Tender Value
₹35 L
EMD Value
₹70,000
Closing Date
29 Jul 2021, 6:00 pmClosed
GE (MIS) MHOW
GE (MAINT) INF SCHOOL 75 MALL ROAD MHOW
M AND O FOR ELECTRIC SUPPLY INSTALLATIONS PUMP HOUSE WATER SUPPLY SYSTEM DG SET INCLUDING REPAIR MAINT OF LT UG CABLES WATER SUPPLY DISTRIBUTION AND OTHER CONNECTED WORKS AT NEW AMMUNITION DEPOT UNDER GE MIS MHOW
2021_MES_456450_1
GE MIS MHOW/35 OF 2021-22
Open Tender
Miscellaneous Works
Item Rate
334 days
GE (MIS) MHOW
Please refer tender documents
8 documents required · 8 mandatory
₹500
GE (MIS) MHOW
₹70,000
Yes
18 Sept 2021
2 Jul 2021
31 Jul 2021
9 Jul 2021
29 Jul 2021
16 Jul 2021
Amount
Manning and operation of 11 KV/440 Sub Station including all switch gears installed at New FAD, round the clock in three shifts (each of eight hours) from 0600 to 1400 hrs, 1400 hrs to 2200 hrs and 2200 hrs to 0600 hrs including maintenance of Daily Log Sheets of all 11 KV feeders, 100 KVA DG set and other installed equipments:-
(a) Transformer of capacity 315 KVA -01 Nos
(b) VCB 630 Amps - 02 Nos
(c) APFC Panel 100 KVAR -01 No
(d) Two pole structure -03 Nos
(e) LT panels of various capacities -03 Nos
(f) DG Set of capacity 100 KVA with AMF Panel -01 Nos
(g) Street light panel - 02 Nos
(h) Daily, Weekly, Monthly, Quarterly and Half Yearly Maintenance as per OEM's instruction should be done in the presence of MES Rep and recorded & signed by the operator in a register as specimen given by the dept and obtain signatures of JE, AGE and contractor. (The Register shall be provided and maintained by contractor without claiming any extra cost to the Govt.) (j) The operator employed by the contractor is capable to attend the breakdown complaint on receipt of any complaint from user. If any material required to rectify the said complaint shall be measured and paid under relevant items of this schedule.
(k) The contractor is responsible for the following :- (a) Maintenance of Batteries of DG set (The cost of distilled water and electrolyte and other materials required for maintenance of batteries is deemed to be included in the quoted rate) (b) Cleaning and upkeep of complete installation premises and equipments. (c) Replacement of drop out fuse on two pole structures in the installation to restore elect supply of 33/11 KV. (d) Elect/ Helper should be capable to identify the faults in HT/LT distribution system attend and rectify minor / major complaints in AOR, (from AWC gate No-4 two pole structure to New FAD Including No light, sparking etc of FAD) (e) Contrator shall provide dress and gum boot to the operators and Helpers.
Manning and operation of 11 KV/440 Sub Station including all switch gears installed at New FAD, round the clock in three shifts as detailed below by employing One helper as per E-in-C's standing orders in three shifts of 0800 hrs each from (0600hrs to 1400hrs , 1400 hrs to 2200 hrs and 2200 hrs to 0600 hrs) (Each shift means complete continuous 08 hrs duration) complete all as specified and directed by Engineer-in-Charge
Excavation in trenches not exceeding 1.5m depth for laying cables and getting out in hard / dense soil for laying cable/erecting poles , stay assembly all as specified.
Returning and filling in soil including spreading levelling watering and well ramming in layers not exceeding 25cm all as specified.
Supply and spread river sand for cable cushioning in trenches all as specified in clause 19.75 of SSR Part-I/
Note:- For the purpose of payment, punned thickness only will be measured
Supply and laying of un-reinforced precast concrete cable cover, class LV, type I, flat, size 250 mm x 150 mm x 40 mm laid in trenches for cable protection complete all as specified and directed.
Removing excavated soil to a distance not exceeding 50m and depositing where directed at a level not exceeding 1.5m above the starting point complete all as specified and directed.
M&L for LT under ground cable XLPE insulated armoured heavy duty electric with aluminium conductor 1100Volts grade in trenches / passing through pipes of following cross sectional area including taking out existing unserviceable cables. complete all as specified and directed.
3.5 core 70 sqmm
3.5 core 50 sqmm
3.5 core 35 sqmm
4 core 25 sqmm
Dismantling of existing unserviceable / broken 11 mtr P.C.C poles complete all as specified and directed.
Supply, transportation and erecting of Prestressed concrete pole 11.0 mtr long 152mm X 152mm at top & 152mm X 260 mm at bottom class 9 all as directed.(painting of pole and excavation/earth work/PCC will be measured & paid for separately)complete all as specified and directed.
Material and labour for danger notice plate of 1.6mm thick mild steel sheet, vitreous enamelled white, with letters, figures and conventional skull and bones in signal red colour and fixed with MS clamps, bolts and nuts of approved size for LT of size 20. x 15 cm complete all as specified and directed.
Material and labour for danger notice plate of 1.6mm thick mild steel sheet, vitreous enamelled white, with letters, figures and conventional skull and bones in signal red colour and fixed with MS clamps, bolts and nuts of approved size for HT of size 20. x 20 cm complete all as specified and directed.
Material and labour for ZEBRA painting of PCC poles 11/9 Mtr long near road side upto 1.5 mtr height from pedestal, with two coats of synthetic enamel paints in 30 CM height complete all as specified and directed.
Dismantling and taking down old unserviceable / rusted/ broken anti climbing device of any type from poles for replacement with new one complete all as specified and directed.
Material and labour for anti climbing device, spikes type fabricate out of MS bars (round, square and flat) incl nuts, bolts, washers and welding in two haves made to shape to suit the cross section of the polecomplete all as specified and directed.
Taking down unserviceable/ rusted / broken stay assembly complete with all accessories including breaking PCC complete all as directed by Engr -I - charge.
Material and labour for stay assembly complete with (30x 30 x 6) mm thick plate and 16 mm dia stay rod all as shown in elect plate NO-1 of SSR-part -1 including stay wire of 7/2.50 mm dia of suitable length all as directed by Engr in charge.
Material and labour for stay assembly complete with (30 x 30 x 6) mm thick plate and 20 mm dia stay rod all as shown in elect plate NO-1 of SSR-part -1 including stay wire of 7/4 mm dia of suitable length complete all as specified and directed.
Note for item sl no. 17 and 18: Loop type insulator, stay clamps , excavation and PCC shall be measured and paid separately under relevant item of schedule.
Material and labour for loop type insulator, porcelain, white, brown or green small size, with overall dimensions 65 x 90 mm, clearance of hole 16 mm complete all as specified and directed.
Material and labour for loop type insulator, porcelain, white, brown or green small size, with overall dimesion (90mmx140mm), clearance of hole 25.5mm complete all as specified and directed.
Material and labour in replacement for old unserviceable with Lightning arresters expulsion type complete with all fittings, transmission class, discharge capacity 65 kilo amp having voltage rating 11 KV, rated frequency 50Hz, suitable for 11 KV, 3 phase, earth distribution system complete all as specified and directed.
Dismantling old unserviceable rusted switch break gang operating device complete set including insulators any type any capacity complete all as specified and directed.
Supply & fixing of switch air break gang operated triple pole mechanically operated mounted on insulator (09 insulators)& steel frame with operating mechanism including spring loaded mechanism set of three working from ground level ,11000 volt including locking arrangement of current rating up to 200 Amps (Vertical type): (GI tube must be of heavy grade or medium grade) Make : JAIPURIA, ATLAS confirming to IS-9921.
Supply and fixing of HT Cable jointing kit for 11 KV (Earthed) grade cable for straight through heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 50 to 95 Sqmm 3 core complete all as specified and directed.
Material and Labour for painting of 11 KV two pole structure steel pole's, channels complete with stay clamps, nuts and bolts with two coats of aluminium paints of max height up to 10 mtr from ground level incl painting of PCC poles/copping/fencing with two coats of synthetic enamel paint after cleaning the surface thoroughly for colouring all as directed at site complete all as specified and directed.
Filtration and dehydration of Transformer oil and removing sludge by continuous circulation through transformers, oil filtration plant with heater strips and improvement of dielectric strength minimum 60 KV at 2.5 mm gap of electrode and improvement of acidity by minimising the % of acidity using suitable chemical reagent direct from existing Transformer 11 KV of capacity 315 KVA and any make including all as directed and specified by Engr- in - charge.
Note :- (i) The job shall be done at site rates is deemed to be included in above quoted rate. (ii) Transformers Capacity 315 KVA - 1 Nos and installed at New Ammunition dump area.
Supply and fixing of LT Cable jointing kit for 1100 V (Earthed) grade cable for straight through heat shrinkable type joint complete with jointing material and accessories suitable for XLPE armoured aluminium conductor cable of following size :-
3.5 core 95 sqmm
3.5 core 70 sqmm
3.5 core 50 sqmm
3.5 core 35 sqmm
4 core 25 sqmm
Disconnecting jumpering & opening ACSR binding from insulator and dismantling /running out of OH conductor of any size and type for carrying out restringing / replacement of OH conductor complete all as specified and directed. by Engr-in-Charge(OH conductor earth continuity wire etc shall be measured for each conductor)
Carrying out restringing of OH conductor of any type or size including binding of insulators using aluminium wire complete all as specified and directed.
M&L for aluminium conductor steel reinforced of any type and size for OH conductor including binding of insulators using aluminium wire complete all as specified and directed.
Dismantling of insulators any type and size from OH conductor poles complete all as specified and directed.
Supply and fixing of 120 KN Disc type porcelain insulator, vitreous white brown , or green insulator including one galvanized mild steel spindle, two galvanised iron washer and one galvanised iron nut of 150 mm height, 150mm dia for 11000 Volts complete all as specified and directed.
Supply and fixing of pin type porcelain insulator, vitreous white brown , or green insulator including one galvanized mild steel spindle, two galvanised iron washer and one galvanised iron nut of 150 mm height, 150mm dia for 11000 Volts complete all as specified and directed.
Dismantling of cross arms / clamps of MS channel angle section strips etc complete and setting aside for re use on necessary replacement complete all as specified and directed.
Material and labour for cross arms, bracings, supports, clamps, MS 'C' channels, equal angles and back plates fabricated from structural steel sections including nuts, bolts, washers, welding, bending cold or hot, drilling holes for bolts, in any shape or size as indicated or directed and inclusive one primer coat, one under coat and one finishing coat of synthetic enamel aluminium paint complete all as specified and directed and required at site.
Carrying out earth testing for earthing provided for lightning protection system using earth megger before under taking repair/Maint work of earthing and lightning protection system and preparation of test sheet complete all as specified and directed.
M&L for earthing with galvanized steel earth plate electrode of size (600 mm x 600 mm x 6.3 mm) buried directly in ground (earth pit not less than 2.25 Mtr below normal ground level), connected to galvanized earth lead strip of size (32 x 6) mm by means of bolts, buts, check nuts and washers of galvanized iron on steel including 40 mm dia medium grade GI tubing for protection of earth lead, MS sheet metal funnel with wire mesh, watering pipe medium grade 20 mm dia, charcoal or coke and common salt in alternative layer of 15 cm compacted thickness all around the electrode with concrete earth pit of PCC (1:3:6) type B I, 50 mm thick precast RCC (1:2:4) type BI pit cover reinforced with 8 mm dia deformed bar and suitable handle made of 10 mm dia round bar including GI strip of size (32 mm x 6 mm) for extension of earth lead and necessary excavation, earth work, in soil/loose soil and disposal of spoils to a distance not exc 50 mtr and necessary connection and testing complete all as shown in electrical plate No. 3 and complete all as specified and directed.
Taking down, broken, disconnected, worn out lighting conductor, earth lead from roof, wall or from structures/ transformers and making good the disturbed surface all as directed by Engineer in Charge
Supply and fixing of earth continuity conductor or earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc as aluminium strip 25 x 3 mm braced with GI strips of suitable size to get earthed with all conducting materials in the structures for down conductor all as directed and required at site.
Trimming /cutting of trees branches /bushes obstructing the HT/LT lines making clear distance of 3 RM from the outer conductors of OH Lines all around including removing of branches/bushes of trees from site complete all as specified and directed.
Taking out old unserviceable/burnt out service connection cable for street/security lights including old/broken PVC conduit and clamps from pole upto light fitting for necessary replacement complete all as specified and directed.
M&L for HRFR PVC insulated, unsheathed, stranded copper conductor cable, three run single core of size 2.5 Sqmm and drawn into conduit including necessary connection complete all as specified and directed. (Make-Anchor/Havells/Finolex)
M&L for rigid non-metallic PVC conduit heavy duty of size 20 mm external dia, exclusive of boxes (junction/ terminal) but inclusive of all tees, bends, elbows, reducers, bell mouth tube ends and fixing accessories such as couplers, lock nuts, saddles, pipe hooks etc, to be fixed along the pole complete all as specified and directed. (Make-Plaza/Pressfit/Havells)
Dismantling and taking down unsv street light fitting of 150 from pole /building complete with GI bracket & fixing arrangement complete all as specified and directed.
Refixing of street light fitting complete with HPSV lamp, ballast, igniters and other accessories for 150 watt lamp incl making connection with 3 runs of 2.5 sqmm single core existing copper conductor PVC insulated and PVC unsheathed cable and testing for entire satisfaction of Engr-in-charge.
Supply and fixing of new generation energy saving and environmental friendly long life LED street light made up of pressure die cast aluminium housing with high power LED as lighting source and top opening separate driver compartment with toughened glass having IP 66 protection and impact resistance of IK07 of capacity 45 Watt, powder coated grey finish including control gear (Inbuilt electronic driver with APFC, Lower THD Output short circuit protection, surge voltage protection, over voltage protection& other reliability test as per IS 15885 Part-2/Sec 13 complete all as specified and directed.
Carrying out cleaning of breather assembly and filling of silica gel in breather suitable for transformer of capacity 315 KVA complete all as specified and directed.
M & L for Topping up of Transformer oil suitable for 11 KV, 315 KVA transformer by filling up insulating oil including filtration to meet the required DI-electric strength not less than 60 KV at 2.5 mm Air gap complete all as specified and directed.
Supply and fixing of Expulsion fuses 11000 volts single pole rating upto 25 amps complete all as specified and directed.
Supply and fix Lead acid battery of 12 V 180 Ah of Make : Exide or equivalent complete all as specified and directed.
Carrying out B-check maintenance to DG set of 100 KVA, including replacing the fuel filter, oil filter cleaning of Air filter including replacing the engine oil complete testing after servicing complete all as specified and directed. Note Engine oil will be measured and paid separately
Supply and fill engine oil 15 W 40 on site complete all as specified and directed.
M&L for cement concrete (1:3:6) type C-2 using 40mm graded stone aggregate in foundation, filling and mass concrete, complete all as specified and directed.
M&L for cement concrete (1:2:4) type B-1 for coping of poles using 20 mm graded stone aggregate including weathering, slightly rounded or chamfered angles as directed with & including necessary form work complete all as specified and directed.
Supply and fixing in replacement moulding compound Street light junction box of size 250 mm x 200 mm x 105mm complete with shock and rust proof, termite resistant, tamper proof , front openable type and including suitable provision for single phase, two wire cable (size upto 2.5 Sqmm 2 Core) incoming & outgoing loop -in loop connection and including one no. MCB SP 6 Amp including non metallic clamps and GI nut bolts and washers of suitable size and fixed on pole / wall complete all as specified and directed. Make - Sintex Cat part No GSJB 2520 or equivalent in Hensel/ABB.
Supply, installation testing and commissioning in replacement of street light control box as a pole mountable enclosure conforms to IP-66 suitable for 440/230V, AC, 50 Hz, consisting of a light sensitive control system, 3 Nos of power contactor for load switching, 3 No of MCB for incoming and 3 No of MCB for outgoing of 20-32 Amps each MCB's for incoming and out going and copper circuit wiring of min 10 Sq mm with terminal plate as required suitable for 3 phase four wire system, 8 KW -12 KW load blocks complete all as specified and directed. by Swadeep Nature Switch model No 02EC8KW3P - VMS or equivalent in CG/L&T/Phillips
M & L for street light pole painting of steel tubular type with two coat of synthetic enamel aluminium paint over a coat of primer after preparing the surfaces, painting on cross arms/FI clamps/street light brackets of any type including ZEBRA painting with synthetic enamelled paint up to 1.5 Mtr height from ground level & writing the pole numbers with black paint on poles all as specified and directed.
Disconnecting existing tanks, setting aside (or lowering if required) for repairs, cleaning, etc. and hoisting if required reconnecting and refixing in position including cleaning and removing all scale and dirt, etc, from tanks and from mouths of circulating pipes, etc of capacity exceeding 250 Ltrs & not exceeding 500 Ltrs complete all as specified and directed.
Disconnecting existing tanks, setting aside (or lowering if required) for repairs, cleaning, etc. and hoisting if required reconnecting and refixing in position including cleaning and removing all scale and dirt, etc, from tanks and from mouths of circulating pipes, etc of capacity exceeding 500 Ltrs & not exceeding 1000 Ltrs complete all as specified and directed.
Disconnecting existing tanks, setting aside (or lowering if required) for repairs, cleaning, etc. and hoisting if required reconnecting and refixing in position including cleaning and removing all scale and dirt, etc, from tanks and from mouths of circulating pipes, etc of capacity exceeding 1000 Ltrs & not exceeding 2000 Ltrs complete all as specified and directed.
Rotational moulded polyethylene water storage tanks (cylindrical vertical with closed top) hoisted and fixed in position of capacity 500 litres capacity all as specified in SSR Part -I.
Rotational moulded polyethylene water storage tanks (cylindrical vertical with closed top) hoisted and fixed in position of capacity 1000 litres capacity all as specified in SSR Part -I.
Supply and fixed of Ball valves, high pressure of PTMT with epoxy coated aluminium rod & high density plastic ball screwed for iron pipe and fixed suitable for 20mm bore dia of pipe ( Minimum weight 20 mm-210 gms) including taking down old Unserviceable one(fixed in repairs) complete all as specified and directed.
Supply and fixed of Ball valves, high pressure of PTMT with epoxy coated aluminium rod & high density plastic ball screwed for iron pipe and fixed suitable for 25mm bore dia of pipe ( Minimum weight 25 mm-455 gms) including taking down old Unserviceable one(fixed in repairs) complete all as specified and directed.
Supply and fixed of Ball valves, high pressure of PTMT with epoxy coated aluminium rod & high density plastic ball screwed for iron pipe and fixed suitable for 40mm bore dia of pipe ( Minimum weight 40 mm- 690 gms) including taking down old Unserviceable one(fixed in repairs) complete all as specified and directed.
Manning and operation of New Ammunition Depot pump house at Adm area including installation/ equipments detailed below by employing one FGM, in three shifts of Eight hours duration of each shift (from 0600 hrs to 1400 hrs, 1400 hrs to 2200 hrs and 2200 hrs to 0600 hrs) including maintaining of log sheets. complete all as specified and directed by Engineer-in-Charge. NOTES:- I. Machinery/Equipment to be manned and operated:-
Machinery/Equipment to be manned and operated:- 1. Monoblock Pump sets 5HP with all accessories- 02 Nos.. 2. Altoch Dosing system -02 sets (4 Pcs). 3. Decrin Dosing Pumps-02 Nos 4. Pump house -01 No. 5. RCC Sump Capacity 25000 Gallon -01 No 6. DG Set Cap 100 KVA -01 No 7. Electric panel of pump set including area lightning.
NOTE:- (for item No 9.00 ) 1. The operator employed by the contractor must be a skilled FGM sub to ITI qualified in appropriate trade with five years of experience in concerned operation field and fully concern to maintenance. 2. The operator must adhered the dress code as directed. 3. The operator must be known to attend the telephone calls and to maintain the record. 4. The operator must be smart in conversation and well behaved. 5. The contractor is responsible for cleaning and upkeep of installation premises and equipments. 6. Daily Log sheets shall be provided and maintained by the Contractor as per specimen given by the department without claiming any extra cost from department. 7. Surrounding area inside the installation should be kept clean & tidy. 8. As per Industrial act one person should not be continued on duty more than six days in a week and he should be given weekly off day for his personal maintenance and one reliever off duty should be employed by the contractor without claiming extra cost from the dept. 9. Plant running record, log book & long sheets for DG Sets, Pump Sets and other eqpts etc. at the installation as per specimen given by the department shall be provided and maintained by the operator as per procedure in vogue. 10. If the installation found unclean (i.e. not upto the satisfactory level of the Engr-in-Charge), a penalty of Rs-500/- for that day will be deducted from the RAR/ Bill. 11. Operator should be capable of attending the minor / major complaints.
11. Daily, Weekly, Monthly, Quarterly and Half Yearly Maintenance as per OEM's instruction should be done in the presence of MES Rep and recorded & signed by the operator in a register as specimen given by the dept and obtain signatures of JE, AGE and contractor. (The Register shall be provided and maintained by contractor without claiming any extra cost to the Govt.) 12. The operator employed by the contractor is capable to attend the breakdown complaint on receipt of any complaint from user. If any material required to rectify the said complaint shall be measured and paid under relevant items of this schedule.
M&L for cleaning of under ground Sump of capacity 25000 Gallons, by scraping with the help of hard wire steel brushes and physical cleaning of sump after lowering/drying the water with the help of Pump sets/ manual/ washout valves etc. deposit the muddy and other waste materials and taking them out with the help of manual labour and depositing them at a distance of not more than 50Mtrs all as directed and specified and making sump complete clean and washing properly with bleaching mixed in water and applying two coat of thick quick drying lime wash on entire inner surface of the sump including writing of Date of cleaning with white paint on black painted surface at minimum two places out side /top of sump and painting of steel ladder of tank with two coats of synthetic enamel paint including painting and rewriting of water level indicator with existing colour complete all as specified and directed by Engineer- in – charge. Note:- 1. Necessary T & P and material for the Job will be arranged by contractor and ensure uninterrupted water supply to Mhow cantt.
Dismantling mono block/centrifugal pump set motor from the existing foundation after disconnecting the inlet / out let pipe connections, disconnecting electrically and taking to civil authorised KIRLOSKAR dealer workshop for repair/strip opening and repairing of pumping sets by replacement the worn out defective/unserviceable parts such as bearing, bush, Gland plate, gland rope check nut, shaft sleeves etc. complete. Reassembling including oiling, greasing replacement of worn out nuts, bolts, gasket etc, and re-fixing in its original position at site, making all connections, commissioning and testing for smooth and noise free operation including bringing back the same from workshop after necessary servicing and testing the same after proper mounting/refixing for entire satisfaction of Engr - in - Charge all as directed/specified of capacity 5 HP.
Disconnecting/ removing the defective starter from the LT panel board and Supply & fixing new Cosmic Star-Reversing Starter 415 volts 3 phase with single phase protection feature with overload relay range 7 to 10 Amp and Contactors suitable for 5 HP electric motor at the existing panel board in position and making electric connections complete all as specified and as directed by Engr-in-Charge.
Rewinding the monoblock induction motor of capacity 5 HP using suitable size super enamelled insulated copper wires replacing the worn out bushes bearing etc complete and reassembling pump and motor lowering the complete assembly in the bore well up to the original depth including jointing weather proof cable with water proof sealing kit of M seal make including testing etc complete for satisfactory operation complete all as specified and directed.
Supply only calcium based granular disinfectant for water treatment, available Chlorine 60% to 70% by weight of the compound as per manufacturers instruct ructions and packed in 45 Kg plastic drums complete all as specified & directed. Make :- Aquafit/ Declibac
Supply only Bleaching powder grade -I ISI marked having stable available chlorine % by mass minimum 35% as per IS 1065,1971 and packed in 25 Kg bag complete all as specified and directed. Make : Vikram.
Supply only Alum Crystal complete all as specified and directed.
Taking up or down steel tubing along with fittings such as tee, bends etc fixed to walls and ceilings or laid in flours/trenches and connections incl removal from site of following sizes:-
20mm bore
25 mm bore
40 or 50 mm bore
Material and labour for 'Medium grade' galvanised iron tubes with all fittings and fixed complete fixed on walls and ceilings or laid on floors of following sizes:-make- TATA /Jindal
20 mm bore.
25 mm bore.
40 mm bore
Material and labour for 'Medium grade' galvanised iron tubes with all fittings such as tees bends etc laid in trenches of following sizes:-make- TATA /Jindal
20 mm bore.
25 mm bore.
40 mm bore
50 mm bore
Taking out sluice valves refacing, regrinding and refixing of following sizes :-
80 mm bore
100 mm bore
150 mm bore
Supply and fixing external supply system layout plan of Ammunition depot made of clear acrylic sheet of 2 mm thick with interior lighting arrangement in cubical enclosure of size 2 M x 1.5 M including hanging on wall and connecting to existing socket. Note. Rough Layout plan shall be printed and get approved from GE/AGE E/M for final printing on Acrylic sheet.
Supply and fix cast iron Bulk water meter enclosed type (metallic gears) with flanged ends of size 80mm bore Make : KRANTI/KUSHAL
Supply & Fix in repair Sluice valves cast iron body, double flanged, ISI marked (IS-14846), heavy duty, class PN-1.6 gun metal, with rising spindle of solid forged bronze and operating handle, including rubber gaskets, nuts, bolts, washers etc including taking up. Make "Kirloskar/Upadhaya/Zoloto" complete of following sizes: -
(a) 80 mm bore
(b) 100 mm bore
(c) 150 mm bore
Servicing to trolley mounted Diesel engine driven fire pump including replacing the fuel filter, oil filter including replacing the engine oil complete testing after servicing all as directed and specified of capacity 36.8 KW. Note Engine oil will be measured and paid separately
Supply and fix cast iron foot valve, swing Horizontal type foot valve with rubberised steel ball and CI body flanged fixed between exit of the pump and delivery pipe line of size 80 mm bore including dismantling old unserviceable one:- (Make : NORMEX or Equivalent make as approved).
Supply and fix Lead acid battery of 12 V 180 Ah of Make : Exide or equivalent
Supply only RRL hose type - A of 15 meter long
Supply and fixing ,mechanical Joints made of Ductile iron K-12 suitable for following sizes:-
(a) 80 mm bore DI pipe
(b) 100 mm bore DI pipe
(c) 150 mm bore DI pipe
Supply and fill engine oil 15 W 40 on site
M& L for preparation of surfaces on old painted surfaces of trolley mounted Fire DG pump set and painting with two coat of synthetic enamel paint of capacity 36.8 KW in situ and writing the SM/MES No on two visible places on Fire DG set all as directed at site
Supply, laying and testing of centrifugally cast (Spun) ductile iron pressure pipe Class K-9 pipes duly applied with zinc coating with finishing layer of bitumen on external surfaces and cement mortar lining with bituminous seal coat on internal surfaces complete confirming to IS-8329 (2000), in and including rubber gasket complete all as specified and directed by the Engineer-in Charge at site of following sizes. Make : Electro steel Casting Ltd/TATA Metaliks/ Jindal Ltd / SAW Pipes.
(a) 80 mm bore
(b) 100 mm bore
(c) 150 mm bore
Supply, and fixing of fitting for centrifugally cast (Spun) ductile iron pressure pipe Class K-12 duly applied with zinc coating with finishing layer of bitumen on external surfaces and cement mortar lining with bituminous seal coat on internal surfaces complete confirming to IS-8329 (2000), in and including rubber gasket complete all as specified and directed by the Engineer-in Charge at site of following sizes. Make : Electro steel Casting Ltd/TATA Metaliks/ Jindal Ltd / SAW Pipes.
(a) 80 mm bore
(b) 100 mm bore
(c) 150 mm bore
Notes :- For all Items of BOQ ; If the quoted amount is less than the estimated cost of the work i.e. 35.00 Lakhs, then the lowest bidder will have to deposit FDR/BGB in favour of Accepting Officer within 07 days of opening of finacial bid for the difference in estimated cost i.e. 35.00 Lakhs & quoted amount. In case the said FDR/BGB is not submitted within stipulated period mentioned above, the contractor shall be banned for 06 months & his bid will be rejected. The said Amt deposited by the lowest bidder will be released after two months of certified completion of work.
MODI CORPORATION
RAJPATI CONSTRUCTION
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .