old underground cable of any grade/type of size as below from pole/wall/cable duct/underground trench etc, keeping serviceable cables from site all as specified as directed by Engineer-in-Charge.
Dismantling/ taking down of old unserviceable pole box complete all as specified and directed.
Dismantling/ taking down of old unserviceable LT PCC/RCC/Steel pole complete all as specified and directed.
Dismantling/ taking down of old unserviceable Flood light/security light/post top light any type and size complete all as specified and directed.
Excavation in trenches not exceeding 1.50m wide and not exceeding 1.50m depth for foundation, laying of cables/pipes/poles etc., and getting out in anytype of soil, complete all as specified and directed.
All as per description of serial item No.5.00 above but exc 1.50m and n.exc 3.0m deep complete all as specified and directed
Returning, filling in, including spreading, levelling, watering and well ramming in layers not exceeding of 25 cm thick in soft/loose soil complete all as specified and directed
Removal of surplus soil as obtained from excavation to a distance not exc. 50 metre and depositing where directed at a level not exc. 1.5 metre above the starting point, all as specified and directed.
Supply and laying dry river sand for cable cushioning in trenches to required width at bottom and top of cable including spreading levelling watering and consolidation complete all as specified and directed by Engineer-in-charge Note:-Punned thickness only shall be measured and paid.
Supply and laying old size brick covering with width equal to length of brick as the mechanical protection to cable with well burnt sub class 'B' laid in trenches flat complete all as specified and directed by Engineer-in-charge.
Supplying and fixing or laying, 40mm bore, light grade , galvanised mild steel pipe / tubing, complete with all fittings, laid under roads, drain, paths, fixed to poles/ walls with suitable mild steel clamps , bolts , nuts and washers complete all as specified and directed as for cable proction. . (Note:- Excavation & earth work shall be measured and paid for separately under appropriate item of this schedule ):-
M&L for drilling horizontal holes under roads/ pavements/ hard standing etc. at a depth as directed but not less than 1.00 m below existing Ground level, of suitable dia to accomodate pipes upto 40 mm dia, with using pneumetic drills/ ultra sound machanism for horizontal boring for passing of cable etc. complete all as specified & directed.
Supply, Laying, jointing and testing LT underground cable, heavy duty, 1100 Volts, XLPE insulated and sheathed, armoured with multi-stranded aluminium conductor cable of cross sectional area 16 Sqmm, 2 core , laid in trenches/ducts or fixed to poles/walls or laid under roads/paths/drains/culverts duly encased in galvanised steel pipe of suitable sizes including cable gland of suitable sizes and aluminium lugs for connection, complete all as specified and directed. Note :- (i)Excavation and earth work shall be measured and paid separately under BOQ
All as per description of serial item No 13.00 above but cross sectional area of cable 16 Sqmm, 4.0 core
All as per description of serial item No 13.00 above but cross sectional area of cable 10 Sqmm, 2.0 core
All as per description of serial item No 13.00 above but cross sectional area of cable 10 Sqmm, 4.0 Core
Labour only for taking down street light/security light/garden light/flood light from any position, checking the serviceability of different spares / components / parts of security light fittings LED light fittings etc, any wattage/capacity) of any description and in any position, replacement of un-serviceable/damaged/ broken part(s) either in single or in combination, re-assembling the fittings and making the light fittings serviceable, fixing the fittings in position, connecting to electric supply and its testing on installation complete all as specified and directed by Engineer-in-Charge. NOTES :- (i) Fixing element of the new replaced part(s) is deemed to be included in the rates quoted by the contractor for above item and new parts shall be measured and paid separately as supply only against respective items of Sch ‘A’. (ii) Necessary T&P i.e. ladder, tools etc and screws, insulating tapes, internal wiring wire and other minor items excluding the required spares parts for repairing and making the street light fittings/security light fittings in serviceable condition, will be arranged & supplied by the contractor and cost of which is deemed to be included in the rates quoted by the contractor in above respective item.
Supply only Electronic Driver PCB for 60 Watts LED materials suitable for various type of street light, security light for replacing make as per existing available on site complete all as specified and directed by Engineer-in-Charge. Make of spares -CG/Havells/Halonix
Supply only Electronic Driver PCB for 70 Watts LED materials suitable for various type of street light, security light for replacing make as per existing available on site complete all as specified and directed by Engineer-in-Charge. Make of spares -CG/Havells/Halonix
Supply only Electronic Driver PCB for 90 Watts LED materials suitable for various type of street light, security light for replacing make as per existing available on site complete all as specified and directed by Engineer-in-Charge. Make of spares -CG/Havells/Halonix
Supply only Electronic Driver PCB for 120 Watts LED materials suitable for various type of street light, security light for replacing make as per existing available on site complete all as specified and directed by Engineer-in-Charge. Make of spares -CG/Havells/Halonix
Supply only Electronic Driver PCB for 120 watt LED materials suitable for street light/flood light for replacing make as per existing available on site complete all as specified and directed by Engineer-in-Charge. Make of spares -CG/Havells/Halonix
Supply only Electronic Driver PCB for 150 watt LED materials suitable for street light/flood light for replacing make as per existing available on site complete all as specified and directed by Engineer-in-Charge. Make of spares -CG/Havells/Halonix
Supply only Electronic Driver PCB for Garden Light Bollard/Post Top 20/30/40 Watt for replacing make as per existing available on site complete all as specified and directed by Engineer-in-Charge. Make of spares -CG/Havells/Halonix
Taking down old unserviceable Street Light fittings and S&F 90W LED street light with pressure die cast aluminum housing & toughened glass with IP-66 degree of protection, Individual LED's must have peanut lenses for better throw across & along the road ,with luminaire efficacy of greater than 85Lumen/Watt (Minimum lumen output of luminaire should be 3800Lumens ), color rendering (CRI) of ≥ 75 and co-related colour temperature (CCT ) of 5700K (± 500K) , The luminaire should have 5KV surge protection, PF ≥ 0.95, and total harmonic distortion of THD ≤ 10% , voltage range of 140-280V should be provided. Luminaire should have top maintainable driver compartment for easy access to driver during maintenance. The Driver used must be a constant current driver with efficiency of ≥ 85% The manufacturers LOGO must be Embossed/ Engraved in the housing of the luminaire complete all as specified and directed. Make: Havells/Crompton/Philips
Taking down old unserviceable Street Light fittings and S&F 70W LED street light with pressure die cast aluminum housing & toughened glass with IP-66 degree of protection, Individual LED's must have peanut lenses for better throw across & along the road ,with luminaire efficacy of greater than 85Lumen/Watt (Minimum lumen output of luminaire should be 3800Lumens ), color rendering (CRI) of ≥ 75 and co-related colour temperature (CCT ) of 5700K (± 500K) , The luminaire should have 5KV surge protection, PF ≥ 0.95, and total harmonic distortion of THD ≤ 10% , voltage range of 140-280V should be provided. Luminaire should have top maintainable driver compartment for easy access to driver during maintenance. The Driver used must be a constant current driver with efficiency of ≥ 85% The manufacturers LOGO must be Embossed/ Engraved in the housing of the luminaire complete all as specified and directed. Make: Havells/Crompton/Philips
Supply and fix bracket for street light fittings made out GI pipe of light grade 1.2 m long 40 mm pipe each bent to shape & size required & fixed to pole with and including flat iron clamps 02 Nos made out of 32 x 6 mm flat iron including GI Nuts, bolts and washers and painting of clamps and street light brackets with one coat of aluminium paint over a coat of red oxide primer including taking down old unserviceable bracket of any shape and size all as specified and as directed.
Taking down old unsv and Supply and fix bracket for street light fittings made out GI pipe of light grade 1.2 m long 32 mm pipe each bent to shape & size required & fixed to pole with and including flat iron clamps 02 Nos made out of 32 x 6 mm MS flat fixed iron including GI Nuts, bolts and washers and painting of clamps and street light brackets with one coat of aluminium paint over a coat of red oxide primer including taking down old unserviceable bracket of any shape and size all as specified and as directed.
Taking down old unsv and Supply and fix bracket for street light fittings made out GI pipe of light grade 1.2 m long 40 mm pipe each bent to shape & size required & fixed to pole with and including flat iron clamps 02 Nos made out of 40 x 6 mm MS flat fixed iron medium grade including GI Nuts, bolts and washers and painting of clamps and street light brackets with one coat of aluminium paint over a coat of red oxide primer including taking down old unserviceable bracket of any shape and size all as specified and as directed.
Taking down steel tubular LT poles of 9 mtr long from trenches and re-fixing in the other location including re-connecting of street light fittings and testing on load complete all as specified and directed. Note: - Earth work and PCC work shall be measured and paid separately.
Taking down old unserviceable contactor and Supply & fixing contactor 3 phase 40 amps in existing panel with incoming and outgoing connection complete all as directed. Make: Schneider Electric Easy Pact TVS -957024, LC1 E18004
Taking down old unserviceable contactor and Supply & fix 3 Pole AC Coil Contactors ,415 volt, 32 Amp 240V AC of size including taking down old one complete all as specified and directed. Make :- Havells HGS32,IHPHA032101T
Supply and fixing post top lantern LED type 40 watt 230 watt volts AC outdoor type with decorative post top for 360 degree indirect light IP 65 protection with impact and corrosion resistant complete with driver and lamp complete all as specified and directed. Make :- Havells/Bajaj/Crompton
Material & Labour for applying two coats of aluminium paint on Steel tubular LT poles including painting to cross arms and clamps etc., after necessary preparation of surfaces by scrubbing and cleaning with wire brush complete all as specified & directed.
S&F in repairs IP65/IP66 Thermoplastic Polycarbonate cable Junction box for street lights; size not less than 205mm x 255mm x 112 mm suitable for cable dimensions of size 10 to 25 sq mm, with 25 sqmm terminal of 32 Amps rating for three phase & neutral mounted on din rail with locking arrangement fixed to PSC/Steel Poles by means of suitable size of clamps made of MS flat 20 x 4mm - 2 Nos with nut, bolts & double washers and including provn for fixing 01 No. single pole, MCB, 10 amps,10KA, ‘B’ series with ON/OFF flap complete all as specified and directed. Make :- Hensel Cat part No:- DK2525 G or equivalent make and model as approved by GE.
S&F high density polyethylene pipe (HDPE) 15mm bore fixed to electric pole fixing with 20 x 3 GI/aluminium clamps with every 1 m spacing. Make : Oriplast / Bansal / Supreme
Material and labour for preparation of old painted surface of LT Concrete electric pole of any size by removing all dirt, dust,etc and painting complete surface up to pole top including connected accessories with dual coat of apex exterior , synthetic enamel paint over a coat of primer of approved colour of black and white strip 30 cm height (Total 5 Nos), including painting the cross arms/bracing support on poles with a coat of aluminium paint, silver colour aluminium paint with coating of primer and writing of identification Nos with proper stencil cut etc complete all as specified & directed by Engineer-in-charge.
M&L for Marking of Pole Number on PCC pole and steel tubular LT pole with suitable size 15cmx15cm using with sythentic enamal paint colour and using Black colour for Pole numbers etc complete all as specified & directed by Engineer-in-charge.
Taking down old solar light and S&F Lithium based energy efficient Integrated solar street light of 20 watt in single FRP body with duly polyurenthane coating encases with monocrystalline solar PV panel of 45Wp, Lithium battery 11.1/12.8 Volt, 24.2Ah with inbuit BMS, IP 65, High brightness W-LED (160-180 Im/Watt) lamp with aluminium reflector for better lighting distribution, CRI 70, colour temperature 5700 K-6500 K, Microcontroller based charge controller cum driver, automatic dimming function with PIR motion sensor,Dusk to dawn operation weight not more than 10-12 KG with adjustable MS Clamp suitable for existing pole/wall mounting etc complete all as specified and directed by Engineer-in-charge. Note : Short Circuit, over load, reverse polarity and battery protections to be provided. OEM should provide vital parameters test report from NABL accredited lab and should be of made in India with CE & TOHS complaint).
Supply and laying or fixing or passing through pipe, 1100 volts grade heavy duty cable with PVC insulated solid aluminium conductor served with an inner sheathing of PVC tape armoured with galvanised steel wire or tape and overall PVC sheathed 6 sq. mm nominal cross section in service connections complete all as specified & directed by Engineer-in-charge.
M&L for earthing complete with galvanised steel earth plate electrode 60cmx60cmx6 mm thick buried directly in ground vertically to a depth not less than 2.25m below ground level with top edge of the earth plate at a depth not less than 1.5m below ground level, connected to galvanised earth lead wire 4.00 mm dia by means of bolts, nuts, check nuts and washers of galvanised iron or steel and other end of earth wire connected to main switch board and protected by galvanised iron pipe light grade 15mm bore and water pipe 20 mm bore GI med grade with funnel and wire mesh PCC chamber in cement concrete 1:3:6 type C-2 and RCC cover with handle all as specified and shown in elect plate No 3 of SSR Part-I of 2009 incl dismantling of old unserviceable existing earthing complete all as specified and directed. (Note : 1. If the desired earth resistance is not found earthing shall be re-done by the Contractor at no extra cost to govt.)
M&L for earthing complete with using galvanized mild steel earth plate (electrode) 600 mmx 600 mmx 6 mm thick buried directly in ground, earth pit not less than 2.25 mtr deep below ground level with top edge of the earth plate not less than 1.50 m below ground level and earth plate surrounded with adequate quantity of charcoal dust mixed with salt to a packed thickness of 15 cm all round the plate using 32X6 mm GI earth strip as earth lead moulded and riveted to earth plate at one end and connected to main equipment at switch/control board at another end, GI earth lead incased in and including 50 mm dia GI ‘light grade’ pipe from upper end of earth plate upto equipment with & including 20 mm dia bore GI pipe ‘light grade’ as water pipe from earth chamber to upper edge of the earth plate, GI funnel with wire mesh fixed on water pipe and provision of PCC 1:2:4 type B1(using 20 mm graded stone agg) as in pits chamber and RCC pit cover 50 mm thick of precast RCC 1:2:4 type B-1 (using 20 mm graded stone aggregate) duly reinforced with mild steel round bars 6 mm dia @ 150 mm c/c both ways with 10 mm dia mild steel bars as in lifting handles with and including necessary excavation & earth work in any type of soil including laying the GI pipe concealed in floor /wall all as per plate No. 3 of SSR Part I complete all as specified and directed and testing on completion.. (Note : 1. If the desired earth resistance is not found earthing shall be re-done by the Contractor at no extra cost to govt.)
Taking out old unserviceable MCBs Supply and fixing SPN 240V, 40 to 63 AMP 10KA 'C' curve miniature circuit breaker (MCB) of following poles and current carrying capacity in the MCB DB complete with connection testing and commissioning. complete all as specified and directed.
Taking out old unserviceable MCBs and S & F of MCB SP, 240 volt, 6 Amp to 32 Amp capacity, 10 KA, 'C' curve complete all as specified and directed.
Taking down old unsv pole & Supply ,erecting and fixing the true vertical position,steel tubular swaged pole(410 SP-31),09 mtr long, complete with cast iron base plate,pole cap/final taper plug ,bolts, nuts and washers, welded reduced section and longitudinal weld throughout entire lenght of pole ,including two coats of black bituminous paint externally upto planting depth and remaining exterior portion of pole shall be provided with one coat of red oxide primer and two coats of aluminium paint complete all as specified and directed.(Numbering of the poles shall be done with synthetic enameled painted letter of shape & size as directed. Note:- (a) Cost of numbering of pole shall be deemed to included in unit rate. (b) Excavation, Earth work and PCC foundation will be measured and paid for separately.
M & L for in repair replacement of of LED aviation light luminaries comprising of aluminuim housing with polycarbonate enclosure complete all as specified and directed. Make: Bajaj/Havells/Philips
M&L for PCC 1:4:8, type D-2 using 40mm graded stone aggregates as in foundation of PCC pole/struts including necessary form work, complete, all as specified and directed.
M&L for PCC 1:3:6, type C-2 using 40mm graded stone aggregates as in foundation of stay assembly etc including necessary form work, complete, all as specified and directed.
M&L for PCC 1:2:4, type B-1 using 20mm graded stone aggregates as in coping around pole including necessary form work, finisged even and fair, complete, all as specified and directed.
Taking down existing flood light fitting any type and Supply and fixing LED flood light 120 watt 230 V AC outdoor type with thermal management in multiple optics and equipped with IP66 protection, with impact and corrosion resistant complete with driver and lamp.with all fixing arangement, nuts, bolts and washer connecting to electric system with 1.5 sqmm PVC copper stranded conductor 2/3 core as required length from light fitting to street light control box /control Switch on pole/Panel/Timer, testing on completion, complete all as specified and directed. MAKE: Havells Cat Part No JETAIRISFL120WLED757ARWBLTG and Crompton Pluto Neo 120W Warm White Flood Lighting, LFLN-120-CDL/ 60-M
Taking down existing flood light fitting any type and S&F Integral LED flood light luminaire of 170/180 W 230 V AC outdoor type with thermal management in multiple optics and equipped with IP66 protection, with impact and corrosion resistant complete with driver and lamp.with all fixing arangement, nuts, bolts and washer connecting to electric system with 1.5 sqmm PVC copper stranded conductor 2/3 core as required length from light fitting to street light control box /control Switch on pole/Panel/Timer, testing on completion, complete all as specified and directed. MAKE: Havells Cat Part No JETAIRISMAXFL180WLED757PWBLTG or Crompton Pluto Neo 180W Warm White Flood Lighting, LFLN-180-CDL/60-M
Taking down old and Supply and fix three core 1.5 sqmm PVC insulated and PVC sheathed stranded copper conductor for post top ligh/street light complete all as specified and directed.
Taking down old and Supply and fix three core 2.5 sqmm PVC insulated and PVC sheathed stranded copper conductor street light complete all as specified and directed.
Taking down old and Supply and fix five core 6 sqmm PVC insulated and PVC sheathed stranded copper conductor for high mast light complete all as specified and directed.
Taking out old unsv high mast ligh motor and high mast light motor rewinding of copper complete all as specified and directed.
S&F in repair automatic nature switch sensor complete all as specified and directed. Make : KAKATIYA HSN CODE :8538 9000
Supply, fixing and testing Street light automatic Nature switch of capacity 5 KW single phase complete with using infrared sensor based NATURE SWITCH for automatic switching of street lights. Nature Switch operation should be based on Nautral Light Lux* level. Required illuminance level for switching ON is ≤ 30 Lux and for swiching OFF ≥ 10 Lux. The sensor should also have part night operation facility of min.4 hrs to max 12 hrs. The sensor along with suitable power contactor(s) and incoming-outgoing MCBs should be enclosed in a pole/wall/panel mountable Rust proof, Electric Shock Proof, Termite proof and FR grade thermoplastic polycarbonate Enclosure ( with Hinged LID) conforming to IP66 protection class 2. The circuit should also have provision for Manual Operation(i.e Sensor By-Pass option). Make- Kakatiya Energy system Model SWADEEP-02EC-5KW1P (With SMC Enclosure Confirmingto IP 54)
Supply, fixing and testing Street light automatic Nature switch of capacity 8 KW three phase complete with using infrared sensor based NATURE SWITCH for automatic switching of street lights. Nature Switch operation should be based on Nautral Light Lux* level. Required illuminance level for switching ON is ≤ 30 Lux and for swiching OFF ≥ 10 Lux. The sensor should also have part night operation facility of min.4 hrs to max 12 hrs. The sensor along with suitable power contactor(s) and incoming-outgoing MCBs should be enclosed in a pole/wall/panel mountable Rust proof, Electric Shock Proof, Termite proof and FR grade thermoplastic polycarbonate Enclosure( with Hinged LID) conforming to IP66 protection class 2. The circuit should also have provision for Manual Operation(i.e Sensor By-Pass option). Make - Kakatiya Energy system Model SWADEEP-02EC-5KW3P(With SMC Enclosure Confirmingto IP 54)
M & L for trimming of branches of trees touching LT Electric over head line and making clear about 5 m in radius and carrying and disposal where directed not exceeding 50 m complete all as directed.
PD GUPTA AND COMPANY
DEMROT ELECTRICAL WORKS
M/s SUNIL ENTERPRISES
kirtiman traders
M/s Shiv Builder and Suppliers
VISHAL ENGINEERING COMPANY
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .