| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹39.4 LAccepted-AOC HOUSE NO 3 GALI NO 1 THANDEWALA ROAD BASANT VIHAR DISTT SRI MUKTSAR SAHIB | SRI MUKTSAR SAHIB | PUNJAB | L1 | Accepted-AOC Lowest Amount Quoted | |
| 2 | L2₹41.4 L+₹2.1 L (5.22%)Rejected-Finance PATIALA | PATIALA | PATIALA | PUNJAB | L2 | Rejected-Finance Highest Amount Quoted | |
| 3 | L3₹42.0 L+₹2.6 L (6.56%)Rejected-Finance JALANDHAR | PUNJAB | 144029 | L3 | Rejected-Finance Highest Amount Quoted |
Tender Value
₹48.7 L
EMD Value
₹97,460
Closing Date
28 Feb 2024, 11:00 amClosed
Executive Enginer (Electrical) SAS Nagar
Executive Enginer (Electrical) Vikas Bhawan Sector 62 SAS Nagar
Renovation of Electrical Installation in School of Eminence at GSSS Boha Distt Mansa
2024_DRDP_117524_1
PRD/E/SASN/2024/01
Open Tender
Electrical Works
Item Wise
180 days
School of Eminence at GSSS Boha Distt Mansa
Please refer Tender documents.
6 documents required · 6 mandatory
₹5,000
₹97,460
28 Nov 2024
13 Feb 2024
28 Feb 2024
13 Feb 2024
28 Feb 2024
13 Feb 2024
Amount
RECESSED PVC CONDUIT PIPE WIRING SYSTEM WITH MODULAR SWITCHES: Wiring in PVC insulated copper conductor single core FR cable (ISI marked) overall 1.5sq. mm, 1100volts grade to be laid in heavy gauge PVC conduit pipe 20mm/ 25mm dia. (ISI Marked) recessed in wall etc., complete with powder coated/anodized concealed metal boxes (1.6mm thick with Brass lugs) required for suitable number of modules (Modular accessories) for having Step type electronic fan regulators (two module) 100watts, bell push, 6Amp. 2/3 universal socket (shuttered), 16/20Amp. combined/ universal Socket (shuttered), 6/10Amp. Switches, 16/20Amp. switches with indicator etc. and covered with Frame Plate etc., PVC connector (For Fan Box and Call Bell), Steel Hooks, Sheet metal fan box (1.6mm thick shape hexagonal), Circular junction Boxes (Four way PVC 1½" deep for walls and CI 3" deep for ceiling), bonding to earth with PVC insulated copper conductor single core FR cable (ISI marked) 1sq. mm, 1100volts grade (For 6Amp. wall socket & plug control point) and other petty material etc., including the cost of above material, cutting and filling up of chases (with finishing the surface):- Wiring fan point (With fan box)
Wiring light point
Wiring 6Amp. Plug control comprising wall socket point
Wiring 16/20Amp. power plug control point
REPLACEMENT OF WIRES, COVER FRAMES, MODULAR SWITCHES, CONCEALED METAL BOXES AND OTHER ACCESSORIES IN THE EXISTING RECESSED CONDUIT PIPE WIRING SYSTEM (WITH MODULAR TYPE ACCESSORIES) Derived from 34.01: Replacement of PVC insulated copper conductor single core FR cable (ISI marked) overall 1.5sq. mm, 1100volts grade to be laid in existing heavy gauge welded conduit pipe 20 mm/25 mm dia (1.6mm thick) ISI Marked, recessed in wall etc., complete with powder coated/anodized concealed metal boxes (1.6mm thick with Brass lugs) required for suitable number of modules (Modular accessories) for having Step type electronic fan regulators (two module) 100watts, bell push, 6Amp. 2/3 universal socket (shuttered), 16/20Amp. combined/ universal Socket (shuttered), 6/10Amp. Switches, 16/20Amp. switches with indicator etc. and covered with Frame Plate etc., PVC connector (For Fan Box and Call Bell), PVC Bush, bonding to earth with PVC insulated copper conductor single core FR cable (ISI marked) 1sq. mm, 1100volts grade (For 6Amp. wall socket & plug control point) and other petty material etc. including the cost of above material, cutting and filling up of chases (with finishing the surface):- (Derived From CSR 34.01) Wiring fan point (Without fan box)
Wiring light point
Wiring call-bell point
Wiring 6Amp. Plug control comprising wall socket point
Wiring 16/20Amp. power plug control point
RECESSED AIR CONDITIONER SUPPLY TERMINAL POINT (USED FOR HGW, PVC CONDUIT & HDPE PIPE WIRING SYSTEM WITH MODULAR ACCESSORIES): Wiring air conditioner supply terminal point recessed in wall etc., complete with powder coated/anodized concealed metal boxes required for suitable number of modules (Modular accessories) for having 25Amp. combined/ universal Socket (shuttered) and modular motor starter 25Amp. (2Module), covered with Frame Plate and other petty material etc. including the cost of above material, cutting and filling up of chases (with finishing the surface):- Wiring AC supply terminal point having 1No. 25Amp. universal Socket (shuttered) erected at AC height and 1No. Motor starter 25Amp. erected at switchboard height.
RECESSED COMPUTER SUPPLY TERMINAL POINTS (USED FOR HGW, PVC CONDUIT & HDPE PIPE WIRING SYSTEM WITH MODULAR ACCESSORIES): Wiring Computer supply terminal points recessed in wall etc., complete with powder coated/anodized concealed metal boxes required for suitable number of modules (Modular accessories) for having 6Amp. 2/3 universal socket (shuttered), 16/20Amp. combined/ universal Socket (shuttered), 6/10/16/20Amp. Switches and blanking plate etc., and covered with Frame Plate and other petty material etc. including the cost of above material, cutting and filling up of chases (with finishing the surface):- Wiring Computer terminal point having 2 Nos. 6Amp. 2/3 universal socket (shuttered), 1No. 16/20Amp. universal Socket (shuttered) and 2Nos. 16/20Amp. switch with indicator (Modular accessories).
RECESSED TV, TELEPHONE & NETWORKING SOCKETS OUTLET POINTS (USED FOR HGW, PVC CONDUIT & HDPE PIPE WIRING SYSTEM WITH MODULAR ACCESSORIES): Supply and erection of TV socket, Telephone socket and Networking socket points in powder coated/anodized concealed metal boxes recessed in wall required for suitable number of modules (Modular accessories) for having TV sockets, Telephone sockets RJ11 &Networking socket RJ45 (one module), covered with Frame Plate and other petty material etc., including the cost of above material, cutting and filling up of chases (with finishing the surface):- Wiring Telephone socket point RJ11 (one module)
Wiring Telephone socket point RJ45 (one module)
PVC INSULATED SINGLE CORE FR COPPER CONDUCTOR CABLE: Supply and erection of PVC insulated FR single core Unsheathed copper conductor cable (ISI marked) suitable upto 1100 volts grade confirm to IS:694/1990 left bare in pipe or casing of suitable size complete in all respect as desired by the Engineer-in-charge:- Overall size 1.5sq.mm (Un-sheathed)
Overall size 4.0sq.mm (Un-sheathed)
Overall size 10sq.mm (Un-sheathed)
XLPE INSULATED UN-ARMOURED CABLES (LOOSE): Supply, laying and erection of aluminium conductor XLPE insulated PVC sheathed Un-armoured and served cable 1100 volts grade as per IS 7098 (Part-1)1988 to be laid loose in the existing trench or pipe as per PWD General Specifications:- Overall size 50sq.mm (3½ Core) Un- Armoured (Loose)
Overall size 185sq.mm (3½ Core) Un- armoured (Loose) for full building load
PVC, HDPE PIPES & PVC FLEXIBLE PIPES: Supply & erection of PVC Conduit Pipes (ISI marked) as per IS9537:Part-III & HDPE pipes (ISI marked) as per IS:4984:1995 for wiring purposes including bends, junction boxes, Steel hooks, M.S. saddle clamps and other petty materials etc., as per PWD General Specifications:- Heavy Gauge PVC Conduit Pipe 25mm dia. (Flushed)
Heavy Gauge PVC Conduit Pipe 32mm dia. (Flushed)
Heavy Gauge PVC Conduit Pipe 40mm dia. (Flushed)
Earthing with electrolytic Copper Tape rivetted (with 5Nos. copper rivets)/Steel Nut & bolts (with 4Nos. 32mm long, 8mm thick with washer and double nut) to 30cm x 120cm x 2mm thick copper plate (made cylindrical) burried 4.50 metre (14.76 feet) below ground level in the hole of excavation having bore dia. 125mm and surrounded by salt & charcoal dust mixture (20 kg.) including fixing the Copper Tape recessed in wall and in floor etc., up to 8metre in Length (including bore Length). G.I. pipe 20mm dia. (A-class), 3metre long should be laid in the hole of excavation 1 feet below ground level and having GI Reducer 50mm x 20mm with PVC Cap (For pouring water) fixed on the top level of the pipe. 300mm x 300mm x 300mm deep haudi of First class bricks finished with 1:4 cement plaster and haudi covered with cast iron lid having size 300mm x 300mm (Heavy) around the hole of excavation:- Earthing with 25mm x 3mm Copper Tape (upto 8Metre in Length)
Additional Length 25mm x 3mm thick Copper Tape
Earthing with 8 SWG (4mm dia.) electrolytic copper wire thimbled (1No. copper thimble with suitable size steel bolt, washers & double nut) with 30cm x 60cm x 2mm thick copper plate (made cylindrical) burried below ground level in the hole of excavation having bore dia. 125mm and surrounded by salt & charcoal dust mixture (20 kg.) including fixing the copper wire run through 20mm dia. G.I. pipe (A-Class) recessed in wall and in floor etc., up to suitable Length in metre (including bore Length). G.I. pipe 20mm dia. (A-class) of suitable Length should be laid in the hole of excavation 1 feet below ground level and having GI Reducer 50mm x 20mm with PVC Cap (For pouring water) fixed on the top level of the pipe. 300mm x 300mm x 300mm deep haudi of First class bricks finished with 1:4 cement plaster and haudi covered with cast iron lid having size 300mm x 300mm (Heavy) around the hole of excavation. Earthing with 8 SWG (4mm dia.) copper wire thimbled with 30cm x 60cm x 2mm thick copper plate burried 4.50 metre (14.76 feet) below ground level (up to 14metre in Length) with G.I. pipe 20mm dia. (A-class), 3metre long
Additional Length copper wire 8 S.W.G. (4mm dia.) in 20mm dia. G.I. pipe (Flushed)
MINIATURE CIRCUIT BREAKERS: Supply and erection of Miniature Circuit Breaker MCB's for circuit protection against overload and short circuit current fault suitable for 240/ 415 volts 50cycles AC supply with breaking capacity of 10kA, Curve-C and low watt losses as per IS/IEC 60898-1, energy limitation class-3, true contact indication, label holder facility in the existing MCB distribution board as per PWD General Specifications including connections with suitable size of thimbles/lugs:- MCB Single Pole 6-32amp. (10kA, Curve-C)
MCB Double Pole 63 (10kA, Curve-C)amp
MCB Four Pole 50, 63amp. (10kA, Curve-C)
SHEET METAL DOUBLE DOOR DISTRIBUTION BOARD FOR MCB's/ RCBO's/ RCCB's: Supply and erection of sheet metal Double Door Distribution Boards IP 43- IK09 metal door (dust protected) as per IS 8623-1&3, IEC 61439-1&3 suitable for flush mounting with fully insulated copper busbars, shrouded neutral bars, earth bars, cement spill protector, colorcoded interconnecting wire set, cable ties, blanking plates and circuit identifications label and of required no. of ways for mounting miniature circuit breakers/ RCBO's/ RCCB's in the distribution board (For SP&N distribution board with provision DP MCB's/ RCCB's/ RCBO's as incomer and SP MCB's as outgoings and for TP&N horizontal distribution board with provision TPN/ FP MCB's/ RCCB's/ RCBO's as incomer and SP MCB's as outgoings) as per PWD General specifications including connections with suitable size of thimbles and bonding to existing earth etc:- SP&N Double Door Distribution Board 12way each
SP&N Double Door Distribution Board 16way each
TP&N Horizontal Double Door Distribution Board 4 way each
TP&N Vertical Double Door Distribution Board 12 way each
MOULDED CASE CIRCUIT BREAKERS: Supply and erection of Moulded Case Circuit Breaker (Panel mounting Cubical type) in the existing Cubical Panel (confirm to IEC:60947-2) having Ics=100% Icu, 100% neutral with spreader terminal links, Extended rotary handle and relevant PWD general specifications complete with G.I. Bolts, Nuts & Connection on both sides of MCCB with suitable size of thimbles etc:- MCCB Four Pole 100amp., 415volts, ≥25kA Fixed Magnetic and Adjustable Thermal Setting
MCCB Four Pole 160amp., 415volts, ≥25kA Fixed Magnetic and Adjustable Thermal Setting
MCCB Four Pole 400amp., 415volts, ≥25kA Fixed Magnetic and Adjustable Thermal Setting
DOUBLE WALLED CORRUGATED (DWC) HDPE PIPES: Supply and erection of Double Walled Corrugated (DWC) HDPE pipe to be laid 1mtr. below ground level including excavation placing the pipe in position and back filling with excavated soil etc. of the required size:- Double Walled Corrugated HDPE Pipe 63/51mm (Outer/ Inner dia.)
Double Walled Corrugated HDPE Pipe 120/ 103.5mm (Outer/ Inner dia.)
Providing and fixing of FIRE EXTINGUISHER, ABC Powder type (stored pressure) as per IS: 15683 complete with all accessories as per Manufactures Specification. ISI Mark complete in all respect. 4 Kg. Capacity
Providing and fixing of FIRE EXTINGUISHER, CO2 type as per IS: 15683 complete with all accessories as per Manufactures Specification. ISI Mark complete in all respect. 4.5 Kg. Capacity
Supply and erection of sheet metal Cable End Box (Make is same as MCB Distribution Board) mounting on the top or bottom of the MCB Distribution Board (Either Horizontal or Vertical) to keep loose wires & cables as per PWD General specifications including petty materials etc as required:- Cable End Box for SPN 8 Way
Cable End Box for SPN 16 Way
Cable End Box for TPN 4 Way
Cable End Box for TPN Vertical 4/8/12Way
Supply/Erection of Projector and Sound System Supply Terminal to be fitted on MS box moudular series (Powder Coated/Anodised) of good quality should be recessed in the wall etc.Including ,3 Pin 6Amp Socket 6 no. 16amp swtich 2 no., 6M sheet 2 no., 2M Sheet 1 no. 6M box 2 no & 2M box 1 no. making all necesary connections etc. Complete in all respects.
LT PANELS & MCCB's (MOULDED CASE CIRCUIT BREAKERS): LT PANELS Designing, Supply, Erection, Testing & commissioning of indoor Type LT cubical panel enclosure (dust, vermin and interchangeable modules with facilites for extensions or reduction as per the space or requirments). The Panel shall be suitable for operation at 415+6% Volts, 50HZ, 3 phase 4 wire & earth system. The assembly manufacturer should be ISO approved and CPRI tested for short circuit of (minimum 50kA) as well as IP degree of protection (IP 54/55). LT Panel enclosure having space for 1No. Incomer MCCB 400Amp. and 8Nos. outgoing MCCB's 40amp. to 160amp. according to the requirement at site (Approx. size 1750 x 1750 x 400mm) (as per SBD/DNIT)
Providing & fixing in position Water Cooler without Stablizer of approved make (to the approval of Engineer-in-charge ) including carriage complete in all respect. Water Cooler Semi Steel Body 80/120 ltr Capacity without Stablizer
AUTOMATIC VOLTAGE STABLIZER: Supply and erection of Single phase copper wound Automatic voltage stablizer of suitable capacity electronically controlled circuit with input voltage 140-260 volts single phase AC supply and output voltage 220 ± 5% volts single phase AC supply having main silicon core copper wound step up transformer with suitable nos. of turns on primary side and secondary side the transformer should be fully insulated inside the MS sheet box of suitable size. There should be power control relay and single pole MCB (C-curve, 10kA) of suitable capacity complete with internal copper wiring along with amp. meter and volt meter, high voltage cut off 280 volt input (240 volt output) and 90 volt maximum boost and overloading protection to be provided:- Automatic Voltage Stablizer 4 KVA
Providing & fixing in position Commercial RO without reservoir with four no cartridge/ membrane having flow rate 50 ltr/hr with stage purification process of approved make(to the approval of Engineer-in-charge ) including carriage and fixing in position complete in all respect
Supply & Erection of BLDC 5 Star Ceiling Fans 1200 Sweep 48" (Regulator operated) including flexible wire & petty material etc. Complete in all respects as appd and desired by the Engineer-in-charge at site. Makes- Crompton Energion Riviera/Bajaj Energos 28/ Havells Efficiencia Neo (BLDC 26w) without remote
Supply & Erection of Exhaust Fan 12”, 900 RPM. With Aluminium louver Shutter And plyboard complete in all respect as appd. And desired by the Engineer in-charge at site.
Supply/erection of LED Batten 40w. High quality aluminium extruded having efficacy of LED fixture mimimum 100 lumens per watt and operating voltage between 140 to 270 volt, input AC frequency 50 Hz ± 3 % complete along with erection of the same with connections, testing etc. complete in all respects as approved and desired by the Engineer-in-charge at site.LED Fitting as per Specifications approved by Hon. Tech. Advisor to CM Punjab vide ION No:- AT/2021/GL/1410-1422 Dated:- 06.05.2021.. Complete in all respect as appd. And desired by the Engineer in-charge at site.
SSupply and erection of Recessed mounted 36watt LED panel 1x4 feet (including LED driver) with CRCA sheet having efficacy of LED fixture minimum 100 lumens per watt and operating voltage between 140 to 270 volt, input AC frequency 50 Hz ± 3 % complete along with erection of the same with connections, testing etc. complete in all respects as approved and desired by the Engineer-in-charge at site.The certification and Specifications of the LED Fitting's should be as approved by O/o Advisor (Technical), Govt of Punjab vide Letter no.AT/2021/GL/1410-1422 Dated 06/05/2021.
Supply and erection of LED Flood Light 120 watt (including LED driver) with pressure die cast aluminium housing with control gear ( IP 66 protection),THD< 10%, CRI minimum 70, High power LED with mandatory secondary lenses, toughened glass fitting, 10 KV SPD within driver , efficacy of LED fixture minimum 120 lumens per watt, complete in all respects as approved and desired by the Engineer in-charge at site. LED Fittings as per specifications approved by Hon'ble Technical Advisor to CM Punjab vide letter No. AT-2021/GL 1410-1422 Dated 06/05/2021.
Supply and erection of Wall Mounted 6U Rack with power point and fan. complete in all respect as approved and desired by the Engineer in-charges at site
Supply installation Testing and commissioning of 16 port 10/100/1000 PoE swtich, 16 PoE port + 2 SFP ports, power budget 150W, IEEE 802.3af/at extended range 250 mtr complete along with erection of the same with connections, testing etc. Complete in all respects as aaproved and desired by the Engineer-in-charge at site.
Supply, installation, testing & commissioning of Category 6 UTP , 4 Pair This cable well exceeds the requirements of TIA/EIA-568-C.2 and IEC/ISO 11801. Construction: 4 twisted pairs separated by cross separator, 4 channel, polymer spine / full separator. Half shall not be accepted. Cable should be Armoured. Operates at bandwidth of 250 MHz, Conductor Solid Bare Electronic Grade Copper. Inner jacket should be PVC and outer should be PE, suitable for direct burial. Insulation: Polyethylene, Attenuation (< 36 db/100m), Pair – to – pair and PS NEXT, ELFEXT and PSELFEXT, Return Loss, ACR and PS ACR., Nominal Outer Diameter of Cable should be 9.70 mm and Conductor Diameter 0.56 mm (23 AWG), Cable should support operating Temperature from -20° to +60°C, Cable should come with printed sequential Length Counter on each meter, Cable support Conductor Resistance 93.5 OHMS/1000MTR@20 Degree, Mutual Capacitance of cable should be < 5.6nF/100m, Max Resistance Unbalance of cable should be 5% Max, Capacitance Unbalance of cable should max 330pF/100m, Cable support Delay Skew: < 45nS, Operating Voltage: 72V and NVP: 69%, Shall Supports Gigabit Ethernet (1000 base-T) standard and Operates at bandwidth of 250MHz complete along with erection of the same with connections, testing etc. complete in all respects as approved and desired by the Engineer-in-charge at site.
Electrical and General Mercantile Copr.
M/s Simran Enterprises
stage.html
html • 0.04 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .