Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹30.5 LAdmitted-Finance | ₹30.5 L | L1 | Admitted-Finance |
| 2 | L2₹34.6 L+₹4.1 L (13.3%)Admitted-Finance | ₹34.6 L+₹4.1 L (13.3%) | L2 | Admitted-Finance |
| 3 | Rejected-Technical | - | - | Rejected-Technical Firm is one class below and not enlisted for requisite category of wk as stipulated in NIT |
| Sl No | Description | Qty | Unit | M/s Habib Electronics L2 | WATT ELECTRICAL CONTRACTORS L1 |
|---|---|---|---|---|---|
| 1.00 | Supply, installation, testing and commissioning of copper wound step-down Distribution Transformer, outdoor, floor mounted type, suitable for 11 KV / 433 V, 3 phase, 4 wire, 50 Hz AC system, of capacity 100 KVA , oil immersed, naturally cooled ONAN (Oil Natural Air Natural) type, complete with all standard accessories, fittings and mounting arrangements. The transformer shall conform to latest amendments of IS-1180 (Part-1):2014. Transformer shall be suitable for outdoor operation under Indian climatic conditions.
The transformer shall have:
HV side: Delta connected
LV side: Star connected with neutral brought out
Vector group: DYN-11
Tapping: Off-load tap changer on HV side with taps of ±2.5%, ±5%, ±7.5% in steps of 2.5%
Cooling: ONAN with radiators/cooling fins
Technical requirements
i. Winding: Electrolytic grade copper
ii. Insulation: As per IS standards
iii. Percentage impedance: As per IS 1180
iv. Losses: As per Energy Efficiency Level-2 / latest BEE norms
v. Temperature rise limits: As per IS 1180
vi. Vector group: DYN-11 mandatory
vii.Neutral brought out and suitable for solid earthing
Accessories & fittings
i. Cable end box on HV side suitable for 95 sqmm 3 core size XLPE cable.
ii. Cable end box on LV side suitable for 95 sqmm 3.5 Core size XLPE cable with cable glands. | 2 | Each | 5,50,000 ₹11,00,000 | 4,75,000 ₹9,50,000 Lowest |
| 1.01iii. Conservator with oil level indicator (min/max marking). iv. Silica gel dehydrating breather (first filling included). v. Cooling radiators / fins. vi. Explosion vent / pressure relief device (PRD). vii. Oil temperature indicator (OTI) with maximum reading and reset. viii. Thermometer pocket. ix. Oil filling hole with cap. x. Oil drain valve with sampling facility. xi. Air release valve. xii. Earthing terminals: Minimum 2 nos. for body earthing .Minimum 2 nos. for neutral earthing (separate bushing) xiii. Lifting lugs and pulling lugs. xiv. HV bushings with arcing horns. xv. LV bushings (porcelain/epoxy as per standard). xvi. Rating plate (as per IS) and terminal marking plate. xvii. Danger plate and phase indication markings. xviii. First filling of new, unused, ISI marked transformer oil conforming to IS 335. Notes:- (i) The drawing of transformer shall be approved by accepting officer on receipt of request from the contractor through GE. (ii) The transformer shall be tested as per IS for all routine tests in the factory premises and reports will be deposited with purchase voucher. (iii) Factory inspection and testing of the transformer shall be carried out in the presence of the representative of the Accepting Officer/SEI/IEM, and all associated charges shall be borne by the contractor. | |||||
| 2.00 | S&F 3 phase prodigy (SECURE) distribution transformer meter with built-in-current transformers, energy audit and system analysis, direct connected 3 Ph 4 Wire 415V with current range 40-200A, accuracy class 1.0, frequency 50 Hz, Insulation class protection Class II, Impulse with stand 10KV, IS-13779, dimensions (W x H x D) 365 x 283 x 221mm (with extended terminal cover) complete all as specified and directed. | 1 | Each | 32,000 ₹32,000 Lowest | 35,121 ₹35,121 |
| 3.00 | M&L for cubical panel (dimension of meter to be fixed in panel is 365x283x221mm) for 3 Ph prodigy (Secure) meter along with connected items like nuts & bolts, screws, binding wire, hold fast for fixing in wall/grouting including XLPE UG Cable 95 Sqmm 3.5 Core from transformer to meter and panel complete all as specified and directed.
Note : The quoted rate shall be deemed inclusive of connection of LT UG cable from transformer to panel and meter | 1 | Each Job | 80,000 ₹80,000 | 7,500 ₹7,500 Lowest |
| 4.00 | Supply, installation, commissioning and testing servo voltage stabilizer fully automatic micro processor based control card of capacity 100 KVA, three phase oil cooled with Single phase prevention system, indoor type and designed for input variation between 380 V to 460 V with output voltage stabilized at 415 Volts with accuracy of + 1% and speed of correction 8 V/Sec, no load loss less than 0.5%, operating temp - 15C to 45C above ambient and unbalanced load complete with first filling of oil complete all as specified and directed including additional features as follows:
a. High & low voltage cut off system
b. Change over switch to by-pass the system | 3 | Each | 3,00,000 ₹9,00,000 | 2,50,000 ₹7,50,000 Lowest |
| 5.00 | Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 95 Sq mm 3.5 core complete all as specified and directed. | 230 | RM | 915 ₹2,10,450 | 614 ₹1,41,220 Lowest |
| 6.00 | Supply, laying & testing cable XLPE insulated, screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) with stranded aluminium conductor, 11000 Volts grade 95 sq mm 3 core complete all as specified and directed. | 70 | RM | 1,290 ₹90,300 | 555 ₹38,850 Lowest |
| 7.00 | M&L for earthing complete with galvanized steel earth plate electrode 60 x60 cm and 6 mm thick buried directly in ground (earth pit not less than 2.25 m deep below ground level) with top edge of the plate not less than 1.5 meter below normal ground level connected to GI earth lead wire 4 mm dia by means of bolts nuts, check nut and washers of GI and GI tubing 15 mm bore, medium grade for earth lead protection up to main earth test point and including concrete pit in PCC 1:3:6, type C1 pre cast RCC 1:2:4, type B1 cover slab 450 x 450 x 50 mm reinforced with 8 mm dia TMT bars 100 C to C including one handle for lifting made out of 8 mm dia MS bar, wire mash, 20 mm bore GI tubing medium grade for watering, charcoal and salt in alternate layers including excavation earth work electrical plate no 3 of SSR Part-I complete all as specified and directed. | 4 | Each Set | 6,000 ₹24,000 | 5,555 ₹22,220 Lowest |
| 8.00 | M&L earthing complete with galvanized earth plate electrode 600 x 600 and 6 mm thick buried directly in ground vertically to a depth of not less than 2.25 mtr below ground level connected to 32 x 6mm earth strip with nut, bolts and washers made out of galvanized iron mild steel and 40 mm dia GI pipe "light grade" for protection of earth lead and connected to control board or main switch or as directed by Engineer -in-Charge including earthing pit in PCC 1:3:6, type C1 for chamber & Pre-cast RCC cover of size 380 x 380 x 40 mm with one handle made out of 8 mm dia round bar, 20 mm dia GI pipe light grade for watering funnels , wire mesh and provided charcoal or coke of alternative layers of 15 cm including necessary earth work as Exc, R&F & removal etc. complete all as specified and directed. | 8 | Each Set | 7,000 ₹56,000 | 5,555 ₹44,440 Lowest |
| 9.00 | S&F HT 11 KV outdoor type gang operated air break switch suitable for horizontal type complete with 12 insulators 200 Amps complete all as specified and directed. | 1 | Each | 11,500 ₹11,500 Lowest | 12,121 ₹12,121 |
Tender Value
₹34.8 L
EMD Value
₹69,500
Closing Date
18 Aug 2026, 6:00 pmClosed
CWE, HQ 133 WORKS ENGRS
HQ 133 WORKS ENGRS, C/O 56 APO, PIN- 914133
CWEK/T-44/969 EWS/2026-27 PROVN AND INSTALLATION OF 100 KVA SUB STATION AT IMBRAZALWARI COMPANY OPERATING BASE (COB) AND SPL REPAIR OF TRANSFORMER AND VOLTAGE STABILIZER AGAINST BER EQPT AT VARIOUS LOCATION AT HAWS GULMARG UNDER GE 969 EWS
2026_MES_780038_1
CWEK/T-44/969 EWS/2026-27
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
GE 969 EWS
Class D and above and Category b (ii)
7 documents required · 7 mandatory
₹500
GE 969 EWS
₹69,500
12 Sept 2026
22 Jul 2026
26 Aug 2026
22 Jul 2026
18 Aug 2026
5 Aug 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | Supply, installation, testing and commissioning of copper wound step-down Distribution Transformer, outdoor, floor mounted type, suitable for 11 KV / 433 V, 3 phase, 4 wire, 50 Hz AC system, of capacity 100 KVA , oil immersed, naturally cooled ONAN (Oil Natural Air Natural) type, complete with all standard accessories, fittings and mounting arrangements. The transformer shall conform to latest amendments of IS-1180 (Part-1):2014. Transformer shall be suitable for outdoor operation under Indian climatic conditions.
The transformer shall have:
HV side: Delta connected
LV side: Star connected with neutral brought out
Vector group: DYN-11
Tapping: Off-load tap changer on HV side with taps of ±2.5%, ±5%, ±7.5% in steps of 2.5%
Cooling: ONAN with radiators/cooling fins
Technical requirements
i. Winding: Electrolytic grade copper
ii. Insulation: As per IS standards
iii. Percentage impedance: As per IS 1180
iv. Losses: As per Energy Efficiency Level-2 / latest BEE norms
v. Temperature rise limits: As per IS 1180
vi. Vector group: DYN-11 mandatory
vii.Neutral brought out and suitable for solid earthing
Accessories & fittings
i. Cable end box on HV side suitable for 95 sqmm 3 core size XLPE cable.
ii. Cable end box on LV side suitable for 95 sqmm 3.5 Core size XLPE cable with cable glands. | 2 | Each | - | - |
| 1.01 | iii. Conservator with oil level indicator (min/max marking).
iv. Silica gel dehydrating breather (first filling included).
v. Cooling radiators / fins.
vi. Explosion vent / pressure relief device (PRD).
vii. Oil temperature indicator (OTI) with maximum reading and reset.
viii. Thermometer pocket.
ix. Oil filling hole with cap.
x. Oil drain valve with sampling facility.
xi. Air release valve.
xii. Earthing terminals: Minimum 2 nos. for body earthing .Minimum 2 nos. for neutral earthing (separate
bushing)
xiii. Lifting lugs and pulling lugs.
xiv. HV bushings with arcing horns.
xv. LV bushings (porcelain/epoxy as per standard).
xvi. Rating plate (as per IS) and terminal marking plate.
xvii. Danger plate and phase indication markings.
xviii. First filling of new, unused, ISI marked transformer oil conforming to IS 335.
Notes:-
(i) The drawing of transformer shall be approved by accepting officer on receipt of request from the contractor
through GE.
(ii) The transformer shall be tested as per IS for all routine tests in the factory premises and reports will be
deposited with purchase voucher.
(iii) Factory inspection and testing of the transformer shall be carried out in the presence of the representative of the Accepting Officer/SEI/IEM, and all associated charges shall be borne by the contractor. | - | - | - | - |
| 2 | S&F 3 phase prodigy (SECURE) distribution transformer meter with built-in-current transformers, energy audit and system analysis, direct connected 3 Ph 4 Wire 415V with current range 40-200A, accuracy class 1.0, frequency 50 Hz, Insulation class protection Class II, Impulse with stand 10KV, IS-13779, dimensions (W x H x D) 365 x 283 x 221mm (with extended terminal cover) complete all as specified and directed. | 1 | Each | - | - |
| 3 | M&L for cubical panel (dimension of meter to be fixed in panel is 365x283x221mm) for 3 Ph prodigy (Secure) meter along with connected items like nuts & bolts, screws, binding wire, hold fast for fixing in wall/grouting including XLPE UG Cable 95 Sqmm 3.5 Core from transformer to meter and panel complete all as specified and directed.
Note : The quoted rate shall be deemed inclusive of connection of LT UG cable from transformer to panel and meter | 1 | Each Job | - | - |
| 4 | Supply, installation, commissioning and testing servo voltage stabilizer fully automatic micro processor based control card of capacity 100 KVA, three phase oil cooled with Single phase prevention system, indoor type and designed for input variation between 380 V to 460 V with output voltage stabilized at 415 Volts with accuracy of + 1% and speed of correction 8 V/Sec, no load loss less than 0.5%, operating temp - 15C to 45C above ambient and unbalanced load complete with first filling of oil complete all as specified and directed including additional features as follows:
a. High & low voltage cut off system
b. Change over switch to by-pass the system | 3 | Each | - | - |
| 5 | Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 95 Sq mm 3.5 core complete all as specified and directed. | 230 | RM | - | - |
| 6 | Supply, laying & testing cable XLPE insulated, screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) with stranded aluminium conductor, 11000 Volts grade 95 sq mm 3 core complete all as specified and directed. | 70 | RM | - | - |
| 7 | M&L for earthing complete with galvanized steel earth plate electrode 60 x60 cm and 6 mm thick buried directly in ground (earth pit not less than 2.25 m deep below ground level) with top edge of the plate not less than 1.5 meter below normal ground level connected to GI earth lead wire 4 mm dia by means of bolts nuts, check nut and washers of GI and GI tubing 15 mm bore, medium grade for earth lead protection up to main earth test point and including concrete pit in PCC 1:3:6, type C1 pre cast RCC 1:2:4, type B1 cover slab 450 x 450 x 50 mm reinforced with 8 mm dia TMT bars 100 C to C including one handle for lifting made out of 8 mm dia MS bar, wire mash, 20 mm bore GI tubing medium grade for watering, charcoal and salt in alternate layers including excavation earth work electrical plate no 3 of SSR Part-I complete all as specified and directed. | 4 | Each Set | - | - |
| 8 | M&L earthing complete with galvanized earth plate electrode 600 x 600 and 6 mm thick buried directly in ground vertically to a depth of not less than 2.25 mtr below ground level connected to 32 x 6mm earth strip with nut, bolts and washers made out of galvanized iron mild steel and 40 mm dia GI pipe "light grade" for protection of earth lead and connected to control board or main switch or as directed by Engineer -in-Charge including earthing pit in PCC 1:3:6, type C1 for chamber & Pre-cast RCC cover of size 380 x 380 x 40 mm with one handle made out of 8 mm dia round bar, 20 mm dia GI pipe light grade for watering funnels , wire mesh and provided charcoal or coke of alternative layers of 15 cm including necessary earth work as Exc, R&F & removal etc. complete all as specified and directed. | 8 | Each Set | - | - |
| 9 | S&F HT 11 KV outdoor type gang operated air break switch suitable for horizontal type complete with 12 insulators 200 Amps complete all as specified and directed. | 1 | Each | - | - |
stage.html
html • 0.03 MB
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.32 MB
TENDER44.pdf
Tender Documents • 1.40 MB
BOQ_873733.xls
BOQ • 0.33 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .