| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹1.2 CrAdmitted-Finance | ₹1.2 Cr | L1 | Admitted-Finance |
| 2 | L2₹1.2 Cr+₹9.3 L (8.04%)Admitted-Finance | ₹1.2 Cr+₹9.3 L (8.04%) | L2 | Admitted-Finance |
| 3 | Rejected-Technical SULTANPURA JANIPUR JAMMU JAMMU JAMMU JAMMU KASHMIR 180007 | JAMMU | JAMMU AND KASHMIR | 180007 | - | - | Rejected-Technical Attached |
| 4 | Rejected-Technical | - | - | Rejected-Technical Attached |
| 5 | Rejected-Technical 601 603 EROS APARTMENT 56 NEHRU PLACE NEW DELHI 110019 | NEW DELHI | NEW DELHI | DELHI | 110019 | - | - | Rejected-Technical Attached |
| Sl No | Description | Qty | Unit | BNB Security and Automation Solutions Pvt Ltd L2 | Dhanda enterprises L1 |
|---|---|---|---|---|---|
| 1.00Main Item - Fire Alarm System (as per technical specifications mentioned at point 4 and Warranty as per SCHEDULE of the tender document) | |||||
| 1.01 | Addressable 2 Loop Fire Alarm Control panel (FACP) with battery back up for 48 hours normal operation and 30 minutes alarm operation. It shall include a full featured operator interface control and annunciation panel having liquid crystal display, individual color coded system showing the status through LEDs, and a alphanumeric keypad for the field programming and control of the fire alarm system. The panel including enclosure shall be UL listed complying to UL 864, 10th Edition requirement and FM approved. If the panel programming requires a dongle/key then the same shall be supplied along with the panel. | 5 | Nos | 19,56,920 ₹23,09,165.6 | 15,62,500 ₹18,96,750 Lowest |
| 1.02 | Analogue Addressable Flash scan multi-sensing, low-profile detector (Acclimate type) having Rotary, decimal addressing system with standard base, junction box and other accessories as required. The detector shall be with Visible bi- color LEDs for 360 deg viewing and shall blink green every time the detector is addressed, and illuminate steady red on alarm. Detector shall comply UL 268, 7th edition requirements | 450 | Nos | 12,72,600 ₹15,01,668 Lowest | 12,75,750 ₹15,98,385 |
| 1.03 | Heat detector- Operating Voltage: 17 to 41 VDC Current Consumption: Standby: .55 mA Alarm: .55 mA Detection Temperature Range: 135°F to 150°F (57°C TO 65°C) Ambient Temperature: 32ºF to 120ºF (0ºC to 49ºC) Mounting: 4" SQR, 4" OCT Single gang mud ring Rated Spacing: 70’ between sensors on smooth ceilings. | 15 | Nos | 41,940 ₹49,489.2 | 37,350 ₹47,573 Lowest |
| 1.04 | Analogue addressable Fault isolator module capable of monitoring shorted loop circuit and automatically restore communications when shorted conditions are corrected. Module shall be with back box, LED indication and other accessories all complete as required. It shall work on suitable DC voltage. | 25 | Nos | 76,325 ₹90,063.5 | 71,125 ₹89,427.5 Lowest |
| 1.05 | Addressable Hooter cum strobe unit as per NFPA shall deliver ouput up to 90 db at 1 m from source (adjustable at site or from the panel) and candela setting from 15 to 130 cd from its installed location and 75cd flashing at 1 Hz for visual indication. No external 3rd party power supply shall be permitted. Vendor to include all accessories. | 50 | Nos | 1,69,850 ₹2,00,423 | 1,32,500 ₹1,61,850 Lowest |
| 1.06 | Addressable Manual Pull Stations or Manual Call Point (MCP) of Single action type with an integrally mounted addressable module that monitors and reports contact status. | 45 | Nos | 2,45,160 ₹2,89,288.8 | 1,23,930 ₹1,55,737.4 Lowest |
| 1.07 | Analogue Addressable Control module having Rotary, decimal addressing system and shall be capable of providing DPDT contact rated at 24v DC, 2A | 60 | Nos | 2,11,980 ₹2,50,136.4 Lowest | 2,11,200 ₹2,61,716 |
| 1.08 | Addressable power supply unit with battery backup for hooters with suitable MS enclosure | 10 | Nos | 8,68,790 ₹10,25,172.2 Lowest | 9,00,000 ₹10,64,000 |
| 2.00Main Item - Cable & Accessories (as per technical specifications mentioned at point 4 and Warranty as per SCHEDULE of the tender document) | |||||
Tender Value
Refer Docs
EMD Value
₹2.1 L
Closing Date
15 Feb 2024, 2:00 pmClosed
Sh. Dharmendra Kumar Singh
IIT Jammu
Tender for procurement of Fire Alarm and Public Addressing System for IIT Jagti and Paloura Campus.
2024_IITJU_792149_1
IITJMU/FSSH/SP-199/2023-24
Open Tender
Miscellaneous Goods
Supply
60 days
IIT Jammu
Please refer Tender documents.
2 documents required · 2 mandatory
₹0
₹2.1 L
Yes
26 Mar 2024
25 Jan 2024
16 Feb 2024
25 Jan 2024
15 Feb 2024
25 Jan 2024
25 Jan 2024 - 1 Feb 2024
Main Item - Fire Alarm System (as per technical specifications mentioned at point 4 and Warranty as per SCHEDULE of the tender document)
Addressable 2 Loop Fire Alarm Control panel (FACP) with battery back up for 48 hours normal operation and 30 minutes alarm operation. It shall include a full featured operator interface control and annunciation panel having liquid crystal display, individual color coded system showing the status through LEDs, and a alphanumeric keypad for the field programming and control of the fire alarm system. The panel including enclosure shall be UL listed complying to UL 864, 10th Edition requirement and FM approved. If the panel programming requires a dongle/key then the same shall be supplied along with the panel.
Analogue Addressable Flash scan multi-sensing, low-profile detector (Acclimate type) having Rotary, decimal addressing system with standard base, junction box and other accessories as required. The detector shall be with Visible bi- color LEDs for 360 deg viewing and shall blink green every time the detector is addressed, and illuminate steady red on alarm. Detector shall comply UL 268, 7th edition requirements
Heat detector- Operating Voltage: 17 to 41 VDC Current Consumption: Standby: .55 mA Alarm: .55 mA Detection Temperature Range: 135°F to 150°F (57°C TO 65°C) Ambient Temperature: 32ºF to 120ºF (0ºC to 49ºC) Mounting: 4" SQR, 4" OCT Single gang mud ring Rated Spacing: 70’ between sensors on smooth ceilings.
Analogue addressable Fault isolator module capable of monitoring shorted loop circuit and automatically restore communications when shorted conditions are corrected. Module shall be with back box, LED indication and other accessories all complete as required. It shall work on suitable DC voltage.
Addressable Hooter cum strobe unit as per NFPA shall deliver ouput up to 90 db at 1 m from source (adjustable at site or from the panel) and candela setting from 15 to 130 cd from its installed location and 75cd flashing at 1 Hz for visual indication. No external 3rd party power supply shall be permitted. Vendor to include all accessories.
Addressable Manual Pull Stations or Manual Call Point (MCP) of Single action type with an integrally mounted addressable module that monitors and reports contact status.
Analogue Addressable Control module having Rotary, decimal addressing system and shall be capable of providing DPDT contact rated at 24v DC, 2A
Addressable power supply unit with battery backup for hooters with suitable MS enclosure
Main Item - Cable & Accessories (as per technical specifications mentioned at point 4 and Warranty as per SCHEDULE of the tender document)
2c x 1.5 sq. mm, PVC insulated FRLS copper armored conductor multi core cables.
4 modules back box for installing the Detectors, MCP, and Hooters
Glands for the Detector Back Box
2 Inch FRLS Casing and capping Jointing accessories
2 Inch FRLS Casing and capping
Main Item - Service - FAS (as per technical specifications mentioned at point 4 and Warranty as per SCHEDULE of the tender document)
Supervision, programming, Drawing charges, Testing charges
Main Item - PA System (as per technical specifications mentioned at point 4 and Warranty as per SCHEDULE of the tender document)
Supply, Installation, Testing & Commissioning of 15Watts Wall Mount speaker with max SPL1M/1W 98dB. Frequency response of 160Hz-20KHz. The speaker should have tappings at 15W/7.5W as per technical specification etc. as Required.
500W Amplifier
2c x 1.5 sq. mm, twisted pair PVC insulated FRLS copper armored conductor multi core cables.
Supply and Installation of 12U Rack for Keeping controller and Amplifier setup
Main Item - Services-PAS (as per technical specifications mentioned at point 4 and Warranty as per SCHEDULE of the tender document)
Supervision, programming, testing and Drawing preparation Charges
BNB Security and Automation Solutions Pvt Ltd
stage.html
html • 0.03 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .