Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹16.7 LAccepted-AOC 1001 B BHAVESHWAR BLDG NO 03 BHAVESHWAR LANE GHATKOPAR EAST MUMBAI 400077 | MUMBAI SUBURBAN | MAHARASHTRA | 400077 | L1 | Accepted-AOC Accepted | |
| 2 | L2₹22.3 L+₹5.3 L (31.0%)Rejected-AOC GALA NO 08 D SOUZA SADAN OPP ANULAXMI ART PRINTERS NEAR GANESH MANDIR LOKMANAYA TILAK NAGAR A G LINK ROAD SAKINAKA MUMBAI 400 072 | MUMBAI SUBURBAN | MAHARASHTRA | 400072 | L2 | Rejected-AOC Not Accepted | |
| 3 | L3₹24.7 L+₹7.6 L (44.8%)Rejected-AOC | L3 | Rejected-AOC Not Accepted |
| Sl No | Description | Qty | Unit | EVEREST POWER CONTROL ENGINEERS L1 | joshua construction L2 | NANGIA AND CO L3 |
|---|---|---|---|---|---|---|
| 1.00 | Material and labour for submain wiring in concealed complete with and including 2 runs of 6sqmm, single core FRLS, PVC insulated and unsheathed, multistranded, copper conductor cable, single core, 1100 Volts grade drawn through and including suitable size of PVC FR heavy duty conduit (not less than 25mm dia) for housing the wires from main DB to SPN DB with accessories such as Tees, Elbows, junction box, reducers etc as required and fixed on walls and one run of 6.0sqmm PVC multistranded copper conductor cable for earthing and connected to common earth dolly including taking down the existing submain wiring complete all as specified and as directed by Engineer-in-Charge.
Note : 1. Thimble/ lugs of rating of MCB should be used with wire for fixing in the MCB. 2. Two runs of 6sqmm PVC insulated cable and one run of 6sqmm cable and one run of PVC conduit shall be measured as one unit length.
Make of Cable-Anchor/ havells/finolex /Polycab/Plaza of ISI mark as approved by GE
Make of PVC conduit-Anchor, Modi, Pressfit, Precision, Astral, Panasonic Anchor, Polycab, Presto Plast, Supreme | 200 | RUNNING METRE | 220 ₹44,000 Lowest | 450 ₹90,000 | 500 ₹1,00,000 |
| 2.00 | Material and labour for submain wiring concealed type with and including 2 single core of 4sqmm, single core FRLSH, PVC insulated and unsheathed, multistranded, copper conductor cable, single core, 1100 Volts grade drawn through and including suitable size of PVC FR conduit, heavy grade, ISI marked 25mm dia with accessories such as Tees, Elbows, junction box, reducers etc as required and fixed on walls and one run of 4sqmm PVC multistranded copper conductor cable for earthing and connected to common earth dolly including taking down the existing submain wiring complete all as specified and as directed by Engineer-in-Charge.
Note : Two runs of 4sqmm PVC insulated cable and one run of 4sqmm cable and one run of PVC conduit shall be measured as one unit length.
Make of Cable-Plaza, Finolex, Havells, Polycab
Make of PVC conduit-Anchor, Modi, Pressfit, Precision, Astral, Panasonic Anchor, Polycab, Presto Plast, Supreme | 200 | RUNNING METRE | 180 ₹36,000 Lowest | 379 ₹75,800 | 370 ₹74,000 |
| 3.00 | Material and labour including taking down for Point wiring for complete with PVC insulated FRLSH cable 1100 volts grade with multi stranded copper conductor conforming to IS-694, 1.5 sqmm (nominal area) ( Phase- R, Y , B, Neutral- Black), drawn through and including non metallic PVC casing / capping (not less than 20mm wide) (ISI marked) and accessories on surface of wall/roof with sunken type pressed steel/welded terminal boxes made out of 1.6mm mild steel sheet, 3mm thick laminated sheet cover for mounting of switches, socket outlets, regulators etc., including provision of PVC insulated FRLS cable 1100 volts grade with multi stranded copper conductor 1.5sqmm as earth continuity conductor (green colour) and connecting to common earth dolly complete all as specified and as directed for one light / exhaust fan/ wall fan point controlled by one, one way switch complete all as specified and as directed by Engineer-in-Charge.
Make of Cable- Anchor/ havells/finolex /Polycab/Plaza of ISI mark as approved by GE
Make of PVC Casing Capping-Anchor, Modi, Pressfit, Precision, Astral, Panasonic Anchor, Polycab, Presto Plast, Supreme | 150 | POINT | 675 ₹1,01,250 Lowest | 700 ₹1,05,000 | 700 ₹1,05,000 |
| 4.00 | All as per item No.3 here-in before but for one bell point, controlled by bell push | 15 | POINT | 675 ₹10,125 Lowest | 700 ₹10,500 | 700 ₹10,500 |
| 5.00 | All as per item No.3 here-in before but for one light point controlled by 2, two way switches | 20 | POINT | 800 ₹16,000 | 850 ₹17,000 | 700 ₹14,000 Lowest |
| 6.00 | All as per item No.3 here-in before but One 3 pin, 5Amps socket point on the independent board | 30 | POINT | 675 ₹20,250 Lowest | 700 ₹21,000 | 700 ₹21,000 |
| 7.00 | All as per item No.3 here-in before but for one 3 pin, 5 Amps socket point, on same board | 45 | POINT | 120 ₹5,400 | 100 ₹4,500 Lowest | 100 ₹4,500 Lowest |
| 8.00 | All as per item No.3 here-in before but for 3 pin 15 Amps socket point with 2.5sqmm copper cable and provision of 2.5sqmm PVC insulated, FRLSH cable 1100 volts grade with multi stranded copper conductor for earth continuity conductor connected to common earth dolly connecting up to fittings complete all as specified and as directed by Engineer-in-Charge. | 20 | POINT | 750 ₹15,000 Lowest | 900 ₹18,000 | 800 ₹16,000 |
| 9.00 | All as per item No.3 here-in before but for point wiring on independent board with 4.0sqmm copper cable and provision of 4sqmm PVC insulated, FRLS cable 1100 volts grade with multi stranded copper conductor for earth continuity conductor with 20mm non metallic PVC conduit concealed in wall/ceiling etc complete all as specified and as directed by Engineer-in-Charge. | 15 | POINT | 900 ₹13,500 Lowest | 1,300 ₹19,500 | 1,000 ₹15,000 |
| 10.00 | Material and labour including taking down for Point wiring for complete with PVC insulated FRLS cable 1100 volts grade with multi stranded copper conductor conforming to IS-694, 1.5 sqmm (nominal area) ( Phase- R, Y , B, Neutral- Black) drawn through and including (medium grade) rigid non metallic PVC conduit pipe not less than 20 mm size ISI marked with conduit accessories / fittings / junction box / inspection covers etc of ISI marked and cutting chases for concealed conduit with all surfaces by means of screws and sunk / cup washers, fabricated terminal box made out of PVC, with 3mm thick PVC sheet, ISI marked, top cover with brass/ chromium plated screws and cup washers for housing switches, socket outlets, fan, regulators etc for mounting of switches, socket outlets, regulators etc., including provision of PVC insulated FRLSH cable 1100 volts grade with multi stranded copper conductor 1.5 sqmm as earth continuity conductor (green) and connecting to common earth dolly all as specified and as directed for one light /ceiling fan/ exhaust fan point, controlled by one switch complete all as specified and as directed by Engineer-in-Charge.
Make of Cable- Anchor/ havells/finolex /Polycab/Plaza of ISI mark as approved by GE
Make of PVC conduit-Anchor, Modi, Pressfit, Precision, Astral, Panasonic Anchor, Polycab, Presto Plast, Supreme | 150 | POINT | 675 ₹1,01,250 Lowest | 700 ₹1,05,000 | 800 ₹1,20,000 |
Tender Value
₹26 L
EMD Value
₹52,000
Closing Date
18 Nov 2025, 6:00 pmClosed
Garrison Engineer North Santacruz Mumbai
Garrison Engineer North Santacruz Mumbai Military Engineer Services Santacruz East, Mumbai 400029
MAINTENANCE OF INTERNAL ELECTRIFICATION IN MD AND OTM ACCN AND REPAIR/ REPLACEMENT OF OLD UNSERVICEABLE FAN AND GEYSERS AT DGQA GHATKOPAR AND VIKHROLI UNDER GE (NORTH) MUMBAI
2025_MES_737174_1
8275/E8
Open Tender
Civil Works
Item Rate
180 days
Garrison Engineer North Santacruz Mumbai
As per tender documents
8 documents required · 8 mandatory
₹500
Garrison Engineer North Santacruz Mumbai
₹52,000
Yes
3 Jan 2026
27 Oct 2025
20 Nov 2025
27 Oct 2025
18 Nov 2025
11 Nov 2025
28 Oct 2025 - 2 Nov 2025
Amount
Material and labour for submain wiring in concealed complete with and including 2 runs of 6sqmm, single core FRLS, PVC insulated and unsheathed, multistranded, copper conductor cable, single core, 1100 Volts grade drawn through and including suitable size of PVC FR heavy duty conduit (not less than 25mm dia) for housing the wires from main DB to SPN DB with accessories such as Tees, Elbows, junction box, reducers etc as required and fixed on walls and one run of 6.0sqmm PVC multistranded copper conductor cable for earthing and connected to common earth dolly including taking down the existing submain wiring complete all as specified and as directed by Engineer-in-Charge. Note : 1. Thimble/ lugs of rating of MCB should be used with wire for fixing in the MCB. 2. Two runs of 6sqmm PVC insulated cable and one run of 6sqmm cable and one run of PVC conduit shall be measured as one unit length. Make of Cable-Anchor/ havells/finolex /Polycab/Plaza of ISI mark as approved by GE Make of PVC conduit-Anchor, Modi, Pressfit, Precision, Astral, Panasonic Anchor, Polycab, Presto Plast, Supreme
Material and labour for submain wiring concealed type with and including 2 single core of 4sqmm, single core FRLSH, PVC insulated and unsheathed, multistranded, copper conductor cable, single core, 1100 Volts grade drawn through and including suitable size of PVC FR conduit, heavy grade, ISI marked 25mm dia with accessories such as Tees, Elbows, junction box, reducers etc as required and fixed on walls and one run of 4sqmm PVC multistranded copper conductor cable for earthing and connected to common earth dolly including taking down the existing submain wiring complete all as specified and as directed by Engineer-in-Charge. Note : Two runs of 4sqmm PVC insulated cable and one run of 4sqmm cable and one run of PVC conduit shall be measured as one unit length. Make of Cable-Plaza, Finolex, Havells, Polycab Make of PVC conduit-Anchor, Modi, Pressfit, Precision, Astral, Panasonic Anchor, Polycab, Presto Plast, Supreme
Material and labour including taking down for Point wiring for complete with PVC insulated FRLSH cable 1100 volts grade with multi stranded copper conductor conforming to IS-694, 1.5 sqmm (nominal area) ( Phase- R, Y , B, Neutral- Black), drawn through and including non metallic PVC casing / capping (not less than 20mm wide) (ISI marked) and accessories on surface of wall/roof with sunken type pressed steel/welded terminal boxes made out of 1.6mm mild steel sheet, 3mm thick laminated sheet cover for mounting of switches, socket outlets, regulators etc., including provision of PVC insulated FRLS cable 1100 volts grade with multi stranded copper conductor 1.5sqmm as earth continuity conductor (green colour) and connecting to common earth dolly complete all as specified and as directed for one light / exhaust fan/ wall fan point controlled by one, one way switch complete all as specified and as directed by Engineer-in-Charge. Make of Cable- Anchor/ havells/finolex /Polycab/Plaza of ISI mark as approved by GE Make of PVC Casing Capping-Anchor, Modi, Pressfit, Precision, Astral, Panasonic Anchor, Polycab, Presto Plast, Supreme
All as per item No.3 here-in before but for one bell point, controlled by bell push
All as per item No.3 here-in before but for one light point controlled by 2, two way switches
All as per item No.3 here-in before but One 3 pin, 5Amps socket point on the independent board
All as per item No.3 here-in before but for one 3 pin, 5 Amps socket point, on same board
All as per item No.3 here-in before but for 3 pin 15 Amps socket point with 2.5sqmm copper cable and provision of 2.5sqmm PVC insulated, FRLSH cable 1100 volts grade with multi stranded copper conductor for earth continuity conductor connected to common earth dolly connecting up to fittings complete all as specified and as directed by Engineer-in-Charge.
All as per item No.3 here-in before but for point wiring on independent board with 4.0sqmm copper cable and provision of 4sqmm PVC insulated, FRLS cable 1100 volts grade with multi stranded copper conductor for earth continuity conductor with 20mm non metallic PVC conduit concealed in wall/ceiling etc complete all as specified and as directed by Engineer-in-Charge.
Material and labour including taking down for Point wiring for complete with PVC insulated FRLS cable 1100 volts grade with multi stranded copper conductor conforming to IS-694, 1.5 sqmm (nominal area) ( Phase- R, Y , B, Neutral- Black) drawn through and including (medium grade) rigid non metallic PVC conduit pipe not less than 20 mm size ISI marked with conduit accessories / fittings / junction box / inspection covers etc of ISI marked and cutting chases for concealed conduit with all surfaces by means of screws and sunk / cup washers, fabricated terminal box made out of PVC, with 3mm thick PVC sheet, ISI marked, top cover with brass/ chromium plated screws and cup washers for housing switches, socket outlets, fan, regulators etc for mounting of switches, socket outlets, regulators etc., including provision of PVC insulated FRLSH cable 1100 volts grade with multi stranded copper conductor 1.5 sqmm as earth continuity conductor (green) and connecting to common earth dolly all as specified and as directed for one light /ceiling fan/ exhaust fan point, controlled by one switch complete all as specified and as directed by Engineer-in-Charge. Make of Cable- Anchor/ havells/finolex /Polycab/Plaza of ISI mark as approved by GE Make of PVC conduit-Anchor, Modi, Pressfit, Precision, Astral, Panasonic Anchor, Polycab, Presto Plast, Supreme
All as per item No.10 here-in before but 5 Amps socket outlet point on the independent board.
All as per item No.10 here-in before but for one 5 Amps socket oulet point, on same board controlled by another switch.
All as per item No.10 here-in before but for bell/buzzer point on same board with other switches controlled by one push button or independent with cables 1.5 Sqmm
All as per item No.10 here-in before but for one light point controlled by two way switches
All as per item No.10 here-in before but for 15/16 Amps switch socket point , on independent board with 2.5sqmm copper cable and provision of 2.5sqmm PVC insulated, FRLS cable 1100 volts grade with multi stranded copper conductor for earth continuity conductor connected to common earth dolly connecting up to fittings, on the independent board complete all as specified and as directed by Engineer-in-Charge.
All as per item No.10 here-in before but forpoint wiring on independent board with 4.0sqmm copper cable and provision of 4.0sqmm PVC insulated, FRLS cable 1100 volts grade with multi stranded copper conductor for earth continuity conductor connected to common earth dolly connecting up to fittings, on the independent board complete all as specified and as directed by Engineer-in-Charge.
Supply and fix in repairs Switch Piano, flush type, single pole, one way, 5 Amps, 240 volts, ISI marked complete all as specified and as directed by Engineer-in-Charge. Make: Anchor / Legrand / Havells/.Crabtree/Leader/Benlo
Supply and fix in repairs Switch bell push, flush type, single pole, one way, 5 Amps, 240 volts, ISI marked complete all as specified and as directed. Make: Anchor / Legrand / Havells/.Crabtree/Leader/Benlo
Supply and fix in repairs switch socket outlet, combination 5 Pin, 5 Amps, flush type, universal ISI marked complete all as specified and as directed by Engineer-in-Charge. Make: Anchor / Legrand / Havells/.Crabtree/Leader/benlo
Supply and fix in repairs switch socket outlet, combination 5 in 1, 3 Pin, 5/15 Amps, flush type, universal ISI marked complete all as specified and as directed by Engineer-in-Charge. Make: Anchor / Legrand / Havells/.Crabtree/Leader /Benlo
Supply and fix in repairs stepped type electronic ceiling fan regulator,100W, 230 V etc complete all as specified and as directed by Engineer-in-Charge. Make: Anchor / Legrand / Havells/.Crabtree/Leader
Supply and fix in repairs Modular type switch, single pole, one way, 10 Amps, 1 module, ISI marked complete all as specified and as directed by Engineer-in-Charge. Make:Anchor / Legrand / Havells/.Crabtree/Leader /Benlo
Supply and fix in repairs Modular socket outlet, 2 module, 2/ 3 Pin combined, 6 Amps, flush type, universal ISI marked complete all as specified and as directed by Engineer-in-Charge. Make: Anchor / Legrand / Havells/.Crabtree/Leader /Benlo
Supply and fix in repairs Modular type switch, single pole, one way, 16 Amps, 1 module, ISI marked complete all as specified and as directed by Engineer-in-Charge. Make:Anchor / Legrand / Havells/.Crabtree/Leader /Benlo
Supply and fix in repairs Modular socket oulet , 2 module, 2 in 1, 2/ 3 Pin combined, 6/16 Amps, flush type, universal ISI marked complete all as specified and as directed by Engineer-in-Charge. Make: Anchor / Legrand / Havells/.Crabtree/Leader
Supply and fix in repairs ceiling rose, 3 plate of 28x500mm , PVC/Polycarbonate type with back plate suitable for batten fittings complete all as specified and as directed by Engineer-in-Charge. Make: Legrand /crabtree/ Honeywell/ Anchor/Benlo
Supply and fix in repairs modular fan regulator AC, 230 volts , 120 watts (2 module), electronic type, deluxe (stepped type) complete all as specified and as directed by Engineer-in-Charge. Make: legand/havells/crabtree/Havells/SSK
Supply and fix in repairs angle holder, PVC/Polycarbonate type with back plate suitable for batten fittings complete all as specified and as directed by Engineer-in-Charge. Make: Anchor / Legrand / L&T
Supply and fix in repairs Call bell electric (Ding Dong type) suitable for working on 230 volts AC supply multi music type complete all as specified and as directed. Make: Anchor / Legrand / L&T
Supply and fix surface in repairs mounted 4 ft, 6500k surface mounted, 20 watts LED tube light fitting with rechargeable inverter LED batten , automatic DC mode feature on power failure fixtures, energy efficient light fitting, internally prewired and connecting up with copper 3 core flexible cord of minimum size 0.5 sqmm from ceiling rose to fitting complete all as specified and as directed by Engineer-in-Charge. Make : Philips/crompton/Bajaj/Havells.
Supply and fix LED lights fitting 1x 20 W, 220V, AC decorative box type with driver, holder including LED tube light connecting up with three core flexible copper conductor cable of suitable size from ceiling rose including 02 Nos of PVC square /round boxes , screws clips including taking down existing light fittings etc complete all as specified and as directed by Engineer-in-Charge. Make: Phillips Cat No BNO21C LED20S PSU CW GR S2 or equivalent of Havells cat part No LHEXARP7SN1W020 / Bajaj, as approved by GE.
Supply and fix LED light fitting mirror type with high out put diffuser 2 feet, 10 watt 220 V AC decorative type with driver holder and LED lamp including connecting up with three core flexible copper conductor cable of suitable size including taking down existing light fittings etc complete all as specified and directed by Engr-in-charge. Make : Havells Cat No LHEXACP5IN1W010 or equivalent of Philips / Bajaj.
Supply and fix Indoor Decorative light, wall mounting, Metal, glass home, 220-240 V with B22 LED bulb of 12 Watts iand holder including taking down existing light fittings etc complete all as specified and directed by Engr-in-charge. Make: Philips 58184 platina model No. - 34303/11C/86 or equivalent in Bajaj/ wipro
Supply and fix in repairs recess mounted LED ceiling light fitting, 600mmx600mm, 35/36w, 230v, 50Hz with diffuser suitable for indoor units complete with all accessories internally pre wired and including connecting up with twin core twisted flexible copper conductor cable fixed on the false ceiling with necessary cutting of false ceiling wherever necessary etc complete all as specified and directed by Engineer-in-Charge-in-Charge, Make : Philips/Bajaj / CG / Havells
Supply and fixing in repair LED street light / building security light fitting 35 Watt, luminaire fixture in IP 66 protection level output of LED lamp efficiency minium 100 luman per watt after all losses , pressure die-cast aluminium housing LED Street light complete with GI clamp including connected accessories and bracket made of GI Pipe light grade, bend to shape with two sets of MS flat iron clamps, nuts, bolts, washers etc. complete all as directed by Engineer-in-Charge. Make Wipro/Bajaj/ Havells.
Material and labour for electrical meter box with 1mm CRCA sheet for accomodating existing single electric meter and 8 way Distribution Box concelead on walls, connecting all wires, making good the disturbed surfaces as per existing including brick work, plaster, white wash and paint as per existing, box should have seven way process powder coating to protect from rust including taking down old meter box complete all as specified and directed by Engr-in-Charge. Note : 8 way DB will be paid seperately under relevent items of schedule.
Supply and fix in repairs sheet metal enclosures, double door, for DBs when MCBs to be used 240 volts 8 way with 200 Amps rated bus bar, single pole and neutral , fixed on wall duly grouted in solid block wall or on wooden board in and including copper lugs/thimbles duly crimped for connection complete all as specified and directed. Make: Havells / Legrand / L&T/Benlo
Supply and fix in repairs sheet metal enclosures, double door, for DBs when MCBs to be used 240 volts 6 way with 200 Amps rated bus bar, single pole and neutral , fixed on wall duly grouted in solid block wall or on wooden board in and including copper lugs/thimbles duly crimped for connection complete all as specified and directed. Make: Havells / Legrand / L&T/Benlo
Supply and fix in repairs sheet metal enclosures, double door, for DBs when MCBs to be used 240 volts 4 way with 200 Amps rated bus bar, single pole and neutral , fixed on wall duly grouted in solid block wall or on wooden board in and including copper lugs/thimbles duly crimped for connection complete all as specified and directed. Make: Havells / Legrand / L&T/Benlo
Supply and fix in repairs MCB SP 5-32 Amps, 240 volts, 10KA 'C' curve complete all as specified and as directed by Engineer-in-Charge. Make :Legrand / L&T / Havells/Benlo
Supply and fix in repairs MCB SPN 40 to 63 Amps, 240 volts, 10KA 'C' curve complete all as specified and as directed by Engineer-in-Charge. Make :Legrand / L&T / Havells/Benlo
Supply and fix in repairs double door, sheet metal enclosure powder coated DB VTPN 4 way with 200 Amps rated bus bar, 415 volt, vertical type, IP 43 protection with provision for DPX 100 MCCB as incomer and SP/TP MCB as outgoing, flush in walls including making good of disturbed surface to match with existing surface complete all as specified and as directed by Engineer-in-Charge. Make: Havells Cat part No. DHDLVSRWGOFO04 or equivalent of Legrand / Larsen &Toubro/ ABB/ Siemens/ Schneider/ Indo ASIAN/ C & S Electric/ Bhartia Cuttler Hammer (BCH) as approved by GE
Supply & fix in repairs LED light fitting 10W bulkhead luminaires outdoor type including LED light driver holder connecting up with three core flexible copper conductor cable of suitable size including all necessary fittings complete all as specified and directed by Engineer-in-Charge. Make: Havells/Crompton Greaves /Philips/ Bajaj
Supply and fix in repairs outdoor Decorative light, wall mounting, Metallic body, 220-240 V with 2x3W IP54 UD LED 2700K, 160 lumen complete all as specified and directed by Engr-in-charge. Make : Wipro Cat No. DW30627 or equivalent of Philips / Bajaj.
Supply and fix in repairs MCCBs 100 Amps, 25 KA, 4 pole with adjustable thermal and magnetic settings including taking down unserviceable complete all as specified and as directed by Engineer-in-Charge. Make : Cat Part No 420055 of Legrand / Larsen &Toubro/ ABB/ Siemens/ Schneider/ Havells/ Legrand/ Indo ASIAN/ C & S Electric/ BhartiaCuttler Hammer (BCH)/Benlo
Supply and fix in repairs MCB TPN, 40 Amps to 100 Amps, 415 volts,10 KA including taking down old unserviceable complete all as specified and as directed by Engineer-in-Charge. Make : Larsen &Toubro/ ABB/ Siemens/ Schneider/ Havells/ Legrand/ Indo ASIAN/ C & S Electric/ Bhartia Cuttler Hammer (BCH)
Material and labour for Earthing complete with Galvanised steel earth plate electrode 60 cm x 60 cm x 6.0 mm thick, buried directly in ground (earth pit not less than 2.25 metres deep below normal ground level) with top edge of earth the plate not less than 1.5 metres below normal ground level, connected to and including galvanised earth lead wire 4 mm dia, 7.5m long, by means of bolts, nuts, check nuts and washers made out of galvanised iron or steel with provision of charcoal & common salt packed upto minimum 150 mm all around the earth plate, and protected by 15 mm bore medium grade galvanised iron pipe and connected to control board / panel / equipment complete all as shown in electrical plate No.3 of MES schedule Part I with PCC pit in PCC 1:2:4 type B1 using 20 mm graded stone aggregate, MS angle iron frame of size 50mm x 50mm x 5mm, cast iron cover with locking arrangements, GI 20 mm bore medium grade pipe and CI funnel with wire mesh for watering arrangement including necessary excavaion and earth work in any type of soil/strata & testing complete all as specified and as directed by Engineer-in-Charge.
Taking down ceiling fan/exhaust fan/wall mounted fan of any make /type/size/sweep, at site from any height of the building for any defects, servicing complete,repairs /overhauling including replacement of worn out parts/rewinding as required , spare parts and refixing in same position incl. sucessful testing on full load wit blade complete all as specified and directed by Engineer-in-Charge. Note- (i) Capacitor, ball bearing, condenser, bushes, split pin, 'U' clamp with rubber reel, shaft PVC canopy and flexible wire will be measured and paid separately as "Supply only" (ii) Serviceable spares shall be reused. (ii) Rewinding shall be measured and paid separately.
Material and labour for preparing old surfaces of ceiling fan/exhaust fan/wall mounted fan/Geyser of any capacity or sweep, by scrapping and removing dust etc and filling cavities with one coat of filler and spray painting with synthetic enamel paint and writing MES Nos in block letters as per existing complete all as specified and as directed by Engineer-in-Charge.
Material and labour for opening the motor of ceiling fans of sweep 1200mm/1400mm, 230 volts, AC single phase, removing old unserviceable wire, cleaning of slots properly and rewinding of burnt ceiling fan with super enamelled copper winding wire of existing gauge with insulating material, heating, varnishing, grasing, re-assemabling the same after testing on full laod with blade and replacement of worn out minor parts including provision of PVC insulated and PVC sheathed flexible copper wire , three core of size 16/0.20mm of length 750mm complete all as specified and as directed by Engineer-in-Charge. Make-Deen Dayal,finolex,Atlas Note- (i) Capacitor, ball bearing, condenser, bushes, split pin, 'U' clamp with rubber reel, shaft and PVC canopy will be measured and paid separately as "Supply only" (ii) Serviceable spares shall be reused.
Material and labour for opening the motor of exhaust fans of sweep 450mm, 230 volts,AC single phase, removing old unserviceable wire, cleaning of slots properly and rewinding with super enamelled copper winding wire of existing gauge with insulating material, heating, varnishing, grasing, re-assemabling the same after testing on full laod with blade and replacement of worn out minor parts including provision of PVC insulated and PVC sheathed flexible copper wire , three core of size 16/0.20mm of length 750mm complete all as specified and as directed by Engineer-in-Charge. Make-DeenDayal,finolex,Atlas Note- (i) Capacitor, ball bearing, condenser, bushes, split pin, 'U' clamp with rubber reel, shaft and PVC canopy will be measured and paid separately as "Supply only" (ii) Serviceable spares shall be reused.
All as per item no. 51 above but of 250/300mm sweep complete all as specified and directed by Eng-in-charge.
Material and labour for opening the motor of wall mounted fans of sweep 400/450mm, 230 volts,AC single phase, removing old unserviceable wire, cleaning of slots properly and rewinding with super enamelled copper winding wire of existing gauge with insulating material, heating, varnishing, grasing, re-assemabling the same after testing on full laod with blade with replacement of worn out minor parts including provision of PVC insulated and PVC sheathed flexible copper wire , three core of size 16/0.20mm of length 750mm complete all as specified and as directed by Engineer-in-Charge. Make-Deen Dayal, finolex,Atlas Note- (i) Capacitor, ball bearing, condenser, bushes, split pin, 'U' clamp with rubber reel, shaft and PVC canopy will be measured and paid separately as "Supply only". (ii) Serviceable spares shall be reused. (iii) contractor has to collect the unserviceable fans from MES complaint cell and after repair ,testing of fans the same shall be deposited in same place .
Supply only following items for ceiling fan, pedestal fan, wall fan and exhaust fan of any sweep,make , model and type complete all as specified and as directed by Engineer-in-Charge.
Fan capacitor 2.5 MFD, 230V, AC complete all as specified and as directed by Engineer-in-Charge. Make: Usha, Fentex, Tesla, Epcos, Havells
Fan capacitor 4.0 MFD, 230V, AC complete all as specified and as directed by Engineer-in-Charge. Make: Usha, Fentex, Tesla, Epcos, Havells
Fan capacitor 1.0 MFD, 230V, AC complete all as specified and as directed by Engineer-in-Charge. Make: Usha, Fentex, Tesla, Epcos, Havells
Ball bearing suitable for ceiling fan of any sweep, exhaust fan, wall fan, pedestal fan as per sample ( 6201 to 6204) complete all as specified and as directed by Engineer-in-Charge. Make: SEICO, NBC, SKF, TATA
Supply only Gun metal bushes for fans of different sizes complete all as specified and as directed by Engineer-in-Charge.
Supply only MS nut, bolt 8mm dia of suitable size for hanging of the ceiling fans complete all as specified and as directed by Engineer-in-Charge.
Flexible wire 1.5 Smm, twin core, 1100 Volt, twisted, PVC insulated, copper conductor, multistranded, FRLS for connection complete all as specified and as directed by Engineer-in-Charge. Make: Polycab, Havells, Plaza
Top/bottom canopy suitable for ceiling fan of any sweep, make , model and type
Supply and fix and testing of ceiling fan blade of motor suitable for 1200mm sweep including taking down of old fan blade and removing, complete all as specified and directed
Supply & Fix in repair down rod, for hanging of the ceiling fans, 45cm long, made out of 15mm dia GI pipe, heavy duty, having provision for fixing of U clamp including drilling holes at top and bottom for fixing fan motor assembly, painting with superior quality of white colour synthetic enamel paint complete all as specified and as directed by Engineer-in-Charge. Make of GI pipe-Tata/jindal
Cutting openings/redressing , through brick walls built in cement mortar for exhaust fan upto 300mm size, cleaning and stacking bricks, removing surplus serviceable bricks, etc.. to store, rubbish outside MD land and making good in cement concrete 1:2:4 type B-0 as required, rendering 10mm thick in CM (1:6) to match with the existing surfaces including grouting of bolts for mounting of exhaust fan complete all as specified and as directed by Engineer-in-Charge.
Taking down carefully storage type electric water heater (Geyser) of any capacity, carrying out servicing including replacement of various parts, if necessary, such as different sizes of screws and clamps, base assembly, washers, glands of all types/ valves / heating elements / Thermostat pipes / drain plug / thermal cut-out / safety valve and worn out minor parts to ensure water tightness including re-fixing in the position after testing complete all as specified and as directed by Engineer-in-Charge. Note : Base plate assembly, Heating elements,thermostat pipes,thermal cut out and safety valve will be measured and paid saperately.
Supply only following items for water heater and geyser of any model and type complete all as specified and as directed by Engineer-in-Charge.
Rubber washer for fixing the apparatus plate to inner container suitable to existing storage type water heater of same make and size complete all as specified and as directed by Engineer-in-Charge.
Heavy duty PVC flexible pipe 15mm bore, 18" long for both cold/hot water line with brass adopter and washer at both ends of the pipe complete all as specified and as directed by Engineer-in-Charge.
Indicator lamp round/rectangular complete all as specified and as directed by Engineer-in-Charge.
Thermostat for geyser 30 to 75 degree centigrade.Make: Thecha/DasPass/Victor complete all as specified and as directed by Engineer-in-Charge.
Thermal cut out for geyser complete all as specified and as directed by Engineer-in-Charge.
Heating elements of capacity 1.5/2 KW, AC, 230 Volt complete all as specified and as directed by Engineer-in-Charge.
Inner copper container for geyser of capacity 25 ltr, any make and type complete all as specified and as directed by Engineer-in-Charge.
Safety valve/high pressure release valve, ISI marked for geyser of capacity 25/50 ltr complete all as specified and as directed by Engineer-in-Charge.
Supply and fix 3 core PVC insulated and PVC sheathed 1100 volt grade cable, 2.5 sqmm with stranded copper conductor, duly connected to geyser complete all as specified and as directed by Engineer-in-Charge. Make: Finolex / Plaza / Anchor / Havells / Polycab
Supply and fix in repairs electric water heater, storage type, steel body with copper inner tank and heating element upto 2 KW capacity 25 litre, BEE, 5 Star rated complete with all accessories such as safety valve, thermostate, NRV, connection piece etc, including taking down existing electric water heater etc complete all as specified and as directed by Engineer-in-Charge. Note: Old geyser will be deposited in MES Store yard. Make : Havells / Crompton / Racold/ Bajaj
Taking up or down carefully old rusted concealed / surface GI tubes 15/20mm bore and connection complete by cutting chassis from existing brick walls as required including making good to disturbed surfaces of walls, floors to match with the existing surface, complete all as directed by the Engineer-in-Charge.
Supply and fix in repairs ceiling fan complete with three blades, down rods, electronic regulator and accessories, 230 V, 1200 mm sweep, minimum air delivery 210 CFM with service value 6.00 BEE, Five star rated with brushless direct current motor (BLDC) including suitable size of hanging clamp, nut and bolt etc complete all as specified and as directed by Engineer-in-Charge. Note: Old ceiling fan will be deposited in MES store yard Make: Usha Model Technoair BLDC 5 star or equivalent model of Bajaj, Crompton Greaves, Khaitan, Havells as approved by GE
Supply, fix and jointing steel water tubing of 15mm bore medium grade, galvanised iron with all fittings such as Tees, elbows, sockets, bends, unions, short pieces, nipples, brass nuts and diminishing pieces complete all as per IS 1239 including fixed to wall / floor for water supply connection of geyser complete all as specified and as directed by Engineer-in-Charge. Make: Tata / Jindal / Surya Prakash / Zenith
Supply and fix in repairs exhaust fan, AC, single phase, 230V, 250mm sweep, 1200 RPM, 5 blade, plastic body & blade with louver for protection of bird and rain water including cutting round shape in wall, grouting the foundation bolt in the wall, making good the disturbed surfaces of wall including rendering, painting to match the existing surfaces and connecting up with three core flexible copper conductor cable of size 24/0.20sqmm etc from ceilling rose to fitting complete all as specified and as directed by Engr-in-Charge. Note: Old geyser will be deposited in MES Store yard. Make- Crompton Greaves, Bajaj, Orient, Khaitan, Havells
Supply and fix wall mounting fan 400mm sweep, 230 Volts, RPM not less than 1300 with full copper, motor single phase, pull chain arrangement for speed control, provision of oscillation and tilting up and down arrangements and taking down existing fan and keeping in MES store yard complete all as specified and as directed by Engineer-in-Charge. Make: Havells, Bajaj, Usha, Crompton Greaves, Orient, Khaitan as approved by GE.
Supply and fix in repairs metal clad AC socket SPN sheet metal enclosures with two pin and earth plug and socket, 20Amps, controlled by MCB SP 20Amps, 240 Volts complete all as specified and as directed by Engineer-in-Charge. Make: Havells / Legrand / L&T
Supply and fix in repairs 15mm bore bib taps, chromium plated, cast copper alloy, with crutch or butterfly handle screwed down, screwed for iron pipe or for brass ferrule all as specified and as directed by Engineer-in-Charge. Make : Jaquar/ Marc/ CERA/ Kohler/ Player
Supply and fix of metal fasteners of 12mm dia complete as specified and as directed. Make Havells/HPL.
Note: Deduct Credit for demolished / dismantled material of Rs. (-) 33,581.00 (Minus) as listed in Schedule of Credit. Tenderers will not quote against this item being a tentative amount to be considered to arrive at the 'Contract Sum'
joshua construction (BID ID -3476817)
NANGIA AND CO (BID ID -3477179)
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Tendernotice_1.pdf
PDF • 0.38 MB
GENPAGES8275.pdf
Tender Documents • 0.59 MB
8275PS.pdf
Tender Documents • 0.29 MB
BOQ_825405.xls
BOQ • 0.34 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .