Loading…
Loading…
| # | Company | Amount | Status |
|---|---|---|---|
| 1 | ₹4.1 Craccepted-finance | ₹4.1 Cr | accepted-finance |
Tender Value
Refer Docs
EMD Value
₹6.3 L
Closing Date
21 May 2026, 10:00 pmClosed
Agriculture Produce Marketing Committee
SECRETARY
DEVELOPMENT OF RAITHA SANTHE AT HOLALKERE APMC LIMITS UNDER RIDF-31 SCHEME 2025-26
APMC/2025-26/BD/WORK_INDENT866/CALL-2
APMC/2025-26/BD/WORK_INDENT866/CALL-2
Open
Buildings
Two Tender Document System(Two Cover)
SECRETRAY APMC Office HOLALKERE
5 documents required · 5 mandatory
Minimum financial turnover (civil engineering construction works) not less than two times the annual payments from this contract (Rs. xxxxx Lakhs)
Satisfactoriy completed (atleast 90%) as prime contractor at-least one such similar work of value not less than Rs. xxxxxxx (80% of estimated cost of tender)
Executed in any one year the following minimum quantities of work (Cement Concrete - xxxx cum, Earthwork - xxxx cum, etc) (80% of peak rate of construction)
Tenderer or his identified Sub Contractor should possess valid Electrical License for executing building electrificatio works and should have executed similar electrical works totallng Rs. xxxxxx (not less than 50% of electrical works) n any one year
Tenderer or his identified Sub Contractor should possess valid license for executing water supply / sanitary engineering works and should have executed similar works totallng Rs. xxxxxx (not less than 50% of electrical works) n any one year
Owning the following key and critical equipment for this work (xxxx, xxxx, xxxx)
Liquid assets and /or availability of credit facilities of no less than Rs. xxxxxx Lakhs (estimated cash flow for 3 months of peak construction period)
Total value of civl engineering works executed and payments received in the last five years (year-wise)
List of existing commitments and ongoing works
List of works for which tenders already submitted
Banker Details for reference
Construction equipment owned by the tenderer and equipment proposed to be deployed on this contract, if awarded
Reports on the financial standing of the tenderer, such as profit and loss statements and auditor’s reports for the last five years
Qualification and experience of the key technical and management personnel in permanent employment with the tenderer and those that are proposed to be deployed on this contract, if awarded
List of Financial Resources with Certificates
TERMS AND CONDITIONS AS PER KW-4 DOCUMENT
₹5,000
₹6.3 L
21 May 2026
29 Apr 2026
25 May 2026
21 May 2026
7 May 2026
INTERNAL ELECTRICAL DETAIL
VEGETABLE MARKET BLOCK
EXTERNAL ELECTRICAL DETAIL
PART-A PROVIDING DOUBLE POLE STRUCTURE AT THE TAPPING POINT USING 9MTRS RCC POLES
PART-B EXTENSSION OF 11KV LINE FROM EXISTING FEEDER
PART-C ERECTION OF LT METRING CUBCLE
PART-D ERECTION OF 3-PHASE 11KV/433V,100KVA BEE-5 STAR RATED DISTRIBUTION TRANSFORMER YARD
DISCRIPTION
GROUND FLOOR
LIGHTING LOAD
RAWPOWER LOAD
UPS LOAD
TERRACE FLOOR
LIGHTING LOAD
UPS LOAD
PHE LOADS
DESCRIPTION/SPECIFICATION
Open Conduit System Supplying heavy gauge PVC conduit pipe …….dia .......mm thick confirming to IS 2509 with suitable size bends, junction boxes, adhesive paste etc., and fixing using inverted wood plugs in case of RCC ceiling and RCC wall / stone structure or rawl plugs in case of brick walls and cement plastering the damaged portion using heavy gauge saddles at an interval of 700mm using NF screws.
25mm dia 2mm thick. (KPWD ELE SR 23-24,P.N0.1 ,I.No. 1.1.2)
Concealed Conduit System Supplying heavy gauge PVC conduit pipe ……mm dia .......mm thick confirming to IS 2509 with suitable size bends, metal/PVC junction boxes, adhesive paste etc., and running before concreting the slab. The conduit should be tied to the reinforcement rods by using binding wires and unused ways of junction boxes and pipe ends should be covered using PVC end enclosures, run with 18SWG GI fish wire wherever necessary
19/20mm dia 2mm thick.(KPWD ELE SR 23-24,P.N0.1 ,I.No. 1.2.1)
25mm dia 2mm thick.(KPWD ELE SR 23-24,P.N0.1 ,I.No. 1.2.2)
32mm dia 2.5mm thick. (KPWD ELE SR 23-24,P.N0.1 ,I.No. 1.2.3)
Groove cutting in walls Supplying heavy gauge PVC Conduit Pipe ….dia ....mm thick with suitable size bends, metal junction boxes adhesive paste etc., by groove cutting in the wall and fixing by bracing U or J hooks and cement plastering up to the wall surface and run with 18 SWG GI fish wire run throughout the conduit wherever necessary.
19/20mm dia 2mm thick.(KPWD ELE SR 23-24,P.N0.1 ,I.No. 1.3.1)
25mm dia 2mm thick.(KPWD ELE SR 23-24,P.N0.1 ,I.No. 1.3.2)
32mm dia 2.5mm thick. (KPWD ELE SR 23-24,P.N0.1 ,I.No. 1.3.3)
Supplying andfixingsheetMetalboxmadeoutof18SWGsheet metal with necessary holes for cable/conduit entry as required with one coat of primer of approved make etc.
200 x 200 x 65 mm.(KPWD ELE SR 23-24,P.N0.1 ,I.No. 1.4.7)
Supplying and fixing PVC/metal conduit Deep junction box.
19/20 mm deep Junction box.(KPWD ELE SR 23-24,P.N0.2 ,I.No. 1.5.1)
25 mm deep Junction box.(KPWD ELE SR 23-24,P.N0.2 ,I.No. 1.5.2)
32 mm deep Junction box.(KPWD ELE SR 23-24,P.N0.2 ,I.No. 1.5.2)
Extra for Groove cutting in brick wall/CC floor to the suitable depth for concealing of Conduit/GI pipe and plastering, finishing upto wall surface complete.
upto 50mm conduit in brick wall.(KPWD ELE SR 23-24,P.N0.2 ,I.No.1.7.1)
upto 50mm conduit in CC floor.(KPWD ELE SR 23-24,P.N0.2 ,I.No. 1.7.2)
Supplying and fixing of PVC casing and capping on the wall or ceiling using necessary materials like bends, screws at an interval of 300mm …. etc. as required.
25mm.(KPWD ELE SR 23-24,P.N0.2 ,I.No. 1.8.2)
32mm.(KPWD ELE SR 23-24,P.N0.2 ,I.No. 1.8.3)
Supplying PVC flexible conduit pipe .... mm dia fixing on surface over inverted tapered wooden plugs or phill plugs or rawl plugs and clamped using heavy gauge saddles at an interval of 300 mm using NF screws and on either end of the pipe terminated completely
25mm.(KPWD ELE SR 23-24,P.N0.2 ,I.No. 1.9.2)
32mm.(KPWD ELE SR 23-24,P.N0.2 ,I.No. 1.9.3)
Supplying And Fixing Metal Fan Box with Round Hook.(KPWD ELE SR 23-24,P.N0.3 ,I.No. 1.13)
Point wiring using Copper wire without switch. Supplying and wiring adopting loop system in existing PVC Conduit /casing capping casing capping using 2x1.5Sqmm (Phase & Neutral) & 1x1.0 sqmm (Earth wire) FRLS multi strand PVC insulated copper wire (confirming to IS-694: and latest amendments) without control switch shall be fixed on the existing plastic sheet/ gang box, the other end of the wires shall be terminated with sufficient loose length in a wood/PVC round block. complete for each outlet.
Short point upto 3Mtr from tapping point to out let via switch.(KPWD ELE SR 23-24,P.N0.4 ,I.No.2.2.1)
Medium point above 3M. upto 6M from tapping point to out let via switch.(KPWD ELE SR 23-24,P.N0.4 ,I.No.2.2.2).
Long point above 6Mtr. upto 10M from tapping point to out let via switch.(KPWD ELE SR 23-24,P.N0.4 ,I.No.2.2.3).
Two outlet in a row, above 3Mtr upto 6Mtr from tapping point to out let via switches.(KPWD ELE SR 23-24,P.N0.4 ,I.No.2.2.4).
Three outlet in a row, above 6Mtr upto 10Mtr from tapping point to out let via switches.(KPWD ELE SR 23-24,P.N0.4 ,I.No.2.2.5).
Wiring for lighting/power circuit. using one of FRLS PVC insulated 1100V grade, multistrand copper wire with low conductor resistance single core in open or concealed system of wiring with specified IS-694:confirming to latest amendments.
1 sqmm.(KPWD ELE SR 23-24,P.N0.4 ,I.No.2.3.1).
1.5 sqmm.(KPWD ELE SR 23-24,P.N0.4 ,I.No.2.3.2).
2.5 sqmm.(KPWD ELE SR 23-24,P.N0.4 ,I.No.2.3.3).
4 sqmm.(KPWD ELE SR 23-24,P.N0.4 ,I.No.2.3.4).
6 sqmm.(KPWD ELE SR 23-24,P.N0.4 ,I.No.2.3.5).
Supplying and drawing Flexible Multicore Cable manufactured with electrolytic grade flexible copper with low conductor confirming to IS 8130-1984 and (Virgin) PVC insulation sheathed suitable for working voltage upto 1100V as per IS- 694:2010.
3C x 2.5 mm2.(KPWD ELE SR 23-24,P.N0.5 ,I.No.2.5.7).
Supplying and flush mounting powder coated / galvanized metal box suitable for mounting modular switch plates. The box should be firmly flush mounted after due groove cutting in Brick/Stone/C.C wall
3 Way.(KPWD ELE SR 23-24,P.N0.7 ,I.No.3.3.2).
8Way.(KPWD ELE SR 23-24,P.N0.7 ,I.No.3.3.5).
Supplying and flush mounting powder coated / galvanized metal box suitable for mounting modular switch plates. The box should be firmly flush mounted after due groove cutting in Brick/Stone/C.C wall.
1-2Way.(KPWD ELE SR 23-24,P.N0.7 ,I.No.3.4.1).
3Way.(KPWD ELE SR 23-24,P.N0.7 ,I.No.3.4.2).
4-5Way.(KPWD ELE SR 23-24,P.N0.7 ,I.No.3.4.3).
6Way.(KPWD ELE SR 23-24,P.N0.7 ,I.No.3.4.4).
8Way.(KPWD ELE SR 23-24,P.N0.7 ,I.No.3.4.5).
10-12Way(KPWD ELE SR 23-24,P.N0.7 ,I.No.3.4.6).
18 Way(KPWD ELE SR 23-24,P.N0.7 ,I.No.3.4.8).
Supplying and fixing superior quality modular switch mounting polycarbonate plate with necessary supporting back plate with required nos. of machine screws, bolts nuts etc., complete on the existing metal/PVC box.
1 to 2 Module.(KPWD ELE SR 23-24,P.N0.7 ,I.No.3.5.1).
3 Module.(KPWD ELE SR 23-24,P.N0.7 ,I.No.3.5.2).
4 Module.(KPWD ELE SR 23-24,P.N0.7 ,I.No.3.5.3).
6 Module.(KPWD ELE SR 23-24,P.N0.7 ,I.No.3.5.4).
8 Module.(KPWD ELE SR 23-24,P.N0.7 ,I.No.3.5.5).
12 Module.(KPWD ELE SR 23-24,P.N0.7 ,I.No.3.5.6).
18 Module.(KPWD ELE SR 23-24,P.N0.7 ,I.No.3.5.8).
Supplying and fixing of modular switch/ Socket/stepped electronic fan regulator/ dimmer/telephone socket etc on existing modular switch plate as per IS 3854 and IS 1293 .
6Amps one way.(KPWD ELE SR 23-24,P.N0.8 ,I.No.3.6.1).
6Amps 3way socket.(KPWD ELE SR 23-24,P.N0.8 ,I.No.3.6.3).
Stepped Fan Regulator Two Module.(KPWD ELE SR 23-24,P.N0.8 ,I.No.3.6.4).
16Amps one way switch.(KPWD ELE SR 23-24,P.N0.8 ,I.No.3.6.7).
32A DP Switch.(KPWD ELE SR 23-24,P.N0.8 ,I.No.3.6.9).
6/16Amps universal socket.(KPWD ELE SR 23-24,P.N0.8 ,I.No.3.6.10).
Supplying and fixing hylum plastic sheet 3mm thick with necessary nitches for fixing switches, regulators etc., and fixing on existing wood or metal box using N. F. screws.(KPWD ELE SR 23-24,P.N0.8 ,I.No.3.9).
Supplying 50mm wooden plug, tapered from 50x50mm to 25x25mm and fixing by using binding wire before concreting a roof slab(KPWD ELE SR 23-24,P.N0.8 ,I.No.3.12).
Supplying and fixing of metal clad industrial plugs and sockets.
2pole+earth 250V PLUG.32A.(KPWD ELE SR 23-24,P.N0.8 ,I.No.3.13.2).
3pole+earth 440V PLUG.32A.(KPWD ELE SR 23-24,P.N0.8 ,I.No.3.13.4).
2pole+earth 250V SOCKET.32A.(KPWD ELE SR 23-24,P.N0.8 ,I.No.3.13.6).
3pole+earth 440V SOCKET.32A.(KPWD ELE SR 23-24,P.N0.9 ,I.No.3.13.8).
Supplying And fixing/replacing of 6/16/32A electrical accessories on existing switch board.
6A Bakelite Ceiling Rose.(KPWD ELE SR 23-24,P.N0.9 ,I.No.3.14.5)
6A Batten Holder.(KPWD ELE SR 23-24,P.N0.9 ,I.No.3.14.7)
Supplying and fixing regular MCB distribution boards on wall / wood board / flush mounting using required clamps, bolts, nuts etc., with provision for fixing suitable type capacity MCB's single phase / 3 phase / single door with powder coated painting. Made out of 14 SWG MS enclosure. II - Double Door
8 Way SP & N(KPWD ELE SR 23-24,P.N0.17 ,I.No.5.19.3)
16 Way SP & N(KPWD ELE SR 23-24,P.N0.17 ,I.No.5.19.5)
4 way TPN.(KPWD ELE SR 23-24,P.N0.17 ,I.No.5.19.11)
Supplying and fixing miniature circuit breakers on existing MCB distribution boards using necessary fixing materials and 'C' Type curve, indicator ON/OFF, energy cross-3 with Short circuit breaking capacity of 10K and complete wiring as required confirming to IEC 60898.
5-32 Amps SP.(KPWD ELE SR 23-24,P.N0.16 ,I.No.5.18.1).
6-32 A DP.(KPWD ELE SR 23-24,P.N0.16 ,I.No.5.18.4).
40 A TPN.(KPWD ELE SR 23-24,P.N0.16 ,I.No.5.18.8).
50-63 A TPN(KPWD ELE SR 23-24,P.N0.16 ,I.No.5.18.9).
Supplying, fixing and wiring Residual current circuit breaker (RCCB) 240/450V upto 300mA sensitivity on existing wood/panel board.
16A-25A 2 pole.(KPWD ELE SR 23-24,P.N0.17 ,I.No.5.20.1).
1.1 kV, XLPE or Heat resistant PVC insulated, PVC exutruted Inner Seath Armoured LTUG Cable as per IS-1554 (Part 1) or IS-7098 Part-1, Armouring strip thickness and resistivity as per IS-3975. 16 Sqmm, 4 Core, (11 GI Strips - 4 x 0.8 mm)
1.1 kV, XLPE or Heat resistant PVC insulated, PVC exutruted Inner Seath Armoured LTUG Cable as per IS-1554 (Part 1) or IS-7098 Part-1, Armouring strip thickness and resistivity as per IS-3975.10 Sqmm, 2 Core, (9 GI Strips - 4 x 0.8 mm)
Laying of cable in Existing Trench/GI pipe/Stone Ware/RCC Hume pipe using Wooden/Aluminum Rollers as directed by the departmental staff.2.5 to 25 Sqmm
1.1 kV, XLPE or Heat resistant PVC insulated, PVC exutruted Inner Seath Armoured LTUG Cable as per IS-1554 (Part 1) or IS-7098 Part-1, Armouring strip thickness and resistivity as per IS-3975. 50 Sqmm, 4 Core, (17 GI Strips - 4 x 0.8 mm)
1.1 kV, XLPE or Heat resistant PVC insulated, PVC exutruted Inner Seath Armoured LTUG Cable as per IS-1554 (Part 1) or IS-7098 Part-1, Armouring strip thickness and resistivity as per IS-3975. 95 Sqmm, 3.5 Core, (21 GI Strips - 4 x 0.8 mm)
Laying of cable in Existing Trench/GI pipe/Stone Ware/RCC Hume pipe using Wooden/Aluminum Rollers as directed by the departmental staff.35 to 95 Sqmm
Heavy Duty Copper Terminal Long Barrel.16/25 Sqmm Copper Terminal, Apprx Wt: 11 Gm.
Heavy Duty Copper Terminal Long Barrel.50 Sqmm Copper Terminal, Apprx Wt: 26 Gm
Heavy Duty Copper Terminal Long Barrel.95 Sqmm Copper Terminal, Apprx Wt: 58 Gm
Brass Cable Gland 25mm.
Brass Cable Gland 40mm.
Supplying fixing and wiring earth electrode for grounding of lifts, transformers, DG sets etc. using 40 mm dia 2.9 mm thick 2.5m long GI pipe with GI funnel with mesh and suitable size reducer fixed on the top of the earth electrode.The funnel should be enclosed in a CC chamber of 400x400x400 mm with a cast iron cover. The earth electrode shall have staggered holes of 12 mm dia and the electrode should be covered 150 mm all-round with alternate layers of salt and charcoal from the bottom of the CC chamber. The connection from the electrode is to be established through GI strip using GI bolts and nuts.(KPWD ELE SR 2023-24,P.No.54, I.No.12.56)
Supplying and running GI/Copper conductor for grounding and (along with other wires in conduit system of wiring) using necessary suitable size clamps, nails, guttas/spacers etc.
8 SWG. Copper Wire .(KPWD ELE SR 2019-20,P.No.54, I.No.6.18.6)
Supplying and running of GI/Copper strips for grounding connections, using necessary fixing materials as required.
GI strip GI Strip. 25x3mm (KPWD ELE SR 2023-24,P.No.54, I.No.12.58.1)
25 x 3 mm Copper strip (KPWD ELE SR 2023-24,P.No.54, I.No.12.58.7)
600 x 600 x 3 mm Copper plate (KPWD ELE SR 2023-24,P.No.54, I.No.12.58.11)
2 mm thick perforated cable GI tray with on existing MS angle support using necessary GI bolts/nuts and washer or welding as required.
300 x 50 mm (KPWD ELE SR 2023-24,P.No.54, I.No.12.59.2)
LED Indoor Supplying of 2' feet - LED PVC Square Batten ..W with high quality diffuser with Life of 25000 burning hours & 70% lumen maintenance with CRI > 80. Power Input: 220-240V @ 50Hz & Power factor >0.9 along with CE approved drivers. 5 years Warranty against any manufacturing defect working under standard electrical condition
LED light fitting 1 x 4' - 20/22 W(KPWD ELE SR 23-24,P.N0.42 ,I.No.11.3.2).
LED light fitting 1 x 4' - 36/40 W(KPWD ELE SR 23-24,P.N0.42 ,I.No.11.3.3).
Supplying of recess/surface mounting non integrated type LED down light ...... W luminaire comprising of pressure decast/ extruded aluminium housing, with spring loaded false ceiling clamps, LED of Power/COB with CCT 6500 degree K, CRI> 70%. efficacy >100 lumen per watt, 120degree beam spread, life> 25000 burning hours and Compliance to IS 10322/IEC 60598, LM 79 & LM 80. The lamp compartment is enclosed with anti glare opal diffuser which enhances the lighting level. LEDs are driven by HF electronic driver integrated in a separate control gear assembly., with PF >0.95, power loss should < 5% of lamp wattage., short circuit & open circuit protection to be integrated in the circuit,THD less than 20%, Life as per LM 79. The operating input voltage should be between 130 to 275 volts. BIS Approved and Tested by NABL/CPRI accredited laboratory with 2 years Warranty against any manufacturing defect working under standard electrical condition.
15-18W (KPWD ELE SR 2023-24,P.No.43 I.No 11.4.3)
Supplying of Ceiling Fan with Capacitor rating As per guideline of BEE 5 star rating and IS:374/79 and also comply with IS:1709/1984 with latest amendment, Rated voltage 220 V/ 50 Hz, Rated power input 48 W +/- 10 %, Rated current As per IS:374/79, Rated power factor 0.9 lagging(min), Rated speed 350 +/- 10% RPM, Rated air delivery 210 +/- 10% Cubic Meter Minimum, Rated service value ≥ 4.2 CMM / Watt, Three Blades of blade leaf 1.05mm thick Aluminium Alloy sheet, Class B motor insulation,Bearing Two ball bearings, Top 6202, Bottom 6201 , as per IS specification, Motor wdg. Temp rise Shall not exceed 75 degC over and ambient of 40 0C by resistance method at 245Volts, Insulation resistance Shall not be less than Two Mega Ohms (2 M Ohms), Leakage current Should not exceed 210Micro Amp, Power input, watt& current , Air Delivery & Fan Speed as per IS:374/1979 with latest amendment, 2 year manufacturer Warranty
48" Sweep 5 Star (1200mm)(KPWD ELE SR 2023-24,P.No.29 I.No 6.4.1)
Supply of LED Streetlight luminaire with pressure die cast aluminium housing body for optimal thermal dissipation.Lamp compartment comprising of anti glare clear diffuser with Injection moulded polycarbonate material, delivering superior light output. Rated life Burning Hrs 50000 hr @ Lumen Maintenance of 70%, maximum light intensity should be between 60 degrees to 70 degrees. CCT > 5500K, IP 66 optical and electrical compartment & impact resistance of complete luminaire > IK08. Power Factor >0.9 with mains, Surge Protection- Min 5KV along with Over voltage/ Overload, short circuit/ miss-wiring protection. Compatible for pole mouting with outer dia of 40mm to 50mm. Universal Voltage driver to operate wide voltage range from 100V to 270V 50/60Hz application. Compliance to IS 10322/IEC 60598, LM 79 & LM 80 Adherence with RoHS. UL approved MCPCB. Top access street light with single screw to ensure ease of maintenance at the sight site location with minimized minimal tools. LED Light fixture with ........W System Power consumption. LED Efficiency>130lm/w, nominal CRI >75. Luminaire manufacturer should have in-house facility accredited by NABL/CPRI & any Government certified agency & Design & Development facility certified by ISO 9001:2008 . Housing with supplier word mark /name shall be Engraved / Embossing on the die cast housing/ Body part. Warranty of 2 Years against any manufacturing defect working under standard electrical conditions as mentioned above should be given by LED manufacturer & Cree/Nichia/ Lumileds/Osram make LED Source.LED Streetlight
LED Streetlight 90 W (KPWD ELE SR 2023-24,P.No.45. I.No 11.8.4)
Supplying and Fixing........mm dia class A GI pipe bracket up to 2.7 meters long terminated with a reducing collar of 40x25mm to which extra pipe of 175mm length is fixed forfixing MV/SV/MH/FTL street light fitting of all capacities on rail/RCC/wall/tubular pole, using suitable clamps, bolts, nuts and wiring using suitable capacity wires.
25mm dia GI pipe. (KPWD ELE SR 2023-24,P.NO.55,I No13.2.1)
Fixing halogen/metal halide / SVL / IL / LED floodlight fitting over existing pole / wall ceiling including clamps, bolts, nuts and wiring using suitable capacity wires(KPWD ELE SR 2023-24,P.NO.55,I No 13.5)
Supplying and fixing of 4 pole power contactor with NO/NC contacts on existing wood/panel boaard using necessary bolts,nuts, washers and wiring etc., completee with ac-3 rating and as per IS-13947 40 Amps.
Supply and Installation / Fixing / Provision of Outdoor type Thermoplastic Modular Panel enclosure with transparent Polycarbonate Lid, shock proof, IP65 (Weather Proof), rust proof, dust proof, water proof, corrosion proof having internally Embedded gasket on both lid and flap suitable to fix Single Phase / Three Phase Energy Meter in suitable base plate and having a provision for Fuse / MCB cutout with suitable transparent hinged flap opening for operating MCB along with complete tamper proof SEALING facility.600mmx600mmx170mm.
Supplying and fixing Microprocessor Based Astronomical timer Switch with using necessary bolts, nuts and washers.
Fixing all types and all capacities of fluorescent / false ceiling/ spot light / CFL / LED fittings indoor on the wall / ceiling /rafters / girders using 23/0.0076” twin twisted PVC insulatedwires, required Nos of round blocks and clamps.
On wall/ ceiling / Rafter / Girders (KPWD ELE SR 2023-24,P.NO.55,I No13.7.1)
Fixing a ceiling / wall mounting fan of all capacities and all types, with necessary clamps and 'S' hook made out of 15mm dia MS rod, with 5 amps. ceiling rose of approved quality with necessary length of 23 / 0.0076 inch PVC insulated twin twisted wire of approved quality, mounted on a suitable size wooden board and wired.(KPWD ELE SR 2023-24,P.NO.56,I No13.11)
Fabricating supplying and mounting MS box made out … SWG suitable for floor / wall mounting, fully weather proof with provision for better heat dissipation, provided with hinged front cover, equipped with tamper proof locking arrangements, with suitable size clamps with necessary cable entry pipe with gland and box should be finished with 2 coats of red oxide primer paint and finally finished with approved colour enameled metal paint etc., complete.14SWG
14SWG (KPWD ELE SR 2023-24,P.No.20, I.No.5.42.1)
Supplying ......... amps rated 3phase with neutral bus bar using required capacity electrolytic aluminum strips covered with heat shrinkable coloured PVC sleeve, mounted on phenolic/FRP/DMC insulator which are mounted on powder coated 40x6mm M.S.flat frame work in existing panel board. The bus bar shall have suitable holes for termination of incoming and outgoing cables as per IS specification with necessary bolts, nuts and washers etc., complete.250Amps 4x30x10mm Aluminium Strips
250Amps 4x30x10mm Aluminium Strips(KPWD ELE SR 2023-24,P.No.20, I.No.5.40.2)
Supplying and fixing angle iron frame work fabricated out of M.S. angle iron.. and M.S. flat … with bolts, washers etc., and painted with 2 coats of red oxide and then two coats of approved paint
40*40*6mm (KPWD ELE SR 2023-24,P.No.20, I.No.5.41.1)
Supplying and fixing angle iron frame work fabricated out of M.S. angle iron.. and M.S. flat … with bolts, washers etc., and painted with 2 coats of red oxide and then two coats of approved paint.
50X100X50X6mm C channel 50*6mm (KPWD ELE SR 2023-24,P.No.20, I.No.5.41.4)
Supplying of on load change over switches 4 poles, AC- 23A Duty, 415V, 50Hz, AC Supply. With all accessories. (SM Enclosure Sheet Metal Execution)
200 A (KPWD ELE SR 2023-24,P.No.17, I.No.5.12.4)
Supplying and fixing Moulded Case Circuit Breaker(MCCB) over theexisting wood/panel board using necessary screws,bolts,nuts,necessary phase separators,handle and wiring complete.Protection of Over load and Short circuit with adjustable thermal magnetic release,Microprocessor release shall have Earth Fault as per IS/IEC60947 2.(Icu=100%lcs).In 4P MCCB,all Poles should have protection for Short Cicrcuit / Over Load. For Microprocessor MCCBS Facility for segregating Priority and Non Priority loads must be available in the MCCB.MCCB shall be provided with double insulation(insulation between front cover and internal power circuits to avoid any accidental contact with live current carrying path with the front cover open)Multi-pole breakers shall be designed to break all the poles simultaneously and they shall have a single mechanism.
160 A 25 kA (KPWD ELE SR 2023-24,P.No.17, I.No.5.15.11)
Supplying and fixing Moulded Case Circuit Breaker(MCCB) over theexisting wood/panel board using necessary screws,bolts,nuts,necessary phase separators,handle and wiring complete.Protection of Over load and Short circuit with adjustable thermal magnetic release,Microprocessor release shall have Earth Fault as per IS/IEC60947 2.(Icu=100%lcs).In 4P MCCB,all Poles should have protection for Short Cicrcuit / Over Load. For Microprocessor MCCBS Facility for segregating Priority and Non Priority loads must be available in the MCCB.MCCB shall be provided with double insulation(insulation between front cover and internal power circuits to avoid any accidental contact with live current carrying path with the front cover open)Multi-pole breakers shall be designed to break all the poles simultaneously and they shall have a single mechanism.
100 A 25 Ka (KPWD ELE SR 2023-24,P.No.17, I.No.5.15.9)
Supplying and fixing of Shunt trip suitable for MCCB.CBCT
Supplying and fixing miniature circuit breakers on existing MCB distribution boards using necessary fixing materials and 'C' Type curve, indicator ON/OFF, energy cross-3 with Short circuit breaking capacity of 10K and complete wiring as required confirming to IEC 60898.6-32 Amps SP.
Supplying and fixing miniature circuit breakers on existing MCB distribution boards using necessary fixing materials and 'C' Type curve, indicator ON/OFF, energy cross-3 with Short circuit breaking capacity of 10K and complete wiring as required confirming to IEC 60898.6-32 Amps DP
Supplying and fixing miniature circuit breakers on existing MCB distribution boards using necessary fixing materials and 'C' Type curve, indicator ON/OFF, energy cross-3 with Short circuit breaking capacity of 10K and complete wiring as required confirming to IEC 60898.6-32 Amps TPN.
Supplying and fixing miniature circuit breakers on existing MCB distribution boards using necessary fixing materials and 'C' Type curve, indicator ON/OFF, energy cross-3 with Short circuit breaking capacity of 10K and complete wiring as required confirming to IEC 60898.40 Amps TPN.
Supplying and fixing miniature circuit breakers on existing MCB distribution boards using necessary fixing materials and 'C' Type curve, indicator ON/OFF, energy cross-3 with Short circuit breaking capacity of 10K and complete wiring as required confirming to IEC 60898.50-63 Amps TPN.
Supplying, fixing and wiring earth leakage relay with core balanced current transformer suitable for single phase 50 Hz AC with latest microcontroller based, digital readout of percentage leakage current, programmable delay/auto/ manual reset facility suitable to mount on DIN rail/ flush mounting on panel board
Supplying of multi function digital meter with three line back light LCD type display for voltage, Current, frequency, Power, power factor, KVA, KWH,KVAR suitable for 3 phase, 4 wire LT network with IP 54 degree of protection and completely wired as required with communication Port and Class 0.5s accuracy
Supplying, fixingandwiring50/5to400/5A5VAburdenCurrent Transformer Class 0.5 accuracy with Tape Wound..
Supplying and fixing of LED type panel board indicating lamp with required colour suitable for 220v A.C. 50 Hz 12/24v D.C.
Supplying and fixing Trivector Meter suitable for operation LT operation and -CT operated meter in polycarbonate body in class 0.5 accuracy as per IS 14697 and completely wired.
Supplying and fixing of 3 pole power contactor with NO/NC contacts on existing wood/panel boaard using necessary bolts,nuts, washers and wiring etc., completee with ac-3 rating and as per IS-13947 25 A
Supplying, fixing and wiring heavy duty low voltage capacitors conforming to IS 2834. 3 phase, 400/440 V grade, for power factor improvement of rotating machineries likeinduction motor.
Supplying, fixing and wiring Automatic Power Factor controller circuit unit fully, static units controlled by 14 stage microprocessor operation, relays LED display, self programming function for power stages and operating logic checking facility for healthy and efficient of each individual capacitor bank, measurement of network harmonics with indication when limit values are exceeded, Comprehensive displays with large, three phase LED display, Long term memory for settings, protection for over voltage, power factor correction fault and no voltage, to connect/ disconnect banks, with automatic recognition or with standard programs.
Supply and fixing of Auxiliary contactor relay with 2 NO and 2 NC contact and operating coil voltage of 220V to 260V. fixed on existing wood/panel board using necessary bolts, nuts, washers and wiring etc.,
Supplying & fixing of Porcelain fuse channel with cut out on existing wooden/panel using necessary nuts, bolts and washers. .16Amps
Supplying, fixing and wiring Electronic Trivector Meter (ETV) 5 to 20Amps single phase Class-1 Accuracy with Temper Proof Energy Meter
Supply and Installation / Fixing / Provision of Outdoor type Thermoplastic Modular Panel enclosure with transparent Polycarbonate Lid, shock proof, IP65 (Weather Proof), rust proof, dust proof, water proof, corrosion proof having internally Embedded gasket on both lid and flap suitable to fix Single Phase / Three Phase Energy Meter in suitable base plate and having a provision for Fuse / MCB cutout with suitable transparent hinged flap opening for operating MCB along with complete tamper proof SEALING facility.. 300mmx300mmx214mm
Supplying, erecting, testing & commissioning of ON-LINE UPS system suitable for operation on 230V, 50Hz, A/C supply, with isolation transformer all accessories complete and Excluding batteries and wiring complete.
10 kVA ON LINE UPS (KPWD ELE SR 2023-24,P.No.37, I.No.9.3.5)
Supplying, installation, testing & commissioning of 12V DC, AH batteries in poly propylene container for U.P.S. Sealed maintenance free batteries..
120 AH capacity(KPWD ELE SR 2023-24,P.No.37, I.No.9.5.8)
DESCRIPTION
9 mtrs RCC DP structure using 9 mts RCC Poles. CDS-15, Item no 1
11kV 5KN polymeric Pin Insulator (24mm dia FRP Rod). ESCOM SR Item no 6.06
11 KV 45KN Polymeric(Disc) Insulators. CDS-15, Item no 3
GUY Sets with NO 15 Strain insulators and covering material. CDS-15, Item no 4
Spiral earth electrode. CDS-15, Item no 5
Caution/Danger Boards. CDS-15, Item no 7
Anti Climbing Device(12mtrs/1Kg GI Barbed Wire ) CDS-15, Item no 8
Concreting Material for Guy Set. CDS-15, Item no 6
11KV 200Amps SINGLE break GOS. ESCOM SR Item no 24.01
H frame for mounting GOS. CDS-15, Item no 10
11 kV Lightning Arrester, Metal Oxide 10 kV, 5 kA, Polymetic type with ground disconnector (Set of three nos) CDS-26, Item no 13
Earthing materials pipe type for grounding as per Drawing No. BESCOM/GM/CP/15 & 34/Dt: 24.10.07. CDS-26, Item no 7
DOLO cutout(set/3nos). CDS-15, Item no 11
Concreting Material for 9mtrs RCC DP structure
base concreting cc 1:2:4,650x650x150mm. CDS-28, Item no 9a
pole concreting cc 1:2:4,650x650x1700mm. CDS-28, Item no 9b
Coping 1:2:4 (as per actual). CDS-28, Item no 9c
Rabbit ACSR Conductor with 1.5% sag. ESCOM SR Item no 7.02
Erection of 9 mtrs RCC DP structure using 9 mts RCC Poles. CDS-15, Item no 1
Erection of GUY Sets with NO 15 Strain insulators and covering material. CDS-15, Item no 4
Erection of spiral earth electrode. CDS-15, Item no 5
Fixing ofCaution/Danger Boards. CDS-15, Item no 7
Fixing of Anti Climbing Device(12mtrs/1Kg GI Barbed Wire ). CDS-15, Item no 8
11KV 200Amps SINGLE break GOS. ESCOM SR Item no 13.02
Fixing of H frame for mounting GOS. CDS-15, Item no 9
11 kV Lightning Arrester, Metal Oxide 10 kV, 5 kA, Polymetic type with ground disconnector (Set of three nos). CDS-26, Item no 13
Erection of Earthing materials pipe type for grounding as per Drawing No. BESCOM/GM/CP/15 & 34/Dt: 24.10.07. CDS-26, Item no 7
Fixing of DOLO cutout(set/3nos). CDS-15, Item no 11
Rabbit ACSR Conductor accesaries at 3%on above. CDS-15, Item no 6.02
GRAND TOTAL AMOUNT IN RS
DESCRIPTION
Supply of 11 kV, 3 Core, XPLE HTUG Cable with pressure extruded inner sheeth, ROUND WIRE ARMOURED as per IS-7098 (Part-2) Armouring wires dia and Resistivity as per IS-3975. 95 Sqmm, (54 GI Wires - 2.5 mm Dia).
Supply of Heat Shrinkable Indoor Type Cable Termination Kit for XLPE Cable.3Cx95sqmm indoor.
Supply of Heat Shrinkable Outdoor Type Cable Termination Kit for XLPE Cable 3Cx95sqmm outdoor.
Supply of Cable covering tiles 250x125x40mm..
Supply of M sand.
Supply of RCC humepipes 2000mm long 150mm dia.
Supply of Collars for RCC hume pipes.
Supply of GI pipe 150mm dia.
Supply of Route and Joint indicating stones with MS Anchor rod.
Laying of cable in Existing Trench/GI pipe/Stone Ware/RCC Hume pipe using Wooden/Aluminum Rollers as directed by the departmental staff.3x95 to 150 Sqmm.
Making and Fixing pot head for HT Cable only.Heat shrinkable Type Terminations.3x95 to 3x150 Sqmm.
Covering the cables with tiles.
Spreading and forming with sand alround the cable to a depth of 75mm and width of 500mm .
Laying and Jointing the pipes (100-150 mm Dia) including lowering in Position: Fixing Collars etc., Joining with mud mortor complete.RCC Pipe..
Laying the GI Pipe 80 mm to 150 mm dia at Drainage Water Supply Crossing including fixing collars elbows, bends, Tees and other fitting with Cuts and Threads wherever necessary complete..
Fixing of Route Joint Indicating Slab..
GRAND TOTAL AMOUNT IN RS
DESCRIPTION
Providing Electronic Trivector Meters with Associated CT's Metering Box etc., on LT Side of Distribution Transformer Center.LT CT's 0.5 Accuracy Class Ring Type Ratio 150/5 for 100 kVA DTC.
Fixing of Electronic Trivector Meters with Associated CT's Metering Box etc., on LT Side of Distribution Transformer Center.LT CT's 0.5 Accuracy Class Ring Type Ratio 150/5 for 100 kVA DTC.
supply of Electronic Trivector Meter 3 Phase, 4 Wire, 0.5 Accuracy Class.
fixing of Electronic Trivector Meter 3 Phase, 4 Wire, 0.5 Accuracy Class.
supply of Weather Proof, Verming Proof LT Metering Box with clamping arrangement for mounting on the Transformer structure with necessary terminal strip and CT mounting arrangement for housing the ETV Meters and connecting to the existing ground.
fixing of Weather Proof, Verming Proof LT Metering Box with clamping arrangement for mounting on the Transformer structure with necessary terminal strip and CT mounting arrangement for housing the ETV Meters and connecting to the existing ground.
GRAND TOTAL AMOUNT IN RS
DESCRIPTION
9 mtrs RCC DP structure using 9 mts RCC Poles. CDS-26, Item no 1
11kV 5KN polymeric Pin Insulator (24mm dia FRP Rod). CDS-26, Item no 2
11 KV 45KN Polymeric(Disc) Insulators. CDS-26, Item no 3
GUY Sets with NO 15 Strain insulators and covering material. CDS-26, Item no 4
Spiral earth electrode. CDS-15, Item no 5
Caution/Danger Boards. CDS-26, Item no 8
Anti Climbing Device(12mtrs/1Kg GI Barbed Wire ). CDS-26, Item no 9
Concreting Material for Guy Set. CDS-26, Item no 10
11KV 200Amps SINGLE break GOS. CDS-26, Item no 16
H frame for mounting GOS. CDS-15, Item no 10
11 kV Lightning Arrester, Metal Oxide 10 kV, 5 kA, Polymetic type with ground disconnector (Set of three nos). CDS-26, Item no 13
Earthing materials pipe type for grounding as per Drawing No. BESCOM/GM/CP/15 & 34/Dt: 24.10.07. CDS-26, Item no 7
DOLO cutout(set/3nos). CDS-15, Item no 11
Concreting Material for 9mtrs RCC DP structure.
base concreting cc 1:2:4,650x650x150mm. CDS-28, Item no 9a
pole concreting cc 1:2:4,650x500x1700mm. CDS-28, Item no 9b
Coping 1:2:4 (as per actual). CDS-28, Item no 9c
Supply of 11kV/433V, 100 kVA, 3 Phase, 50 Cys Distribution Transformer BEE - 5 Star Rated with Oil. CDS-26, Item no 6
Erection of 9 mtrs RCC DP structure using 9 mts RCC Poles. CDS-26, Item no 1
Erection of GUY Sets with NO 15 Strain insulators and covering material. CDS-26, Item no 4
Erection of spiral earth electrode. CDS-15, Item no 5
Fixing of Caution/Danger Boards. CDS-26, Item no 8
Fixing of Anti Climbing Device(12mtrs/1Kg GI Barbed Wire ). CDS-26, Item no 9
11KV 200Amps SINGLE break GOS. CDS-26, Item no 16
Fixing of H frame for mounting GOS. CDS-15, Item no 11
11 kV Lightning Arrester, Metal Oxide 10 kV, 5 kA, Polymetic type with ground disconnector (Set of three nos). CDS-26, Item no 13
Erection of Earthing materials pipe type for grounding as per Drawing No. BESCOM/GM/CP/15 & 34/Dt: 24.10.07. CDS-26, Item no 7
Fixing of DOLO cutout(set/3nos). CDS-15, Item no 11
GRAND TOTAL AMOUNT IN RS
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
IMG_0001.pdf
Others - TENDER NOTIFICATION • 1.10 MB
HOLALKERE_RAITHA_SANTE_EST_24-2-26.pdf
Others - CIVIL WORK ESTIMATE • 0.45 MB
HOLLALKERE RIDF-31 KW-4.docx
Instructions to Tenderers • 0.14 MB
Updated_24-2-26_HOLALKERE_SANTHE__ELE_BOQ.xlsx
Others - ELECTRICAL ESTIMATE • 1.65 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .