Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | 1₹34.2 LAccepted-AOC NAGLA UDHA NEAR PRIMARY SCHOOL POST DHANOLI AGRA UP AGRA 282010 | AGRA | AGRA | UP | 282010 | 1 | Accepted-AOC Due to L-1 and credit | |
| 2 | 2₹39.2 L+₹4.0 L (11.3%)Rejected-Finance 111 YADAV ELECRIC MARKET GB MARG LUCKNOW LUCKNOW UTTAR PRADESH 226018 | LUCKNOW | UTTAR PRADESH | 226018 | 2 | Rejected-Finance Being other than L-1 | |
| 3 | 3₹47.1 L+₹11.9 L (33.8%)Rejected-Finance 9 NAROTTAM KUNJ MADHU NAGAR AGRA CANTT 282001 | AGRA | UTTAR PRADESH | 282001 | 3 | Rejected-Finance Being other than L-1 |
Tender Value
₹45 L
EMD Value
₹90,000
Closing Date
20 Jul 2024, 6:00 pmClosed
GE (AF) ADM AREA AGRA
GE (AF) ADM AREA AGRA
REPAIR REPLACEMENT OF LT UG CABLE , POLES BUSBAR, LT OH LINES AND OTHER CONNECTED WORKS AT 4 AREA UNDER GE(AF) ADM AREA AT AF STN AGRA.
2024_MES_661697_1
8000-2155/E8
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
GE (AF) ADM AREA AGRA
Please refer Tender documents.
4 documents required · 4 mandatory
₹500
GE (AF) ADM AREA AGRA
₹90,000
Yes
18 Sept 2024
24 Jun 2024
22 Jul 2024
24 Jun 2024
20 Jul 2024
8 Jul 2024
Amount
Excavating in trenches n.exc 1.5 m wide and n.exc 1.5 m in depth for foundation etc or for laying for cables etc n.exc 10 sqm on plan and getting out in any type of soil including removal of sand, bricks/PCC covers laid for cable proection complete all as specified and directed.
Returning, filling in, trenches including spreading, levelling, watering and well ramming in layers not exc. 25 cm in any type of soil complete all as specified and directed.
Removing surplus excavated material n.exc 50 m and depositing where directed at a level n.exc 1.5 m above the starting point complete all as specified and directed.
Supply and laying in replacement of brick, double walled corrugated (DWC) HDPE duct pipe conforming to IS 16205 Pt -24 of approved color complete with fittings for cable protection of size 94 mm outer dia and 110 mm inner dia complete all as specified and directed.
Supply and laying in replacement of brick, double walled corrugated (DWC) HDPE duct pipe conforming to IS 16205 Pt -24 of approved color complete with fittings for cable protection of size 63 mm outer dia and 50 mm inner dia complete all as specified and directed.
Materail and labour in replacement of GI tubing light grade of 50 mm dia for cable protection on pole/wall and drain etc complete with necessary clamp, nut, bolts and washers and socket and making good the disturbed surface of wall , floor or roof etc complete all as specified and directed.
Re-Laying XLPE LT UG cable PVC insulated , bedded armoured heavy duty electric cable 1100 volts grade with aluminium conductor of 16 to 70 Sqmm 3.5/4 Core including taking out old unserviceable LT UG cables of existing size from trenches, poles/walls and floor for removing of fault and use for relaying etc complete all as specified and directed.
Re-Laying XLPE LT UG cable PVC insulated , bedded armoured heavy duty electric cable 1100 volts grade with aluminium conductor of 95 to 240 Sqmm 3.5/4 Core including taking out old unserviceable LT UG cables of existing size from trenches, poles/walls and floor for removing of fault and use for relaying etc complete all as specified and directed.
Supply and Laying including testing in floor/trenches or fixed on pole/wall XLPE LT UG cable PVC insulated, bedded, galvanised steel strip or wire armoured heavy duty electric cable 1100 volts grade with aluminum conductor of 240 Sqmm 3.5 core , including taking out old unserviceable LT UG cables of existing size from trenches, poles/walls and floor for removing of fault etc complete all as specified and directed.
All as per Srl Item No 9 here-in-before but size of cable 185 Sqmm 3 & 1/2 Core
All as per Srl Item No 9 here-in-before but size of cable 95 Sqmm 3 & 1/2 Core
All as per Srl Item No 9 here-in-before but size of cable 50 Sqmm 3 & 1/2 Core
All as per Srl Item No 9 here-in-before but size of cable 25 Sqmm 3 & 1/2 Core
M & L for drilling suitable dia horizontal bore holes for insertion / laying of 50/100 mm bore GI tubing of any description below/under road surface/floors etc with using mechanical or manual devices as required at site including making good disturbed surface to match with the existing streta after laying pipes complete all as specified and directed
Clearing of bushes/small plants upto root level around and surroundings areas E/M installations (i.e.Two Pole/ Four structures, outdoor-substation yards,& other Misc E/M installations etc)soft and loose soil including removing debris to a distance n.exc 50m complete all as specified and directed.
M & L in replacement of existing unsv MCCB 400 Amps current carrying capacity 36 KA , AC 415 Volts, four pole with thermal and magnetic adjustable type setting complete all as specified and directed.
M & L in replacement of existing unsv MCCB 250 Amps current carrying capacity 25 KA , AC 415 Volts, four pole with thermal and magnetic adjustable type complete all as specified and directed.
M & L in replacement of existing unsv MCCB 200 Amps current carrying capacity 25 KA , AC 415 Volts, four pole with thermal and magnetic adjustable type complete all as specified and directed.
M & L in replacement of existing unsv MCCB 160 Amps current carrying capacity 25 KA , AC 415 Volts, four pole with thermal and magnetic adjustable type complete all as specified and directed.
Cutting the existing road/ Hard standing for passing pipe and making good the disturbed surfaces by using 15 mm thick and 300 mm widh 1:4:8 in foundation type D-2 ( using 40mm graded crushed stone aggregate) as in mass concrete complete all as specified exists complete all as specified and directed.
M&L in replacament of existing old unsv earthing complete with galvanised steel earth plate electrode, 600 x600 x 6mm thick burried directly in the ground (earth pit not less than 2.25 mtr deep below ground level) with top edge of the plate not less than 1.5mtr below ground level connected to galvanised strip 32x6 mm size as earthing lead by means of bolts, nuts, check nuts and washers of GI up to test point, GI tubing 15 mm bore medium grade protection pipe, GI watering pipe 20mm bore light grade with funnel and wire mesh, charcoal, salt complete all as per SSR with PCC chamber, 50mm thick RCC cover in 1:2:4 type B-1 using 20mm graded stone aggregate reinforced with 8mm dia TMT bar @ 80mm c/c both way including earth work in any type of soil , removal of surplus soil to a distance n.exc 50m and connecting , testing on completion all as shown on electric plate No 03 of SSR -2009 Part I complete all as specified and directed.(Note: Excavation and earth work is deemed to be included in the rates quoted).
Supply installation erection commissioning and testing in replacement of exiting unsv of LT panel board cubical out door type ( separate cable chamber on both side and Busbar fully covered) of suitable size for housing of all equipments & proper heat dissipation, CPRI approved weather/dust proof, factory made out of 3 mm thick CRCA sheet powder coated with front and back side openable with suitable cable chamber and front side shutters with locking arrangement panel base of angle iron 50x50x6 mm upto 45 cm height for 433 volts, 3 phase, 4 wire system including TPN Aluminium bus bar of rating not less than 1.5 times the rated capacity of the incomer MCCB. The TPN bus bar shall be insulated with colour coded heat shrinkable sleeves and shall be mounted on F class insulators. All interconnections between the main bus bar as well as outgoing feeders shall be carried out with TPN Aluminium bus bar of rating not less than 1.5 times rated capacity of of individual outgoing feeders. All control wiring shall be with FRLS PVC insulated 6 sqmm multi-stranded copper conductor and shall be properly bunched. The cubical shall have bottom channel of size 75 x 40 mm and complete mounted and fixed on PCC foundation above 0.45 mtr on floor and cable connection with suitable size of aluminium lugs and suitable size chrome plated glands provided for incoming and out-going cables comprising the following :- INCOMING MCCB a) 400 Amp 4 pole MCCB 36 KA breaking capacity with with thermal and magnetic adjustable type - 01 Nos. b) TPN aluminium bus bar of rating not less than 1.5 times OUTGOINGS MCCB a) 63 Amp 4 pole MCCB 25 KA breaking capacity withwith thermal and magnetic adjustable type - 10 Nos. Metering: a) AC digital voltmeter 0-500 volts Size 4"X4" b) 0-500 digital Amp meter 3 Ph suitable Size 4"X4" with CT c) LED Indicating lamps RYB set of three -01 Sets
M & L for dismantling the cable connections of four pole/ three pole Air circuit breaker of capacity upto 1000 Amps ,415 V 50 HZ of any existing make, strip opening the Air circuit breaker, inspecting the parts for serviceability/overhauling complete and carrying out the following repairs/maintenance :- a) Cleaning the insulation parts including bushings with CTC solution. b) Checking the alignment and condition of movable and stationary contacts and adjust them all as per manufacturer's instructional manual c) Check the bolts, nuts, washers, cotter pins and all terminal connections are in place and tights. Replace the worn-out parts. d) Check arc chutes for damage e) Clean and lubricate the operating mechanism with a light machine oil for pins and bearings and with a non-hardening grease for the wearing surfaces . Adjust breaker operating mechanism all as per manufacturer's instructional manual . f) Checking / inspecting shunt trip coil for serviceability and replacing the same if required. g) Checking control device free for operation. j) Check after servicing the circuit breaker to verify the contacts move to the fully opened and fully closed positions, that there is an absence of friction and that the electrical operation is functional
M&L for Straight through joints heat shrinkable for XLPE/PVC insulated and sheathed aluminium conductor under ground cable 3.5 core 70 sqmm to 150 Sqmm and testing after jointing complete all as specified and as directed.
M&L for Straight through joints heat shrinkable for XLPE/PVC insulated and sheathed aluminium conductor under ground cable 3.5 core 185 sqmm to 300 Sqmm and testing after jointing complete all as specified and as directed.
Dismantling of existing and supply and fixing Cross arms, bracings, supports, clamps and back plates fabricated from structural steel sections including nuts, bolts, anchor bolt , washers, welding, bending cold or hot, drilling holes for bolts, in any shape or size as indicated or directed and inclusive of one primer coat, one under coat and one finishing coat of paint complete all as specified and directed.
Supply and fixing in replacement of exiting unsv of LT panel board cubical indoor wall mounted type of suitable size for housing of all equipments & proper heat dissipation, weather/dust proof, factory made out of 2 mm thick CRCA sheet powder coated with front side openable with suitable cable chamber in side and front side shutters with locking arrangement panel base of for 433 volts, 3 phase, 4 wire system including provn of gland for cable and TPN Aluminium bus bar of rating not less than 1.5 times the rated capacity of the incomer MCCB. The TPN bus bar shall be insulated with colour coded heat shrinkable sleeves and shall be mounted on F class insulators. All interconnections between the main bus bar as well as outgoing feeders shall be carried out with TPN Aluminium bus bar / Cupper wire of rating not less than 1.5 times rated capacity of of individual outgoing feeders. All control wiring shall be with FRLS PVC insulated multi-stranded copper conductor and shall be properly bunched. The suitable size of aluminium lugs and suitable size chrome plated glands provided for incoming and out-going cables comprising the following :- Incommer :- 160 Amp 4 pole MCCB 25 KA breaking capacity with thermal adjustable type - 01 Nos. OUTGOINGS MCCB:- (1) 63 Amp TPN MCCB 16 KA breaking capacity with thermal adjustable type - 02 Nos. (2) 40 Amp TPN MCB 10 KA breaking capacity B curve typr type - 04 N (3) LED Indicating lamps RYB set of three -01 Sets (4) AC digital voltmeter and Ameter of sutable size. (5) Dial type DIN rail mounting, Analog Timer Switch 16 Amps suitable 240 Volt AC 50Hz, with battery back up up to 24 Hrs programmable type with 1 NO & 1 NC output contact - 01 No.
Supply and fixing inreplacement Digital Ameter 3 ph , LED display of size 96 X 96 mm accurancy -1 complete all as specified and directed.
Maintenance of LT panel disconnecting the all existing connection ,excavation of loop, removing the damange part of cable / taping on cable , cleaning the panel and dressing the cable including reconnction the cable complete all as specified and directed.
Removing the existing unserviceable duct cover from site and M/L RCC duct cover of size (70X60 X 7.5) cm made of RCC type B-1 (1:2:4) (20mm graded stone aggregate set in CM 1:4 with providing 10mm dia TMT bar @ 150mm C-C spacing complete all as specified and directed.
Removing the existing unserviceable duct cover from site and M/L RCC duct cover of size (110X60 X 7.5) cm made of RCC type B-1 (1:2:4) (20mm graded stone aggregate set in CM 1:4 with providing 10mm dia TMT bar @ 150mm C-C spacing complete all as specified and directed.
Supply , install, charge and connect test and commission of 30 V DC auxiliary power source wih 2 V lead acid cells for for protection of power control system comprising of the following all as standrand practice and as specified including dismantling old power pack system complete. Make :- Amron/Exide/ Tata) (a) 30 V / 250 AH VRLA battery pack consisting of lead acid cell batteries minimum 15 Nos with 2.3 V per cell in float charge condition 2 V per cell in boost charge condition complete with discharge duration of 10 hours. (b) DC buses of flat and of adequate cross section and length fixed to epoxy insulator supports as required. (c) Copper cable of adequate size and length from battery charger to bank of battery and battery bank to auxilary supply panel.
Supply and fix in replacement of battery bank charging unit of 30 volts 250 AH VRLA DC out put, 230 volts AC input including volt meter & Ammeter of suitable range including copper cable of adequate size and length from battery charger to battery bank to auxilary supply panel complete all as specified and directed. Make:- SCS/Luminous/Microtec/Apex
Supply, fixing and connection in replacement solid copper 2.5 Sqmm 12 core XLPE insulated , armoured, inner sheath PVC type control cable, XLPE as per IS -5831 including suitable size of copper lux, 1100 Volt complete all as directed by engr-in-charge.
Supply installation erection commissioning and testing in replacement of exiting unsv of LT panel board cubical out door type of suitable size for housing of all equipments & proper heat dissipation, cable chamber in both side CPRI approved weather/dust proof, factory made out of 3 mm thick CRCA sheet powder coated with front and back side openable with suitable cable chamber in side and front side shutters with locking arrangement panel base of angle iron 50x50x6 mm upto 45 cm height for 433 volts, 3 phase, 4 wire system including provn of gland for cable and TPN Aluminium bus bar of rating not less than 1.5 times the rated capacity of the incomer MCCB. The TPN bus bar shall be insulated with colour coded heat shrinkable sleeves and shall be mounted on F class insulators. All interconnections between the main bus bar as well as outgoing feeders shall be carried out with TPN Aluminium bus bar of rating not less than 1.5 times rated capacity of of individual outgoing feeders. All control wiring shall be with FRLS PVC insulated 6 sqmm multi-stranded copper conductor and shall be properly bunched. The cubical shall have bottom channel of size 75 x 40 mm and complete mounted or fixed on PCC foundation above 0.45 mtr on floor and cable connection with suitable size of aluminium lugs and suitable size chrome plated glands provided for incoming and out-going cables comprising the following :- INCOMING MCCB a) 320 Amp 4 pole MCCB 36 KA breaking capa with thermal and magnetic adjustable type - 01 No b) TPN aluminium bus bar of rating not less than 1.5 times OUTGOINGS MCCB a) 100 Amp 4 pole MCCB 25 KA breaking capacity with thermal adjustable type - 05 No Metering: a) AC digital voltmeter 0-500 volts Size 4"X4" b) 0-500 digital Amp meter 3 Ph suitable Size 4"X4" with CT c) LED Indicating lamps RYB set of three -01 Sets
Dismantling of existing meter panel board removing existig energy meter keeping safe custody and Design ,Supply, installation, testing and commissioning of indoor type wall mounting type Polycarbonate CPRI approved OEM made Meter Panel. The panel shall be made of modular POLYCARBONATE THERMOPLASTIC ENCLOSURES which should be UV resistance in accordance with IEC 61439-1, clause 10.2.4: The panel type wall mounted on mounting structure RAL 7016. The meter panel should be anti-acid & anti corrosive & fully transparant Door foor meter vision. Degree of protection against mechanical load should be IK08 (5 Joule) in accordance with IEC 62262. The manufacturer of panel shall submit a copy of CPRI TEST REPORT IN POLYCARBONATE only . DEGREE OF INGRESS PROTECTION IP65 IN ACCORDANCE WITH IEC 60529. The gasket should be internally embedded made of polyurethane and enclosure make . The manufacturer of board/panel SHALL submit a copy of TYPE TEST REPORT of a board made out of Polycarbonate thermoplastic panel in accordance with IEC 60439-1.
The CPRI test report shall have mention of following tests performed and passed out satisfactorily: Temperature Rise, Dielectric Properties, Short circuit withstand current – Rated peak & short time withstand current and Rated Conditional Short Circuit Current, Effectiveness of Protective Circuits. The board manufacturer must submit the copy of type test reports for Polycarbonate Thermoplastic Board only. Test Reports submitted of other material of construction like MS, SS will not be applicable. The panel should passed glow wire test 960oC in accordance with 60695-2-11 flame retardant and self-extinguishing including cutting , chasses of wall and making good surface complete all as directed with and incl the following (a) Provision for existing electric energy smart meter - 06 nos (b) Four pole MCCB 100 Amps with breaking capacity 25 KA having fixed thermal and fixed magnetic release and spreader link at both incoming and incomming side - 01 No. (c) MCB DP 32 Amp 10 KA , C Curve - 6 Nos (To be connected with 6 Nos Meters) (d) MCB DP 06 Amp 10 KA, C Curve - 1 No (For common lighting + Bldg Security Lights) (e) 14 Nos terminal blocks provided for output supply. (f) MCCB/MCB Nos Operated by flip Cover (g) LED Indicating lamp - 03 Nos. (h) Internal wiring with 1100 Volt grade 6.0 Sqmm FRLS PVC insulated multiflexible copper wire of sizes duly crimped with copper lugs of suitable size & type . Note : Re-fixed the energy meter in this new meter cabinet including all necessary electrical connection.
Dismantling of existing meter panel board removing existig energy meter keeping safe custody and Design ,Supply, installation, testing and commissioning of indoor type wall mounting type Polycarbonate CPRI approved OEM made Meter Panel. The panel approximate size (1580X1100X247)mm and shall be made of modular POLYCARBONATE THERMOPLASTIC ENCLOSURES which should be UV resistance in accordance with IEC 61439-1, clause 10.2.4: The panel type wall mounted on mounting structure RAL 7016. The meter panel should be anti-acid & anti corrosive & fully transparant Door foor meter vision. Degree of protection against mechanical load should be IK08 (5 Joule) in accordance with IEC 62262. The manufacturer of panel shall submit a copy of CPRI TEST REPORT IN POLYCARBONATE only . DEGREE OF INGRESS PROTECTION IP65 IN ACCORDANCE WITH IEC 60529. The gasket should be internally embedded made of polyurethane and enclosure make . The manufacturer of board/panel SHALL submit a copy of TYPE TEST REPORT of a board made out of Polycarbonate thermoplastic panel in accordance with IEC 60439-1.
The CPRI test report shall have mention of following tests performed and passed out satisfactorily: Temperature Rise, Dielectric Properties, Short circuit withstand current – Rated peak & short time withstand current and Rated Conditional Short Circuit Current, Effectiveness of Protective Circuits. The board manufacturer must submit the copy of type test reports for Polycarbonate Thermoplastic Board only. Test Reports submitted of other material of construction like MS, SS will not be applicable. The panel should passed glow wire test 960oC in accordance with 60695-2-11 flame retardant and self-extinguishing including cutting , chasses of wall and making good surface complete all as directed with and incl the following (a) Provision for existing electric energy meter - 08 nos (a) Four pole MCCB 125 Amps with breaking capacity 25 KA having fixed thermal and fixed magnetic release and spreader link at both incoming and incomming side - 01 No. (b) MCB DP 32 Amp 10 KA , C Curve - 8Nos (To be connected with 6 Nos Meters) (c) MCB DP 06 Amp 10 KA, C Curve - 1 No (For common lighting + Bldg Security Lights) (d) 18 Nos terminal blocks provided for output supply. (e) MCCB/MCB Nos Operated by flip Cover (g) LED Indicating lamp - 03 Nos. (j) Internal wiring with 1100Volt grade 6.0 Sqmm FRLS PVC insulated multiflexible copper wire of sizes duly crimped with copper lugs of suitable size & type . Note : Re-fixed the energy meter in this new meter cabinet including all necessary electrical connection.
Supply, erecting and fixing in true vertical position, steel tubular swaged pole (410 SP – 31), 09 meter long, complete with cast iron base plate, pole cap / finial taper plug, bolts, nuts and washers, welded reduced section and longitudinal weld throughout entire length of pole including 2 coats of black bituminous paint externally upto planting depth and remaining exterior portion of pole shall be painted with two coats of aluminum paint from 1.5 mtr above ground level to top of pole and a height of 1.5 mtr from the ground level synethetic enamel paint in alternate strips / layer (30 cm wide) with white and blue colour including taking out old unsv PCC pole complete all as specified and directed.
Material & Labour PCC 1:4:8 type D2 ( using 40mm graded stone aggregate) as in foundation, filling and mass concrete complete all as specified and directed.
Material & Labour PCC1:3:6 Type C2 (using 40mm graded stone aggregate) as in coping of poles etc. complete all as specified and directed.
S&F in replacement S&F Weather Proof thermo plastic (Polysterene) Cable Junction box , having protection class IP-66 and of overall size min (155 x 210 x 92) mm having metric knockouts on the wall, duly fixed with the pole with terminal (25x3mm) clamp, GI bolts, nuts, washers and 2 Nos polymide weather proof cable glands of cable sealing range 10mm to 17mm (Complete with check nut) and including cable Lugs 16 Sqmm -08 Nos complete all as specifed and directed .
S&F in replacement of Lithium based Energy Efficient integrated Solar street light of 40 Watt in single FRP body with duly polylurethane coating , encases with Monocrystalline solar PV Panel of 64/66 Wp, litium battery 11.1/12.8V, 36.0 AH with inbuilt BMS, IP65 high brightness W LED 160-180Lm/watt) lamp with Aluminium reflector , CRI>70, Colour Tempeture 5700K-6500K micro controller based charge controller cum driver automatic dimming function(First four hours at full brightness & rest of the at lower light level with PIR motion sensor), dust to dawn operation suitable to working tempreture -10C to +55C , wight more than 16-18 Kg with suitable size of GI bend pipe, adjustable MS clamp suitable for pole/wall mounting etc complete all as specified and directed.
S & F in replacement (garden light) Aesthetically designed decorative hot dipped galvanised mild steel step pole 4 Mtr long with grey powder finish. Compatible for post top light/ solar light . Window - Plasma cut & duly chamfered opening window for terminal connections & mounting accessories. Window cover is fitted with allen screws to the pole complete all as specified and directed. Make- Havells Cat part No- Pole 4 m (3480) , ORIENT Cat part No-OSL-CANPSPT072 or equivalent in Phlips / Crompton Greaves/ Bajaj
Supply and fixing inreplacement IDMT relay including necessary arangement for fixing of relay byusing MS sheet and making connection as per manufacturer instruction complete all as specified and directed. Make:- L&T Model No- MC-61 or equivalent Schneider/ ABB/C&S
Industrial Traders (BID ID -3068898)
M/s SCHOLASTIC ENTERPRISES (BID ID -3060204)
stage.html
html • 0.04 MB
tech_bid_open.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .