Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹22.7 LAccepted-AOC 110059 NEW DELHI NATIONAL CAPITAL TERRITORY OF DELHI 110059 | WEST DELHI | DELHI | 110059 | L1 | Accepted-AOC L1 bidder | |
| 2 | L2₹26.0 L+₹2.1 L (8.75%)Rejected-Finance | L2 | Rejected-Finance Other than L1 | |
| 3 | L3₹26.2 L+₹2.3 L (9.78%)Rejected-Finance | L3 | Rejected-Finance Other than L1 | |
| 4 | L4₹27.2 L+₹3.4 L (14.1%)Rejected-Finance NA | NA | NA | 121004 | L4 | Rejected-Finance Other than L1 | |
| 5 | L5₹31.3 L+₹7.4 L (31.0%)Rejected-Finance | L5 | Rejected-Finance Other than L1 |
Tender Value
₹35 L
EMD Value
₹70,000
Closing Date
29 Jun 2024, 6:00 pmClosed
GE AF Tughlakabad
GE AF TUGHLAKABAD SANGAM VIHAR PO NEW DELHI 110080
REPAIR/MAINT OF PERIMETER LIGHTS, HIGH MAST LIGHT, SECURITY LIGHTS AND MISC E/M WORKS AT TECH AREA AND VSV, MES COLONY AT AF STN UNDER GE (AF) TUGHLAKABAD
2024_MES_652633_1
GE/TKD-17/2024-25
Open Tender
Civil Works - Others
Item Rate
270 days
GE AF Tughlakabad
MES contractor enlisted having deposited Standing Security with dept. Contractors not enlisted in MES should meet the MES enlistment criteria corresponding to appropriate class and category
9 documents required · 9 mandatory
₹500
GE AF Tughlakabad
₹70,000
Yes
9 Nov 2024
31 May 2024
1 Jul 2024
31 May 2024
29 Jun 2024
15 Jun 2024
Amount
M&L for servicing of High mast of any height and description , opening the mechanical hoisting / lowering assy , steel wire bobbin , replaceing the unservieable meshing gear, easying the steel rope movements, checking the locking mechanism , replaceing of oil, greasing incl necessary tool/equipment, complete and checking for smoot operation of the high mast, complete all as speficied and directed by Engr-in-charge.
M&L in replacement, re-winding of high mast motor 3 HP and removing the burntout windings, re-winding the same with super enamelled copper wire of existing guage,varnishing and oven drying, assembling and testing in position, complete all as speficied and directed by Engr-in-charge.
M&L in replacement, SMC Kiosk looping box 3 phase with 4 No bus bar, 63 Amps aluminium 4 wire and 1 nos Kit kat fuse of 10 amps factory made out of 14 gauge steel sheet locking arrangement front side of suitable size 300x200x100 mm complete all as specified and directed by engg in charge.
S&F in replacement, LED street light fitting of capacity 100 watt, cool white, complete with drivers and all accessories & making all necessary connection complete all as specified and directed
S&F in replacement, LED street light fitting of capacity 60 watt, cool white, complete with drivers and all accessories & making all necessary connection complete all as specified and directed
S&F in replacement, LED street light fitting of capacity 45 watt, cool white, complete with drivers and all accessories & making all necessary connection complete all as specified and directed
S&F in replacement, LED street light fitting of capacity 30 watt, cool white, complete with drivers and all accessories & making all necessary connection complete all as specified and directed
S&F in replacement of MCCB four pole alongwith spreader/link, 415 V , fixed thermal and magnetic setting of capacity 63Amp, breaking capacity 10 KA complete suitable for fixing in inside LT Panel/feeder pillar in replacement of existing MCCB all as speficied and directed by Engr-in-charge .
S&F in replacement MCCB 4 Pole alongwith spreader/link 415 V,adjustable type 160 Amps with breaking capacity 36 KA suitable for fixing in inside LT Panel/feeder pillar in replacement of existing MCCB all as speficied and directed by Engr-in-charge .
S&F in replacement LED integral post top made in die cast aluminium housing with decorative clear opal acrylic diffuser and IP 65 protection capacity 1 x 40 Watt complete all as specified and as directed by Engr-in-charge .
Supply and Fix in replacement of alluminium 4.0 sqmm, 3 core service wire , PVC insulated complete all as specified and directed by Engr-in-charge.
Supply and Fix in replacement of alluminium 2.5 sqmm, 2 core service wire , PVC insulated complete all as specified and directed by Engr-in-charge.
S&F in replacement street light bracket made out of GI pipe, 40mm bore, light grade, 1.50 metres long, bent to shape required, as in street light brackets, fixed to poles/ walls with suitable size MS clamps, nuts & bolts complete all as specified and as directed. including applying one coat of aluminium paint over a coat of red oxide primer complete all as speficied and directed by Engr-in-charge.
Supply and fixing in replacement PVC insulated and sheathed circular flexible copper conductor 1100 volts, of size 6 sqmm 4 core from looping box to street light / panel wiring circuit complete all as per site requirement and specified by Engr-in-charge.
S&F in replacement of PVC insulated multi core copper conductor of size 2.5 sqmm, 4 core, 1100 volts,complete all as specified by Engr-in-charge.
S&F in replacement GI pipe of size 50 mm dia light grade for housing/protection of LT cables cables, complete all as specified & directed by Engr - in- Charge.
M&L for Painting to LT steel tubular pole of 11 mtr long including painting of MS work like cross arms, clamps , channel , bracing etc complete after cleaning and preparation the surface , externally with one coat of aluminium paint, 1 mtr height from ground level with blue paint making back ground and writing numbering of poles complete all as specified and as directed by Engr-in-charge
S&F in replacement of steel tubular swaged poles with cast iron base plate, finial taper plug top, bolts, nuts & screws as complete confirming to IS-2713, 9.0 in long type 410, SP-31 erecting truly vertical welded Including excavation in any type of soil and cement concrete (1:2:4) type B-2 as in foundation filling and cement concrete for coping benching including necessary from work complete all as specified and as directed by Engr-in-charge.
Supplyand Fix in replacement of Copper conductor multistranded standard FRLS PVC insulated 2.5 Sqmm single core complete all as specified and directed by Engr-in-charge.
Supply and Fix in replacement of copper conductor multistranded standard FRLS, PVC insulated 1.5 Sqmm single core complete all as specified and directed by Engr-in-charge.
S&F in replacement of MCB TPN 4 pole 125 amp 415 volt,10KA breaking capacity complete all as speciifed and directed.
S&F integral in replacement of post top made in die cast aluminium housing with decorative clear opal acrylic diffuser and IP 65 protection capacity 25 watts complete all as specified and as directed by Engr-in-charge .
M&L in replacement of High Bay light fitting 150 watts 240 volts, 50 HZs single phase power supply, fabricated with die cast aluminium with high power LEDs as light source, IP 65, hight upto 12 mtr and commissioning & testing the high bay light with all standered accessories complete all as speficied and directed by Engr-in-charge.
M&L in replacement of High Bay light fitting 200 watts 240 volts, 50 HZs single phase power supply, fabricated with die cast aluminium with high power LEDs as light source, IP 65, hight upto 12 mtr and commissioning & testing the high bay light with all standered accessories complete all as speficied and directed by Engr-in-charge.
M&L for Excavation in trenches in soft/loose soil not exceeding 1.5 mtr depth and n.exc 1.5 mtr wide for laying of pipes/cables etc and getting out all as specified and directed by engineer in charge.
M&L Returning, filling in including spreading, leveling, watering and well ramming in layers not exceeding 25 cm thick in soft/loose soil complete all as specified and directed by engineer in charge.
Removing excavated material not exceeding 50mtr and depositing where directed at a level not exceeding 1.5mtr above the starting point complete all as speficied and directed by Engr-in-charge.
M&L for sand cushioning to underground cable provided with layer of sand, 8 cm deep before laying the cable and 15 cm deep after laying the cable i.e. total 23 cm and after punning down sand cushioning will be 18 cm complete all as specified and as directed by Engr-in-charge. Note: 18 cm thick only will be considered for payment purpose.
Supply and laying well burnt sub class ‘B’ bricks of size 23 x 11.5 x 7.5 cm laid feat dry, locally available in trenches for protection of underground cable complete all as specified and as directed by Engr-in-charge.
Taking out U/S, burnt LT cables of any sizes from the trench in any depth complete all as specified and directed by Engr-in-charge. Note:- Necessary earth work if any required shall be measured and paid.
Supply and Laying of cable XLPE insulated screened PVC bedded, galavanised steel strip or wire armored, electric power cables (heavy duty) 1100 volts grade with stranded aluminium conductor of following sizes :-
120 sqmm 3.5 core.
95 sqmm 3.5 core.
70 sqmm 3.5 core.
50 sqmm 3.5 core.
35 sqmm 3.5 core.
25 sqmm 4 core.
16 sqmm 4 core.
10 Sqmm 4core
S&F in replacement, commissioning, testing of panel light 36 watts luminaire suitable for fall celling and grid of size 600 x 600 mm with electronic driver completet all as specified and directed by Engr-in-charge.
M&L for repairing broken coping of pole foundation by using PCC of 1:2:4 type B1 by using 20mm graded aggregate as pole base upto the height of 50 cm from ground level and 600mm dia including necessary form work ,and painting with oil bound distemper over coat of primer and finishing the surfaces all as specified and as directed by Engr-in-charge.
S&F in replacement MCCB 4 Pole alongwith spreader/link, 415 V , adjustable type 250 Amps with breaking capacity 36 KA suitable for fixing in inside LT Panel/feeder pillar of existing MCCB all as speficied and directed by Engr-in-charge .
S&F in replacement MCCB 4 Pole alongwith spreader/link, 415 V adjustable type 125 Amps with breaking capacity 36 KA suitable for fixing in inside LT Panel/feeder pillar in replacement of existing MCCB complete all as speficied and directed by Engr-in-charge.
M&L in replacement street light timer switches complete panel, including testing and commissioning of nature switch for outdoor lighting automation using space grade sensors and an advances micro controller suitable for outdoor use having features automatic switching ON /OFF 230 Volts,50 Hz complete with all connected accessories of rating 12 KW 3 phase, complete all as speficied and directed by Engr-in-charge.
S&F in replacement MCCB 4 pole, alongwith spreader/link, 415 V, adjustable type 200 Amp with breaking capacity 36 KA complete suitable for fixing in inside LT Panel/feeder pillar in replacement of existing MCCB complete all as speficied and directed by Engr-in-charge.
S&F in replacement of driver for LED street ligh/flood /high bay light fittings at high mast/pole/bldg at any hight and refixing the same location of 200 Watt, complete all as speficied and directed by Engr-in-charge.
S&F in replacement of driver for LED street ligh/flood/ high bay light fittings at high mast/pole/bldg at any hight and refixing the same location of 150 Watt, complete all as speficied and directed by Engr-in-charge.
S&F in replacement of driver for LED street ligh/flood/ high bay light fittings at high mast/pole/bldg at any hight and refixing the same location of 100 Watt, complete all as speficied and directed by Engr-in-charge.
S&F in replacement of driver for LED street ligh/flood/ high bay light fittings at high mast/pole/bldg at any hight and refixing the same location of 60 Watt, complete all as speficied and directed by Engr-in-charge.
S&F in replacement of driver for LED street ligh/flood/ high bay light fittings at high mast/pole/bldg at any hight and refixing the same location upto 45 Watts, complete all as speficied and directed by Engr-in-charge.
S&F in replacement of MCB SP 5A to 32 amp, 'C' curve, 240V,10KA breaking capacity complete all as speficied and directed by Engr-in-charge.
S&F in replacement of MCB SPN 32 amp, 'C' curve, 240V,10KA breaking capacity complete all as speficied and directed by Engr-in-charge.
S&F in replacement of MCB TPN 4 pole 16 to 32 amp 415 volt,10 KA breaking capacity complete all as speficied and directed by Engr-in-charge.
S&F in replacement of MCB TPN 4 pole 40 to 63 amp 415 volt 10 KA breaking capacity complete all as speciifed and directed.
S&F in replacement of LED flood light 30 watts Gleam outdoor waterproof fitting with pressure die cast housing with IP65 protection complete all as speciifed and directed.
S&F in replacement of LED flood light 50 watts Gleam outdoor waterproof fitting with pressure die cast housing with IP65 protection complete all as speciifed and directed.
S&F in replacement of LED flood light 100 watts Gleam outdoor waterproof fitting with pressure die cast housing with IP65 protection complete all as speciifed and directed.
S&F in replacement of LED flood light 150 watts Gleam outdoor waterproof fitting with pressure die cast housing with IP65 protection complete all as speciifed and directed.
S&F in replacement of LED flood light 200 watts Gleam outdoor waterproof fitting with pressure die cast housing with IP65 protection complete all as speciifed and directed.
S&F in replacement of Programmable digital timer switches complete panel with battery backup and current capacity upto 63 Amps with 1 No changeove 100 amp complete all as speficied and directed by Engr-in-charge.
S&F in replacement of PVC cable loop box, size not less than 145mm x 145mm x 95mm, 3 phase with 4 No bus bar, 63 Amps aluminium 4 wire out door type, duly fitted to poles with suitable clamp, nuts, bolts & washers including one No of 6 to 32 Amps single pole MCB, porcelain insulated connectors for incoming and outgoing cables, complete all as speciifed and directed.
M&L in replacement for Earthing complete with galvanized earth plate electrode 600mmx 600mm x 6mm thick buried directly in ground (earth pit not less than 2.25mtr deep below ground level) with top edge of the plate not less than 1.5mtr below ground level connected to galvenised earth lead wire of 4 mm dia by means of nuts, bolts, washes of galvanized iron or steel all as shown in electrical plate No 3 and testing on completion including adequate charcoal dust comman salt necessary excavation & earth work PCC (1:3:6) type C-1 pit with precast RCC Cover slab 40 mm thick in PCC (1:2:4) type B-0 reinforced with 6 mm dia MS bars @ 100 mm c/c both ways with funnel wire mesh and 20 mm dia GI pipe medium grade as watering pipe complete all as spfd and as directed.
Supply and fix in replacement 3 pole power Contactors NO type 12 Amps AC3 rating with 1 No +1NC Aux complete all as speficied and directed by Engr-in-charge.
Supply and fix in replacement 3 pole power Contactors NO type 18 Amps AC3 rating with 1 NO +1NC Auxall complete all as speficied and directed by Engr-in-charge.
S&F in replacement spare contact kit for MO12/MO18 type contactors complete all as speficied and directed by Engr-in-charge.
M&L for Painting to LT steel tubular pole of 9 mtr long including painting of MS work like cross arms, clamps , channel , bracing etc complete after cleaning with wire brush and preparation the surface , externally with one coat of aluminium paint, 1 mtr height from ground level with blue paint making back ground and writing numbering of poles complete all as specified and as directed by Engr-in-charge
S&F in replacement of solar panel light fittings 20 watts complete all as specified and as directed by Engr-in-charge
M&L cutting removing the vegetation growth any type any size around the perimeter or near pole for fixing street/perimeter lights and surface dressing all around the installation, complete all as speficied and directed by Engr-in-charge.
M/s Prakash Enterprises
M/S Delhi Engineering Co.
M/s Sagar Construction Company
akenterprises
Deepak Electricals
Surjit and Sons
stage.html
html • 0.06 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .