Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹39.7 LAccepted-AOC | ₹39.7 L | L1 | Accepted-AOC L1 |
| 2 | L2₹42.3 L+₹2.6 L (6.62%)Rejected-AOC | ₹42.3 L+₹2.6 L (6.62%) | L2 | Rejected-AOC L2 |
| 3 | L3₹44.3 L+₹4.6 L (11.6%)Rejected-AOC PLOT NO 1235 JLPL SECTOR 82 SAS NAGAR MOHALI MOHALI PUNJAB 160055 | S A S NAGAR | PUNJAB | 160055 | ₹44.3 L+₹4.6 L (11.6%) | L3 | Rejected-AOC L3 |
Tender Value
₹44.7 L
EMD Value
₹89,440
Closing Date
17 Apr 2023, 5:00 pmClosed
O/O EXECUTIVE ENGINEER WSS DIV NO. 1 JALANDHAR
O/O EXECUTIVE ENGINEER WSS DIV NO. 1 JALANDHAR
DNIT for Provision of HVAC system in MGSIPA Regional Centre Building Near Divisional Commissioner Office at District Jalandhar Under Deposit Work
2023_WSS_98623_1
03-GOVTWORKS-2023
Open Tender
Civil Works
Item Rate
180 days
JALANDHAR
Please refer Tender documents.
2 documents required · 2 mandatory
₹1,000
₹89,440
18 Aug 2023
13 Mar 2023
18 Apr 2023
13 Mar 2023
17 Apr 2023
13 Mar 2023
Amount
PART-A
Variable Refrigerant Volume HVAC System Outdoor Units
Supply, Installation Testing and Commissioning of modular type Variable Refrigerant Volume type air- cooled outdoor units suitable for cooling and heating, having all hermeticaly sealed inverter type scroll compressor(s), minimum two compressors for above 14 HP modules, microprocessor based controller, top discharge type condensing units(s), with R410 A refrigerant, vibration isolators, with suitable foundation etc. complete as required. The unit shall deliver the rate capacity at AHRI conditions and work even at 50 deg C ambienttemperature without tripping. The unit shall be suitable to work on 400V+/- 10% 3 phase, 50 HZ AC power supply. The unit shall be filled with first charge of the refrigerant and ready for use as required. The COP at AHRI conditions shall not be less than 3.1 and IEER not less than 6.5
Outdoor Unit
Indoor Units
Supply Installation testing and commissioning of following minimum capacity 4 way flow VRV/VRF cassette type Indoor Units ceiling mounted unit equipped with synthetic washable media prefilter, fan section with low noise fan/dynamically balanced blower, multispeed motor, coil section with DX copper coil, electronic expeansion valve, outer cabinet, drain pump, grill, necessary supports, vibration isolation, cordless remote control etc. suitable for operation on single phase 230V+/-10%, 50Hz AC supply complete as required. The unit shall have automatic force shut down provision in case of fire on receiving signal from BMS system. The cooling capacity of indoor unit will be at inlet conditions of 27 degree C DB and 10deg C WB temperature.
The Drain pump as a standard accessory and shall be included in the price of Cassette/ FCU unit
3.3TR Cassette
4.13TR Cassette
Supply Installation testing and commissioning of Corded remote controls
Supply, installation, testing & commissioning of hi-wall split unit complete with refrigerant liquid line and insulated suction line piping with nitrile foam insulation(Upto 3 Rmt.), electrical cabling between condenser & evaporator, MS base frame / platform duly epoxy painted for indoor & outdoor units. (For Outdoor units weather protective paint to be provided after taking due approval.) along with suitable capacity stabilizers of 1.5 TR capacity. Brand\model shall be approved by the engineer incharge.
Hi wall AC 1.5 TR- Cooling and Heating
Hi wall AC 1.8 TR- Cooling and Heating
Insulated copper refrigerant insulated piping for suction and liquid line with cable. (Additional Piping)
Supply Installation, Testing and commissioning of Imported fittings (Ref Net) Y-joints etc as per specifications.
Refrigerant Piping for VRV units
Supply, Installation, testing and commissioning of Interconnecting refrigerant pipe work with (19 mm/ 13mm thick) closed cell elastomeric nitrile rubber tubular insulation between each set of indoor & outdoor units as per specifications, all piping inside the room shall be properly supported with MS hanger and all external piping shall run in covered cable tray as per specifications.
Note: The vendor has to get the route and sizing approved from the Consultant/ architect before starting the work at site.
28.6 mm O.D.(insulation : 19 mm)
22.2 mm O.D.(insulation : 13 mm)
19.1 mm O.D.(insulation : 13 mm)
15.9 mm O.D.(insulation : 13 mm)
12.7 mm O.D.(insulation : 13 mm)
9.5 mm O.D.(insulation : 13 mm)
Supply, Installation, testing and commissioning of UPVC piping as per IS-4985 of class 10kg/sqcm complete with fittings, supports as per specifications including cost of insulation 6mm thick complete
32 mm Dia
25 mm Dia
Cutting chase in brick walls in cement or in floor for embedding G.I. or C.I pipes line and making good the same to its original condition.
Size 75 mm x 75 mm
Cable Tray for Running Copper Refrigerant Piping up to 300 mm wide without cover, 16G
Cable Tray for Running Copper Refrigerant Piping up to 300 mm wide with cover, 16G
Control & Transmission Wiring
Providing & fixing control cum transmission wiring of 2 core x 1.5 sq. mm. copper in PVC conduits (heavy duty) between indoor and outdoor unit.
PART-B
VRV Control Panel
INCOMING SUPPLY
160 Amps ,3Pole MCCB,36KA with microprocessor release.The MCCB shall be having ICS=100% ICU = 1nos Make : Schneider/ Siemens/ABB
Spreader Link with phase Barriers = 4sets Make : Schneider/ Siemens/ABB
Rotary Mechanism = 1nos Make : Schneider/ Siemens/ABB
Auto Phase Sequence Section
ATS 160 Amps for Auto Phase sequence with SPP alongwith On delay timer and required equipment for the purpose of auto phase sequence Make of ATS : Socomec/HPL/Schnieder/L&T and allied material such as relay etc of Reputed Make
Metering Section
Control MCB SP C Curve= 3nos Make : Schneider/ Siemens/ABB
CT's 150/5 = 3nos Make: AE/Essma/Newtek/Selec
Indication Lamps LED Type RYB = 3nos Make : ABB/ Schneider/ Siemens/L&T/Reputed
Outgoing Feeder for 20 HP VRV Units - 3 nos
50-63Amps Pole MCCB,25 KA with Thermal magenetic release adjustable type.The MCCB shall be double break & the ICS=100% ICU = 3nos (for VRV unit 20 HP combination) Make : Schneider/ Siemens/ABB
Spreader Link with phase Barriers = 3 sets Make : Schneider/Siemens/ABB
Rotary Mechanism = 3nos Make : Schneider/ Siemens/ABB
Ampere Meter Digital class 1.0 Make of meter: Schnieder/Elmeasure/Selec/Reputed -3 nos
INDICATING LAMPS LED Type Make : ABB/ Schneider/ Siemens/L&T/Reputed
Control MCB SP C Curve for control Make : Schneider/ Siemens/ABB - 3 sets
CT's 60/5 Make: AE/Essma/Newtek/Selec- 3 sets
ELCB 63 Amps 300 MA Four Pole Make Siemens/Schneieder/ABB-3nos
Panel Enclosure
Fabrication of Powder Coated Enclosure made out of TATA/SAIL/ESSAAR/JINDAL/Reputed make CRCA sheet having 2 mm for load bearing surfaces & 1.6 mm for non load bearing surfaces ,duly processsed powder coated having Siemens grey colour. (Outdoor Type with weatherproof canopy design)
Assembly charges of Aluminium Bus Bar 250A TPN Electrolite grade E91 having cross section 1X25X10mm for Phase & 1X25x5 mm for Neutral & Current carring capacity 1 A/Sq. mm2. inclusive of Insulators, colour coded Heat shrinkable Insulation sleeve (RYBN)
Assembly of Hardware (PVC Channels/MCB Channels/Fibre-Glass/Gaskits/nuts/Bolts/washers/ Terminal blocks, etc)
Complete Wiring inclusive of control wiring, power wiring, Aluminium Solid connections/interconnections including insulators, thimbles,etc
VRV Control Panel
Part-C (Comprehensive Maintenance Charges)
Comprehensive Maintenance charges for VRV system including (routine and preventive maintenance with parts including consumables such as gas, oil, filters) and break down maintenance of high & low side of the air conditioning plant comprising of all the machinery during five years after expiry of two years defect liablity period.
3rd year (4.8% of Capital Cost)
4th year (5.4% of Capital Cost)
5th year (5.8% of Capital Cost)
UTILITY SERVICES
ACE COOLING SOLUTIONS
stage.html
html • 0.04 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .