Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹3.8 CrAccepted-AOC NOT SPECIFIED | ₹3.8 Cr | L1 | Accepted-AOC L1 |
| 2 | L2₹3.9 Cr+₹3.6 L (0.94%)Rejected-Finance SHOP NO 10 BMC SHOPPING CENTRE MITHA NAGAR GOREGAON WEST MUMBAI 400 104 | MUMBAI | MUMBAI SUBURBAN | MAHARASHTRA | 400104 | ₹3.9 Cr+₹3.6 L (0.94%) | L2 | Rejected-Finance Other than L1 |
| 3 | Rejected-Technical | - | - | Rejected-Technical Does not qualify for opening of Cover-2 being two classes below the eligible class as per NIT and also having adverse remarks in HQ CE SWC WLR QE Dec 2023. |
Tender Value
₹4 Cr
EMD Value
₹4.8 L
Closing Date
18 May 2024, 6:00 pmClosed
Chief Engineer Pune Zone
Chief Engineer Pune Zone Dakshin Kaman Marg CAMP, Pune PIN- 411001
ADDITION/ ALTERATION AND IMPROVEMENT OF DHANVANTARI AUDITORIUM OF AFMC PUNE
2024_MES_639483_1
CA NO. CEPZ/PNA/TOKEN-20 OF 2023-24
Open Tender
Civil Works
Item Rate
450 days
Pune
Class A, category a(i) and c(i)
Also refer NIT
8 documents required · 8 mandatory
₹2,000
GE (Central) Pune
₹4.8 L
Yes
29 Jun 2024
29 Jan 2024
25 May 2024
29 Feb 2024
18 May 2024
4 May 2024
1 Mar 2024 - 15 Mar 2024
Amount
SCHEDULE 'A' PHASE-I (MAIN WORK)
PRIME COST SUM: Provide Prime Cost sum of Rs 6000000.00 as defined in condition 5 of IAFW-2249 for Design, supply, installation and testing of the following works of accoustic treatement to auditorium hall including all necesary scaffolding, safety measures of building as well as workmen, saftery net and working at any height as per site requirement shall be executed all as specified as under. The complete acoustic treatment (wall panelling and false ceiling) of auditorium shall be got designed from Acoustical consultant/expert agency based on NBC norms :- (a) Sound acoustic Wall Panelling (two types) capableof high soundabsorption 0.9 NRC : 855 Sqm (b) Sound acoustic False Ceing capableof high soundabsorption 0.9 NRC : 170 Sqm
NOTES:- (i) Prime cost sum shall be got executed through the agency nominated by Accepting Officer and ordered by GE as per Condition 5 of IAFW - 2249 (General Conditions of Contract). (ii) The amount of Prime cost sum of Rs. 60,00,000.00 indicated above is Prepriced by MES and the Add/Deduct percentage (%) will be indicated under col 6 of this BOQ over the sum inserted by MES and bidders are requested to quote his lumpsum under col 6 in such a way that the percentage (%) worked out shall not be more than 15% (Fifteen Percent). In case the percentage worked out more than (+) 15% over the lumpsum amount inserted by MES in that case the percentage (%) will be corrected to ensure as (+) 15% only. Also refer Condition 5 of IAFW-2249 (General Condition of Contracts). (iii) Material should be as per IS 2526. (iv) Testing of acoustic material shall be carried out by CBRI Roorkee or equivalent institute. (v) Dismantling of old ceiling sheets and grid adjacent to existing wall panelling shall be carried out carefully and same shall be refixed after new wall panelling work completed for seating portion of Auditorium and same shall be deemed to be included in the quoted rates.
Taking down carefully copper/aluminium point wiring (light, fan, socket or power) complete, including all fixtures and fittings such as switches, ceiling roses, pendants, regulators, sockets, light fitting (except fans) etc. removing materials to store for keeping in safe custody or for taking credit (credit for above items should be made as per conditions separately) and making good disturbed surfaces of walls, floors, etc.; to match with the existing finishes all as specified.
Taking down the existing unserviceable main switch / DBs/ MCB Enclosure of any type / capacity / description as existing at site including MCBs any type and capacity making good the disturbed surfaces to match with the existing finishes all as specified.
Taking down the existing unserviceable sub main wiring of any type / description as existing at site including making good the disturbed surfaces to match with the existing finishes all as specified.
Taking down ceiling fan/ exhaust fan of any sweep, keeping with safe custody and refixing the same with replacement of unsv 3 core PVC insulated multistranded copper conductor cable of size 23/ 0.193 from ceiling rose to fan terminal and material labour over hauling the ceiling fan / exhaust fan including replacement of bearing, winding insulation, capacitor including painting of ceiling fans /exhast fans with synthetic enamel paint by spray painting in one coat including filling cavities with filler after cleaning all dust etc. to achieve smooth surface, complete all as specified.
M&L Point wiring using colour coding as per IS with two numbers of 1.5 Sq mm multistranded copper conductor single core FRLSH PVC insulated unsheathed 1100 Volts, ISI-694 marked cables of any length as required at site, drawn through and including concealed ISI marked PVC conduit medium grade and its accessories (min size of conduit shall be 19 or 20 mm dia), in wall /roof/ floor etc. with GI sunken boxe of 1.6 mm thick, 60 mm depth of suitable size including cutting ,chasing in brick wall, stone masonry/ PCC wall for fixing/ grouting sunken box as per site requirement and making good the surface to match with existing finishes including provision of cover with modular white outer plate with frame and inner plate for mounting the modular switches/ sockets/ regulators etc. including providing and running of one 1.5 Sq mm copper conductor FRLSH, PVC insulated cable as earth continuity conductor along with wiring and connecting to the common earth dolly all as specified for the following:- Note: (i) Circuit wiring of minimum size 2.5 Sqmm from DB to terminal box shall be used. (ii) Rate for M&L for circuit wiring from DB to terminal box shall be deemed to be included in the quoted rate.
a) Two light point controlled by one switch complete all as specified.
b) One fan point controlled by one switch complete all as specified.
c) One three pin 5 Amps socket outlet point controlled by one No one way switch on independent board complete.
Ditto- all as per Item No. 6.00 above but with two number stranded copper conductor 2.5 Sq. mm (nominal area), single core, PVC insulated and unsheathed multistranded FRLSH cable 1100 Volt grade ISI-694 marked for 3 pin, 15 Amp socket outlet, independent, including PVC insulated multistranded FRLSH copper conductor 2.5 Sqmm (nominal area) single core as earth continuity conductor to common earth and connecting to earth dolly, complete all as specified.
S & F for Modular switch one way 6 A, 1 module complete all as specified.
S&F Modular switch one way 16 A, 1 module, with neon indicator complete all as specified.
S&F Modular socket, 6A - 3 pin 2 module complete all as specified.
S&F Modular socket, 3 pin, twin socket, shuttered type 6/16A, 2 module complete all as specified.
S&F Modular stepped type fan regulator 5 steps, 100W, 2 module complete all as specified.
Material and labour for sub main wiring with two single core PVC insulated FRLSH cables with stranded copper conductor of size 1.5 sq.mm, 1100 Volts grade in and including surface, or concealed as per site requirement as directed by Engr-in-Charge, rigid PVC conduit medium grade of suitable size with all fittings & other accessories and additional single core PVC insulated FRLSH multistranded copper conductor cable of size 1.5 sq.mm as a continuous earth wire complete all as specified and as directed. NOTE :-(a) Two runs of 1.5 sq.mm cable with one run of 1.5 sq.mm earth wire along with conduit shall be measured as one unit length for payment purpose. (b) Making good of disturbed surfaces shall be carried out to match the existing surface and rate quoted shall include for the same.
Material and labour for sub main wiring with two single core PVC insulated FRLSH cables with stranded copper conductor of size 2.5 sq.mm, 1100 Volts grade in and including surface, or concealed as per site requirement as directed by Engr-in-Charge, rigid PVC conduit medium grade of suitable size with all fittings & other accessories and additional single core PVC insulated FRLSH multistranded copper conductor cable of size 2.5 sq.mm as a continuous earth wire complete all as specified and as directed. NOTE :-(a) Two runs of 2.5 sq.mm cable with one run of 2.5 sq.mm earth wire along with conduit shall be measured as one unit length for payment purpose. (b) Making good of disturbed surfaces shall be carried out to match the existing surface and rate quoted shall include for the same.
Material and labour for sub main wiring with two single core PVC insulated FRLSH cables with stranded copper conductor of size 4.0 sq.mm, 1100 Volts grade in and including surface, or concealed as per site requirement as directed by Engr-in-Charge, rigid PVC conduit medium grade of suitable size with all fittings & other accessories and additional single core PVC insulated FRLSH multistranded copper conductor cable of size 4.0 sq.mm as a continuous earth wire complete all as specified and as directed. NOTE :-(a) Two runs of 4.0 sq.mm cable with one run of 4.0 sq.mm earth wire along with conduit shall be measured as one unit length for payment purpose. (b) Making good of disturbed surfaces shall be carried out to match the existing surface and rate quoted shall include for the same.
Material and labour for sub main wiring with two single core PVC insulated FRLSH cables with stranded copper conductor of size 6.0 sq.mm, 1100 Volts grade in and including surface, or concealed as per site requirement as directed by Engr-in-Charge, rigid PVC conduit medium grade of suitable size with all fittings & other accessories and additional single core PVC insulated FRLSH multistranded copper conductor cable of size 6.0 sq.mm as a continuous earth wire complete all as specified and as directed. NOTE :-(a) Two runs of 6.0 sq.mm cable with one run of 6.0 sq.mm earth wire along with conduit shall be measured as one unit length for payment purpose. (b) Making good of disturbed surfaces shall be carried out to match the existing surface and rate quoted shall include for the same.
Material and labour for sub main wiring with four single core PVC insulated FRLSH cables with stranded copper conductor of size 6.0 sq.mm, 1100 Volts grade in and including surface, or concealed as per site requirement as directed by Engr-in-Charge, rigid PVC conduit medium grade of suitable size with all fittings & other accessories and two single core additional single core PVC insulated FRLSH multistranded copper conductor cable of size 6.0 sq.mm as a continuous earth wire complete all as specified and as directed. NOTE :-(a) Four runs of 6.0 sq.mm cable with two runs of 6.0 sq.mm earth wire along with conduit shall be measured as one unit length for payment purpose. (b) Making good of disturbed surfaces shall be carried out to match the existing surface and rate quoted shall include for the same.
S&F 4 way VTPN DB, double door, recess mounted/ wall mounted, with 200 A rated aluminium busbar, MCCB as incomer and outgoing MCBs as SP/ TP including 4 pole/ SPN, 415V, 16KA, 100/125A MCCB, all accessories pre-fitted at factory. complete all as specified and as directed. Note : (i) Empty spaces shall be covered by blank plate and connecting with lugs without any extra cost. (ii) Rate for M&L for MCCB 100/125A, 4 pole/SPN, 415V, 16KA is deemed to be included in the quoted rates. (iii) MCBs SP/DP/TP shall be measured and paid separately under respective items of schedule.
S&F MCB SPN DB 12 Way double door with rated capacity 100 amp 240 V
S&F MCB SPN 40-63A, 240 V, breaking capacity 10 KA ,B- curve complete all as specified.
S&F MCB four pole of rated capacity 40-100 amps, 415V breaking capacity 10 KA ,B- curve complete all as specified.
S&F MCB Single pole rated capacity 6 to 32 amps, 240 V breaking capacity 10 KA ,B- curve complete all as specified.
S&F Single pole and neutral enclosure with a two pin and earth plug and socket complete with one single pole 20A MCB complete all as specified.
S&F LED Profile strip light WW/BL 120 LED/Mtr, 12 W /mtr, 12 V complete all as directed.
S&F Aluminium Profile Concealed LPL 1413 suitable for LED Strip complete all as directed.
M&L LED strip driver 16 Amps complete all as specified.
M&L LED Surface Mount Row Marker Light 0.5 Watt, Square/ Rectangular in size, Aluminium Extrusion body, Lamp, SMD & Through Hole Flat LED, Laser Display Engraved Acrylic plate, Surface Screw Mounting with Hidden Screw, Operative Power Supply 12V with Dimmable / Non Dimmable both Option, Colour of fittings Blue/ WW/ Red as directed, minimum size: thickness 7mm, height 70mm, length 100mm including all accessories internally prewired and including connecting of with twin core twisted flexible wire of copper conductor and of suitable size complete all as directed.
S&F heavy duty SMPS (driver) 12 V, 10A for controllimg row marker lights including its controller (actuator) with all necessary accessories & fittings/ fixtures complete all as specified and directed.
S&F recess mounted adjustable LED COB down light 12W round shape madeup of extruded aluminium housing and high power LED and separate electronic driver with all accessories complete all as specified. MAKE: Havells Cat Part No. SPARKLEPROADJDLR12W857MOD40 DWHTNEEM or equivalent in makes as specified in Appendix 'C'. NOTE: Rate for cutting cutouts in the ceiling for fixing of light fitting is deemed to be included in the quoted rate.
S&F in repairs Energy efficient LED security light fitting 45/ 48 watt luminaire in pressure die cast housing in heat resistant cover with IP 66 protection and including GI pipe 40 mm dia 1.2 M length, medium grade tube including two Nos of clamps fixed with suitable size screws and making bend suitable for fixing etc, internally pre-wired and provided with 3 core flexible cable from ceiling rose to fitting complete all as specified.
M&L Earthing with galvanised steel earth plate electrode 60 cm x 60 cm x 6.3 mm buried directly in ground in earth pit not less than 2.25 m deep below normal ground level, with top edge of the plate vertically to depth of not less than 1.5 m below ground level, connected to and including GI wire 4 mm dia and GI pipe 15 mm dia light grade for protection to the extent of 7.5 m as earthing lead by means of GI bolts and nuts etc. connecting to equipment with provision of charcoal and salt in earth pit around plate electrode etc. complete all as per electrical plate No 3 of SSR Part-I including PCC chamber, RCC cover fixed on RCC frame, watering arrangement with GI pipe 20 mm dia and MS funnel including excavation and earth work in any type of soil and testing on completion etc complete all as specified.
Supply and providing Chemical earthing with GI Electrode 3 metre long with ground enhancing back fill compound all including necessary boring at site, installation, transportation, earth work, testing of soil condition, FRP pit cover and GI strip 32 x 6 mm as earth continuity conductor upto 7.5 mtrs long complete all as specified and directed.
Supply, installation, testing and commissioning of 15R 330W phoenix lamp, 330 watt power supply sharpy Moving Head beam light, multi colour lighting, DMX/sound activated, compact housing, 230V IP 20 indoor type high brightness, 1500 to 2000 hrs burning life, double enhanced steped motor, digital control electronic focus,13 pcs Gobos+ open,14pcs colours+open, half colour & Rainbow efect, HTR frost filters, 0-100% linear frost, inbuilt double prism with colour wheel, beam angle shall be adjusted by different gobos. Prism system shall be bi-directional rotating, all including electronic ballast, ON/Off control system by existing DMX512 controller on display complete all as specified and directed.
Supply, installation, testing and commissioning of Follow spot stage light 200 watt input 220V 50/60HZ, 05 colours (RGBYW), 7500k, 4600k, 3200k colour temp. filters, 5-100% linear automization Iris, 1-100% linear audjustable dimmer, remote control system/ Manual adjustable and strobe focus, strobe range 100mtrs, IP20 protectionincluding stand & flight case complete all as specified and directed.
NOTE for item Nos. 32 & 33:- (i) Rates for M&L power point wiring with conduit and its accessories required for functioning of these lights alongwith independent switch, socket, 3 core wire of sufficient length, plug top etc as directed by Engineer-in-Charge and making good the disturbed surface are deemed to be included in the quoted rate.
Supply, laying, testing and commissioning Digital DMX network cable complete all as specified and directed.
Supply, installation, testing and commissioning for XLR-3 DMX connector complete all as specified and directed. Make: Falcon/Canara/Deepcab
Supply, installtion, testing and commissioning of diecast aluminium 'C' Clamps with safety locking chain, duly powder coated in black matt texture finish and technical specifiction as below:- (i) Lock: MS threaded Galvanised lock key, plastic glass filled nylon moulded M6 key. (ii) Receptacle- 28mm standard TV spigot. (iii) Saftey: MS galvanised chain with pin. (iv) Finish: Pretreated and black epoxy polyster powder coated. (v) Self weight- 0.54kg. (vi) Safe working load-150 kg. Make: As approved by GE.
Dismantling and taking down carefully U/S motorised curtain control system with all connected accessories and depositing it to AFMC/ E&M store as directed including making good the damaged surfaces of wall/ ceiling/ flooring etc.
Supply, Installation, testing and commissioning of Automatic motor curtain control system for main curtain and back curtain horizontally operating in two sections consisting of following:- (a) 3 phase motor approximatly 1 HP with worm- gear drive - 02 Nos (b) Motor gear assy- 02 Nos (c) Motor mounting & motor switch - 02 Nos (d) Motor switch and limit switch - 02 Nos (e) Curtain mounting, clippining pulley & wire rope - 02 Nos (f) Motor wiring where the three phase supply is comming and including motor gear arrangements, mounting arrangements etc-01 Job.
WATER-COOLED TYPE SCREW CHILLER UNIT: Supplying, installing, testing & commissioning of water cooled screw chillers with VFD Minimum actual capacity 76-80 TR with compressors comprising of one or semi - Hermetic type screw compressors with capacity control and self motor protection, oil temperature protection etc., Flooded Evaporator, shell and tube condenser, suitable expansion device for operation on R- 407C/410A/ R134A or any new type green Gas refrigerants and of capacity as mentioned & as per specification. All including microprocessor control panel mounted on MS frame, vibration isolators including necessary accessories as per manufacturer's specifications complete all as specified below and for the below mentioned parameters. It shall include flow switch at chiller and condenser, integral insulated refrigerant piping and wiring, first charge of refrigerant and oil, cooling thermostat, thermostatic expansion valves, liquid line strainers, suction and discharge shut-off valves, oil filter, suction filter, refrigerant suction and discharge pressure gauges, accessories as required, automatic and safety controls mounted in central micro-processor based console panel and all mounted on a steel frame etc. complete as per specifications.
(Contd...) Necessary power/control cables from starter panel/ control panel and gauge panel to motors and controls shall also be included. Chiller Panel shall be suitable for termination of cable, contractor to provide necessary adapter box with necessary copper cabling. Motor shall be suitable for 415 +/- 10% 50 cycles, 3 phase AC supply. The Chiller needs to be AHRI/Eurovent Certified. The chiller operation parameters shall be Chilled water in 12°C Chilled water out 7°C. Max operating pressure 150 PSIG (water side/condenser side) Condenser water IN 30°C Condenser water OUT 35 °C. Chiller fouling factor 0.00002 Sq.m deg K/W Condenser fouling factor 0.000044 Sq.m deg K/W. All performance requirements at ARI standard 550/590. Min. COP at 100% load : 5.3 at AHRI Condition. Min. IPLV at 100% load: 6.7 at AHRI Condition. MAKE: Blue Star Model-LCW1-080x010404/ DAIKIN Model No. PFSD0801DARY or equivelent makes as mentioned in Appx 'C'.
NOTES:- The quoted rate shall be deemed to include for following:- (i) RCC/PCC foundation, MS structure work, civil work etc for mounting of Chiller unit as per design, specification and recommendation of manufacturer/ OEM and as directed. (ii) Frame work for mounting of chiller, condensor, compressor, and motor with base plate complete, initial/ first charge of refrigerant gas and compressor oil and other accessories. (iii) Price quoted shall be inclusive of all duties, taxes insurances, transportation, shipment, loading and unloading charges etc from work to site. (iv) The quoted rate shall be inclusive for starters, victaulic coupling and programming of system. (v) Bidder shall visit site before quoting the rates.
Supply, fixing, testing & commissioning of Chiller Plant Manager Software & hardware (description of system control to be as per tender specifications). Chiller Plant consists of 2 Nos Chillers, 2Nos Primary Chilled Water Pumps, 01 Nos Cooling Tower, 02 Nos equipments could operate and control simultaneously. The Controllers need to be BTL Certified. The Chiller Plant Manager and Chiller Supplier shall be responsible to ensure smooth integration. The Controller needs to be factory installed with Algorithms suited for the supplied chiller and including its suitable control cable (Chiller plant manager must be BMS compatible). MAKE: Honey well/ Schnider/ Seimens. NOTE: Rate quoted shall be deemed to include for supply and control cable of chiller plant manager.
CHILLED WATER CIRCULATION PUMP (Variable Primary): Supply, installation, testing and comissoning of horizontal centrally coupled end suction type pump for chilled water circulation system with pump inlet and outlet suitable for connection of pipe size 100 NB and capacity not less than 192 gpm discharged at head of 25m having cast iron casing, enclosed type dynamically balanced bronze impeller , carbon steel pump shaft, mechanical packed sealing , deep groove ball bearings etc with TEFC Sq. cage induction IE3 motor efficiency with class 'F' insulation and suitable for operation 3-Ph, 415 V +/- 10%, 50+/-5 % Hz AC including supply & fixing variable speed drive to regulate water flow, base frame, foundation as per manufacturer recommendation and design, nuts & bolts, mounting channel frame, accessories and fittings, viz Drains, coupling, coupling guard, vibration isolation arrangement by means of spring / rubber type mounting, isolators, mechanical seal etc. The chilled water pumps shall have thermal insulation as per specification. The capacity of motor shall be at least 15% in excess of BHP requirement of pump and other necessary accessories complete all as specified and directed. The insulation of 50 mm thickness for chilled water pump shall be carried out from rigid polyurethane foam having a 'K' value of 0.018 W /m k at mean temperature of 10°C and a density of 40 Kg/cum.
CONDENSER WATER PUMP (Variable speed) - Supply, installation, testing and commissioning of horizontal centrally coupled End Suction type pump for condenser water circulation system with pump inlet and outlet suitable for connection of pipe size 100 NB and capacity not less than 300 gpm discharged at head of 20 m having cast iron casing, enclosed type dynamically balanced bronze impeller, carbon steel pump shaft, mechanical packed sealing, deep groove ball bearings etc. with SPDP operation TEFC Sq. cage induction IE3 motor efficiency with class "F" insulation and suitable for operation 3-Ph, 415 V +/- 10%, 50+/5% Hz AC including Variable supply & fixing speed drive to regulate the flow, base frame, foundation, nuts & bolts, mounting channel frame, accessories and fittings, viz Drains, coupling, coupling guard, vibration isolation arrangement by means of spring / rubber type mounting, isolators, mechanical seal etc. The capacity of motor shall be at least 15% in excess of BHP requirement of pump and other necessary accessories complete all as specified and directed.
FRP INDUCED DRAUGHT COOLING TOWER- Supply, installation, testing and commissioning of CTI Cerified Induced draft with and including Variable speed ross fow cooling towers, factory assembled, field erected, FRP rectangular shape / circular shape, vertical, single cell cooling tower of 200 TR with uniform water distribution and optimal heat transfer, having tough fiberglass reinforced plastic (FRP) casing of sufficient structural strength to withstand vibrations and wind velocity up to 60 m/s, FRP basin, rigid honeycomb type PVC fill of suitable thickness, SS sprinklers and non-clogging sprinkler pipes, suction screen, make up and quick fill arrangement, over flow and drain connection, extended sump, FRP drift eliminator, energy efficient induced draught axial type fans with factory• set and dynamically balanced blades pitch, IE3 TEFC squirrel cage induction motor (1500 pm), suitable for operation on 3- Ph, 415 V, 50 Hz AC supply with IP 65 protection for enclosure, conforming to IS 12615: 2018, complete with all required accessories. All steel members and supports inside the cooling tower, heavy duty cat ladder, fan & motor support shall be Grade 304 / HDG steel construction. The bolts/nuts and fasteners of the cooling tower shall be of Grade 304 stainless steel construction. External metal parts of the cooling tower, such as cooling tower support legs, shall be of hot-dipped galvanized steel, Epoxy-coated and finish with two coats of enamel paint.
EXPANSION TANK FOR CHILLED WATER PIPING- Supply, installation, testing and commissioning of Expansion tank 500 ltrs capacity duly insulated with the insulation of 50 mm thickness shall be carried out from rigid polyurethane foam having a 'K' value of 0.018 W /m k at mean temperature of 10°C and a density of 40 Kg/cum complete with and including inlet, outlet, drain and over flow, make up comprising connections with float valve, control valve, gauges, gate valves, vent piping etc. Make: Anergy/K D Agency
(Contd...) Pressurized chilled water expansion tank suitable for total volume of water in chilled water circuits along with necessary accessories such as centrifugal air separator, pumps etc. in order to keep chilled water system under (+) pressure and to prevent entrapment of pressure and to prevent entrapment of air in the system. The system shall also include a fully automatic pressurisation unit with 2 pumps with IP44 protection giving 2.5 USGPM flow rate @ 10m with pressure switch & control panel completely assembled on skid with all necessary valves & manifolds. The tank shall be precharged steel expansion tank with replaceable heavy duty butyl rubber bladder. The tank shall have a system connection with isolation valve, drain connections with ball valves and charging valve connection to facilitate the on site charging of the tank to meet system requirement. The expansion tank and air separator shall have pressure gauges fitted with isolation valves and high capacity auto air vents with isolation valves. Note: (i) For expansion tank the bottom of tank shall be atleast 0.7 m above the highest point of system (ii) The quoted rate shall be deemed to include for RCC / PCC foundation and civil work, structural MS work etc., for staging and installation of expansion tank.
HDPE MAKE-UP WATER TANK FOR COOLING TOWER- S & F multilayered HDPE make-up water tank of 5000 litre capacity made up of 100% virgin material, having 100% UV stabilised white outer layer, threaded lid, extra insert lid for protection against algae formation complete with inter-connection piping and non-return valve etc. NOTE: The quoted rate shall be deemed to be included for the following:- (i) RCC / PCC/ MS structure/ civil work required for mounting make-up water tank on staging at required height. (ii) Interconnection piping with UPVC heavy duty 25 mm dia/ bore with PVC gate valve of size 25 mm and Float valve.
Air Handling Units (OUTDOOR TYPE): Supply, installation, testing and commissioning Factory made Double Skin sandwitched panel, chilled water type, floor mounted, outdoor type AHU with canopy and fabricated out of extruded aluminium section with 0.8 mm pre- plasticized / pre-coated galvanized steel sheet outside and 0.8mm galvanised steel sheet having various sections, inside with SISW/DIDW Backward curved centrifugal blower in MS Construction, blower section, fan and fan section, fan motor TEFC type suitable for operation on 415 volts, 50 Hz +5% AC supply 6 row made of aluminium finned copper tube MS header with coil section, pre filter section with non woven synthetic media of 10 micron particle size with an efficiency of 90% polished stainless steel drain pan made out of 22 G sheet duly insulated complete with motor, belt drive packaged, guard etc. without face and bypass dampers. The AHU sandwitched Panels shall be openable / removable and thermal insulated with 50 mm thick and 40 Kg/Cu.m density CFC free PUF panels. The motor and blower assembly shall be mounted on Aluminium extruded section only.
Supply, Installation, testing & Commissioning of duct mounted / Installed in AHU Electric finned strip Heater of Cap 94 KW for monsoon reheating with thermostatic controller including power & control wiring. Unit shall be of corrosion resistant steel frame with control box. Unit shall start only after air supply is active and automatically cutoff as package unit stop. Actual KW shall be considered as per Manufacturer standard, complete as required. Make: Danposs or equivalent
CONDENSER WATER PIPING MS ERW CLASS- C PIPE- Supply, laying / fixing, testing and commissioning of condenser water piping confirming to IS 1239 code including, supply & fixing necessary weldable fittings viz. bends, nut bolts, washers, gaskets, slip on type flanges, tees, reducers, air purge valves, drain valves, structural support, necessary clamps, vibration isolators, etc. including painting and supporting / fixing the pipe in excavated trenches or on floor / wall / ceiling with clamps, hangers, angles, channels (using anchor fastners) with necessary accessories complete all as specified of following sizes:- Note: Rate quoted shall deemed to be included for:- (i) Pipes shall be given one primary coat of red oxide paint and other two finished coats of paint and flow directions marking as approved / as directed by GE (ii) All pipes shall be adequately supported and braced with angles, studs, bolts, clamps, hangers, fasteners, hooks, PCC etc as specified / directed and space between 2 supports should be as per specification. (iii) The piping shall be laid overhead in plant and underground/ wall mounted outside the plant room incliding excavation, earth work and fixing arrangement etc as per site condition and as directed. Make: Jindal, Hissar, Tata Steel, Zenith, JSW
BUTTERFLY VALVE- Supply, installation, testing and commissioning of wafer type PN 1.6 rated short pattern Cl butterfly valve having Gr. FG-200 Cl body conforming to IS 210: 2009, seat having EPDM rubber lining, CF 8 stainless steel disc, AISI- 410 stainless steel stem, 2.4 MPa body test pressure & 1.6 MPa seat test pressure and standard flange end conforming to BS 10 Table D/E & ANSI B 16.1 Cl- 125 with necessary accessories complete all as specified. All chilled water butterfly valves shall have an extended stem. Lever operated Butterfly Valves of approved make (PN10 rating) complete with mating flanges, gaskets, flow control and accessories required to complete the installation of following sizes:-
Supply, Installation, Testing and Commissioning of Modulating Motorised butterfly valve with required accessories and fittings of following sizes:- Make: Belimo, Honeywell, Johnson Control, Siemens, Advance, Kitz, VTM
NON-RETURN VALVE- Supply, installation, testing and commissioning of 100 mm NB wafer type PN 1.6 rated swing check type multidoor reflux valve (NRV), designed & tested as per IS 5312 (Part- 2): 1986, suitable to handle clear water having turbidity up to 5000 PPM, having Cl body, door and diaphram, leaded tin bronze seat rings and flange drilling standard end connection, etc. with other necessary accessories complete all as specified of size100 mm.
Y- STRAINER- Supply, installation, testing and commissioning of 100 NB cast steel bolted cover Y- type strainer with CCS body conforming to ASTM A- 216 Gr.WCB, AISI, SS304 screen with 1.2 mm diameter perforation, 20 kg/cm2 body test pressure & 20 kg/cm2 maximum working pressure and standard flange end conforming to BS 10 Table F / Class-150 with necessary accessories complete all as specified of size 100 mm. Make: Emerald/ Leader/ DS Engg/ Anergy/ C&R
POT STRAINER - Supply, installation, testing and commissioning of pot strainer with Stainless steel strainer body, stainless steel strainer bonnet, SS perforated screen, black rubber gasket and SS 410 drain plug with necessary fittings and accessories of size 100 mm. Make: Emerald/ Leader/ DS Engg/ Anergy/ C&R
CHILLED WATER PIPING MS ERW CLASS- C PIPE WITH INSULATION- Supply, laying / fixing, testing and commissioning of chilled water circulation piping confirming to IS 1239 duly insulated as specified including supply & fixing necessary weldable fittings viz. bends, tees, reducers, slip on type flanges, nut bolts, washers, gaskets / packing, air purge valves, drain valves, structural support, necessary clamps, vibration isolators, etc. including painting and supporting / fixing the pipe in excavated trenches or on floor / wall / ceiling with clamps, hangers, angles, channels (using anchor fastners) with necessary accessories duly insulated with FM approved highly- flexible, closed-cell thermal insulation of elastomeric foam based on synthetic rubber (NBR) of 25mm thickness laminated with 12 micron aluminium foil facing with reinforced glass scrim along with adhesives and other necessary accessories complete all as specified and as following sizes:- Note: Rate quoted shall deemed to be included for:- (i) Pipes shall be insulated with nitrile rubber sheet as specified and mark flow directions as approved/ as directed by GE. (ii) All pipes shall be adequately supported and braced with angles, studs, bolts, clamps, hangers, fasteners, hooks, PCC etc as specified / directed and space between 2 supports should be as per specification. (iii) The piping shall be laid overhead in plant and underground/ wall mounted outside the plant room incliding excavation, earth work and fixing arrangement etc as per site condition and as directed. Make: Jindal, Hissar, Tata Steel, Zenith, JSW
BUTTERFLY VALVE WITH INSULATION -Supply, installation, testing and commissioning of wafer type PN 1.6 rated short pattern Cl butterfly valve having Gr. FG 200 Cl body conforming to IS 210: 2009, duly insulated as specified seat having EPDM rubber lining, CF 8 stainless steel disc, AlSI-410 stainless steel stem, 2.4 MPa body test pressure & 1.6 MPa seat test pressure and standard flange end conforming to BS 10 Table D/E & ANSI B 16.1 Cl- 125 duly insulated with FM approved highly-flexible, closed-cell thermal insulation of elastomeric foam based on synthetic rubber (NBR) of appropriate thickness laminated with 12 micron aluminium foil facing with reinforced glass scrim along with adhesives and other necessary accessories complete all as specified and of following sizes:-
Supply, Installation, Testing and Commissioning of Modulating Motorised butterfly valve with required accessories and fittings of following sizes:- Make: Belimo, Honeywell, Johnson Control, Siemens, Advance, Kitz, VTM
(a) 100 mm (insulated)
(b) 150 mm (insulated)
Y- STRAINER WITH INSULATION- Supply, installation, testing and commissioning of cast steel bolted cover Y-type strainer with CCS body conforming to ASTM A-216 Gr. duly insulated as specified WCB, AISI 304 screen with 1.2 mm diameter perforation, 20 kg/cm2 body test pressure & 20 kg/cm2 maximum working pressure and standard flange end conforming to BS 10 Table F / Class-150 duly insulated with FM approved highly- flexible, closed-cell thermal insulation of elastomeric foam based on synthetic rubber (NBR) of appropriate thickness laminated with 12 micron aluminium foil facing with reinforced glass scrim along with adhesives and other necessary accessories complete all as specified of following sizes:- Make: Emerald/ Leader/ DS Engg/ Anergy/ C&R
Supply, installation testing and commissioning of digital display type thermostat for AHU and inside auditorium including temperature sensor. The thermostat shall have provision of setting of space temperature as per requirement, complete all as specified and directed. Make: Mextech/ Fluke/ Carent
NON-RETURN VALVE WITH INSULATION- Supply, installation, testing and commissioning of 100 mm NB wafer type PN 1.6 rated swing check type multidoor reflux valve (NRV), duly insulated designed & tested as per IS 5312 (Part- 2): 1986, suitable to handle clear water having turbidity up to 5000 PPM, having CI body, door and diaphram, leaded tin bronze seat rings and flange drilling standard end connection, eto. duly insulated with FM approved highly- flexible, closed-cell thermal insulation of elastomeric foam based on synthetic rubber (NBR) of appropriate thickness laminated with 12 micron aluminium foil facing with reinforced glass scrim along with adhesives and othernecessary accessories and of size 100 mm all as specified and directed.
MANUAL BALANCING VALVE WITH INSULATION-Supply, installation, testing and commissioning of size 100 mm, precise balancing, double regulation type cast iron flange type with built in pressure drop and flow measuring facility. balancing valve having FG 200 cast iron body conforming to IS 210: 2009, BS 1152 copper alloy trim, stainless steel 2 Cr. 13 stem, 2.4 MPa body test pressure & 1.6 MPa maximum working pressure and standard flange ends duly insulated with FM approved highly- flexible, closed-cell thermal insulation of elastomeric foam based on synthetic rubber (NBR) of appropriate thickness laminated with 12 micron aluminium foil facing with reinforced glass scrim along with adhesives and other necessary accessories of size 100 mm complete all as specified and directed. Make: Advance Valve, Danfoss, Honeywell, VTM
2-WAY PICV -TEMPERATURE CONTROL VALVE WITH INSULATION- Supply, installation, testing and commissioning of 125 mm NB electronic, self-balancing, pressure independent type dynamic balancing valve rated for minimum 25 bar working pressure with integrated 2- Way modulating control valves in a single body and actuator capable of accepting upto 10 V DC and up to 20 mA electric signal and provide similar transduced feedback output to control system duly insulated with FM approved highly- flexible, closed-cell thermal insulation of elastomeric foam based on synthetic rubber (NBR) of appropriate thickness laminated with 12 micron aluminium foil facing with reinforced glass scrim along with adhesives and other necessary accessories and of size 125 mm complete all as specified and directed. Make: Danfoss, Oventrop, Flowcon, Belimo, VTM
DRAIN & INSTRUMENTATION PIPING GI CLASS- B PIPE- Supply, laying / fixing, testing and commissioning of GI drain piping medium grade of size 25 mm including necessary fittings viz. bends, tees, reducers, flanges, air purge valves, drain valves, structural support, nec mmessary clamps, vibration isolators, etc. including painting and supporting / fixing the pipe on floor / wall / ceiling with clamps, hangers, angles, channels (using anchor fastners) with necessary accessories.
BALL VALVE- S & F of CL 150 # rated ball valve, designed & manufactured as per IS: 9890 (1981) and tested as per BS 6755 Part- I, having floating type three piece design, CS body, SS- 304 ball, PTFE seal/ packing/ gasket, CS fasteners and lever and screwed/ socket weld end connection, etc. with accessories of following sizes:- Make: RB, Leader, Zoloto, Emerald, Rapid Control, VTM
AUTO AIR-VENT- Supply, installation, testing and commissioning of automatic air-vent valve with 20 mm end connections, brass OT 58 body and cover, polyacetal lever, high density expanded polyethylene float, EPDM rubber plug, stainless steel spring, polyamide cap etc. suitable for maximum operating pressure of 16 bar and maximum operating temperature 115 °C respectively, installed on all high points in the water piping system to automatically remove the trapped air complete all as specified and directed.
TEMPERATURE GAUGE- Supply, installation, testing & commissioning of 4" dual scale (°F/°C), lower mount (radial), bimetal thermometer having 0.5 NPT process connection, Grade A accuracy class as per ASME B40.200, stem diameter 6.35 mm, laminated safety glass window, stainless steel 304 case, steam, process connection & joint, aluminium dial & pointer, IP-67 protection, scale range 0-50 °C complete with accessories, etc. as specified and directed by Engineer-in-Charge. Make: General, WIKA, TSI, H-Guru. Note- To be provided at supply return ,condenser,cooling coil etc.
TEMPERATURE AND RH SENSOR- Supply, installation, testing and commissioning of temperature and RH sensor for various AHU units. The sensor shall be display type, modulating, suitable for 24V AC. The sensor shall be suitable for the PICV valves.
Ultrasonic flowmeter- Supply, installation, testing & commissioning of Ultrasonic flowmeter for measurement of flow across chilled water & hot water line. Unit shall be compatible to CPM communication, power supply required for flowmeter to be arraned from CPM panel. Type- Flow Cell type Service - chilled water at 7 deg C & hot water at 55 deg C Supply- 24 VDC Accuracy- +/- 1% of rate Output - 4 to 20mA 100 mm dia. Make: Schnider/ Meco or equivalent.
PRESSURE GAUGE-Supply, installation, testing & commissioning of 4" bourdon tube pressure gauge conforming to EN 837-1, having copper alloy process connection & pressure element, plastic black pointer & case, plastic crystal-clear window, snap-fitted in case, accuracy class 2.5, scale range 0-25 bar complete with accessories, etc. as specified and directed by Engineer-in-Charge. Note- As per IS 3624-1987 to be provided at suction and discharge of pump, supply and return of condenser. Make: General/ WIKA/ TSI/ H-Guru
GI DUCTING WORK (FACTORY MADE)- Supply, fabrication, installation, commissioning and testing of GSS sheet metal ducting complete with splitter damper, duct damper, vanes, including collars, conforming to IS 277 including supports and hangers, bracing, flanges, turning vanes, fastners, rivets, gaskets, nuts & bolts, etc. as per specifications. All exposed ducting fabricated out of galvanised sheet class VIl 120gm/ sqm zinc coating conforming to IS 277-1965 all as required and as per approved drawings. Note: Rate quoted are deemed to be included for the following: (i) S & F for MS angle supports, MS rod, fastners, GI rod, Hangers, nut bolts, screw, clamps etc. (ii) Wastage of GI sheet if any or fabrication of flanges out of GI sheet. (iii) MS structure, PCC, RCC and any civil work required at site for ducting work. (iv) All ducts shall be rigid and shall be adequately supported and braced and shall be independently supported from building elements and with hangers, clamps, MS rods, Angle iron, fasteners, nut, bolts, hooks etc. approx 2m apart. (v) Size of duct shall be such to accomodate on the side walls and in the existing available space of acoustic panels. Contractor shall ensure sufficient air throw and cooled air shall be circulated in the whole auditorium. (vi) Method of mearurement of ducting shall be finished the ducting area measurement at the centre line of ducting (Length), Straight including all flanges, joints, overlappings, bracings, splitter etc multiplied by average perimeter (width) of duct along the centre line. (vii) The contracor shall submit drawing based on actual site condition before execution of work & get it approved from Engr-in-Charge.
(a) 24 Gauge
(b) 22 Gauge
(c) 20 Gauge
GI DUCTING WORK (SITE FABRICATED)- Supplying, fabrication, commissioning, installation and testing of GSS sheet metal ducting for supply air & return air ducts complete with splitter damper, duct damper, vanes, including collars, conforming to IS 277 including bracing, flanges, turning vanes, fasteners, rivets, gaskets, nuts & bolts, etc. as per as per specifications. All exposed ducting fabricated out of galvanised sheet class VIl 120gm/ sqm zinc coating conforming to IS 277-1965 all as required and as approved drawings. Note:- Rate quoted are deemed to be included for the following:- (i) S & F for MS angle supports, MS rod, fasteners, GI rod, Hangers, nut bolts, screw, clamps etc (ii) Wastage of GI sheet if any or fabrication of flanges out of GI sheet. (iii) MS structure, PCC, RCC and any civil work required at site for ducting work. (iv) All ducts shall be rigid and shall be adequately supported and braced and shall be independently supported from building elements and with hangers, clamps, MS rods, Angle, iron, fasteners, nut, bolts, hooks etc. approx 2m apart. (v) Size of duct shall be designed such that which should accomodate on the side walls and in the existing available space of acoustic panels. Contractor shall ensure sufficient air throw and cooled air shall be circulated in the whole auditorium. (vi) Method of mearurement of ducting shall be finished the ducting area measurement at the centre line of ducting (Length), Straight including all flanges, joints, overlappings, bracing, splitter etc mutlipied by average perimeter (Width) of duct along the centre line. (vii) The contractor shall submit drawing based on actual site condition and get it approved by Engr-in-Charge before execution.
(a) 24 Gauge
(b) 22 Gauge
(c) 20 Gauge
AIR TERMINALS
Supply & Fixing of return air grilles of powder coated aluminium with volume control dampers.
Supply & Fixing of return air grilles of powder coated aluminium without volume control dampers.
Supply & Fixing of GI Volume control damper. Note: Grill shall be equal to maintain asthetic look of foundation.
JET NOZZLE- S&F air Jet Nozzle with collar size 400 mm. Adjustable sphere with inbuilt cone. Aluminium constuction. Attached with butterfly volume control damper. Powder coated finish. Make: Caryaire/ Cosmos/ Systemair/ Dynacraft/ Air products.
FIRE DAMPER- Supply, installation, testing and commissioning of 16 gauge GI fire damper, at least of 90 minutes fire-rating, spring activated on melting of fusible link having melting point 67.13 °C complete with smoke detector / thermister, fusible link etc. and tested as per ULL- 555 and certified by CBRI. The fire dampers shall meet the following criteria:- (a) Bare fire dampers with 150 mm sleeve (b) Sealing any openings around the sleeve of the fire dampers with approved fire sealant as per the specification & recommendations of the manufacturer. Make: Systemair, Air Flow, Caryaire, Air Products, Sagar Air
(i) Fire and smoke damper
(ii) Fusible link
THERMAL INSULATION- Supply, installation, testing and commissioning of FM approved highly- flexible, closed-cell thermal insulation of elastomeric nitrile rubber foamed insulation, laminated with 12 micron aluminium foil facing with reinforced glass scrim tested for service temperature range 0- 105 °C as per EN 14706, EN 14707 & EN 14304, thermal conductivity λ ≤ 0.037 W/mK at mean temperature θm = 20 °C as per EN 12667 & EN ISO 8497, water vapour diffusion resistance factor µ ≥ 12000 as per EN 12086 & EN 13469, water absorption by volume 0.2% as per ASTM C 1763 & ASTM C 209, Class 0 fire performance as per BS 476 Part 6: 1989, Class 1 surface spread of flame as per BS 476 7: 1997, flammability HB, V-0 as per UL- 94, having good resistance to mechanical impact, excellent resistance to ozone, oil and chemicals, zero ozone depletion potential along with factory recommended adhesives and joints finished with 3 inches wide aluminium foil faced self adhesive tape with other necessary accessories.
Where supply air / return air ducts are installed outside the building, exposed to weather, the thickness of insulation material for supply air and return air shall be 32 mm over the ducts. The insulation provided for the ducts exposed to sunlight UV / mechanical protection should be applied after minimum 36 hours of curing of adhesive. (a) The UV / mechanical protection shall have 2 component system of woven glass cloth / Chopped Strand Mat (CSM) and special UV resistant paint. (b) Apply paint liberally on insulation, immediately spread the 7 mil woven glass cloth / 225 GSM Chopped Strand Mat (CSM) (with minimum overlap of 25 mm at joints) on insulation without allowing paint to dry. (c) Immediately apply another coat of paint liberally on woven glass cloth/CSM. Even out with brush & allow it to dry for 2-3 hours. (d) All exposed duct insulation shall be covered with chicken mesh and aluminium sheet cladding over it all around the outer surface of insulation (for supply and return air duct at stage and outside building, quoted rate is deemed to be included for the same, no extra cost shall be admissible to the contractor in this respect).
All as per item above but 19 mm thick thermal insulation with aluminium laminated flim but excluding chicken mesh/ Al sheet cladding (For Supply air duct and return air duct inside building)
Acoustic Insulation: Supplying and fixing of acoustic lining of duct with 13 mm thick resin bounded fiber glass having a density of 33 kg/m3 and covered with 0.5mm thick perforated aluminium sheet all as specified and directed upto five metres of duct from the canvas connection of AHU.
Supply, Installation, testing & Commissioning of 3 phase and neutral, 415 volts indoor type, factory made free standing, floor mounting, dust and vermin proof cubicle type, CPRI approved LT panel fabricated from 2 mm thick CRCA sheet duly compartmentalized for each switch gear, front and rear openable (front hinged opening) and with both side vertical cable alloys for incoming and outgoing cables, locking arrangement with chromium plated 19mm dia locks (min 2 nos in each compartment) lifting ups of suitable size on top, louvers and air vent gasket for natural air, U shape rubber gasket, voltmeter, ammeter, frequency meter. Panel shall be anti corrossive coating and finally epoxy polyster powder coating of siemens grey shade (RAL-7032) Protection class IP 43 suitable for 600 amps with suitable colour coded heat shrinkable sleeve and shall mounted on suitable aluminium earth strips confirming to IS with danger notice plate, necessary cable glands, cable connection with proper copper / aluminium lugs. The cubical incomer MCCB as well as outgoing shall have copper TPN extension link of current carrying capacity not less than 1.5 times the rated capacity of individual feeders. The extension link of min 500mm long supported on suitable size F class insulator to be provided for termination on incomer and outgoing cables. All interconnection between main bus bar of rating not less than 1.5 times rated capacity of individual outgoing feeders. The panel shall be mounted on bottom channel of suitable size with proper mounting arrangement as directed leaving min 500mm all around the panel board for movements all as specified with supply and fixing the following:-
OUTGOING:- (i) MCCB 200A, 4 pole, 415 V AC, 50 HZ, ultimate breaking capacity 35 KA C curve - 2 Nos. (Chiller no. 1, 2) (ii) MCB TP 32 A, 3 Pole, 415 V AC, 50 Hz, ultimate breaking capacity 10 KA C curve including suitable VFD starter - 02 nos for chilled water pump (iii) MCB TP 32 A, 3 Pole, 415 V AC, 50 Hz, ultimate breaking capacity 10 KA C curve including suitable VFD - 02 nos for condenser water pump (iv) MCB TP 32A, 3 pole, 415 V AC, 50 HZ ultimate breaking capacity 10 KA C curve including suitable VFD -01 Nos cooling tower) MCCB TP 100 Amps, 3 pole, 415V AC, 50 Hz, ultimate breaking capacity 25 KA C curve including VFD -01 no (AHU) (v) MCCB TPN 200 A, 3 Pole, 415 V AC, 50 Hz, ultimate breaking capacity 10 KA C curve including - 01 no for HEATING COIL (94 KW) (vi) MCB SP 6-32 Amps - 01 No (For Plant Manager) Make for VFD: Danfoss/ Seimens/ ABB
Power & Control Cables- Supply, handling, laying propoer connections testing and commissioning of following sizes of 1.1 KV grade XLPE insulated armoured copper/ aluminium conductor cables with required accessories in an approved manner as required:-
(a) 3.5 C x 150 Sqmm Alu arm cable for chiller
(b) 3.5 C x 120 Sqmm Alu arm cable for heating coil
(c) 3.5 C x 50 Sqmm Alu arm cable for AHU panel
(d) 3.5 C x 25 Sqmm Alu arm cable for AHU motor
(e) 4 C x 16 Sqmm Alu arm cable for Pump
(f) 4 C x 10 Sqmm Alu arm cable for Cooling tower
(g) 3 C x 1.5 Sqmm Cu arm cable for interlocking
(h) 5 C x 1.5 Sqmm Cu arm cable for Humidistat & Thermostat
Supply, fabricate and install following size of perforated MS sheet cable trays including horizontal and vertical bends, reducers, tees, cross members duly painted with two coats of synthetic paint over a coat of red oxide primer and other accessories as required, duly suspended from the ceiling with and including MS suspenders (10mm dia threaded rod, anchor fasteners and angle of 40 x 40 x 5 mm thick) complete all as specified and directed for the following sizes:-
(a) 300 mm width x 50 mm depth using 1.6 mm MS sheet
(b) 150 mm width x 50 mm depth using 1.6 mm MS sheet
M&L for Earthing complete with galvanised iron earth plate electrode 600 x 600 x 6 mm thick buried directly in ground earth pit not less than 2.25 m deep below normal ground level with top edge of the plate not less than 1.5 m below normal ground level connected to GI strip of size 32 x 6 mm thick by means of nuts/bolts check nuts and washers including necessary excavation and earth work, GI pipe 15 mm bore light grade for watering with Funnel and wire mesh and protection to earthing strip shall be provided with GI pipe light grade 40 mm dia up to 7.5 m from the earth plate electrode and refilling of soil including adequate quantity of charcoal dust and common sall etc including earth work in any type of strata, PCC pit chamber in cement mortar 1:3:6 type C-2 provided with 40 mm thick precast RCC cover slab 1.2.4 type B1 reinforced with 8 mm dia TMT bar as directed, complete all as per Electric plate No. 3 of SSR Part-l and testing on completion for required earth resistance, complete all as specified and direted.
S&F Earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc. as required using 32 x 6 mm GI strip complete all as specified and directed.
S&F Earth contuinity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/ pipe or fixed to poles or any other indicated situation for loop earthing etc. as required GI wire of 4.0 mm diameter complete all as specified and as directed.
Notes applicable to all items of Air Conditioning from 39.00 to 81.00:- (a) All bidders shall check the requirements, Air conditioning items, heat load calculations etc as per details given. In case any defficiency/ discrepancy is noticed between requirements as per their calculation and as provided for in Sch 'A', the same shall be ascertained by the bidder and unit rate quoted shall be included for such modifications to be done and nothing extra shall be payable on this account including misunderstanding, if any. (b) All bidders shall note that if any item is needed to be incorporated which is not covered in BOQ but required as per site requirement as assessed and ascertained as well as decided by the Accepting Officer to meet the desired parameters (i.e. inside temparature 22 degree +-2 degree C and humidity- 55% +- 5%) of air conditioning plant, the same shall be provided by the contractor without any extra cost to th edepartment. (c) Any enhancement of capacity of AC equipment specified in BOQ required to satisfy the required parameters shall be deemed to be included in the unit rates quoted by the bidder for the relevant items and nothing extra shall be paid by the department on this account to the contactor.
(Contd...) (d) Phase I Test: For 24 hours will be carried out after completion of AC works and production of all test certificates to observe the efficiency, behavior of various systems and capacity of plant achieved by making arrangement for providing artificial load to compensate for the internal load as necessary. Provisional completion of AC works shall be given after successful completion of Phase-l tests. Provisional completion of AC work shall match with Phase-l completion of entire work of building portion. (e) Phase-ll Tests: Shall be carried out in summer, monsoon and winter in presence of the authorized representative of Accepting Officer and in the presence of the contractor and each test shall be carried out continuously for 72 hrs. The Phase-ll test shall be carried out as soon as the stipulated load and weather conditions are available but not later than 1 year after Phase-l test. in case the required load is not available, arrangements shall be made by the contractor to provide artificial load. The installation shall be finally taken over after satisfactory completion of Phase-ll tests as certified by the authorized representative of Accepting Officer. (f) The Defects Liability Period as per condition 46 of IAFW-2249 shall start from the date of provisional completion of AC work after Phase-l tests.
Dismantling of existing UNSV central AC plant along with connected items/ equipments and deposit to AGE E/M Store yard as directed. Note: Central AC plant including compressor, condenser, pumps, motors, panels, cooling tower, valves, pipes, cables, chillers, AHU, external and internal ducting, dampers, diffusers, grills, GI sheet etc.
Dismantling of Wall and ceiling boards (fibre, pulp, insulation, etc.) or insulation boards/ slabs / blankets, any thickness, including cover fillets, complete all as specified and directed.
Dismantling boarding, any description, fixed in any position with screws complete all as specified and as directed.
Dismantling timber scantlings in fillets, rails, posts, rafters, purlins, etc. under 40 sq. cm in section, in any position, complete all as specified and directed.
Dismantling floor, hearth or wall tiling in cement mortar bedding (but not backing) removing serviceable tile to stores & rubbish off the premises (out of MoD land) complete all as specified and directed.
Taking down cement plaster on brick/ block walling including raking out joints, hacking for key, scrubbing down with water etc. complete, complete all as specified and directed.
Taking down chowkats or frames (wooden/steel) of any type with shutters (without taking off shutters from the frame) n.exceeding 1.5 Sqm each complete all as specified and directed including making good disturbed wall surfaces/jambs with cement plaster in 1:4 of thickness as required at site or disturbed masonry, if any, in PCC 1:3:6 type C-1 using 20 mm graded stone aggregates finished even & smooth using extra cement all as specified and directed.
Taking down chowkats or frames (wooden/steel) of any type with shutters (without taking off shutters from the frame) exceeding 1.5 Sqm but not exceeding 4 Sqm each complete all as specified and directed including making good disturbed wall surfaces/jambs with cement plaster in 1:4 of thickness as required at site or disturbed masonry, if any, in PCC 1:3:6 type C-1 using 20 mm graded stone aggregates finished even & smooth using extra cement all as specified and directed.
Demolition of un-reinforced cement concrete in ground floor or pavings of any description and in any position not exceeding 15 cm thick (below or above ground level) complete all as specified and directed.
Dismantling wrought iron or mild steel work of any description not otherwise provided for complete all as specified and directed.
Demolition of un-reinforced cement concrete of any description and in any position complete all as directed.
M&L 2nd class hardwood Plain fillets sectional area exceeding 13 but not exceeding 25 sqcm, square, rectangular or triangular in section, clean sawn, secured with screws complete all as specified and directed.
M&L Granite 18 to 20 mm thick (of any type) work (table rubbed and polished) in steps, jambs, pillars, window-cills, cooking platform, floor and like laid over 15 mm thick cement mortar (1:6) as screed or bed on any type i.e. stone/ brick/ concrete wall including pointing in white cement (1:2) using marble dust with admixture of pigment to match with shade of granite, complete all as specified and directed.
M&L Chamfer, splays or arris in facework of granite or trap stones exceeding 15 mm and not exceeding 30 mm wide complete all as specified and as directed.
M&L Rendering 15 mm thick on other than fair faces of brick work or concrete surfaces or stone masonry surfaces with cement mortor (1:6); finished even and smooth (without using extra cement) complete all as specified and as directed.
M&L Preparation of newly plastered surfaces of walls and applying two or more coats of 100% Premium acrylic emulsion paint having VOC less than 50 gm/litre and UV resistance as per IS 15489:2004, alkali & fungal resistance, dirt resistance exterior paint of required shade (Company Depot Tinted) with silicon additives @ 143 litre/10 sqm over and including priming coat of exterior primer applied @ 0.90 litre/ 10 sqm over new surfaces including average 2 mm thick wall care putty complete all as specified and directed.
M&L Preparation of old painted surfaces of walls of any description including washing, rubbing down and stopping of distempered and painted surfaces and priming the surfaces with alkali resistance paint and applying two coats of oil bound distemper, complete all as specified and as directed.
S&F Aluminium powder coated frame for doors, windows, ventilators with one or more rebates including joining cleat for fixing etc complete all as specified and directed
S&F Aluminium powder coated of any colour (Thickness or powder coating not less than 50 micron) window and ventilator shutters, fixed / sliding type without sash bar, aluminium section weighing 0.55 kg/m including necessary joining cleats, glazing clips, rubber packing, anodised aluminium snap beading, screws etc. complete all as specified and as directed.
S&F Aluminium powder coated of any colour (Thickness or powder coating not less than 50 micron) door shutters, aluminium section weighing 0.55 kg/m including including necessary joining cleats, glazing clips, ruber neoprene packing, handles 2 Nos in each door, hinges, anodised aluminum snap beading screws etc. complete all as specified and as directed.
S&F Sheet glass 4.0mm thick, ordinary quality and glazing with oil putty or in beading provided with framework of aluminiun windows /doors etc. as directed in square n exc 0.5 sq. m in each pane complete all as specified and as directed.
S&F Sheet glass 4.0mm thick, ordinary quality, ground or obscured or frosted on one side and glazing with oil putty or in beading provided with framework of aluminiun windows /doors etc. as directed in square exceeding 0.5 sq. m in each pane complete all as specified and as directed.
S&F 12 mm thick particle board exterior grade, prelaminated both side with decorative choice lamination, fixed as in door / window panels in aluminium framework complete all as specified and directed.
S&F Double action floor spring hydraulically regulated made of of minimum 1.25mm thick aluminium alloy sheet foundation box, main body with stainless steel cover, governing pivot made of brass, other parts made of mild steel heavy duty of approved make as per sample approved, complete all as specified and as directed.
S&F 6 mm thick Aluminium composite panel (ACP) flat or bent panel, decorative, consisting of two thin aluminium sheets bonded to a non aluminium core used for external cladding etc. including necessary aluminium framework complete on walls, columns etc. all as per manufacturers standards and instructions complete all as specified and as directed. Notes: (i) Colour, pattern and make shall be as approved by GE. (ii) Rate shall include for arrangement and providing necessary scaffolding as well as providing nylon security mesh for preventing any damage to existing building or men to any height at required at site. (iii) Proving safety measures to workers shall also be mandatory. (iv) The work shall be executed to any site as per site conditions and the contractor shall quote the unit rate accordingly.
S&F Anodised aluminium snap grid frame work for false ceiling of size 605 x 605 mm provide with Hangers 6 mm dia. G.I. (upto 1200 mm length) adjusting level fixed to roof slabs by means of ceilling cleats made out of G.I. flat 40 x 3 mm size 60 mm long and expansion hold fasteners 12.5mm dia. 40mm long including providing and fixing Gypsum Board 12mm thick tile of size perfectly fitting in snap grid framework in ceiling fixed with screw as per manufacturers instructions, complete all as specified and as directed.
M&L Non skid ceramic coloured tiles 7 to 8 mm thick in floors etc, area of each tiles exceeding 0.11 sq.m but not exceeding 0.18 sq.m; set and jointed in neat cement slurry and pointed in white or coloured cement to match with the colour of tile, over and including 15 mm thick screed bed in cement mortar (1:6) complete all as specified and directed.
M&L Non skid ceramic coloured tiles 7 to 8 mm thick in skirting / dado or on vertical surfaces etc, area of each tiles exceeding 0.11 sq.m but not exceeding 0.18 sq.m; set and jointed in neat cement slurry and pointed in white or coloured cement to match with the colour of tile, over and including 10 mm thick backing coat of plaster in cement mortar (1:4), complete all as specified and directed.
M&L 75 mm thick PCC (1:3:6) type C-2 (using 40mm graded stone aggregate) as in plinth protection / hard standing, finishing the concrete surfaces even and smooth without using extra cement, complete all as specified and as directed.
M&L Providing and fixing stainless steel (Grade 304) railing made of hollow tubes, channels, plates etc., including welding, grinding, buffing, polishing and making curvature (where ever required) and fitting the same with necessary stainless steel nuts and bolts complete, includingfixing the railing with necessary accessories & stainless steel dash fasteners, stainless steel bolts etc., of required size, on the top of floor or the side of waist slab with suitable arrangement, complete all as specified and as directed.
M&L Preparing surfaces of wood or wood based materials, new or old, of any description or girth, not otherwise described and treated with creosote oil complete all as specified and as directed.
M&L 75 mm thick PCC (1:3:6) type C-1 (using 20 mm graded stone aggregate) as in sub base leveling course for staging of auditorium chairs, finishing the concrete surfaces even and fair, complete all as specified and as directed.
M&L 40 mm thick PCC (1:2:4) type B-0 (using 12.5 mm graded stone aggregate) as in leveling course for staging of auditorium chairs, finishing the concrete surfaces even and smooth without using extra cement, complete all as specified and as directed.
S&F Polypropylene yarn heat scaled carpet coloured and printed with height of pile 12.5 mm average height 11 mm, weight 1800 GSM. Roll size 4 mtr x 2.5 mtr or as per site requirement and specified below complete all as specified and directed:- (a) Construction: Loop pile Scrool (b) Make: M/s Imperial Knots, M/s Konak Floors, M/s Consolidated carpet industries, M/s Unitex, M/s Divine or technocommercially equivalent as approved by GE. (c) Pile Fiber Composition: 100% Olefin (d) Yarn Type : BCF (e) Pile Weight :/50 gms/m² (f) Total weight: 1750 gms/m² (g) Pile Height: (2.5-4.8-5.5) mm (h) Total thickness : 7.00 mm (j) Turf Density: 228343/m² (k) Tufting Gauge: 1/10" (l) Primary Backing : Woven polypropylene (m) Secondary Backing: Action back or bluc felt (optional) (n) Broadloom Width : 3.55 m or 4.00 m (optional)
Supply and Fix in repairs CYCLORAMA frame with 1.8 Power Grandview High gain matt white projector screen of HD fabric material with 8 inch blace masking studs on the side duly streched on dual frame structure made from tubular Mild Steel frame welded self-supporting construction for supporting projection screen. This frame shall be grouted with rear wall and stage floor all as per manuacturers instructions including all tools, tackles, machineries, manpower, staging, all consumables etc. for entire completion of job complete all as specified and as directed. Note: MS framed work shall be measured and paid seperately.
S&F Rolled Mild steel structural work in tubular trusses or any type of frame work inculding special shaped washer etc. complete using ERW or induction butt welded tubes conforming to IS:1161-1979 grade St- 240, cutting to dead length where required, notching, drilling, fitting, welding or connecting with bolts and nuts (including bolts and nuts), providing and fitting angle cleats, fish plates, gusset plates etc., also for wedging, plumbing, truing up and fixing complete including one coat of shop primer, complete and specifed and directed.
S&F 18 mm thick MDF board prelaminated both side with decorative choice lamination as in Office Cabinet, pelmet box, drawer, CB shutter etc fixed with screw including 6mm thick lst Class HW (TW) beading all around on exposed edges of MDF board, complete all as specified and as directed.
S&F Autocado stainless steel hinges type B for cupboard of size 30 x 30 mm and 12 gauge complete all as specified and directed.
S&F Panasonic slider for drawer of size 300 mm x 45 mm, heavy duty, side mount, full extension steel drawer slide, self close movement, maximum laod capacity 30 kg, maximum side length 12.7 mm, with ball bearing, black colour etc. complete all as specified and directed.
S&F 125 mm brass fancy type cupboard handles fixed with nuts, screws and washer of brass polished complete all as specified and directed.
S&F Megnetic catcher assembly steel for cabinets with screws for fixing complete all as specithed and directed.
S&F Brass 2 lever Locks for drawers, Grade I, size 50 mm complete all as specified and directed.
S&F Push back auditorium chairs available in centre to centre size of 585 / 610 mm and height of 900 mm with cup holder, VIP, complete all as shown in Sketch-I attached and all as specified below and as directed. Make of Push Back Chair:- Penworkers model No PW009-LB or any other equivalent model in Godrej/ Featherlite/Methodex as approved by GE.
(a) Functional Specification: Push back seat shall have a simultaneous movement of seat and back, with an auto Stop at all places. It shall have lateral movement of the back and an inclined movement of the seat. (b) Technical Specification: Push back chair shall have a metal sheet mechanism duly embossed of size 450 x 440 x 1.6 mm. Block shall be 2 triangular blocks duly embossed of size 300 x 300 mm with 4 of 9 mm holes. Longitudinal tubes shall be of size 40 x 20 x 490 mm with 2 tubes each and shall also have 4 longitudinal tubes of size 20 x 6 mm duly bent in shape to shape riveted/ welded and approximately 350 mm long. Seat back bracket shall be interconnected/ riveted / welded and back bracket to be 200 x 60 x 1.6 mm/ Seat bracket shall have stopper cup with 5 rivets and approximately 170 x 340 x 1.5 mm - 2 pairs for seat / back. All rivets shall be with nylon washers and pneumatic machine only. Rollers shall be able to withstand temperatures up to 200 ⁰C and shall be of sizes 22 mm width & 38 mm Dia, duly riveted and/or welded. All stopper material shall be reinforced by nylon tubes of size 30 mm.
(c) Metal stand: It shall be 300 x 300 x 3 mm duly bent in 1 piece supported by 3 structures of size 20 x 40 x 270 mm each. (d) Seat: Seat shall be of 19 mm plywood BWR grade of size 480 x 490 x 19 mm with PU moulded foam of density 50 ± 5 kg/m³, duly upholstered in fabric of standard quality and make as approved by GE. (e) Back: Back shall be of 15/16 mm bent plywood BWR grade of 450 mm width and 570 mm height with PU moulded foam of density 48 ± 5 kg/m³, duly upholstered in fabric of standard quality and make as approved by GE. (f) Arm rest: PP cup holders shall be of size 530x 100 x 150 mm. The insert shall be duly cushioned and upholstered in the same fabric quality of seat and back. (g) Standard Upholstery Fabric: Upholstery fabric shall be 100% polyester stretch fabric and shall be used with 3 /5/ 7.5 mm foam lamination wherever quilting is required. (h) Installation: Chairs shall be bolted to the ground / floor using chemical fasteners of Hilti / Ruth or any other similar brand.
S&F Push back auditorium chairs available in centre to centre size of 560 mm and height of 900 mm with cup holder, complete all as shown in Sketch-II attached and all as specified in BOQ items 125.10 to 125.20 above and as directed. Make of Push Back Chair: Penworkers model No PW009-LB or any other equivalent model in Godrej/ Featherlite/Methodex as approved by GE.
SCHEDULE 'A' PHASE-II WORK (MANNING & OPERATION OF AC PLANT DURING DEFECTS LIABILITY PERIOD)
Manning and Operation (M & O) of Air Conditioning Plant including all connected equipment & accessories during Defects Liability Period (DLP) after completion of Phase-1 test of the plant, in one shift per day of 08 hours, by deploying 01 skilled operator on all days including Saturday, Sunday and holidays complete all as specified and as directed by Engr-in-Charge.
Notes for item No. 128.00:- (a) The contractor shall quote the rate for Manning and Operation only. Replacement of defective parts & providing spares shall be covered under Defect Liability Period. (b) The operator deployed by the contractor for M&O shall have minimum qualification of ITI (Refrigeration & AC)/ ITI (Mechanical) having minimum 02 years experience in relevant field. Necessary technical qualification certificate shall be submitted to Engr-in-Charge for verification and approval shall be taken before deployment in the work. (c) SOP and proper logbook with vital AC plant running parameters shall be maintained by personnel deployed by contractor. Everyday entries shall be submitted to Engr-in-Charge for signature duly completed along with attendance sheet and payment register. (d) Proper & efficient functioning of AC plant shall be ensured by the contractor through regular bi-monthly inspection by a qualified engineer preferably by OEM or by his authorised agency. Cost on this effect shall be deemed to be included in the quoted rate. The payment for M&O shall be made only when the plant is running satisfactorily & no payment will be made for the period when the plant is unserviceable due to any cause. (e) The Work Order for M & O (Phase-II) shall be placed by GE at appropriate time & no price adjustment during the whole period shall be admissible due to change in minimum fair wages. The quoted rate shall be deemed to include this provision. (f) No T & P, equipment shall be issued by the department for the above work. It shall be arranged and provided by the contractor at his own cost to ensure proper functioning of AC plant.
(Notes contd…) (g) As per the Govt policy, adequate amount of insurance of all the workers shall be made by the contractor against any accident before commencement of the work without any extra cost to the department. (h) The contractor shall check and implement all the labour laws/ precautions for health and safety of labour/ OEM operator working in hygienic conditions. (j) The contractor shall pay the wages to the operators through e-payment i.e. Aadhar linked bank accounts (Credit to their bank account). Engr-in-Charge shall ensure that e-payment made to operators and their wages shall not be less than prevailing minimum wages fixed by State Govt or Central Govt, whichever is higher. Monthly e-banking statement shall be furnished by the contractor to the Engineer-in-Charge and the same shall be kept on record duly verified. (k) It is the responsibility of contractor to deposit the Employees Provident Fund (EPF) to the concerned authority as per the prevailing scales as laid down by the Ministry of labour for all operators and necessary proof to this regard shall be submitted to Engr-in-charge for verification and records. The quoted rate shall be deemed to be inclusive of above provisions. In case the contractor fails to produce the proof of EPF, he shall be liable for action as deemed fit. Decision of GE in this regard shall be final and binding.
(Notes contd…) (l) The contractor shall not deploy same tradesmen continuously for more than 11 months. (m) If the personnel deployed by contractor is found absent from the duty, recovery shall be effected at double the rates worked out from the quoted rates at the proportional basis. For that purpose, proper duty roster and attendance register shall be maintained by the contractor and got verified & signed by the Engineer-in-Charge. (n) The rates quoted by the contractor shall be inclusive of providing proper uniform, safety gears such as rubber hand gloves & rubber shoes etc., and other safety equipments to the technicians/ operators deployed by him as directed by Engr-in-Charge. Necessary recovery shall be effected on non compliance of this provision. Decision of GE in this regard shall be final & binding. (o) The contractor shall provide necessary stationery at the installation required for the work at his own cost as directed by Engr-in-Charge. (p) The contractor shall bear the cost of identity cards, daily in/ out passes of the deployed staff for the work.
Shree Ayyappa Engineering
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .