| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹30.4 LAccepted-AOC 58 B T ROAD KOLKATA 700 002 | KOLKATA | KOLKATA | WEST BENGAL | 700002 | L1 | Accepted-AOC L1 bidder | |
| 2 | L2₹36.0 L+₹5.6 L (18.3%)Rejected-Finance 19 LAKE TEMPLE ROAD KOLKATA 700 029 | KOLKATA | KOLKATA | WEST BENGAL | 700029 | L2 | Rejected-Finance Rejected_Fin | |
| 3 | L3₹40.1 L+₹9.6 L (31.6%)Rejected-Finance 11TH FLOOR ECO CENTRE BUSINESS TOWER P NO 4 EM BLOCK SECTOR V KOLKATA 91 | KOLKATA | 24 PARAGANAS NORTH | WEST BENGAL | 700091 | L3 | Rejected-Finance Rejected_Fin | |
| 4 | L4₹40.1 L+₹9.7 L (31.8%)Rejected-Finance 2ND FLOOR 39 4166 SHEMA BUILDING M G ROAD RAVIPURAM KOCHI ERNAKULAM KERALA 682016 | KOCHI | ERNAKULAM | KERALA | 682016 | L4 | Rejected-Finance Rejected_Fin | |
| 5 | Rejected-Technical 117 A MULLICK COLONY KOLKATA 700 036 | KOLKATA | KOLKATA | WEST BENGAL | 700036 | - | Rejected-Technical Disqualified in technical evaluation |
Tender Value
₹32 L
EMD Value
₹64,000
Closing Date
29 Apr 2024, 6:55 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
O/O Exe. Engr, Kolkta South Health El. Divn, PWDte
75 D H Road Khidderpore Kolkata 23
SITC of Airconditioning System at 4th floor of New Casualty Building inside Sambhu Nath Pandit Hospital Annex II of IPGMER SSKM Hospital
2024_WBPWD_676194_1
WBPWD/EE-I/KSHED/Q89/23-24
Open Tender
A/C ORG
Item Rate
60 days
Sambhu Nath Pandit Hospital Kolkata
Please refer Tender documents.
3 documents required · 3 mandatory
₹64,000
O/O Exe. Engr, Kolkta South Health El. Divn, PWDte
4 Apr 2025
28 Feb 2024
2 May 2024
28 Feb 2024
29 Apr 2024
7 Mar 2024
22 Apr 2024
Amount
SUB-HEAD 1--CEILING SUSPENDED AIR HANDLING UNIT
SITC of Factory designed Ceiling Suspended Air Handling Unit with 0.6 mm pre coated GI (outside) & 0.6mm plain GI (inside) double skin casing having 25 mm thick PUF insulation (38 kg/cum), 6 row deep chilled water type cooling coil, DIDW backward curved centrifugal fan with high efficiency motor, synthetic pre-filter 90% down to 10 micron 18 SWG SS drain tray and all other accessories complete as per specification for the following capacity. The AHU shall consist of 1 no. Centrifugal Blower with 2 nos.(1W + 1S) TEFC Squirell cage induction motor. The AHU shall be complete with VFD.The VFD shall be of IP20 rating. AHU MAKE - Zeco & VFD MAKE - ABB / Danfoss / Bluestar
7000 CFM Nominal Capacity, 60 MM TSP (Male Ward)
5000 CFM Nominal Capacity, 60 MM TSP (Female Ward)
SUB-HEAD 2-- WATER LINE VALVES, STRAINERS & ACCESSORIES
SITC of the following Water line Butterfly-Valve of PN 16 rating as per standard complete with flanges, nut-bolts, gasket and welding arrangements. Valves shall be made out of Cast Iron body, SG iron disc with Nylon coated, SS-431 Stem, EPDM integrally moulded liner with detachable hand lever. (Make - Advance / C & R / Audco)
SITC of the following Water line Balancing - Valve of PN 16 rating as per standard complete with flanges, nut-bolts, gasket and welding arrangements. The valves of following sixes of cast iron construction with internal parts of SS 410 and EPDM seat with flanged ends. The test cocks should be long enough to protrude out of valve insulation. (Make- Advance / Leader / Zoloto)
SITC of 3-WAY Modulating Valve suitable for operation with a signal of 0-24 volt DC, WITH ACTUATOR, LINKAGE & THERMOSTAT in chilled water line to the cooling coil of AHU actuated by a proportionate thermostat. The valve shall consist of bronze metal body with stainless steel trim. The pressure drop across valve shall not exceed 5.0 PSI. The valve linkages shall be of the same make as of valves & modulating motor. (Make- Danfoss )
SUB-HEAD 3-- DUCT WORK
SITC of GI DUCT of Class - VIII grade for supply/return air duct along with pre fabricated plenum for supply and return air with necessary supports, flanges etc. as required and as per IS 655 and IS-277 standards of following gauges. (Make - Sail / Tata Steel)
24 SWG thick
22 SWG thick
Supply, design, engineering, fabrication and fixing of new pre-insulated Air Plenum made out of 20 SWG, 120 GSM, Class-VIII GI Sheets and 25 mm thick class O closed cell Aluminium foil faced nitrile rubber insulation and suitable sufficient adhesive. The job also includes making connection of with duct, scaffolding, as per direction of E.I.C
SUB-HEAD 4-- THERMAL / UNDERDECK / ACOUSTICS INSULATION
Supplying & fixing of 19 mm thick duly laminated aluminum foil of mat finish closed cell Nitrile rubber (Class “O”) insulation on existing duct after applying suitable adhesive for Nitrile rubber. The joints shall be sealed with 50 mm wide and 3 mm thick self adhesive nitrile rubber tape insulation. (Make - Armacell / K Flex)
Supplying & fixing of acoustic insulation inside ducting with 10mm thick open cell nitrile rubber(class O) of density 140Kg/cu.m-160 Kg/Cum insulation with bolts nuts GI washers etc as required. (Make - Armacell / K Flex)
Supply & fixing of underdeck insulation with 50mm thick TF quality Expanded polysterene slab. (Make - Thermowell )
SUB-HEAD 5-- CHILLED WATER PIPING (MS HVY CLASS)/TANK
SITC of following MS heavy class ERW pipe for CHILLED WATER CIRCUIT in accordance to IS-1239 standards including providing necessary qunatities of flanges, fittings, bends, elbows, gasket, nut-bolts etc. as follows: Make - TATA/Jindal
SITC of following THERMAL INSULATION OF CHILLED WATER PIPE with 50 mm thick TF quality expanded polystyrene having density 16 Kg/CuM covered with vapour barrier, GI chicken wre mesh and 12 mm thick sand cement plaster and finally covered with 28 SWG Aluminium sheet cladding Make: Beardsel/Astha Polymer/Thermowell
SITC of Drain piping with schedule 40 PVC pipes with fittings duly insulated with with 13 MM THICK Nitrile rubber .Make - Armaell / KFlex/ AFlex along with necessary quantities of supports, flanges, bends, elbows, fittings, nut-bolts, gaskets etc. (MAKE - Finolex / Supreme/Ashirbad/Astral/Ajay )
SUB-HEAD 6 -air diffusers/grills/ DAMPER
Supply & Fixing of Aluminium powder coated supply air diffusers/grilles with volume control damper (Make - Systemair / Air Enterprise / Premire / Caryaire / Airmaster)
SITC of fire dampers in supply air duct/main branch and return air path as and where required of required sizes i/c control wiring. The damper shall be motorized and spring return so as to the damper in the event of power failure automatically and open the same in case of power being restored The spring return action shall be inbuilt mechanism and not external mounted The damper shall also be closed in the event of fire signal complete as required and as per specifications (Make - Systemair / Air Enterprise / Caryaire / Airmaster)
Motorised Fire damper
Accutuator with motor drive
Supply & Fixing of Fresh air package with damper, cowl and bird net arrangement (Make - Systemair / Air Enterprise / Premire / Caryaire / Airmaster)
SUB-HEAD 7 - VFD Bypass AHU Starter Panel / Exhaust fan / Control cable etc
SITC of wall mounted cubical type LT control panel & VFD Bypass Starter Electrical Panel Board fabricated from sheet steel comprising with following accessories incl. internal wiring earthing & painting. (Make - EAP/ Genpower/ CPRI Approved Vendor) as per direction of EIC.
MCB of suitable rating as incomer & MCBs as outgoing as per the rating of AHU motor .
DOL / SD starter as per HP ratings.--2 nos
VFD Bypass Starter as per HP ratings
Terminal block for power distribution.
Contactor, auxilary contractor, over load relay, Phase sequence & single phasing preventer.
Phase indicating lights and indicating light for ON , OFF & TRIP status.
Wiring for microswitch for stopping the fan when fire damper closes.
Panel mounted 3phase digital Ammeter - 1 no
One no 24V DC Relay for inter connection with Fire Detection system.
24V AC & 24V DC of 1A capacity for operation of fire damper & fire relay.
Danger Board.
Supply and Laying of 4 Core 16 sqmm XLPE Insulated & Sheathed Armoured Aluminium Conductor cables for Working Voltage up to 1100 Volts on cable tray with earthing attachment in 2 x 10 SWG GI (Hot Dip) Wire, etc. as necy., mending good damages and painting [ Make: Havells/ Gloster/Polycab]
Supplying and fixing compression type gland and finishing those for following XLPE / PVC armoured cable (3/4 )Core as per GS.
4 Core 16 sqmm
CONTROL CABLING :- Supply & Laying of 1.1 KV Gr. PVC/XLPE insulated, PVC- Sheathed cable, copper unarmoured control cables incl. to laid on wall surface by suitable clamping, proper glanding & finishing the cable ends with solderless sockets for following cables . (Make - Gloster / Polycab / Havells / Mescab)
7 Core 2.5 sqmm XLPE Cu Cable
3 Core 2.5 sqmm XLPE Cu Cable
Supply and Laying of 2x8 SWG GI wire as to GS
Supply & Fixing of perforated GI cable tray with perforation not more than 17.5% laid on roof top incl. S&F GI connector, bolts & nuts, steel fastener etc. as required of the following size. Incl. Al painting of MS support With 25x25x3mm angle iron chair of 150mm height. (Make - Legrand)
200x50x1.25mm (18SWG)
MS Supports Structures for installation of AHUs, Pipes, Ducts, Cable & Cable Trays
Scaffolding charges with suitable MS strcutures from Ground to 4th Floor ceiling level
Charges for minor civil cutouts for laying pipe, duct, cables, cable trays etc and making good of the same
Charges towards loading unloading lifting shifting and positioning of AC equipment and accessories
S&D of minimum 13KW nominal cooling capacity ceiling suspended [ concealed] Split Air Conditioner with R410A / R407C / R-32 Refrigerant, with single Scroll Compressor / Swing compressor in inverter machine, suitable for operation on 415V,+_ 5% , 50Hz, 3Ph AC Supply. with precharged refrigerant, Wired/ Wireless remote & all other accessories complet with refrigerent (Make : DAIKIN model FDMF140BRV16/ RZMF140BRY16 / Mitsubishi heavy industries model FDUM125CSV-S6/FDC125CSV-S6 / O General model ARG60F/AOG60F).
TERMS & CONDITIONS :- The Agency must procure the materials from the Manufacturer / OEM or from their authorised sales channel so that the standard warranty / support of the Manufacturer / OEM becomes applicable to the products to be delivered and installed by them. Documents that authenticates such procurement from the Manufacturer / OEM or from their authorized sales channel and standard warranty / support should be sent from the e-mail of the Manufacturer / OEM / authorized sales channel to the e-mail of Engineer-in-Charge and hard copy of it to be submitted during execution, of work/ submission of bill. If any refurbished material is supplied and installed, penal action will be taken as per existing rules
Defect Liabibility Period 1 (One) year
Make & model of each and every material to be approved by EIC
Shinryo Suvidha Engineers India Pvt. Ltd.
BLUE STAR LIMITED
VOLTAS LIMITED
technical_1470623.pdf
PDF • 0.08 MB
techsummary_1470623.pdf
PDF • 0.08 MB
finance_1470623.pdf
PDF • 0.08 MB
BOQ Comparative Chart
xlsx • 0.02 MB
finsummary_1470623.pdf
PDF • 0.55 MB
AOC.pdf
PDF • 0.17 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .