Executive Engineer
Office of Executive Engineer, Electricity 400 KV Sub Station Division, Motiram Adda, Gorakhpur
WORK OF REPAIRING AND REPLACEMENT OF 245KV ISOLATOR (STANDARD/TANDOM) OF 500 MVA ICT-I BAY AT 400 KV S/S MOTIRAM ADDA, GORAKHPUR UNDER ELECTRICITY 400 KV SUB STATION DIVISION GORAKHPUR.
2024_UPTCL_924566_1
E-Tender No.-02/E400 KV S/S D(G)/2024-25
Open Tender
Electrical Works
Item Rate
90 days
400 KV Sub Station Motiram Adda
Please refer Tender Documents
2 documents required · 2 mandatory
₹590
Executive Engineer, E400KV S/S Division, Gorakhpur
₹1,500
10 Jun 2024
10 May 2024
10 Jun 2024
10 May 2024
10 Jun 2024
10 May 2024
Amount
Replacement of low rating (1000 A) 220 KV Standard type Bus isolator jaw & blade of 500 MVA ICT-I Bay. Work included dismentling of all three phase from structure and a new high rating (2500 A) isolator jaw & blade Erected to place of old isolator with fixing PI and base chanel. All isolator accessories i.e. jaw, blade, base chanel, PI etc provided by department. Checking Open - Close of isolator for smooth operation. And T & P required for the job will be provided by the firm.
Replacement of damaged GI pipe with MOM box (E/S& BSI) to earth switch rotary part by means of welding process of LV side (220 KV) 500 MVA ICT -I Bay, with all cost of men, welding machnie etc.
Replacement of damaged gear assembly, connection link rod by new ones then alignment & setting the gears for smooth and frictionless operation of each operating mechanism of 500 MVA ICT-I, LV side (220KV) Tandom Isolator.
Replacement of defective AC/DC control switches, 220V DC contactors and 0.8-1.6Amp thermal overload relays of 220KV Side earth switch MOM boxes installed in the switchyard, then complete rewiring of the control & power circuit for motorised operation of the earth switches as & when required with all cost of men, material T&P etc required for the completion of work.
M/S PRABHATT ENGINEERING WORKS
Ojas Enterprises
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .