EEMCPH-1, Sec-11, Chd
EMERGENT REPAIR OF 600MM AND 1000MM SLUICE VALVES AT INLET OF RAW WATER TANK NO 6 7 8 AND FILTRATION PLANT AT WATER WORKS SECTOR39 CHANDIGARH CH TO REVENUE HEAD
2026_MCC_94707_1
2026_MCPH1_131
Open Tender
Public Health Estate Works
Percentage
30 days
Chandigarh
Please refer Tender documents.
2 documents required · 2 mandatory
₹0
₹4,880
1 Sept 2026
12 Aug 2026
20 Aug 2026
12 Aug 2026
20 Aug 2026
12 Aug 2026
This is a percentage-rate BOQ. The schedule below shows estimated quantities and rates. Bidders quote a single percentage above or below the total estimated cost.
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | Repairing of 600mm dia sluice valve by replacement broken stem/spindle with new stem madeout of SS 410 round bar and new wedge nut madeout of gun metal material along with repairing of wedge by means of re-metalling, tuning, grinding machining to make accuratesize for fixing of wedge nut including cost of replacement of packing sheet, nut and bolts, gland dori, charges of crane for lowering and lifting, fabrication of spindle & wedge nut along with labour charges for dismentling and refixing complete in all respect. | 1 | P. job | 44,000 | ₹44,000 |
| 2 | Repairing of 1000mm dia sluice valve by replacement broken stem/spindle with new stem madeout of SS 410 round bar and new wedge nut madeout of gun metal material along with repairing of wedge by means of re-metalling, tuning, grinding machining to make accurate size for fixing of wedge nut including cost of replacement of packing sheet, nut and bolts, gland dori, charges of crane for lowering and lifting, fabrication of spindle & wedge nut along with labour charges for dismentling and refixing complete in all respect. | 2 | P. job | 75,000 | ₹1,50,000 |
| 3 | Repair of gear assembaly of 1000/1200mm dia sluice valve by replacement of driven and driven gear, pinion gear, pinion shaft along with making way replacement of nut bolts, packings, grease/oil etc. including opening and refixing of gear assembly complete in all respects. | 2 | P. job | 27,000 | ₹54,000 |
| 4 | Deduction against old material (-) | 1 | P. job | 4,000 | ₹4,000 |
stage.html
html • 0.03 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 5.57 MB
BOQ_116217.xls
BOQ • 0.31 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .