Chief Engineer Pune Zone
Chief Engineer Pune Zone Dakshin Kaman Marg Camp Pune 411001
PROVN OF NEW TECH ACCN (OTM ) AT KLP FOR MDC AURANGABAD
2021_MES_409181_3
84476E8
Open Tender
Civil Works
Lump-sum
455 days
Aurangabad under GE South Ahmednagar
CLASS B CATEGORY a i
6 documents required · 6 mandatory
₹2,000
GE (South) Ahmednagar
₹2.8 L
Yes
2 Jun 2021
23 Mar 2021
14 Apr 2021
23 Mar 2021
13 Apr 2021
26 Mar 2021
24 Mar 2021 - 25 Mar 2021
Amount
NOTE: Schedule ‘A’ Part I to XI are Prepriced by MES. Bidders shall insert their lumpsum amount in the Green coloured field under Col-13 only.
Total amount of Sch 'A' Part-I (Building Works)
Total amount of Sch 'A' Part-II (Internal water supply)
Total amount of Sch ‘A’ Part III (Internal Electric Supply)
Total amount of Sch ‘A’ Part IV (External Water Supply)
Total amount of Sch ‘A’ Part V (External Electric Supply & Standby power Supply)
Total amount of Sch 'A' Part-VI (Road, Path & Culvert)
Total amount of Sch 'A' Part-VII (Sewage Disposal)
Total amount of Sch ‘A’ Part VIII (Area drainage)
Total amount of Sch ‘A’ Part IX (Compound wall, Fencing and Gate)
Total amount of Sch ‘A’ Part X (Excavation, Earthwork & Site Clearance)
Total amount of Sch ‘A’ Part XI (Demolition of Existing Building)
SCH 'A PART XII (Miscellaneous B/R and E/M works) Note: This schedule is not pre-priced by MES and the rate indicated as "Rs 0.00" under Col 6 signifies this fact only
M &L for submain wiring with 2 single core FRLS PVC insulated unsheathed, multi stranded flexible copper conductor 1100 volts grade cables 4.0 Sqmm drawn through consealed conduit and including PVC conduit heavy grade with and including 1 single core 4.0 Sqmm 1100 V grade FRLS PVC insulated unsheathed multi stranded flexible copper conductor cable as continuous earth wire and connecting to common earth terminals complete all as specified & directed. Note: 3 runs ( 2+1) of single core FRLS PVC insulated unsheathed multi stranded flexible copper conductor and one run of PVC conduit heavy duty shall be measured as one unit.
M &L for submain wiring with 4 single core FRLS PVC insulated unsheathed, multi stranded flexible copper conductor 1100 volts grade cables 6.0 Sqmm drawn through consealed conduit and including PVC conduit heavy grade with and including 2 single core 6.0 Sqmm 1100 V grade FRLS PVC insulated unsheathed multi stranded flexible copper conductor cable as continuous earth wire and connecting to common earth terminals complete all as specified & directed. Note: 6 runs (4+2) of single core FRLS PVC insulated unsheathed multi stranded flexible copper conductor and one run of PVC conduit heavy duty shall be measured as one unit.
M &L for submain wiring with 4 single core FRLS PVC insulated unsheathed, multi stranded flexible copper conductor 1100 volts grade cables 10.0 Sqmm drawn through consealed conduit and including PVC conduit heavy grade with and including 2 single core 10.0 Sqmm 1100 V grade FRLS PVC insulated unsheathed multi stranded flexible copper conductor cable as continuous earth wire and connecting to common earth terminals complete all as specified & directed. . Note: 6 runs (4+2) of single core FRLS PVC insulated unsheathed multi stranded flexible copper conductor and one run of PVC conduit heavy duty shall be measured as one unit.
M &L for submain wiring with 4 single core FRLS PVC insulated unsheathed, multi stranded flexible copper conductor 1100 volts grade cables 16.0 Sqmm drawn through consealed conduit and including PVC conduit heavy grade with and including 2 single core 16.0 Sqmm 1100 V grade FRLS PVC insulated unsheathed multi stranded flexible copper conductor cable as continuous earth wire and connecting to common earth terminals complete all as specified & directed. Note: 6 runs (4+2) of single core FRLS PVC insulated unsheathed multi stranded flexible copper conductor and one run of PVC conduit heavy duty shall be measured as one unit.
Supply & fix ceiling fan, 1200 mm (48") sweep with BLDC motor, 5 star rating BEE mark (after assembling the same with the fan hook/box) with the fan hook/box and connecitng up complete with and including electronic fan regulator stepped type, modular type, 2 module flush and with and including three core copper conductor flexible cord of 0.5 sqmm cross sectional area of required length from ceiling rose to porcelain connector block of fan. Make : Havells Cat No ES-60 or equivalent in makes listed in Appendix 'C', complete all as specified and as directed.
S & F LED tube along with CRCA LED Batten complete LED light fitting fixture including LED Tube and Batten, LED Tube fitting consist of Polycarbonate housing with extruded aluminium heatsink for mounting LED chip, LED tube system wattage consist of 18 / 20 W, 140-260V AC, system Lumen output min 1800 Lumen in 18 W and 2000 lumen in 20 W with 5700-6500 K CCT with PF>0.95 CRI>=80 and with <=10 % THD, with Min 2.5 KV Surge protection in Built LED Batten consist of powder coated CRCA box type batten with decorative end caps should be supplied for installing above LED tubes complete of Havells Cat Part No. LUMILINEPLUSBS20WLED865SPCSS or equivalent model in the makes as per Appendix ‘C'.
S & F of linear 550 - 600 mm tiltable surface mounted 10 w to 12 w Decorative LED Batten Fixture consist of Aluminium Extrusion housing with PC Diffuser, LED Fixture System wattage of 10 w /12 w, 140V - 260V AC, System Lumen Output min 1000 Lumen in 10 w or 1200 lumen in 12 w with 5700 - 6500 K CCT with pf > 0.95 and with < = 20% THD, with min 2.5 KV Surge protection in Built and complete LED fixture with BIS R mark and R Registration no. complete all as specified and as directed of Havells Cat Part No. LUMILINEPLUSBS10WLED865SPCSS or equivalent model in the makes as per Appendix ‘C’.
S & F of 2ft x 2ft Grid ceiling surface type 36 w - 40 w ceiling mounted bottom opening LED Cleanroom fitting including LED Fixture powder coated CRCA housing and polycorbonate diffuser, LED fixture system wattage of 36 w - 40 w, 140V - 260V AC, system lumen output min 3600 lumen in 36 w or 4000 lumen in 40 w, with 5700 - 6500 K CCT with PF > 0.95 CRI > = 80 and with < = 10 % THD with min 2.5 KV surge protextion in built and complete LED fixture with BIS R mark and R Registration no. complete of Havells Cat Part No. PLANO2X2PLR34WLED8575S or equivalent model in the makes as per Appendix ‘C’.
S & F of LED light fitting out door type Building security light 25W to 30W fixture consist of Extruded Aluminium Extrusion housing with PC Diffuser, LED Fixture System wattage of 36W /40W, 140V - 260V AC, System Lumen Output min 3960 Lumen in 36W or 4400 lumen in 40W with 5700 - 6500 K CCT with pf > 0.95, CRI >=80 and with < = 10% THD, with min 2.5 KV Surge protection in Built and complete LED fixture with BIS R mark and R Registration no. All as per Philips Cat No SM 365C LED 32-6500 PSU OD WH or Havells Cat Part No. ENDURAPEARLSL25WLED 757SASY TOPC or equivalent model in the makes listed in Appendix ’C’ with and including brackets made of 40mm dia GI tubung light grade bent to shape required includnig 2 Nos of Flat Iron brackets duly welded with nuts, bolts and washers.
S & F 2' x2' grid ceiling outdoor type recess 36w-40w ceiling mounted bottom opening LED cleanroom fitting including LED fixture powder coated CRCA housing and polycorbonate diffuser, LED fixture system wattage of 36w to 40w, 140-260V AC, system Lumen output min 3600 Lumen in 36 W or 4000 Lumen in 40W, with 5700-6500 K CCT with PF>0.95 CRI>=80 and with <=10 % THD, with Min 2.5 KV Surge protection in Built and complete LED fixture with BIS Mark and R Registration no. of Havells Cat Part No. VENUSNEOHE2X2PLP18-42WLED865MOD or equivalent model in the makes as per Appendix ‘C’ and shall confirm all above specification of respective suitable Cat reference.
S&F MCB Single pole 240 volts 6 Amps to 32 Amps 10 KA , 'C' series, complete all as specified and directed.
S&F MCB TPN 240 volts 32 Amps 16 KA complete all as specified and directed.
S&F MCB TP, 240 volts, 63 Amps 25 KA complete all as specified and directed.
S&F MCCB 4 Pole, 415 volts, 63 Amps 16 KA complete all as specified and directed.
S&F MCCB 4 Pole, 415 volts, 32/40 Amps 16 KA complete all as specified and directed.
S&F MCCB 4 Pole, 415 volts, 125 Amps 25 KA complete all as specified and directed.
S&F TV Socket modular complete all as specified and directed.
S&F Telephone socket modular complete all as specified and directed.
Supply & fix PVC body exhaust fan 225mm sweep, 1400RPM, single phase, light weight, white/ivory plastic rust proof body & blades, self opening louvers for protection from birds and rain water, fixing by means of rugged bolts, nuts and washers etc on the round hole cut in wall, including three core copper conductor flexible cord of 0.5sqmm cross sectional area of required length from ceiling rose to porcelain connector block of exhaust fan suitable on working AC, SP 230 V electric supply. Make as listed in Appendix 'C', complete all as specified and as directed.
Supply, installing, connecting, testing and commissioning of electric water heater storage type capacity 25 Litrs BEE 5 star rated (2017) with stainless steel innner tank duly insulated with 50mm thick glass wool and duly powder coated outer container, indicating lamps, thermostat with 1.5KW ISI marked heating element, horizontal or vertical type with ISI certification mark, installing on wall with suitable size bolts, nuts, etc and connecting up with water and electric connections including hot and cold connection pipes complete all as specified and as directed.Make as listed in Appendix 'C'.
Supply, installing , connecting , testing and commissioning storage type water cooler 80 Litrs capacity and cooling capacity 40 Litrs per Hour, based on eco friendly gas R-134a all as directed at site including extending drain out pipe to the nearest drain system complete of make Blue Star/Usha/Voltas, all as specified and as directed.
Supply, installing, connecting, testing and commissioning of refrigerators, electric driven (single phase) of capacity more than 150 Litrs upto 165 Litrs, 220 Volts, 50Hz , BEE 5 star rated (2017) based on eco friendly gas R-134a complete of make Blue Star /LG /Voltas /Godrej, all as specified and as directed.
Supply, connecting and testing digital copper wound automatic voltage stabilizer for automatic operation. Single phase naturally air cooled indoor type & designed for input varation between 170V to 250V with output voltage stabilized at 230V with accuracy of (+)2.5%/(-)2.5% and capacity 2KVA complete all as specified and as directed.
Supply and Installation, commissioning of Hi-wall mounted split AC unit outdoor/indoor complete with cordless remote control unit and with in built air ioniser and plasma filter for better indoor air quality of capacity 1.5 TR, working with R410A refrigirent and defrosting sensor technology copper condenser coil, BEE 5 star rating (2019) complete all as specified of make as listed in Appendix 'C'.
Supply and Installation, commissioning of Hi-wall mounted split AC unit outdoor/indoor complete with cordless remote control unit and with in built air ioniser and plasma filter for better indoor air quality of capacity 2 TR, working with R410A refrigirent and defrosting sensor technology copper condenser coil, BEE 5 star rating (2019) complete all as specified of make as listed in Appendix 'C'.
Supply and fix voltage stablizer for automatic operation, single phase naturally air cooled indoor type and designed for input variation between 170 volts to 250 volts with out put voltage stablized at 230 volts with accuracy of + 2.5% and capacity 3 KVA suitable for A/C complete all as specified of any of make listed in Appendix 'C'.
M& L for Earthing complete with galvanised steel earth plate electrode 600 x 600 x 6.3 mm thick, buried vertically in ground (Earth pit not less than 2.25 metres deep below normal ground level and top edge of the plate not less than 1.5 m below ground level), connected to and including Galvanised steel earthing wire 4mm dia by means of bolts, nuts & checknuts and washers etc; GI pipe 15 mm dia medium grade pipe for protection of G.I earth strip, both to be provided to the extent of 7.5 metres, all as shown on electrical plate No 3 of MES SSR-2009 Part-I, other end connected to electrical main switch board (inside the bldg) GI protection pipe buried in ground, laid under floors/plinths or fixed on walls or concealed in walls etc; with provision of mixture of charcoal dust & common salt packed upto minimum 150 mm all around the earth plate , including PCC 1: 2 : 4 type B-1 earth pit with M.S angle iron frame, cast iron cover with locking arrangement, with G.I 20 mm dia medium grade pipe and M.S funnel with wire mesh for watering arrangement, including necessary excavation and earth work in any type of strata & testing on completion.
M& L for Earthing complete with galvanised steel earth plate electrode 600 x 600 x 6.3 mm thick, buried vertically in ground (Earth pit not less than 2.25 metres deep below normal ground level and top edge of the plate not less than 1.5 m below ground level), connected to and including GI strip 32x6 mm by means of bolts, nuts & checknuts and washers etc; GI pipe 40 mm dia medium grade pipe for protection of G.I earth strip, both to be provided to the extent of 7.5 metres, all as shown on electrical plate No 3 of MES SSR-2009 Part-I, other end connected to electrical main switch board (inside the bldg) GI protection pipe buried in ground, laid under floors/plinths or fixed on walls or concealed in walls etc; with provision of mixture of charcoal dust & common salt packed upto minimum 150 mm all around the earth plate , including PCC 1: 2 : 4 type B-1 earth pit with M.S angle iron frame, cast iron cover with locking arrangement, with G.I 20 mm dia medium grade pipe and M.S funnel with wire mesh for watering arrangement, including necessary excavation and earth work in any type of strata & testing on completion.
M& L for Earthing complete with copper earth plate electrode 600 x 600 x 3.15 mm thick, buried vertically in ground (Earth pit not less than 2.25 metres deep below normal ground level and top edge of the plate not less than 1.5 m below ground level), connected to and including copper strip 20x3 mm by means of bolts, nuts & checknuts and washers etc; GI pipe 40 mm dia medium grade pipe for protection of G.I earth strip, both to be provided to the extent of 7.5 metres, all as shown on electrical plate No 3 of MES SSR-2009 Part-I, other end connected to electrical main switch board (inside the bldg) GI protection pipe buried in ground, laid under floors/plinths or fixed on walls or concealed in walls etc; with provision of mixture of charcoal dust & common salt packed upto minimum 150 mm all around the earth plate , including PCC 1: 2 : 4 type B-1 earth pit with M.S angle iron frame, cast iron cover with locking arrangement, with G.I 20 mm dia medium grade pipe and M.S funnel with wire mesh for watering arrangement, including necessary excavation and earth work in any type of strata & testing on completion.
Supply, installing, testing and commissioning of weather, dust and vermin proof wall mounted LT distribution panel board factory made, indoor type of suitable size so as to accomodate the following accesories, depth not less than 500mm, IP 54, and all as per IE rules, prewired and fabricated with 2mm thick CRCA sheet epoxy power coated double door with aprons, duly powder coated after seven tank process with fully compartmentalised / modular construction with Bus bar and cable ally, mounted on MS 50x50x6mm angle iron frame and in shape with two coats of synthetic enamel paint over a coat of red oxide primer including necessary fixing and mounting on wall including connection cable with cable glands, lugs etc and consisting of the following:- .
(a) Copper bus bar 300Amps ( 04 Nos) - mounted on epoxy based insulator installed with colour sleevs - 01 Set (3 Phase and neutral)
(b) Incoming
i) MCCB 125 Amps, FP, 415V, 50Hz ICU 50 KA breaking capacity adjustable magnatic release ( 3.5 to 10.0In) , over load release of adjustable thermal release ( 0.64 to 1.0) - 01 No
(c) Outgoing
i) MCCB 63 Amps, FP, 415V, 50Hz ICU, 35 KA breaking capacity adjustable magnatic release ( 3.5 to 10.0In) , over load release of adjustable thermal release ( 0.64 to 1.0) - 03 No
ii) MCCB 32 Amps, FP, 415V, 50Hz ICU, 35 KA breaking capacity adjustable magnatic release ( 3.5 to 10.0In) , over load release of adjustable thermal release ( 0.64 to 1.0) - 04 No
iii) Voltmeter digital type 3 phase, 500 V AC-01 No
iv) Ammeter digital type 3 phase, 0-200 Amps with CTs-01 No
v) LED phase indicator lamp (R,Y,B) set of Three. - 01 Nos.
vi) Panel control wiring complete with suitable size copper conductor cable and suitable size gland for LT cables
Note: Panel shall be manufactured by the reputed manufacturer who is possession of type test certificate by CPRI not older than ten years.
M&L for 60mm thick machine pressed pre-cast cement concrete interlocking paver blocks with grey cement and pigment, rubber moulded any shape and size confirming to IS 15658-2006, M-35 grade as in floor/pavement laid over and including 30mm thick crushed stone sand complete all as specified and as directed.
Material & labour for construction of valve pit chamber having internal dimensions 900mmx900mmx600mm in PCC 1:4:8 type D-2 using 40mm stone aggrgate for foundation of 150mm thick, 150mm wide offses around over 100mm thick hard core, 200mm thick PCC solid block walls in cement mortar 1:4, PCC coping 50mm thick in cement concrete 1:2:4 using 20mm graded stone aggregate finished smooth, rendering cement plaster 10mm thick in cement mortar 1:4 and finished even and smooth without using extra cement internally all round and externally upto 300mm from top including fabrication of MS cover embedded to chamber, using 40x40x6mm angle iron, MS plate of size 1200mmx1200mm and 3.00mm thick, handle made out of flat iron of size 25x4mm, butt hinges heavy weight, cold rolled mild steel of size 125mm-2Nos,including painting to steel surfaces with two coats of synthetic enamel paint over a coat of red oxide primer including excavation and earth work in hard /dense soil complete all as specified and directed by Engr-in-charge.
Supply, install, test & commissioning of outdoor type plinth mounted transformer step down, outdoor type trnasformer 100 KVA double copper wounded with all standard fittings, HT 11 KV 3 Ph, LT 433 Volts, 3 Phase, 4 wire with off load tappings on HT side to vary secondary voltage to +/- 2.5% in step up 7.5% within limit, all as per IS:2026 star delta as per Vector group DYN -11 solid insulation class A, the temperature shall not exceed 50 degree centigrade measured by thermometer. The Transformer shall be equipped including first fill of transformer oil necessary mounting on PCC platform as per manufacturer's recommendations/Specifications. . Note: Neccessary fencing for the transformer shall be provided as per TD drg and cost of the plinth alongwith 50mm ballast to be spread inside the transformer yard shall be deemed to be included in the cost of transformer. .
(a) Externally hand operated off load tap changer switch with locking arrangement /device.
(b) Oil conservator tank with drain plug and filling cap.
(c) Silica Gel dehydrating breather charged with silica gel.
(d) Oil filter and drain valve
(e) Oil level gauge
(f) Marshalling box consisting oil temperature gauge & winding temperature
(h) Diagram and rating plate
(j) Air Vent
(k) Explosion Vent
(l) Lifting Lugs, Jacking Pads
(m) HT cable box suitable for connection cable
(n) LT cable box suitable for connection cable
(o) Four Nos bi-directional plain/flat roller
(p) Earthing terminal
(q) Skids
(r) First fill of oil
(s) Buchholz relay with one No alaram & one No trip contact
Supply, laying and testing XLPE insulated, screened, PVC bedded galvanised steel strip armoured electric power cable , heavy duty with aluminium conductor, 11000Volts grade earthed, laid in trenches, ducts, along pole, along transformer cross sectional area 95Sqmm 3 Core complete all as specified and as directed.
Supply, laying, testing and commissionnig of UG LT cables 1100 volts grade, XLPE insulated, screened and PVC sheathed, galvanised steel strip or wire armoured with multi stranded aluminum conductor, ISI marked, heavy duty including cable glands, cable lugs in LT panel/MDB in building etc to suit the cable including material and labour for all jointing/connecting material as required size, cables laid in trenches/ducts/under plinth floors passing through pipes etc, fixed on wall complete of following sizes :-
(a) 95 sqmm x 3.5 core
(b) 70 sqmm x 3.5 core
(c) 50sqmm x 3.5 core
(d) 10 sqmm x 2 core
S & F in replacement of LED street light 45 watt, Lumens output 7000 with high luminious effeciency, protected to IP-65 with front toughened glass and connecting with 4 Sqmm twin core aluminium cable approx 2 m length with and including bracket made of 40mm dia GI light grade tube with two NOs clamps of Flat Iron 40x4mm , nuts, boltsd and washers complete all as per Bajaj Cat No 169910,BBRLEP 45W LED V2 65 or Havells Cat Part No. ENDURAPEARLSL45WLED757SASYTOPC or equivalent model in the makes listed in Appendix 'C', complete all as specified and as directed.
S & F factory made PVC weather proof, hinged door, Junction boxes of size 250x200x80mm for street light fittings, weather proof IP-54 protection, hinged door, with Bakalite connector 100 Amps capacity, 4 way and 01 No MCB SP of 6Amp, necessary fixing arrangement such as clamps, nuts, bolts, with and including 2 Nos GI pipe of 25mm bore light grade, 1m long each for cable entry and exit all as specified and as directed.
M & L for cutting the existing road/hard standing surface to a depth of 60cm and 50cm width and getting out for laying under ground cable including returning filling in, watering well ramming in layers not exceeding 25cm in soil and filling the top 15 cm with PCC 1:2: 4 type B-1 (using 20mm graded coarse stone aggregates) all as specified and as directed.
Supply, installing, testing and commissioning, weather, dust and vermin proof LT panel board factory made, outdoor type of suitable size so as to accommodate the following accessories, depth not less than 500mm, IP 54 and all as per IE rules, prewired and fabricated with 3.15mm thick CRCA sheet exoxy power coated double door with aprons, duly powder coated mounted on MS angle iron frame 50x50x6mm welded in shape with two coats of synthetic enamel paint over a coat of red oxide primer including necessary grouting in PCC 1:3:6 type C-1 using 20mm graded coarse stone aggregates complete with leg 50cm grounted in ground in PCC at 40cm above ground including connection cable with cable glands, lugs etc and consisting of the following : .
(a) Copper bus bar 300Amps mounted on epoxy based insulator installed with colour sleeves - 01 Set( 3 Phase and neutral)
(b) Incoming
(i) MCCB 4 Pole, 415 Volts, 200 Amps, 35 KA , 50 Hz, with thermal adjustable between 70-100% -01 No
(c) Outgoing
(i) MCCB 4 Pole, 415 Volts, 125 Amps, 25 KA , 50 Hz, with thermal adjustable between 70-100% -02 No
(ii) MCB TPN, 32 Amps, C series, 440 Volts, 10 KA , 50 Hz -01 No
(iii) MCB SPN 10 Amps C series 10 KA,230 V 50 Hz ICU -01 No
(d) Voltmeter digital type of range 0 to 500 Volts -01 Nos
(e) Ammeter digital type of range 0-200 Amps with suitable capacity CTs-01 Nos
(f) LED phase indicator of Red, yellow, blue-01 set of 03
(g) S & capacitor mtealized poly propylene heavy duty ( MPP-H) for 3 phase, 440V, 50 Hz system for permissible non linear load 15% of 15 KVAR capacity
(j) Panel wiring with suitable capacity of copper conductor cable of 1100 V grade
(k) PCC Foundation (1:2:4) type B1 of suitable size as directed by Engr-in-Charge.
Supply, install, testing and commissioning silent Diesel Engine driven generating set 415 Volts, 3 phase 4 wire with 5 Yrs warranty as per BS 5514/IS-10002 complete with automatic ON/OFF on main failure (AMF) panel, complete with all standard accessories as per IS and norms, the capacity of DG set shall be continuous rating 75KVA at NTP conditions with acoustic enclosure and canopy cover considering all derating factors and as applicable at Pune comprising of the following :-
(a) Alternator : Self regulated with brushless self excitation 415 V, 3 Phase, 4 wire 50 Hz, 0.8 PF, 1500 RPM with voltage variation plus or minus 2.5% of rated voltage from no-load to full-load foot mounted screen protected drip proof type with class 'F' insulation, steel ball/roller bearings at both ends of the alternator shaft with necessary controls as recommended by manufacturers confirming to BS-5000/IS-4772/13364, capable of supplying unbalanced load.
(b) Engine : Multi Cylinder compression Ignition, heavy duty, turbocharged, compact diesel engine water cooled through radiator with water pump, hydraulic governing mechanism, all as per BS - 5514/ IS - 3046 : 1500 RPM class A-1, governing/control guages, RPM / Hours meters etc. shaft H.P suitable for generating application and capable of giving an output of 75 KVA for coupled alternator under NTP conditions, complete with following : -
(i) Flywheel housing with flywheel to suit double bearing coupled alternator.
(ii) Flexible coupling set directly mounted to engine and alternator with coupling guard.
(iii) Air cleaner dry type with vacuum indicator.
(iv) Fuel pump and fuel piping 15 mm dia MS pipe with bends, flanges etc.
(v) Fuel filter with water separator and filter element.
(vi) Lub - Oil filter with filter element.
(vii) D.C starter 12 Volts.
(viii) Maintenance free Storage type Batteries of suitable voltage and Ampere - hours as recommended by the manufacturers.
(ix) Industrial type silencer including MS exhaust pipe lagged with asbestors rope of 5 mm dia all around and over this 50mm thick flat mineral wool insulator sheet cover and then, 24 SWG Aluminium sheet cladding with rivets, all over the length.
(x) Support / fixing arrangement for muffler with ceiling through anti vibration pads.
(xi) Engine overspeed stop / trip switch.
(xii) Radiator with fan.
(xiii) Dynamo for battery charging.
(xiv) Corrosion inhibitor coolant.
(xv) Engine control panel electronic, digital display type consisting of battery voltage indicator, lub oil temp and pressure guages, coolant water temp guage, RPM indicator-cum-hour meter etc.
(xvi) Safety controls for alarm due to high water temp (HWT) and low lub oil pressure (LLOP)
(xvii) Any other devices /accessories recommended / supplied by the manufacturers as standard eqpt.
(c) Skid : The engine and alternator shall be coupled, aligned and mounted on a specially designed common base frame fabricated from MS channels of suitable cross sectional area and length with bottom drilled holes suitable for and including supplying and fixing anti vibration pads. Make : - Anti vibration pads:-Dunlop / Polybond of required size and numbers as recommended by the manufacturers for mounting of 50 KVA DG set.
(d) Alternator control Panel: Floor mounted, vertical, totally enclosed cubicle, out door type, dust and vermin proof, standard industrial pattern, factory fabricated out of 2mm thick CRCA steel sheet duly painted with powder coated paint of approved colour, complete with all mounting structures, insulators, bolts, nuts, washers etc, with necessary control wiring / internal connections with proper size of copper conductor cables, suitable for 3 phase, 4 wire, 50HZ, 440 volts AC system, comprising of required Nos / rating / capacity of MCCBs for Incoming cables (Main / DG) and out going cables, multifunction meter displaying KWH, hours, current, voltage etc, set of LED type indicating lamps "LOAD ON" "SET RUNNING", power contactor suitable for 75 KVA DG set including over current, earth-fault protection realys, high voltage, No voltage, single phasing, relay. (OEM/CPRI Panel). 1 No battery charger, control circuit fuses, reverse power relay, alarm for high water / lub oil temp and low lub oil pressure, push buttons for start / stop, any other control devices / measuring instruments as recommended / supplied by the standard equipment manufacturers, complete with cable glands with gland plate for cable entry, control cabling with copper conductor armoured mult-core cables of required cross sectional area from DG set to control panel, including taking out of manual panel after disconnecting incoming and outgoing cables and reconnecting the same cables in new panel complete all as specified and directed.
(e) Diesel tank of adequate capacity for 12 hours continuous run on full load with caliberated scale (fuel level indicator) dip stick, fuel inlet / outlet, Air vent, drain plug and inlet arrangement for direct filling, including suitable size gun metal gate valve in outlet, tank shall be fitted all as per manufacturer's requirements / specification.
(f) Acoustic enclosure with canopy cover shall be provided as per latest CPCB norms.
(g) PCC platform for instalation of DG set as per specification and design given by the manufacturer.
(h) Documents : Three sets of following documents : - Maintenance and operation manuals for engine and alternator, spare parts catalogue, warranty / test certificates, schematic diagrams of control panels.
(j) Connecting cable in new panel with required accessories etc complete.
(k) Optional items : list of tools and as per manufacturers recommended lists, duly priced, item wise.
Make of DG Set :- Any of the Make listed in Appx 'C' enclosed herewith.
Notes:- (i) Contractors shall satisfactorily conduct load test of each DG set for 12 hours including run on 10% overload for 1 hour.
(ii) Testing eqpt will be arranged by the Contractor under his own arrngement and cost.
(iii) A Common PCC platform / foundation for DG sets shall be provided for above DG sets as per manufacturers instructions. Rate quoted shall be deemed to include for the same.
SUYOG CONSTRUCTIONS
N. H. Saluji & Associates
MS. G.A. CONSTRUCTION
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .